Beruflich Dokumente
Kultur Dokumente
0A Electronic Trip
Units
Unidades de disparo electrnico Micrologic 2.0A, 3.0A,
5.0A y 6.0A
Dclencheurs lectroniques MicrologicMC 2.0A, 3.0A, 5.0A et
6.0A
Instruction Bulletin
Boletn de instrucciones
Directives d'utilisation
48049-136-05
Rev. 01, 04/2012
Retain for Future Use. /
Conservar para uso futuro. /
conserver pour usage ultrieur.
ENGLISH
Instruction Bulletin
48049-136-05
Rev. 01, 07/2012
Retain for future use.
ENGLISH
48049-136-05
Rev. 01, 07/2012
ANSI
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
DANGER
IEC
WARNING
WARNING indicates a hazardous situation which, if not avoided, can
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, can
result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The
safety alert symbol is not used with this signal word.
Please Note
FCC Notice
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense. This
Class A digital apparatus complies with Canadian ICES-003.
2-EN
48049-136-05
Rev. 01, 07/2012
SECTION 1:
GENERAL INFORMATION
...................................................................................................................... 5
Introduction ................................................................................................. 5
Communications ......................................................................................... 5
Trip Unit Settings ........................................................................................ 5
Micrologic 2.0A Trip Unit ....................................................................... 6
Micrologic 3.0A Trip Unit ....................................................................... 6
Micrologic 5.0A Trip Unit ....................................................................... 7
Micrologic 6.0A Trip Unit ....................................................................... 8
Zone-Selective Interlocking ......................................................................... 9
Trip Unit Switches ..................................................................................... 10
Long-Time Protection .......................................................................... 10
Short-Time Protection ......................................................................... 11
Instantaneous Protection ..................................................................... 12
Ground-Fault Protection ...................................................................... 13
Indicator Lights .......................................................................................... 13
Overload Indicator Light ...................................................................... 13
Trip Indicator Lights ............................................................................. 14
Ammeter ................................................................................................... 14
Trip Unit Testing ........................................................................................ 14
Micrologic Trip Unit Configuration ............................................................. 14
Control Power ...................................................................................... 14
External Power Supply ........................................................................ 15
SECTION 2:
AMMETER
.................................................................................................................... 16
Display ...................................................................................................... 16
Ammeter Measurements ........................................................................... 16
Accessing Information ............................................................................... 16
Current Menu ...................................................................................... 17
Peak Menu .......................................................................................... 18
Switch Settings Menu .......................................................................... 19
SECTION 3:
OPERATION
.................................................................................................................... 20
Switch Setting Adjustment ........................................................................ 20
Examples .................................................................................................. 20
Micrologic 2.0A Trip Unit ..................................................................... 20
Micrologic 3.0A Trip Unit ..................................................................... 21
Micrologic 5.0A Trip Unit ..................................................................... 21
Micrologic 6.0A Trip Unit ..................................................................... 22
Zone-Selective Interlocking (ZSI) .............................................................. 23
Communication Module values ................................................................. 24
Trip Unit Settings Check ........................................................................... 26
Trip Unit Operation Verification ................................................................. 26
Equipment Ground-Fault Trip Functions Testing ...................................... 27
Trip Unit Resetting .................................................................................... 27
Trip Unit Status Check .............................................................................. 27
SECTION 4:
.................................................................................................................... 28
Required Tools .......................................................................................... 28
Preparation ............................................................................................... 28
Record Switch Settings ....................................................................... 28
Circuit Breaker Disconnection ............................................................. 28
Circuit Breaker Accessory Cover Removal ......................................... 28
Rating Plug Removal ........................................................................... 29
Trip Unit Removal ................................................................................ 29
3-EN
ENGLISH
Table of Contents
48049-136-05
Rev. 01, 07/2012
ENGLISH
SECTION 6:
BATTERY REPLACEMENT
.................................................................................................................... 34
Circuit Breaker Disconnection ................................................................... 34
Circuit Breaker Accessory Cover Removal ............................................... 34
Withstand Module Shifting ........................................................................ 34
Battery Replacement ................................................................................. 34
Withstand Module Replacement ............................................................... 35
Circuit Breaker Accessory Cover Replacement ........................................ 35
Circuit Breaker Reconnection ................................................................... 35
.................................................................................................................... 36
List of Registers ........................................................................................ 36
4-EN
48049-136-05
Rev. 01, 07/2012
A
06133249
Figure 1:
06134858
Introduction
ENGLISH
gic
Microlo
7.0 A
Micrologic 3.0A
Type of protection
2Basic IEC protection (LS0)
3Basic UL protection (LI)
5Selective protection (LSI)
6Selective protection plus ground fault
protection for equipment (LSIG)
Trip unit series
0Indicates the first version
100 %
40 %
alarm
menu
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
tr
(s) 4
2
1
.5
8 12
16
20
24
Ir
@6
D
C
Type of measurement
NoneProvides protection only
AProvides protection plus ammeter measurements
Communications
Micrologic trip units can communicate with other devices if the optional
Circuit Breaker Communication Module (BCM) is installed. For information
on the communication module, see the product catalog and Modbus
Communications System, Data Bulletin 0613IB1201.
