MinimumSmokeLayerDepthinAtriumSmokeControl
Withoutasufficientminimumsmokelayerdepth,buildingoccupantscanbe
exposedtodangeroussmokeduringafire
ByJOHNH.KLOTE,DSC,PE,Consultant,Leesburg,Va.
SHARE

Tweet

Recommend

Mar1,2009
0

COMMENTS 1

Manysmokecontroldesignersdonotknowthereisaminimumsmokelayerdepthfor
atriumsmokecontrolsystems.Section4.4.1.1ofNFPA92B,StandardforSmoke
ManagementSystemsinMalls,Atria,andLargeSpaces,requiresthattheminimum
designdepthofasmokelayerbe20percentofthefloortoceilingheight,unlessan
engineeringanalysisisperformed.This20percentrequirementsignificantlylimitswhat
architectsandownerscandowithanatrium.Inthisarticle,thetermatriumisusedin
http://hpac.com/firesmoke/minimumsmokelayeratrium0309

1/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

agenericsensetomeananylargevolumespace,includingstadiums,arenas,and
airplanehangars.
Itshouldsurprisenoonethatthe20percentrequirementisnotpopularwitharchitects
andowners.Afewyearsago,Imetaseniorengineerwhoerroneouslythoughtanatrium
smokecontrolsystemcouldbedesignedforanysmokelayerdepthhewanted,evenas
littleas1in.Washeeverwrong!Thesmokelayerthatformsunderaceilinghasa
minimumdepthforreasonsdiscussedlaterinthisarticle.Designsthatdonotallowthe
20percentmentionedpreviouslymayresultinexposingbuildingoccupantstosmokeina
firesituation.

LatestWhitePapers
WHITE

OCT30,2015

PAPER

DiamondControls
SolutionsEmpowering
InnovativeBuilding
Management
WHITE

MAR19,2014

PAPER

TheminimumsmokelayerdepthrequirementsofNFPA92Bapplytoalmostallplacesin
theUnitedStatesbecausethestandardhasbeenadoptedbytheInternationalBuilding
Code(IBC).AbookpublishedbytheInternationalCodeCouncil(ICC)1presents
discussionsofIBCsmokecontrolrequirementsandextensiveengineeringinformationto
meetthoserequirements.Regardlessofthecodes,ifthesmokelayerisnotofsufficient
depth,occupantscanbeexposedtosmokeduringfiresituations.

EvolvingEnergy
Efficiency
Regulationsfor
HVACR

TheDecember2008issueofHPACEngineeringincludedanarticle(StateoftheArt
AtriumSmokeControl)thatprovidedanoverviewofsmokecontroltechnology,
includingbasicconcepts,smokestratification,makeupair,plugholing,andminimum
smokelayerdepth.2Minimumsmokelayerdepth,includingthereasonforthe20
percentrequirement,engineeringanalyses,anddesignapproaches,isexplainedin
greaterdetailinthisarticle.
WHY20PERCENT?

Asmokeplumerisesaboveafire.Whentheplumereachestheceiling,smokeflowsaway
fromthepointofimpactinaradialdirection,formingaceilingjet.Whentheceilingjet
reachesawall,thesmokeflowgoesaroundandundertheceilingjet(Figure1).The
ceilingjethasadepthofabout10percentofthefloortoceilingheight,asdoesthesmoke
flowundertheceilingjet.Thismeansthesmokelayerdepthisabout20percentofthe
http://hpac.com/firesmoke/minimumsmokelayeratrium0309

Webinars
SEP15,2015
2/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

floortoceilingheight.Thesmokemaydescendlowerthanthisminimumsmokelayer
depth.Designsneedtohavesufficientroomforthesmokelayertoform.

WEBINAR

ANewEraof
Efficiency:Advances
inWaterSourceVRF
Technology
AUG11,2015
WEBINAR

ImprovingHVAC
EnergyEfficiency
ThroughAccurate
Humidity
Measurement
FIGURE1:Formationoftheminimumsmokelayer.

JUL22,2015
WEBINAR

Duringthe1970s,fundamentalresearchaboutceilingjetswasconductedbyRonAlpert

HowtoGettheMost
OutofYourBuilding
AutomationSystem
withService

ofFactoryMutual.3,4Basedonhisresearch,Alpertdevelopedcorrelationsforthe
thickness,temperature,andvelocityofceilingjets.Thesevariablesarefunctionsofthe
heightoftheceilingaboveafireandtheradialdistancefromtheaxisofthesmoke
plume.Inmostsituations,the10and20percentvaluesmentionedpreviouslyare
conservativelylarge.Foradetailedtreatmentofceilingjets,includingAlpert'sresearch,
seeChapter2ofSection2oftheSFPEHandbook.5Whileanengineeringanalysiscould
relyonthesecorrelations,thereareadvantagestousingcomputationalfluiddynamics
(CFD).
ENGINEERINGANALYSIS

