Beruflich Dokumente
Kultur Dokumente
EFFECT OF THERMO-ELECTRICAL
STRESSES AND ULTRA-VIOLET
RADIATION ON POLYMERIC
INSULATORS
By
Dr. Y.Z. Khan, Prof. A.A. Al-Arainy,
Prof. N.H. Malik, and
Dr. M.I. Qureshi
Ramadan
October
1427 H
2006 G
Table of Contents
Page
iii
iv
vii
viii
ix
x
List of Tables
List of Figures
Acknowledgement
Abstract (Arabic)
Abstract (English)
Nomenclature
CHAPTER 1: INTRODUCTION
1.1
1.2
1.1.1 Advantages
1.1.2 Disadvantages
3
5
Introduction
Basic Polymeric Insulators Components
2.2.1
2.2.2
2.2.3
2.2.4
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
2.14
2.15
2.16
2.17
Core
Weather Sheds
Housings
End Fittings
8
9
9
10
13
14
Insulator Types
Weathersheds of Polymeric Materials
Testing Methods of Composite Insulators
Test Results of Composite Insulators
Ranking of Materials for Outdoor Insulation
Effect of Voltage Polarity on Performance
Properties of Pollution on Polymeric Insulators
Artificial Contamination on Polymeric Insulators
Aging of Polymeric Insulators and Mechanisms of Failure
Aging from Exposure to Ultraviolet Radiation
Detection of Faults on Composite Insulators
Effect of Rain on Electric Field Distribution
Hydrophobic Properties and Fluid Diffusion to the Surface
Saudi Arabian Experience in the Use of
Polymeric Insulators: A Survey
Nature of the Problem
-i-
14
17
21
22
26
28
30
32
33
36
37
39
39
41
43
Page
CHAPTER 3: EXPERIMENTAL SETUP AND PROCEDURES
3.1
3.2
3.3
Conclusions
Recommendation for Future Work
45
45
47
48
58
58
60
62
64
65
72
72
73
REFERENCES
74
ANNEX I
88
ANNEX II
90
-ii-
List of Tables
Table No.
Title
Page
42
3.1
53
4.1
69
2.1
-iii-
List of Figures
Fig. No.
Title
Page
1.1
1.2
2.1
2.2
12
14
2.4
15
2.5
16
2.6
16
2.7
17
2.8
24
29
34
2.3
2.9
2.10
-iv-
List of Figures
Fig. No.
2.11
Title
Page
38
3.1
48
3.2a
Schematic diagram.
49
3.2b
49
51
52
Dead
End/
Suspension
insulator(EPDM and TPE).
52
3.3
3.4a
3.4b
polymeric
3.5a
53
3.5b
54
3.6
55
Temperature
Chamber.
56
3.7
rise
and
fall
variation
in
3.8
57
4.1
59
-v-
List of Figures
Fig. No.
4.2
Title
Page
59
60
61
4.5
62
4.6
64
4.7
67
4.8
68
4.3
4.4
-vi-
ACKNOWLEDGEMENT
The authors would like to thankfully acknowledge the assistance and
financial support provided by the Research Center, College of Engineering,
through research project grant No. 18/426. Sincere thanks are extended to the
staff of High Voltage Laboratory, Electrical Engineering Department where
most of the experimental work was carried out.
-vii-
.
.
.
.
.
)(
) (IEC 61109 .
.
) (TPE
) (SiR
) (SiR
%10 %7
) . (TPE
) (SiR
) . (TPE ) (SiR
.
-viii-
ABSTRACT
Polymers are widely used for a variety of electrical applications and are
being produced and used in the Kingdom of Saudi Arabia. Polymeric
insulators are finding increasing applications in overhead transmission and
distribution lines. The electrical properties of such polymers are strongly
influenced by environmentally induced degradation mechanisms. A survey
was carried out by the authors to determine the state of non-ceramic insulators
being used by the power utilities in the Kingdom. To check the suitability of
the polymeric insulators, an experimental investigation was also carried out.
This experimental investigation is aimed at assessing the performance of
polymeric insulators used in high voltage overhead transmission and
distribution networks in the environmental conditions of central Saudi Arabia.
The effects of ultraviolet radiation and heat on the polymeric insulators were
studied. To achieve this objective, an accelerated aging test chamber was
designed and implemented to simulate local atmospheric conditions based on
the modified IEC standard 61109. Electrical withstand and Scanning Electron
Microscopy
(SEM)
based
optical,
visual
and
X-Ray Photoelectron
-ix-
NOMENCLATURE
SEM
XPS
TPE
SiR
UV
PTFE
PE
EPDM
EPR
RTV
HTV
EPM
IEC
EVA
HDPE
PUR
ATH
ANSI
NEMA
ESDD
NSDD
ESCA
FTIR
LMW
GC
MS
TGA
RIV
SEC
EOA
LI
STRI
HC
-x-
CHAPTER 1
INTRODUCTION
tracking and erosion of polymer sheds, chalking and crazing of sheds which
lead to increased contamination collection, arcing and flashover, bonding
failures and electrical breakdowns along the rod-shed interface, corona
splitting of sheds and water penetration which lead to electrical breakdown.
