MGE G3
Multimeter
Characteristics
Waveform capture in the Modbus buffer for all three phases (current and voltage)
Universal three phase connection, balanced and unbalanced load, or single phase.
Serial communication RS 485 protocol Modbus RTU and RS 232 for local configuration
Nonvolatile Bulk storage memory, supports up to 48 hours without power supply with correct time register.
This functionality register the date, time and the variables configured (e.g. if it was chosen 12 variables,
sampling time 15 minutes, it is possible to store 40 days). Though the configuration software it is possible
read, salve and configure the bulk memory.
Events register nonvolatile memory configurable through software, which register events like undervoltage,
overvoltage, undercurrent, etc. The instrument register date, time, value of variable in the instant of the
event and when the variable is on normal value.
Technical data
abb
Input
Voltage (Vn)
Current (In)
0500VAC phase-phase
1A , 5A
Signal limit
U = 10120%
I = 10...120%
Consumption
Nominal
frequency
Overload
Auxiliary supply
50; 60 Hz 10%
Permanent: 1,5 x Un ; 2 x In
Short time: 4 x U/1s; 50 x I/1s
Maximum: 250A /1s
85 265VAC/90300VDC
Consumption ~ 6VA
Impact
Vibration
Fastening
Pair of clamps
Protection degree
IP50 housing
IP20 connectors
Weight
~ 0,45 kg
Climatic conditions
Outputs
Digital outputs
1 fail resume
Maximum voltage: 24Vcc
Maximum current: 20mA
Operating temperature
-20...+60C
Storage temperature
-40...+80C
Relative humidity
75%
Influence variables
Error limit
0,5%
I = 10%...100%;
U = 10%...100%
U = 10120%
I = 10...120%
Input:
Frequency:
Additional error input 1,2xI
or 1,2xU
Linearity deviation
0,2%
0,2%
(included in the error limit)
0,2%/10 K;
Nominal Temperature 25C
Temperature error
Auxiliary supply
85 265VAC/90300VDC
Electrical Tests
Test voltage
Mechanical tests
abb
Caution
Be sure that all connected voltage and current are
compatible with the technical specification and if the
connection are in accordance with the connections diagrams.
Mounting Instructions
The installation must regard the climatic conditions. It is
important verify the vibration, dust, temperature and
humidity, which must be in the specified limit. The
mechanical fastening in the panel door is done through a pair
of clamps, which is included with the instrument. The
connection of the input voltage, auxiliary supply and RS 485
User guide
Verify the connection diagrams and user manual to configure
the instrument. Configure the PT ratio and the CT primary,
connection, and communication (address, baud rate and
byte are according to the local installation
Dimensional (mm)
Product specification
abb
MGE G3
N 0 0 4 0 0
Nominal frequency
50 Hz
60Hz
Connection (Universal)
Single phase/ Three phase
Current signal
1A
5A
Voltage signal
63V (fase/neutral) / 110V (phase/phase)
127V (fase/neutral) / 220V (phase/phase)
254V (fase/neutral) / 440V (phase/phase)
Auxiliary supply
85265VAC e 90300VDC
Digital outputs
5 Digital outputs
Additional information
Standard configuration:
Default configuration, class 0,5%.
Special configuration
Inform a special configuration
1
2
4
1
2
1
2
4
3
2
1
C
Example:
Frequency:60Hz
Input current: 5A
Input voltage: 0440Vca (phase-phase)
Auxiliary supply: 85265VAC/90300VDC
Standard Configuration
Code: N004002424321
Contact
ABB Ltda.
Avenida dos Autonomistas, 1496
Osasco So Paulo - Brazil
Zip code 06020-902
Telephone 0800 014 9111
Email: abbatende@br.abb.com
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB BR does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.