On the face of the trip unit are adjustable switches to allow changing of trip
characteristics. Trip units are shipped with the long-time pickup switch set at
1.0 and all other trip unit adjustments set at their lowest settings.
5-EN
A
06134246
Micrologic 2.0 A
06134245
G
D
E
menu
Ir
Isd
long time
Ir
.7
.6
.5
.4
.8
x In
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
alarm
@ 6 Ir
instantaneous
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
setting
Figure 3:
06133243
Micrologic 3.0 A
B. Alphanumeric display
C. Three-phase bar graph
D. Scroll button
E. Menu button
F. Long-time pickup (Ir) switch
06133201
ENGLISH
48049-136-05
Rev. 01, 07/2012
G
D
H
0
Ir
Ii
long time
Ir
menu
.7
.6
.5
.4
.8
x In
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
alarm
@ 6 Ir
instantaneous
Ii
4
3
8
2
10
1.5
12
x In
setting
I
*Short-time delay is factory set at 0 (no delay), thus short-time
pickup provides instantaneous protection.
6-EN
48049-136-05
Rev. 01, 07/2012
Figure 4:
A
06133244
ENGLISH
Micrologic 5.0 A
B. Alphanumeric display
C. Three-phase bar graph
D. Scroll button
E. Menu button
C
06133202
F
G
I
J
.7
.6
.5
.4
.8
x In
e
short time
setting
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
Isd
4
5
3
2.5
6
8
2
1.5
10
x Ir
long time
menu
Ir
F
G
Ir
Isd
Ii
@ 6 Ir
instantaneous
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
Ii
(s)
on
I t
off
6
4
3
2
10
12
15
off
x In
delay
7-EN
Figure 5:
T S R Q
A
06133245
Micrologic 6.0 A
B. Alphanumeric display
H
D. Scroll button
E. Menu button
100 %
I.
menu
Ir
F
G
I
K
.7
.6
.5
.4
Ii
I t on
x In
tsd
.4 .3
(s)
tsd .4
.2
.3
.1
.2
.1 2 0
on I t off
setting
D
C
B
A
@ 6 Ir
Isd
4
5
3
6
2.5
8
2
1.5
10
x Ir
Ig
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
short time
Isd
long time
Ir
40 %
ENGLISH
06133202
48049-136-05
Rev. 01, 07/2012
delay
tg
F
G
H
J
(s)
.3
.2
.1
I t
instantaneous
4
3
5 6 10
12
15
off
2
x In
test
.4 .4 .3
on
Ii
.2
.1
0
off
I t off
Ig
N
M
ground fault
8-EN
48049-136-05
Rev. 01, 07/2012
NOTE: Use I2t off with ZSI for proper coordination. Using I2t on with ZSI is
not recommended as the delay in the upstream device receiving a restraint
signal could result in the trip unit tripping in a time shorter than the published
trip curve.
NOTE: Setting short-time delay (tsd) or ground-fault delay (tg) to the 0
setting will eliminate selectivity for that circuit breaker.