Today polymeric insulators are in use on lines operating up to 765 kV.
However, they are more popular on transmission levels from 69 kV through
345 kV. A recent worldwide survey showed that there are thousands of
polymeric insulators in service at all voltage levels.
Fig. (1.1) shows the results of a CIGRE survey done in 2000 to
investigate the global distribution of composite insulators at voltage levels
above 100 kV [1].
1000000
SiR
Others
No of Insulators
100000
Total
10000
1000
100
10
1
Europe
USA
Canada
Australia
Asia
Africa
Middle
East
1.1
1.1.1 Advantages
The primary impetus for polymeric insulators increased acceptance by
the usually cautious electric power utilities as discussed before, is their
substantial advantage compared to inorganic insulators which have primarily
been porcelain and glass. One of their major advantages is their low surface
energy and thereby maintaining a good hydrophobic surface property in the
presence of wet conditions e.g. fog, dew and rain. Other advantages include:
(1)
light weight of the composite insulators also obviates the need to use
heavy cranes for their handling and installation and this saves on cost,
(2)
(3)
Line post insulators are less prone to serious damage from vandalism
such as gunshots which cause the ceramic insulators to shatter and drop
the conductor to the ground,
(4)
(5)
(6)
(7)
1.1.2 Disadvantages
The main disadvantages of composite polymeric insulators are:
(1)
(2)
Suffer from erosion and tracking which may lead ultimately to the
failure of the insulator,
(3)
(4)
1.2
in the electrical power industry. All such materials can broadly be classified
into different categories:
composites [2,3].
Materials
Conductor
Gases
Insulator
Liquids
Organic
Solids
Polymer
Thermoplastic
Semiconductor
Vacuum
Composite
Inorganic
Thermosetting
Nylon
Polyethylene
Epoxy resins
Crosslinked
polyethylene
Polystyrene
Polypropylene
Phenolics
Urea
Formaldehyde
Polycarbonate
Polyvinyl
chloride
Melamine
Elastomers
The weather conditions in the Middle East including Saudi Arabia are
significantly harsh and changing from the daytime to the night. The inland
areas are very hot, dry and dusty. The ultraviolet (UV) radiation that causes
chemical changes on the composite insulators are extremely high in this
region. In order to select a proper material with satisfactory resistance to
weathering, it is necessary to understand weather factors and how they affect
the various materials. These conditions demand a more precise and systematic
research to optimize design criteria for deserts and dry areas of Arabian Gulf.
The aim of this study was to determine the degree of degradation and
decomposition of the Silicon Rubber (SiR) and Thermoplastic Elastometer
(TPE) insulators due to UV radiations and atmospheric heat that is common in
the central region of Saudi Arabia. In this regard, experimental investigations
were carried out to study the effect of ultraviolet radiations as well as heat, on
the performance of these two composite insulators.
Chapter two of this report contains a brief literature review and data
collection.
methods used, various important test results and the Saudi Arabian experience
on this subject. Chapter three of this report explains the experimental set up and
method, whereas Chapter four presents the main results and discussion. Chapter
five outlines the conclusions of this investigation.
CHAPTER 2
LITERATURE REVIEW AND DATA COLLECTION
2.1
INTRODUCTION
Polymeric insulators are being accepted increasingly for use in outdoor
2.2
applications consists of a core, weather sheds, and metal end fittings as shown in
Fig. (2.1).
10
11
12
13
14
employ a sheath made of insulating material between the weathersheds and the
core. This sheath is part of the housing.
2.2.4 End Fittings
End fitting transmit the mechanical load to the core. They are usually
made of metal.
2.3
INSULATOR TYPES
Three types of insulators are in common use i.e. the suspension/dead-end
type, line post insulators and Guy strain type insulator, as shown in Figs. (2.3)
and (2.4). The only significant differences among these are in the design of the
attachment hardware and in the size of the core, which is much larger for post
insulators.
Fig. (2.3): Dead End / Suspension type polymeric insulators (~15 kV).
15
16
17
(c)
years. They cover a wide range of materials and formulations. These include
bisphenol epoxy resins which were used commercially for indoor applications
in the mid 1940s. In the 1950s cycloaliphatic epoxy resins were used in the
United Kingdom (UK) in outdoor service due to their better performance.
They were used as suspension insulators up to 400 kV and in station circuit
breakers for up to 500 kV in the early 1960s [1].
18
This was
19
20
cycloaliphatic and aromatic epoxy resins. For low voltage, outdoor or indoor
applications, additionally high-density polyethylene (HDPE), polytetrafluoro
ethylene (PTFE), polyurethene (PUR), polyolefin elastomers and other
materials are also employed.