Anengineeringanalysisofminimumsmokelayerdepthcanbeperformedwithdatafrom
fullscalefiretests,scalemodeling,orCFDanalysis.Fullscaleandscalemodeltestsare
relativelyexpensive,whichexplainswhytheyarenotusedoftenforthiskindofanalysis.
Becausezonefiremodels,suchasConsolidatedModelofFireGrowthandSmoke
Transport(CFAST),6arewellknownandeasytouse,someengineersmaybetemptedto
trytouseonetoanalyzeminimumsmokelayerdepth,butzonemodelsareinappropriate

ViewAll

Blogs&Opinions
Blogs

Columns

FundingHVACREnergyEfficiency
ResearchandDevelopment
byLawrence(Larry)Clark,
QCxP,GGP,LEEDAP+
Posted6daysago
inClark'sRemarks

GivingThanks
http://hpac.com/firesmoke/minimumsmokelayeratrium0309

3/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

forthisapplication.

byLawrence(Larry)Clark,
QCxP,GGP,LEEDAP+
Posted2weeksago
inClark'sRemarks

AcceleratingEnergyProductivity
byLawrence(Larry)Clark,
QCxP,GGP,LEEDAP+
Posted4weeksago
FIGURE2:Atriumsmokeflow.

inClark'sRemarks

Inaroomoranatriumwithafire,smokerisesandformsasmokelayeraspreviously
described,andthereisagradualtransitionbetweenthesmokelayerandtheairbelow
(Figure2[a]).Zonefiremodelsconsiderthesmokelayertohaveuniformproperties
throughout.Inzonefiremodeling,thebottomofthesmokelayerisconsideredtobea
horizontalplane,sothatat0.01in.abovethisplane,theconcentrationofcontaminantsis
thesameaseverywhereelseinthesmokelayer(Figure2[b]).Whilezonefiremodelsare
usefulformanyapplications,theyroutinelypredictsmokelayersofunrealisticallysmall
depthintheearlystagesoffiredevelopment.Forthisreason,zonefiremodelsmustnot
beusedtoanalyzeminimumsmokelayerdepth.
Page2of2
TheideaofCFDmodelingistodividethespaceofinterestintoalargenumberofcells
anduseacomputerprogramtosolvethegoverningequationsforeachcell.IfthatCFD
modelingisdoneproperly,itcansimulateatriumsmokeflowinrealisticdetail,including
smokelayerformation.Idealforanalysisofaminimumsmokelayer,CFDmodelingalso
cansimulateatransitionzone,whichisimportantfortenabilitydesigns,whichare
discussedlater.CFDmodelingrequiresalevelofspecializedknowledgeforproperuse,
andaCFDsimulationcantakemanyhours,evendays,asdiscussedinpastarticlesin
HPACEngineering.2,7
http://hpac.com/firesmoke/minimumsmokelayeratrium0309

4/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

TheNationalInstituteofStandardsandTechnology(NIST)hasdevelopedaCFDmodel
specificallyforfireapplications:FireDynamicsSimulator(FDS).8Traditionally,CFD
modelsareexpensive,buttheFDSmodel,includingdocumentation,canbedownloaded
freeofchargefromwww.fire.nist.gov/fds.
DESIGNAPPROACHES

TheIBCrequiresthatthebottomofasmokelayerbeatleast6ftabovethehighest
walkingsurfacethatformsaportionoftherequiredmeansofegressinanatrium.This
meansthatabovethehighestrequiredmeansofegressinanatrium,6ftplusspaceforat
leasttheminimumsmokelayershouldbeavailable.Ifthismuchspaceisnotavailable,
otherapproachescanbeused:separationofthetopfloor(s),thedesignofadummytop
floor,minimizationoffoldback,and/ordesigningfortenability.Engineersarecautioned
thatalternateapproachesneedtobebasedonappropriateengineeringanalyses.
Separationoftopfloor(s)

Thetopfloor(s)ofanatriumcanbeseparatedfromtherestofthebuildingtomeetthe
minimumsmokelayerdepthrequirement.Thisseparationcanbedonewithglasssothe
occupantscanseeintotheatrium,buttherequiredmeansofegressonthetoplevel(s)are
notinsidethelargeopenspaceoftheatrium.Whilethisapproachmaybeunpopular
witharchitects,itmaybetheonlypracticalwaytoprovidetheessentialspaceforthe
formationofasmokelayer.