Figure 6:
Zone-Selective Interlocking
06133376
9-EN
ENGLISH
Zone-Selective Interlocking
48049-136-05
Rev. 01, 07/2012
Ir
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
.7
.6
.5
.4
x In
@ 6 Ir
10-EN
.7
.6
.5
.4
x Ir
6
8
10
2
1.5
B
.8
x In
@ 6 Ir
setting
tsd
(s)
Ii
.4 .4 .3
.3
.2
.1
on
.2
.1
0
I t off
2
4
3
Ir
.7
.6
.5
.4
.8
x In
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
10
12
15
off
2
x In
long time
instantaneous
short time
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
Isd 4
5
3
6
2.5
2
8
1.5
10
x Ir
8
10
12
x In
long time
.7
.6
.5
.4
@ 6 Ir
setting
Ir
x In
4 5 6
3
setting
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
instantaneous
delay
tsd
(s)
D
C
B
A
.2
.1
.3
.2
.1
0
I t off
2
on
4
3
2
x In
delay
tg
F
G
H
J
Ii
.4 .4 .3
setting
Ig
Ir
Ii
3 4 5
2
1.5
long time
instantaneous
2.5
long time
Isd
06133203
Figure 7:
06133351
NOTE: Micrologic trip units are powered from the circuit to always provide
fault protection. All other functions (display, metering, communications, etc.)
require external power. See 15 for more information.
06133204
ENGLISH
Long-Time Protection
(s)
10
12
15
off
test
.4 .4 .3
.3
.2
.1
on
.2
.1
2
I t
0
off
ground fault
Table 1:
Setting1
tr at 1.5 x Ir
12.5
25
50
100
200
300
400
500
600
tr at 6 x Ir
0.5
12
16
20
24
tr at 7.2 x Ir
0.343
0.69
1.38
2.7
5.5
8.3
11
13.8
16.6
1Ir
= In x long-time pickup. In = sensor rating. Trip threshold between 1.05 and 1.20 Ir.
accuracy +0/-20%
3For Micrologic 5.0A and 6.0A trip units, when tsd is set to 0.4 on or 4.0 off, then tr = 0.5 instead of 0.34.
2Time-delay
48049-136-05
Rev. 01, 07/2012
06133204
on/I2t
The
off option provides improved
selectivity with downstream protective
devices:
With I2t off selected, fixed time delay is
provided.
.7
.6
.5
.4
.8
x In
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
Isd 4
5
3
6
2.5
2
8
1.5
10
x Ir
setting
long time
Ir
.7
.6
.5
.4
@ 6 Ir
instantaneous
short time
long time
Ir
tsd
(s)
Ii
.4 .4 .3
.3
.2
.1
on
.2
.1
0
I t off
2
4
3
ENGLISH
Figure 8:
06133351
Short-Time Protection
.8
x In
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
10
12
15
off
x In
delay
.4 .4 .3
.2
.3
.1
.2
.1 2 0
D
C
B
A
Ii
(s)
on
setting
Ig
tsd
I t
off
delay
tg
F
G
H
J
(s)
4
3
2
x In
10
12
15
off
test
.4 .4 .3
.3
.2
.1
on
.2
.1
2
I t
0
off
ground fault
Table 2:
Setting
Short-Time Delay
0.1
0.2
0.3
0.4
0.1
0.2
0.3
0.4
20
80
140
230
350
80
140
200
320
500
NOTE: Use I2t off with ZSI for proper coordination. Using I2t on with ZSI is
not recommended as the delay in the upstream device receiving a restraint
signal could result in the trip unit tripping in a time shorter than the
published trip curve.
11-EN
Figure 9:
06133203
06134243
long time
Ir
alarm
tr
.8
.7
.6
.5
.4
x In
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
long time
Ir
@ 6 Ir
2
1.5
x Ir
6
8
10
x In
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
setting
long time
Ir
.7
.6
.5
.4
@ 6 Ir
instantaneous
short time
Isd 4
5
3
6
2.5
2
8
1.5
10
x Ir
setting
tsd
(s)
Ii
.4 .4 .3
.3
.2
.1
on
.2
.1
0
I t off
2
4
3
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
10
12
15
off
2
x In
8
10
12
x In
long time
.8
2
1.5
@ 6 Ir
4 5 6
3
setting
Ir
x In
instantaneous
Ii
3 4 5
2.5
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
.7
.6
.5
.4
instantaneous
Isd
06133204
ENGLISH
06133351
Instantaneous Protection
48049-136-05
Rev. 01, 07/2012
delay
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
on
setting
Ig
D
C
B
A
I t
off
4
3
2
x In
10
12
15
off
delay
tg
F
G
H
J
Ii
(s)
(s)
test
.4 .4 .3
.3
.2
.1
on
I t
.2
.1
0
off
ground fault
Table 3:
Setting
Interruption Current
1.5
2.5
10
3.0A Ii (= In x..)