SiR was first produced in 1944.
polysiloxane is very long (the number of the units of the siloxane is given as
several thousands, the silicone fluid becomes viscous with a gum-like
consistency from which SiR is made by adding fillers and curing agents.
In the compounding of the weather-sheds, fillers are added to enhance
the resistance to tracking and erosion as well as to provide improved
mechanical performance in tensile strength, abrasion resistance, tear strength,
modulus and to reduce flammability.
21
2.5
These
include IEEE [14], IEC [15], CIGRE, American National Standards Institute
(ANSI) [16] and National Electric Manufacturers Association (NEMA) etc.
The IEC test [15] has been criticized as being more of a pollution test and not
being an aging test and therefore suggestions for improvements in the test
procedure were made [17], [18]. Most existing laboratory tests for accelerated
weathering are primarily useful for ranking of the compounded materials [71][79].
Only tests in field stations and actual performance on power lines and
in outdoor substations could yield realistic results on outdoor service
performance of such insulations.
In accelerated aging tests in the fog chambers the specimens are
subjected to a simultaneous salt-fog and electric stress. The leakage current,
the pulse current and the accumulated charge are determined during a
prolonged test which can last up to 1000h [15], using an automatic data
acquisition system [19]. Often NaCl is added to the tap water (250 to 300
S/cm) to obtain a much higher conductivity of 14.7 mS/cm (10 0.5 kg of
salt per m3 of water). However, micro-organisms are known to be present in
the tap water which may grow rapidly and form a jelly layer on the insulator.
22
The effect of
23
ultraviolet (UV) radiation on the aging was also included in that test. It was
found that the aging caused erosion and cracks were observed. The EPR
formulations generally performed better than the epoxy resins [24]. 72 kV and
230 kV composite rod insulators made of EPDM, EPM and HTV-SiR were
tested by aging with cement coating and clean fog, salt-fog and cement
coating and salt-fog. Substantial differences in the ability to withstand the
aging were found amongst the different insulator types [25].
It was concluded in [26] that the weather-shed design plays an
important role in the erosion and tracking of the insulator.
HTV-SiR
insulators, with 27.6 mm per kV leakage path, showed that dry band arcing did
not develop in the presence of severe salt storms while with 17.3 mm/kV,
large leakage currents developed. A large power utility reported that during a
severe weather condition there were no flashovers in any of their 138 kV (377
units) and 230 kV (1430 units) SiR insulators while there were many
flashovers in their 138 kV and 230 kV EPDM and porcelain insulators [27].
HV porcelain and glass outdoor insulators coated with RTV-SiR
performed better than silicone grease under dc test under salt-fog where dry
band arcing was present [28]. Other metals such as aluminum, stainless steel,
brass and copper were tried [29] but were found unsatisfactory because they
corroded which left corrosion by-products on the specimens surface.
Polymeric coatings of RTV-SiR on 66 kV systems were first used in 1973 [30]
and are now very widely used. Their purpose is to render a hydrophobic
24
coated with RTV-SiR had higher flashover voltages than uncoated porcelain
insulators when contamination was present on their surface in the range of
Equivalent Salt Deposit Density (ESDD) of 0.07 to 0.16 mg/cm2.
25
26
SiR the changes in these elements were not significant. On the surface of SiR
the content of ATH was reduced after 5 yr on the lines. Similar observations
were reported on SiR and EPDM insulators which had been energized at 300
kV. These results were independently confirmed using ESCA after tests in
salt-fog which also indicated a higher concentration of oxygen on the surface
than in the bulk of SiR [36]. It was suggested that this was due to the
crosslinking reactions of the silanols from dry band arcing. The oxidation of
the surface of EPDM and the EPDM/SiR alloy was evaluated by removing a
small amount of the polymer and analyzing it with Fourier Transform Infrared
(FTIR) and X-ray Photoelectric Spectroscopy (XPS) [37].
2.7
tests.
insulators performed well under severe contamination and usually better than
ceramic insulators [38], [39], [40] and [41]. The withstand voltage of SiR,
EPR and epoxy resin in the presence of pollution was higher than that of
porcelain. Some EPDM insulators (34 kV to 500 kV) performed poorly and
showed punctured holes and damaged sheds. EPR performed better than
epoxy resin [24].
combined salt-fog and cement, followed with 1 hour and longer (up to 6.5 h)
drying time, was significantly and consistently higher than that for EPM and
EPDM, and for EPM was higher than for EPDM [25].
27
decreased when tested with increasing steam input rate [43]. SiR had a higher
flashover voltage than EPR and porcelain. However, the difference between
SiR and EPR (and porcelain) was significantly reduced under heavier wetting
conditions [43].