Signuptoreceiveourfreenewsletters
HPACEngineeringFastrack
(BiWeekly)ViewSample
HPACEngineeringGreenBuildings
(Monthly)ViewSample
FireProtectionEngineeringEmerging
Trends(Monthly)ViewSample
ProductSpotlight(Monthly)View
Sample
EMAIL*
COUNTRY*

UnitedStates

Enteryouremailabovetoreceivemessagesabout
offeringsbyPenton,itsbrands,affiliatesand/orthird
partypartners,consistentwithPentonsPrivacyPolicy.

Designofadummytopfloor

Someatriaaredesignedwithadummytopfloorthatoccupantscannotaccess.Theonly
peoplewhohaveaccesstothedummytopflooraremaintenancepeople.Becausethese
fewpeopleareveryfamiliarwiththebuilding,theycanleavethedummyfloorquicklyin
theeventofafire.Therefore,thecodecanbeinterpretedtomeanthatthewalkwayson
thesefloorsarenotpartoftherequiredmeansofegress.Assuch,thesmokelayercan
includethedummyfloor.Ifthisapproachisdesired,localcodeofficialsshouldbe
contactedearlyintheprojecttoseeiftheyconcurwiththiscodeinterpretation.
http://hpac.com/firesmoke/minimumsmokelayeratrium0309

ConnectWithUs

TwitterFacebook
LinkedIn
RSS

5/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

Minimizationoffoldback

FIGURE3:Foralong,narrowatrium,foldbackcanbeminimized
byexhaustingfrombothends.

Asstatedpreviously,whenaceilingjetreachesawall,itfoldsunderitself,formingthe
minimumsmokelayer.Forlong,narrowatria,thisfoldbackcanbeminimizedby
exhaustingsmokefromsmokereservoirslocatedattheends(Figure3).Theregenerally
arenoacceptedalgebraicequationsforanalysisofthisapproach,anditissuggestedthat
CFDmodelingbeused.Minimumsmokelayerdepthinthiscaseisabout10percentof
thefloortoceilingheight,butaproperlydoneCFDanalysiscanprovidemoreaccurate
information.Also,thesmokecontrolsystemcanbecomeatenabilitydesign.
Designingfortenability

Alloftheapproachesmentionedarebasedontheideathatoccupantsneedtobekept
awayfromsmoke,butanotherapproachistodesignsystemsthatprovideatenable
environmentforoccupantsduringevacuation,eventhoughtheremaybesomecontact
withdilutedsmoke.NFPA92Brecognizessuchtenabilitydesigns.Section909.1ofthe
IBCstatesthatsmokecontrolsystemsareintendedtoprovideatenableenvironmentfor
occupantevacuationorrelocation.Tenabilitydesignsareanalternativeapproachto
prescriptivecoderequirements,andlocalcodeofficialsshouldbenotifiedearlyina
projectthatanalternativeapproachmaybeused.
Atenabilitydesignneedstobebasedonsmoketransportandtenabilityanalyses.CFD
http://hpac.com/firesmoke/minimumsmokelayeratrium0309

6/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

modelinghasthepotentialtorealisticallysimulatesmoketransportandisrecommended
forsmoketransportanalysis.Thesmokelayerhasrelativelyhighconcentrationsof
contaminantsneartheceilingandlowerconcentrationsinthetransitionzone.Many
tenabilitydesignstakeadvantageofthelowerconcentrationsnearthebottomofthe
smokelayer.AproperlyconductedCFDanalysiscansimulatetheformationofasmoke
layer,includingthetransitionzonebetweenthesmokelayerandtheairbelow.
InadditiontoCFDsimulationsofsmoketransport,atenabilitydesignneedstoincludea
tenabilityanalysisthatevaluatestheeffectofexposuretoheat,toxicgases,andreduced
visibility.Tenabilityanalysisistoolargeatopictodealwithinthisarticle,butistreatedin
PrinciplesofSmokeManagement.9
Arealisticanalysisofdesignfiresisessential,andinformationaboutdesignfireanalysisis
providedinvarioussources.1,5,9,10Adesignfireprovidesresultsintheheatreleaserateof
firesandthematerial(s)burned.Ifanatriumisdesignedtohavealmostnomaterialsthat
canburn,adesignfirestillneedstoaccountfortransientfuels,whichareitemsthatmay
beintheatriumforashortperiodoftime.Examplesoftransientfuelsincludetrash
waitingtoberemoved,paintingsolvents,constructionmaterialsduringarenovation,and
newitemsawaitingmovement.
SUMMARY

Manyatriumsmokecontroldesignersdonotknowthereisaminimumsmokelayer
depthforatriumsmokecontrolsystems.InmostplacesintheUnitedStates,thecodes
requirethatsmokelayerdepthbeatleast20percentofthefloortoceilingheight,unless
thereisanengineeringanalysis.Whilethisrequirementisnotpopularwitharchitectsand
owners,itisbasedonacceptedresearchresults.Ifasmokelayerisnotofsufficientdepth,
occupantscanbeexposedtosmokeduringfiresituations.
Engineeringanalysisofthisminimumlayercanbedonebycomparisonwithdatafrom
fullscalefiretestsorbyscalemodeling,butthecommonmethodisbyCFDmodeling.A
properlyconductedCFDanalysiscansimulatetheformationofasmokelayerinrealistic
http://hpac.com/firesmoke/minimumsmokelayeratrium0309

