Current transformer
Page 1/3
October 2003
Characteristics
Application
plastic
B (max. 130C)
Primary circuit: passing cable or conducting
bar
Secondary circuit: terminals with lock and
screws
Primary circuit: P1 and P2
Secondary circuit: S1 and S2
Primary cable or bar (normal)
Loose delivered primary bar (optional)
1 A or 5 A
0,6kV (r.m.s.)
50/60 Hz
1,5 Irtd
4,0kV / min - 60 Hz
60 x Irtd / 1 s
150 x Irtd / 0,1 s
HB 602 0,35kg .
HB 603 0,4...0,6kg (according to the field).
Notes:
As a current transformer elevates the voltage, it must have the
secondary circuit always short-circuited before disconnecting the
measuring instrument.
Same indexes correspond to same polarities.
In delivery included accessories:
HB 602 - holder for fastening on cable or bar.
2 fastening supports for base.
HB 603 - 1 fastening support with screws for bar.
2 fastening supports for base.
In case of currents under 50 A, the primary conductor has to be
Winded through the window around the transformer with a
number of windings corresponding to the relation between the
measuring current and the primary current of the used transformer.
Example: Measuring current = 10 A
Primary current of the transformer =50 A
Number of windings of the conductor = 5 windings
( 1 winding = 1 passage of the primary conductor
through the window)
Specification text
Primary
Current
Code
(A)
HB 603
50
0050
3 C 2,5
60
0060
3 C 2,5
75
0075
3 C 2,5
100
0100
1,2 C 2,5
1,2 C 3,75
150
0150
0,6 C 3
0,6 C 2,5
200
0200
0,6 C 3
0,6 C 2,5
250
0250
0,6 C 3
0,6 C 3,75
300
0300
0,6 C 5
0,6 C 5,0
400
0400
0,6 C 5
0,6 C 5,0
500
0500
0,6 C 5
0,6 C 5,0
600
0600
0,6 C 5
0,6 C 7,5
800
0800
-----------
0,6 C 7,5
CT HB 602, HB 603
Current transformer
Dimensional Drawing
Dimension ( in mm)
CT 602
CT 603
CT HB 602, HB 603
Current transformer
Page 3/3
October 2003
Ordering information
Catalog number
Current Transformer
Type
HB 602, ring type, secondary/1A
HB 602, ring type, secondary/5A
HB 603, window type, secondary/1A
HB 603, window type, secondary/5A
Measuring range
Inform primary according specification of text.
Version
HB
Export
----
2
3
4
5
xxxx
H
E
Additional information
Normal