Comparison between the naturally aged RTV-SiR coating on porcelain
and aged SiR insulators indicated that the former exhibited lower
hydrophobicity than the latter material [46]. It has been reported that RTVSiR coated porcelain long rod insulators had peak currents for both dc (+300
kV) and ac (130 kV phase-to-ground) energized insulators equivalent to those
of SiR insulators [46].
It was also shown that SiR insulators preserved their hydrophobicity
while EPDM became completely hydrophilic after 7 years in field tests and
energized to positive 300 kV [47]. SiR performed better than ceramic, and
EPDM performed worse than SiR. However, EPDM enhanced with Low
Molecular Weight (LMW) SiR additives showed good hydrophobicity and
low leakage current [47]. Porcelain insulators coated with RTV-SiR gave
28
29
1
2
3
4
EPDM (dc)
EPDM (ac and =dc)
SILICONE RUBBER (dc)
SILICONE RUBBER (ac and +dc)
Fig. (2.9): Cumulative charge in EPDM and HTV-SiR rods during exposure
to energized salt-fog showing the differences between ac (60 Hz),
+dc and dc. Conditions: conductivity of the saline water forming
the fog is 250 S/cm; electrical stress is 0.6 kV/cm [29].
30
2.9
The salt-fog
31
During hurricane strength winds, ESDD values of 0.1 to 0.2 and ESDD
in the range 0.061 to 0.159 mg/cm2 were measured on insulators [22].
Pollution layers of silica powder (SiO2), manganese dioxide (MnO2) and
kaolin were used on SiR and EPDM [52]. It took up to 5 days for the
hydrophobicity to recover for SiO2 and MnO2 and for kaolin did not recover
by 7 days [52].
In an industrial area near a steel plant, Fe2O3 (hematite) contamination
was found while CaSO4, SiO2 and CaSO4.0.5 H2O (bassanite) were found on
insulators in both agricultural and industrial areas [53].
The insoluble
contaminants were SiO2, Fe2O3, CaO, MgO, and K2O. The particle size of the
contaminants varied from 1 to 80 m. The average size of the particles was
~2x the size of that of Tonoko (62 m and powder density 2.76 g/cm3 [50])
which is used in the standard of insoluble contaminants in artificial
contamination tests. Natural industrial contaminants deposited on 110 kV SiR
insulators which were located near a copper producing plant included
insoluble substances (80 to 90%) of SiO2, Al2O3, Fe2O3 and metal sulfide.
The remainder constituted soluble sulfates (CuSO4) and soluble carbonates
(MgCO3) [54].
32
2.10
rather difficult to apply artificial contaminants and to ensure that they adhere
to the surface for the duration of the test. A method of application of artificial
contamination on SiR which was reported to provide a uniform contamination
layer was discussed in [55].
It employs powdered Tonoko [50] which is deposited after spraying the
surface with a fine mist of water droplets and allowing it to dry. Then the
deposited Tonoko is washed off with running tap water. The insulator is then
immersed in the slurry of contaminants and dried. This method was reported
to have been applied successfully to SiR and EPDM insulators [55].
Attempts have been made to coat polymeric insulators with a pollution
layer for testing purposes by first destroying the hydrophobic nature of the
surface by sand blasting or adding wetting agents. The usual procedure to coat
insulators is to contaminate the insulator with a slurry containing water and
NaCl and an insoluble material which is usually kaolin.
The insoluble
material content is typically 40 g/l [22]. The slurry is allowed to dry on the
insulator, before the test. This test represents service condition in which
subsequent wetting occurs of insulators which have already a layer of
contamination built-up on the surface.
33
2.11
service starts with the loss of hydrophobicity due to weathering and then dry
band arcing follows, and in the case of SiR, with a reduction of low molecular
weight (LMW) fluid on the surface. This leads to increased current, increased
surface roughness, depolymerization of the top surface layer, changes in the
structure due to crystallization of the polymer and clustering of the filler and
then tracking and/or erosion failure. X-ray diffraction studies indicated an
increase in the crystallinity of the SiR with aging in salt-fog and dry band
arcing [28].
The difference in the flashover voltage performance for the same
ESDD was attributed to the difference in the solubility of the contaminants.
The ambient temperature has a significant influence on the solubility of the
salts and therefore on the contamination flashover voltage. The solubility of
the salt depends on several factors, the most important of which are
temperature, pH (hydrogen potential) and the presence of strong ionic
components. In outdoor conditions near the coast, highly soluble salts such as
Ca(NO3)2, NaNO3, MgCl2, CaCl2, KC1, NaCl and poorly soluble salts such as
MgSO4, Na2SO4, Na2CO3, K2SO4, NaC1, CaCO3, CaSO4.2H2O, Ca(PO4)2 and
MgCO3 have been identified on insulators. The density of the deposits varied
from 0.003 to 0.168 mg/cm2 [32].