1.5
10
12
5.0A Ii (= In x..)
10
12
15
off
6.0A Ii (= In x..)
10
12
15
off
12-EN
48049-136-05
Rev. 01, 07/2012
Figure 10:
ENGLISH
Ground-Fault Protection
06133351
long time
Ir
.7
.6
.5
.4
Neutral protection and equipment groundfault protection are independent and can
operate concurrently.
x In
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
@ 6 Ir
instantaneous
short time
tsd
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
.8
(s)
D
C
B
A
5
4
3
0
2
I t off
on
2
x In
delay
tg
.2
.1
.3
.2
.1
setting
Ig
Ii
.4 .4 .3
F
G
H
J
(s)
10
12
15
off
test
.4 .4 .3
.3
.2
.1
on
.2
.1
2
I t
0
off
ground fault
B
Table 4:
Ig (= In x....)
In d 400 A
0.3
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
In > 1200 A
In = sensor rating.
Ig = ground-fault pickup.
Table 5:
Setting
Ground-Fault Delay
I2t
0.1
0.2
0.3
0.4
I2t
0.1
0.2
0.3
0.4
20
80
140
230
350
140
200
320
500
NOTE: Use I2t off with ZSI for proper coordination. Using I2t on with ZSI is
not recommended as the delay in the upstream device receiving a restraint
signal could result in the trip unit tripping in a time shorter than the
published trip curve.
Indicator Lights
Figure 11:
06133352
long time
Ir
.7
.6
.5
.4
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
instantaneous
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
on
setting
I t
delay
(ms)
230
10
140
20
30
60
7
Ii
4
5
3
2.5
6
2
8
1.5
10
x In
100 %
test
In
3
2
1
.5
@ 6 Ir
short time
(A)
alarm
350
40 %
800
earth leakage
13-EN
ENGLISH
Figure 12:
A B C D
06133245
48049-136-05
Rev. 01, 07/2012
Micrologic 6.0 A
Ammeter
Figure 13:
Ammeter
100 %
40 %
B
menu
Trip unit functions can be tested using primary injection testing or secondary
injection testing.
The A trip unit was designed to be used with or without an external 24 Vdc
power supply.
Pickup Values
4001200 A
16006300 A
500 A
The following will be powered and functional even if the trip unit is not
externally powered:
Fault protection for LSIG functions. The A trip unit is fully circuit powered
for fault protection.
All display functions and trip unit features power-up with current flow on
one phase greater than or equal to the values in Table 6.
14-EN
48049-136-05
Rev. 01, 07/2012
All of the above functions which are functional without external power.
Trip settings and max. current readings can be accessed on the display
be pressing the navigation buttons with or without current flowing
through the circuit breaker.
Ammeter and bar graph displays are functional with or without current
flowing through the circuit breaker. With current flow between 0 and 20%
of sensor value, the ammeter may not be accurate.
CAUTION
Table 7:
Function
Power for Trip Unit Alone
24 Vdc, 50 mA
2400 V
5%
3 kV rms
Connections
Connections UC3
F1 (-)
F2 (+)
Specification
24 Vdc
Power supply is used for graphic scree display when the circuit breaker is
open or not carrying current.
15-EN
ENGLISH
48049-136-05
Rev. 01, 07/2012
Section 2Ammeter
NOTE: The ammeter display will function only if the trip unit is powered. The
trip unit is powered by the circuit breaker carrying more than 0.20 x In of
load current, by being connected to a 24 Vdc external power supply, or by
having the Full-Function Test Kit or Hand-Held Test Kit connected and on.
Even with external power supplied, current through the circuit breaker must
exceed 0.20 x In for the ammeter reading to be accurate to within 1.5%.
Figure 14:
06133245
Ammeter
B
100 %
40 %
D
menu
Ammeter Measurements
Micrologic A trip units measure the true RMS
value of currents. They provide continuous
current measurement from 0.2 to 20 x In with an
accuracy of 1.5% (including sensors). No
auxiliary source is needed where I > 0.2 x In.
The optional external power supply (24 Vdc)
makes it possible to display currents where
I < 0.2 x In and to store values of the interrupted
current.
A digital LCD screen continuously displays the
most heavily loaded phases (Imax) or displays
the Ia, Ib, Ic, Ig, and (on 4-pole circuit breakers
only) In stored current and setting values by
successively pressing the navigation button.