34
Shah et al. [49], [56] postulated that the flashover mechanism of SiR
was different from that of porcelain and glass insulators because the latter two
wet and accumulate contaminants differently.
heating due to leakage current, interaction between the water droplets and the
electric field, generation of conductive regions and filaments and spot
discharges caused by field intensification, which lead to flashover along the
wetted filaments.
Contamination severity in the range of ESDD of 0.03 to 0.6 mg/cm2
and the degree of wetting were treated as probabilistic variables in assessing
the flashover of insulators in [57].
Weight (%)
Virgin
Aged
Temperature (C)
Fig. (2.10): TGA of field aged HTV-SiR in the presence of oxygen [58].
A depolymerization was reported of HTV-SiR and RTV-SiR which had
been in service near the coast for 7 year, compared to virgin specimens [58].
35
36
2.12
37
This is
important because the shorter wavelength is more energetic and thus less
energy remains to cause damage to the surface of the polymer.
2.13
[14].
Insulators were
considered acceptable if the discharge did not exceed 3 pC and the initiation
voltage of corona was >17.5kV for the above insulators. The most effective
test method to detect flaws was reported to be the RIV [64].
38
insulators could be found by visible inspection from the towers and these
presented the largest percentage of failures. An inspection from the ground
using binoculars was not sufficient.
Electric field testing permitted the detection of non-visible defects
which had occurred at the interface between the fiberglass rod and the
covering polymeric material. It was reported that in the area of a defective
shed there was a decrease in the longitudinal field along the string [65]. Fig.
(2.11) shows the effect on the electric field along the insulator surface when a
defect is present in one of the sheds of an EPDM insulator.
16 cm
32 cm
none
antistatic 32 cm
Shed No.
Fig. (2.11):
39
2.14
RTV-SiR changed when artificial rain was applied to it [66]. The sensitivity
of the field distribution and the discharge activity to the precipitation rate of
the rain (0.4 and 1.6 mm/min) was small for conductivities of 50 and 250
S/cm at low voltage. At high conductivity of the rain and high precipitation
rate, higher fields at the upper sheds were observed [66].
In artificially contaminated SiR and EPR insulators, the phenomenon of
sudden flashover without a prior leakage current was investigated.
The
sudden flashover was attributed to the high electric field at the edges of the
dried high resistance regions. When sufficient recovery time was allowed,
SiR did not experience sudden flashover while EPR insulators did. It was
reported that in rain tests, hydrophobic surfaces prevent an increase in the dry
zones and significantly reduce the radial field strength.
2.15
40
Lower Molecular Weight (LMW) fluid from the bulk to the surface including
the contaminant layer.
This phenomenon was first suggested in 1981 [68]. After exposure of
SiR to corona it was found that the hydrophobicity was lost and on the surface
SiH decreased by 50% while OH increased by 500%. After the recovery of
hydrophobicity it was observed that SiH had increased again.
This was
41
and following dry band arcing and therefore during the recovery of
hydrophobicity were also reported in [70].
2.16
insulators that are in use by Saudi Electric Company (SEC), a survey was
conducted by these investigators. On this context a questionnaire as shown in
Annex-I was sent to all operating areas of Saudi Electricity Company working
in different parts of the Kingdom. Whereas, for getting the month-wise
environmental data (maximum and minimum temperatures, humidity level,
and average rainfall), another questionnaire (Annex-II) was sent to
Environmental Department of the Riyadh. The investigators received the
response only from the SEC-EOA region which is presented in Table (2.1).
SEC- Eastern Operating Area (EOA) power transmission grid extends
more than 11,000 circuit km covering an area of 285,000 sq. km. The
transmission lines operate at voltage levels of 69 kV, 115 kV, 230 kV and 380
kV, and most of these lines are close to coast of the Arabian Gulf [71]. The
lines are generally affected by desert, marine and industrial pollution. Weather
is characterized by high temperature, large daily and seasonal temperature
variations and high humidity levels through the summer months of June to
October. SEC-EOA applies different techniques such as adopting large
creepage distance, applying grease on some station insulators and using costly
42
Type
Manufacturer
Material of
Polymer
Insulator
No. of
Years in
Service
No. of
Failures
Reasons of
Failures
NA
NA
NA
NA
NA
NA
NGK
Sediver
McLean
Power
Silicone
Rubber
Introduced
in 1996
do
do
do
13.8
33
34.5
69
132
230
380
Suspension
One
Mishandling
mechani
cal
failure
Being introduced
43
44
45
CHAPTER 3
EXPERIMENTAL SETUP AND PROCEDURES
3.1
46
47
3.2
dry heat.
48
Heating (57C)
Radiation (1 mW/cm)
Voltage (28 kV)
Time (hours)
In Operation
2~8 AM 8 AM ~
2 PM
2~8
PM
8 PM ~
2 AM
Out of operation
3.3
[15] as discussed in sections 3.1 and 3.2, a wooden chamber was constructed
in our laboratory. The dimensions of the chamber are approximately 120cm
(wide) x 120cm (high) x l80cm (long). Up to 12 post insulators of 28 kVL-L, or
an equivalent number of suspension dead end insulators, can be subjected to
accelerated aging cycle in this chamber. Higher voltages are possible with
slight modifications in the chamber. A schematic diagram of the chamber is
shown in Fig. (3.2a) whereas photo of front view of the chamber with 28 kV
suspension insulators in place is shown in Fig. (3.2b). It is worth mentioning
that data was transferred from sensor's to the PC with the help of CASSY
laboratory software version 1.53 (Leybolds LD Didactic GMBH).
49
50
i)
i)
UV-A lamps
ii)
Polymeric insulator
iii)
Electric Heater
iv)
Timers
v)
Blower/fan
vi)
Power Transformer
vii)
UV light meter
polymers whereas UVB (315-280 nm) and UVC (100-280 nm) are found in
the outer space filtered by earth's atmosphere; germicidal. Because UVA
lamps do not have any UV output below the normal cut-off of 295 nm. The
UVA-340 lamps provide the best possible simulation of sunlight in the critical
short wave length region from 365 nm down to the solar cut-off of 295 nm.
Its peak emission is at 340 nm.
In the chamber, the ultraviolet (UV-A) radiation system duplicates
exposure in the portion of the solar spectrum (300340 nm) that is responsible
for aging of noncernmic insulators UV-A lamps. The spectrum produced by
these lamps as compared with that of sunlight and UVA-351 * UVB-313, is
shown in Fig. (3.3) where the solar and lamp cutoff wavelength may be seen.
51
52
Fig. (3.4b): Dead End/ Suspension polymeric insulator (EPDM and TPE).
Table (3.1) shows the salient dimensions of both of the tested
insulators.
53
Unit
SiR
TPE
kVL.L.
28
28
mm
433
438
mm
290
285
Leakage Distance
mm
590
675
Dry
kV
135
130
Wet
kV
105
114
kV
225
211
Voltage class
Power Frequency
Flashover
Impulse flashover
iii)
Power Supply
90 kV, 5 kVA, HV testing transformer is used for energizing the
insulators to the required voltage stress. To reduce the corona and for good
cooling the transformer was placed in an insulating oil bath as shown in Fig.
(3.5a).
(3.5b).
54
CB
Test
Insulator
220 V, ac
CB
220 V / 100 kV
Heating Arrangement
Since temperature affects the aging of polymeric materials, heat is the
most important stress since the aging rate is accelerated by some factor for
each degree rise in temperature [80]. A 2000W tubular heater is used to
develop heat. A PC based ON-OFF control system is used to maintain a
relatively stable temperature in the chamber. The heat generated by the heater
is uniformly distributed by an axial blower installed inside the chamber. In the
central region of Saudi Arabia, the maximum daytime temperature which
remains almost stable from 1 PM to 4 PM varies during summer months in a
range of 42 ~ 50C, with around 46C being the average value. This situation
lasts for six months (May ~ October). To simulate this temperature profile,
the thermostat was set at a temperature of 57C. This 57C is selected such
that the average ambient temperature is 46C + around 11C is temperature
rise on the insulator surface (under no load conditions) as measured on the
insulator surface placed outdoors at the King Saud University HV Laboratory.
55
This 11C is also considered to play role in accelerated aging process. Fig.
(3.6) shows the actual variations of temperature on the porcelain and polymer
insulators surfaces as well as the UV-A radiation level in Riyadh.
60
60
50
50
40
40
Amb. Temp
30
30
Temprature (C)
10
10
Months
56
60
55
Temperature (C)
50
Ambient Temp
45
Temp fall (when
heater OFF)
40
35
30
25
20
15
0
10
20
30
40
50
60
70
80
90
Time (min)
Timers
To control the time dependent cycles of aging, the heat and UVA
radiation are applied to the tested insulators in a cyclic manner. Each heater
and UVA lamps are put ON & OFF after every 6 hours. The control of heater
and UVA lamps is automatically achieved by the electric timers type TH-30A
(Kawamura, Japan). The photograph of timer is shown in Fig. (3.8).
57
72
CHAPTER 5
CONCLUSIONS AND RECOMMENDATIONS
CONCLUSIONS
1.
73
The SEM analysis revealed that SiR based insulators experience much
higher surface roughness due to aging whereas negligible surface
roughness was observed in case of aged TPE insulators. Similarly the
XPS analysis exhibit much higher decomposition of SiR material than
TPE polymer.
3.
5.2
58
CHAPTER 4
RESULTS AND DISCUSSIONS
After completion of the accelerated aging test of the SiR and TPE
composite insulators, as per modified IEC 1109 procedure as discussed in
Chapter 3 of this report, various electrical, SEM based optical and visual tests
were performed and the results are summarized and discussed next.