Figure 15:
Menus
06133355
CSwitch Settings
BPeak Currents
ACurrents
06133353
Accessing Information
06133354
ENGLISH
Display
Max
A
Ir=
100 %
40 %
16-EN
1.125 x Ir
1 x Ir
0.8 x Ir
0.6 x Ir
0.4 x Ir
100 %
100 %
40 %
40 %
48049-136-05
Rev. 01, 07/2012
A
menu
u
Figure 17:
Current Menus
BB-Phase Current (IB)
06133342
06134248
06133354
06134248
Current Menu
Navigation Buttons
ENGLISH
Figure 16:
06133356
100 %
100 %
40 %
40 %
06133344
06134248
100 %
100 %
40 %
40 %
06134248
06133345
100 %
100 %
40 %
40 %
06134248
06134248
17-EN
Figure 18:
06134247
06133354
menu
Max
A
40 %
Peak Menus
Max
A
06134248
Max
06133355
40 %
Figure 19:
100 %
06134248
100 %
100 %
40 %
40 %
Max
A
100 %
100 %
40 %
40 %
Max
06134248
18-EN
Max
06134248
06133347
06134248
06133349
ENGLISH
Peak Menu
Current Menu
06134248
Peak Menu
48049-136-05
Rev. 01, 07/2012
Max
A
100 %
100 %
40 %
40 %
48049-136-05
Rev. 01, 07/2012
menu
Ir=
06134248
Max
06133353
Peak Menu
ENGLISH
06134247
Figure 20:
06133355
Btr Setting
Ir=
06133383
AIr Setting
06133382
06134248
Figure 21:
100 %
06134248
100 %
06134248
tr=
Isd=
06133385
Dtsd Setting
06134248
CIsd Setting
06133384
tsd=
06133388
06134248
Ii=
06134248
06133387
FIg Setting
Ig=
Gtg Setting
06133382
06134248
06133389
AIr Setting
Ir=
tg=
Figure 22:
Ir=
menu
06133354
Current Menu
06134247
100 %
19-EN
48049-136-05
Rev. 01, 07/2012
Section 3Operation
Figure 23:
06133207
06133206
06133205
C
B
Examples
Figure 24:
06133208
In 2000 A
Figure 25:
06134251
long time
Ir
.7
.6
.5
.4
alarm
.8
x In
.9
.95
.98
1
Ir = 0.7 x In = 1400 A
Isd = 2 x Ir = 2800 A
06134245
ENGLISH
instantaneous
Isd
2.5
2
3 4 5
1.5
x Ir
6
8
10
setting
20-EN
Ir
Isd
48049-136-05
Rev. 01, 07/2012
ENGLISH
Figure 26:
06133211
tr = 1 s (at 6 x Ir)
long time
tr
(s) 4
2
1
.5
alarm
12
16
20
24
t
06133212
@ 6 Ir
1s
tr
long time
Ir
alarm
.8
.7
.6
.5
.4
.9
.95
.98
1
x In
Ir = 0.7 x In = 1400 A
Ii = 3 x In = 6000 A
06133210
Figure 27:
06133209
6 x Ir
t
Ir
instantaneous
Ii
3
2
4 5 6
1.5
8
10
12
x In
setting
Ii
06133211
Figure 28:
long time
.5
alarm
12
16
20
24
t
06133212
tr
(s) 4
2
1
@ 6 Ir
1s
tr
long time
Ir
.7
.6
.5
.4
.8
x In
alarm
Ir = 0.7 x In = 1400 A
.9
.95
.98
1
Ii = 6 x In = 12000 A
instantaneous
short time
Isd
4 5
3
2.5
6
2
8
1.5
10
x Ir
Ii
off
Ir
Isd = 2 x Ir = 2800 A
10
12
15
2
off
x In
6
4
3
t
06133214
06133213
Figure 29:
6 x Ir
6000 A
1400 A
Isd
setting
Ii
12000 A
2800 A
1400 A
21-EN
ENGLISH
06133215
Figure 30:
long time
tr
(s) 4
2
1
.5
alarm
12
16
20
24
06133217
48049-136-05
Rev. 01, 07/2012
@ 6 Ir
short time
tsd
on
tr
1s
.4 .4 .3
.2
.3
.2
.1
.1 2 0
I2t on
I2t off
I t
delay
tsd
0.2 s
Figure 31:
long time
Ir
.7
.6
.5
.4
alarm
.8
x In
In = 2000 A
.9
.95
.98
1
Ir = 0.7 x In = 1400 A
short time
Isd