4.1
aged as well as the control (new) insulator samples of each type (SiR and
TPE) were subjected to impulse voltage applications. The impulse generator
was adjusted to produce standard Lightning Impulse (LI) waveforms
(1.2/50s) of both positive and negative polarities.
positive lightning impulse voltage wave whereas the schematic diagram of this
test set up is shown in Fig. (4.2). The voltage was increased in small steps of
1.0 kV till a flashover occurred at a critical level. This procedure was repeated
3 to 5 times and an average value of tests on 3 units in case of aged and 1 unit
in case of unaged sample was registered for the purpose of comparison.
59
Test
Insulator
60
Insilator (Aged)
Insulator (New)
250
200
150
100
50
0
+LI (SiR)
-LI (SiR)
+LI (TPE)
-LI (TPE)
power transformer. Circuit diagram for the test arrangement is shown in Fig.
(4.4). Artificial rain was used as per IEC-383 [87] and adjusted to meet IEC60-1 [86] requirements for the resistivity and rain intensity (precipitation) for
both horizontal and vertical components of the insulators. The water resistivity
was adjusted to 105-m while the rain fall rate was kept 1.5 mm/min.
61
62
140
Insulator (aged)
Insulator (New)
135
130
125
120
115
110
105
100
Dry (SiR)
Wet (SiR)
Dry (TPE)
Wet (TPE)
end of each insulator and their surface analysis was performed using type
JEOL JSM-6360-A (Japan) Scanning Electron Microscope (SEM). The
analyses were made in high vacuum mode in order to avoid sample charging.
Secondary Electron Imaging (SEI) was performed to study the surface
morphology at an accelerating voltage of 20kV.
SEM photographs were captured for analyzing surface condition for
both SiR and TPE insulators at magnifications of 1000 and 2000. To
compare the two surfaces (aged and new), the probing depth of the electron
63
beam in both types of the electron beam in both types of materials was kept at
5 m. Fig. (4.6) shows SEM results of new and 1000 hours laboratory aged
samples. The overall visual observation is that there is no major degradation,
such as cracking, however, it can be seen that these micrographs have different
microstructures. The unaged (new) samples have a smooth, more homogenous
and less porous surface while the surface roughness and porosity increases
with aging as shown in Fig. (4.6 b&d) for aged SiR and aged TPE insulators,
respectively. Moreover, it may be pointed out that surface roughness of an
aged sample of SiR is more than compared with that of the TPE. This surface
roughness has resulted due to localized degradation of SiR.
4.4
HYDROPHOBICITY
Hydrophobicity or water repellency is an expression of the fundamental
64
Fig. (4.6): SEM micrographs for new and the aged samples of SiR and TPE
insulators.
65
Hydrophobicity test was carried out for new and artificially aged
insulators and the results were compared with STRI guide for hydrophobicity
classes (HC) [82]. It was found that the hydrophobicity lies between HC =
1&2, which means that the effect of ageing is negligible for both types of
tested insulators. However, the hydrophobicity of aged SiR is poorer than that
of TPE insulators.
The electrical impulse tests, power frequency tests, SEM results and
hydrophobicity results indicate that aging cycle deteriorates the SiR, whereas
the TPE insulator surface shows just minor effect due to accelerated aging.
4.5
were performed using JEOL-JSM-6360 (A) SEM and the results obtained are
described next.
XPS technique was used to obtain qualitative as well as quantitative
information on the surface composition of samples. The XPS spectrum recorded
for both new and aged samples of SiR and TPE are shown in Figs. (4.7) and
(4.8) respectively. These spectrum identify all the major elements such as
oxygen, carbon, silicon, aluminum, etc. in the investigated samples.
66
Figs. (4.7) and (4.8) show the peaks from the photoionization of oxygen
(O15) and carbon (C15) at 525 eV and 277 eV, respectively. It is also evident
from these spectrums that % share of carbon and oxygen has rapidly increased
from 17.97% and 34.06% to 20.13% and 45.81% respectively in case of SiR
(Fig. 4.7) and from 45.31% and 34.58% to 47.29% and 39.30%, respectively in
case of TPE (Fig. 4.8), due to exposure to UV-radiation and heat. The increase
of C could be from the scission of CH3 bonds and the formation of various
products due to reaction between C and O2 during oxidation.
In these samples, the presence of oxygen detected by XPS both in SiR
and TPE on the new and aged surfaces is attributed to the availability of oxygen
from the additives or from the moisture in the atmosphere or due to oxidation of
the rubber during manufacturing [85]. Peaks of Al are also observed in all
samples as shown in Figs. (4.7) and (4.8). Slight traces of Ti were observed in
case of TPE (new) as shown in Fig. (4.8a) which disappeared due to aging where
instead some traces of Vanadium were detected. This could be due to additives
or any other decomposition process in the material during aging process.