instantaneous
Ii
Isd = 2 x Ir = 2800 A
0
t
D
C
B
A
BoIg = 640 A
F
G
H
J
06133359
setting
ground fault
Ig
Figure 32:
640 A
12000 A
x In
Ii = 6 x In = 12000 A
10
12
15
off
2800 A
6
4
3
2
1400 A
Is
3 4 5
2.5
6
2
8
1.5
1
x Ir
Ig
Ir
06133214
06133357
10 x Ir
6 x Ir
06133358
long time
tr
(s)
2
1
.5
short time
alarm
12
16
20
24
tr = 1 s (at 6 x Ir)
@ 6 Ir
tg
off
tg = 0.2 s I2t on
06133361
(s)
I t
10 x Ir
0
I2t on
delay
.4 .4 .3
.2
.3
.1
.2
.1 2 0
tsd
0.2 s
instantaneous
6 x Ir
tsd .4 .4 .3
(s)
.2
.3
.1
.2
.1 2 0
on I t off
on
tr
1s
ground fault
tg
0.2 s
22-EN
48049-136-05
Rev. 01, 07/2012
15
15
15
26
15
15
15
15
15
15
15
15
15
15
15
15
Figure 33:
Jumpered Terminals
UC1
Z5
M1
Z3
Z4
Z1
Z2
Auxiliary Connections
23-EN
ENGLISH
Downstream Device
(sends output to RIM)
Upstream Device
(receives input from RIM)
ZSI Combinations
Table 8:
Figure 34:
Z4
Z1
Z2
UC1
Z5
M1
Auxiliary
Connections 1
Secondary
Connector
Position
Z1
Z2
Z3
Z4
Z5
Figure 35:
Description
ZSI out signal
ZSI out
ZSI in signal
ZSI in short time
ZSI in ground fault
Z3
Z4
Z1
Z2
Auxiliary
Connections 2
Z3
Z4
Z1
Z2
06133703
06133707
UC1
Z5
M1
Auxiliary
Connections 3
Current Menu
06133354
ENGLISH
48049-136-05
Rev. 01, 07/2012
100 %
100 %
24-EN
48049-136-05
Rev. 01, 07/2012
Communications Address
ENGLISH
06134248
Baud Rate
06133703
Figure 36:
06134248
06133704
06134248
Baud Rate
06134248
Language
06134888
06134248
06133705
Parity
06134248
06134248
06134888
Language
06134248
25-EN
06134247
Ir
Long-Time
Pickup
tr
Long-Time
Delay
Isd
Short-Time
Pickup
tsd
Short-Time
Delay
Ii
Instantaneous
Pickup
Ig
Ground-Fault
Pickup
menu
menu
Ir=
06133384
06134248
Isd=
06133385
tsd=
06133388
06134248
Ii=
Ig=
06133389
Ground-Fault
Delay
06133387
06134248
06134248
tg
tr=
06134248
06133383
06134248
tg=
Figure 37:
06133205
ENGLISH
Setting
06133382
Table 9:
06134247
48049-136-05
Rev. 01, 07/2012
26-EN
NOTE: Trip unit must be powered to test ground-fault trip function. The trip
unit is powered if the circuit breaker is carrying more than 0.20 x In of load
current, if the 24 Vdc external power supply is connected or if the FullFunction Test Kit or Hand-Held Test Kit is connected and on.
Figure 38:
6.0
logic
Micro
06134249
100 %
40 %
menu
Figure 39:
06133379
Micrologic 6.0 A
Figure 40:
B
06133379
Micrologic 6.0 A
Charged
Half-Charged
Change Battery
lithium battery
1.2AA, 3.6 V, 800 ma/h
For instructions on replacing battery, see
Section 6Battery Replacement.
27-EN
ENGLISH
48049-136-05
Rev. 01, 07/2012
48049-136-05
Rev. 01, 07/2012
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Failure to follow these instructions for installation, trip test and primary
injection testing may result in the failure of some or all protective function.
Required Tools
Preparation
Record Switch Settings
28-EN
48049-136-05
Rev. 01, 07/2012
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
shor
t time
Isd 4 5
3
6
2.5
8
2
10
1.5 Ir
x
tr
(s)
2
1
8 12
16
20
24
.5 @ 6 Ir
tsd 4 .4 .3
.
.2
.3
.1
.2
0
.1 2t
I
on delay
ntaneous
insta
ntaneous
insta
Ii
4 5
3
6
2.5
8
2
10
1.5 In
x
shor
t time
Isd 4 5
3
6
2.5
8
2
10
1.5 Ir
x
g
settin
setting
tsd 4 .4 .3
.
.2
.3
.1
.2
0
.1 2
I t
on delay
Ii
4 5
3
6
2.5
8
2
10
1.5 In
x
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
tr
(s)
2
1
8 12
16
20
24
.5 @ 6 Ir
06134854
Figure 42:
06134853
Install Battery
A
06133375
Figure 43:
LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN
NOTE: Battery holder with battery is located under the side flap in the
cardboard box the trip unit is shipped in.
Figure 44:
B
06133245
Battery Installation
Micrologic 6.0 A
29-EN
ENGLISH
B
06133222
06133221
Figure 41:
06133205
48049-136-05
Rev. 01, 07/2012
Figure 45:
06135451
06135453
ENGLISH
C
B
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Check installation of trip unit to assure proper
connections and seating.
Failure to follow this instruction can result
in equipment damage or improper circuit
breaker tripping.
30-EN
48049-136-05
Rev. 01, 07/2012
ENGLISH
Figure 46:
06134855
Must be
seated
7 lb-in
[0.8 Nm]
Must be flush
06134856
Figure 47:
alarm
06134244
06133223
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
ntaneous
insta
shor
t time
Isd 4 5
3
6
2.5
8
2
10
1.5 Ir
x
setting
tsd 4 .4 .3
.
.2
.3
.1
.2
0
.1 2
I t
on delay
Ii
4 5
3
6
2.5
8
2
10
1.5 In
x
test
shor
alarm
8 12
(s) 4
16
.8 .9
Ir
2
20
.7
.95
1
24
.6
.98
.5 @ 6 Ir
.5
1
.4 x In
long
time
tr
t time
Isd 4 5
3
6
2.5
8
2
10
1.5 Ir
x
tr
(s)
2
1
8 12
16
20
24
.5 @ 6 Ir
ntaneous
insta
Ii
tsd 4 .4 .3
.
.2
.3
.1
.2
0
.1 2t
I
on delay
4 5
3
6
2.5
8
2
10
1.5 In
x
7 lb-in
[0.8 Nm]
g
settin
31-EN
48049-136-05
Rev. 01, 07/2012
Field installation of a trip unit requires secondary injection testing with the
Full-Function Test Kit. to ensure that the newly-installed trip unit is
functioning properly. The test will require opening and closing the circuit
breaker. Follow the procedures outlined in the instruction bulletins shipped
with the circuit breaker and the test kit.
1. Make sure the circuit breaker is isolated from all upstream and
downstream devices.
2. Perform secondary injection testing as outlined in the instruction bulletin
shipped with the test kit. Verify that all applicable trip unit functions are
operating properly.
3. Repeat step 2 with the circuit breaker in the open position.
NOTE: The test kit states that the circuit breaker should be closed when
performing the test. Do not close the circuit breaker for this step.
4. If any test fails, do not put the circuit breaker into service and contact the
local sales office for factory authorization service.
1. If an auxiliary power supply is being used for the Micrologic trip unit,
reconnect the auxiliary power supply.
2. Reset the trip unit switches to original values, as recorded at the
beginning of this section.
32-EN
48049-136-05
Rev. 01, 07/2012
ENGLISH
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Figure 48:
C
06133222
06133221
06133205
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
shor
t time
Isd 4 5
3
6
2.5
8
2
10
1.5 Ir
x
tr
(s)
2
1
8 12
16
20
24
.5 @ 6 Ir
ntaneous
insta
ntaneous
insta
Ii
tsd 4 .4 .3
.
.2
.3
.1
.2
0
.1 2t
I
on delay
4 5
3
6
2.5
8
2
10
1.5 In
x
shor
t time
Isd 4 5
3
6
2.5
8
2
10
1.5 Ir
x
g
settin
tsd 4 .4 .3
.