67
68
69
SiR
Elements
TPE
New
Aged
New
Aged
C (0.277 keV)
17.97
20.13
45.31
47.29
O (0.525 keV)
34.06
45.81
34.58
39.30
Al (1.486 keV)
21.69
17.95
17.29
13.08
Si (1.739 keV)
26.28
16.11
--
--
Ti (4.508 keV)
--
--
2.88
--
V (4.949 keV)
--
--
--
0.33
70
(1)
R + O2 ROO
(2)
ROO + RH ROOH + R
(3)
Heat or Light
ROOH RO + OH
(4)
(5)
RO + RH ROH + R
(6)
HO + RH ROH + R
(7)
71
74
REFERENCES
[1]
[2]
[3]
[4]
[5]
[6]
75
[7]
[8]
[9]
[10]
E.A. Cherney, G. Karady, W.T. Starr, F.J. Hall, G.E. Lusk, H. Dietz, L.
Pargamin and T. Moleff, "Minimum Test Requirements for NonCeramic Insulators", IEEE Trans. on PAS, Vol. 100, pp. 882-890,
1981.
[11]
[12]
76
[13]
[14]
IEEE Std. 1133-1988, "IEEE Application Guide for Evaluation NonCeramic Materials for HV Outdoor Applications", 1988.
[15]
[16]
[17]
[18]
[19]
77
[20]
[21]
P.J. Lambeth and H.M. Schneider, "Clean Fog Test for HVAC
Insulators", IEEE Trans. on PWRD, Vol. 2, pp. 1317-1326, 1987.
[22]
[23]
[24]
[25]
78
[26]
[27]
[28]
[29]
[30]
79
[31]
[32]
[33]
S.H. Kim, E.A. Cherney and R. Hackman, "The Loss and Recovery of
Hydrophobicity of RTV Silicone Rubber Insulator Coating", IEEE
Trans. on PWRD, Vol. 5, pp. 1491-1499, 1990.
[34]
[35]
[36]
[37]
80
[38]
[39]
[40]
H.M. Schneider, W.W. Guidi, J.T. Burnham, R.S. Gorur and J.F. Hall,
"Accelerated Aging and Flashover Tests on 138 kV Non-Ceramic Line
Post Insulators", IEEE Trans. on PWRD, Vol. 8, pp. 325-336, 1993.
[41]
R.S. Gorur G.G. Karady, A. Jagota, M. Shah and A.M. Yates, "Aging
in Silicone Rubber Used for Outdoor Insulation", IEEE Trans. on
PWRD, Vol. 7, pp. 525-538, 1992.
[42]
[43]
A. De La O, R.S. Gorur and J. Chang, "AC Clean Fog Tests on NonCeramic Insulating Materials and a Comparison with Porcelain", IEEE
Trans. on PWRD, Vol. 9, pp. 2000-2007, 1994.
[44]
81
[45]
[46]
[47]
[48]
[49]
[50]
82
[51]
[52]
[53]
[54]
[55]
[56]
83
[57]
[58]
[59]
[60]
[61]
[62]
84
[63]
[64]
[65]
[66]
[67]
85
Aging in Fog Chamber", IEEE Trans. on PWRD, Vol. 3, pp. 11571164, 1988.
[68]
C.L. Lee and G.R. Homan, "Silicone Elastomer Protective Coatings for
HV Insulators", IEEE CEIDP, pp. 435-441, 1981.
[69]
[70]
[71]
[72]
[73]
86
[74]
[75]
[76]
H.M. Schneider, W.W. Guidi, G.W. Nicoholls, J.T. Burnham, J.F. Hall,
"Accelerated Aging Chamber for Non-Ceramic Insulators", 7th ISH, pp.
199-202, 1991.
[77]
[78]
[79]
87
[80]
[81]
[82]
[83]
[84]
[85]
R. Sundarajan, E. Sundarajan, A. Mohammad and J. Grames, "Multistress Accelerated Aging of Polymer Housed Surge Arresters Under
Simulated Coastal Florida Conditions", IEEE Trans. on DEI, Vol. 13,
No. 1, pp. 211-228.
[86]
IEC Standard 60-1, "High Voltage Test Techniques", 2nd Ed. 1989.
[87]
88
Annex I
89
90
Annex II
91
I: Polymeric Insulators
Voltage Class
Type *
Material of
Manufacturer
the polymer
/ Supplier
insulator
No. of years
in service
No. of failures
occurred
Reasons of
failure
13.8 kV
33 / 34.5 kV
* Dead end type /
Suspension type /
Line post /
Guy strain Insulator
II.
III.
Any investigative studies carried out internally by SEC on the performance and pollution related problems of polymer insulators in
use?
Feb.
March
April
May
June
July
Aug.
Sept.
Oct.
Nov.
Dec.