.2
.3
.1
.2
0
.1 2
I t
on delay
Ii
4 5
3
6
2.5
8
2
10
1.5 In
x
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
setting
tr
(s)
2
1
8 12
16
20
24
.5 @ 6 Ir
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
ntaneous
insta
shor
Figure 49:
06133223
t time
Isd 4 5
3
6
2.5
8
2
10
1.5 Ir
x
setting
tsd 4 .4 .3
.
.2
.3
.1
.2
0
.1 2
I t
on delay
shor
Ii
4 5
3
6
2.5
8
2
10
1.5 In
x
test
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
tr
(s)
2
1
8 12
16
20
24
t time
Isd 4 5
3
6
2.5
8
2
10
1.5 Ir
x
tr
(s)
2
1
8 12
16
20
24
.5 @ 6 Ir
ntaneous
insta
Ii
tsd 4 .4 .3
.
.2
.3
.1
.2
0
.1 2t
I
on delay
4 5
3
6
2.5
8
2
10
1.5 In
x
g
settin
.5 @ 6 Ir
33-EN
48049-136-05
Rev. 01, 07/2012
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on or inside
equipment. Follow instructions shipped with circuit breaker to disconnect
and reconnect circuit breaker.
Figure 50:
06123145
Battery Replacement
Figure 51:
06133375
LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN
Replace Battery
LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN
Figure 52:
06133374
06133373
LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN
ENGLISH
34-EN
48049-136-05
Rev. 01, 07/2012
ENGLISH
Figure 53:
06123146
4.4 lb-in
[0.5 Nm]
35-EN
48049-136-05
Rev. 01, 07/2012
List of Registers
Module
Module Name
Equation
Address Range
BCM
147
CCM
5197
PM
BCM + 100
101147
MM
BCM + 200
201247
BCM + 50
Register List
Number of
Registers*
Register*
Module* Units
Scale/Bitmask
810DBrkrStatus
661
BCM
810DBrkrTripStat
661
BCM
BCM_SN
516
BCM
ASCII text
BkrPos
661
CCM
Bit 8 = disconnected
Bit 9 = connected
Bit 10 = test position
DT_3Regs
679
BCM
EnableCloseBkr
669
BCM
EnableOpenBkr
669
BCM
EnableRemCtrl
669
BCM
IA
Current A
8821
PM
IA_PCT
Current A % Load
8837
PM
Unity
IB
Current B
8822
PM
Unity
Unity
IB_PCT
Current B % Load
8838
PM
Unity
IC
Current C
8823
PM
Unity
IC_PCT
Current C % Load
8839
PM
Unity
IG
Current G
8825
PM
Unity
IG_PCT
Current G % Load
8841
PM
Unity
IG_PCT_VIGI
8842
PM
Hundredths
IG_VIGI
Current G (VIGI)
8826
PM
Thousandths
IMax
8820
PM
Unity
IN
Current N
8824
PM
Unity
IN_PCT
Current N % Load
8840
PM
Unity
LDPUValue
8756
PM
MaxIA
Max Current A
8827
PM
Unity
MaxIB
Max Current B
8828
PM
Unity
MaxIC
Max Current C
8829
PM
Unity
MaxIG
Max Current G
8831
PM
Unity
MaxIG_VIGI
8832
PM
Thousandths
MaxIN
Max Current N
8830
PM
Unity
NominalCurrent
8750
PM
Unity
ReadyToClose
661
BCM
36-EN
48049-136-05
Rev. 01, 07/2012
Table 10:
Register*
Module* Units
TU_BATT_PCT
8843
PM
TU_SN
8700
PM
ASCII text
TUCommStatus
552
BCM
ENGLISH
Scale/Bitmask
Unity
For register entries that are not listed, please refer to the Micrologic device type register list. Contact your local sales office.
BCM = Circuit breaker communication module. CCM = Cradle communication module. PM = Trip unit protection module.
3-register date/time format: register 1: month (byte 1) = 112, day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year), hour
(byte 2) = 023; register 3: minutes (byte 1) = 059, seconds (byte 2) = 059. Note: Bits 14 and 15 of the month/day register must be masked.
**
Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999). Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1]
+ R1. Range is zero to 9,999,999,999,999,999.
37-EN
ENGLISH
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
Schneider Electric
3700 Sixth St SW
Cedar Rapids, IA 52404 USA
1-888-778-2733
www.schneider-electric.us