7/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

detail.Suchananalysisrequiresalevelofexpertise.Fordesignsforwhich20percent
spaceisnotavailableatthetopofanatrium,anumberofapproachescanbeused.
REFERENCES
1. Klote,J.H.,&Evans,D.H.(2007).Aguidetosmokecontrolinthe2006IBC.

CountryClubHills,IL:InternationalCodeCouncil.
2. Klote,J.H.(2008,December).Stateoftheartofatriumsmokecontrol.HPAC

Engineering,pp.3640.
3. Alpert,R.L.(1972).Calculationofresponsetimeofceilingmountedfiredetectors.

FireTechnology,8,181195.
4. Alpert,R.L.(1975).Turbulentceilingjetinducedbylargescalefires.Combustion

ScienceandTechnology,11,197213.
5. SFPE.(2002).TheSFPEhandbookoffireprotectionengineering(3rded.).

Bethesda,MD:SocietyofFireProtectionEngineers.
6. Peacock,R.D.,etal.(2005).CFASTConsolidatedModelofFireGrowthand

SmokeTransport(version6)user'sguide.Gaithersburg,MD:NationalInstituteof
StandardsandTechnology.
7. Klote,J.H.(2006June).CFD:Anewwaytodesignatriumsmokecontrol.HPAC

Engineering,pp.1927.
8. McGrattan,K.,etal.(2008).FireDynamicsSimulator(version5)User'sguide.

Gaithersburg,MD:NationalInstituteofStandardsandTechnology.
9. Klote,J.H.,&Milke,J.A.(2002).Principlesofsmokemanagement.Atlanta:

AmericanSocietyofHeating,RefrigeratingandAirConditioningEngineers.
10. Klote,J.H.(2002,September).Designfires:Whatyouneedtoknow.HPAC
http://hpac.com/firesmoke/minimumsmokelayeratrium0309

8/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

Engineering,pp.4351.
AsmokecontrolconsultantandmemberofHPACEngineering'sEditorialAdvisory
Board,JohnH.Klote,DSc,PE,developedandconductsaseriesofsmokecontrol
seminarsfortheSocietyofFireProtectionEngineers.For19years,heconductedfire
researchfortheNationalInstituteofStandardsandTechnology.Heisacoauthorof
thebooksAGuidetoSmokeControlinthe2006IBCandPrinciplesofSmoke
Management.

SHARE

DiscussthisArticle

Tweet

Recommend

onFeb14,2015

Protech

InanopenstadiumwithsprinklersintheconcourseoverheadasrequiredbyNFPAupto50ft
ceilingheight,the20%smokereservoircreatesatemperaturesinkinsummertempsabove
100degF.Theheightoftheceilingrequireslowtemperaturesprinklersthatarenotallowper
NFPA13withceilingsthatcanreach100degF.Thetwoindependentmeansofsmoke
mitigationisprovidedbysprinklerdecayandbyventilationdilution.Whatisthesolutionwe
canthavebothperNFPA.
reply

POSTINGAS:

abco

(SignOut)
YOURCOMMENT:*

http://hpac.com/firesmoke/minimumsmokelayeratrium0309

9/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

SUBMITCOMMENT

Newsletter Signup
Signuptoreceiveourfreenewsletters
HPACEngineeringFastrack(BiWeekly)ViewSample
EMAIL*
COUNTRY*

UnitedStates

EnteryouremailabovetoreceivemessagesaboutofferingsbyPenton,itsbrands,affiliatesand/orthirdpartypartners,
consistentwithPentonsPrivacyPolicy.

Related Articles
StateoftheArtAtriumSmokeControl
ASHRAELaunchesOnlineDiscussionForum
ASHRAESeekingPapersfor2015WinterConferenceinChicago
SeattleAreaYoungEngineersinASHRAEPlanningSeriesofFreeEvents
MeettheHPACEngineeringEditorialAdvisoryBoard

http://hpac.com/firesmoke/minimumsmokelayeratrium0309

10/11

12/14/2015

MinimumSmokeLayerDepthinAtriumSmokeControl

HPAC.com
AirConditioning BuildingControls Fire/Smoke Heating HumidityControl IAQ&Ventilation Motors/Drives Piping/Pumping

Site Features

HPAC Engineering Corporate

MediaCenter

PrivacyPolicy

RSS

TermsofService

Sitemap

Contact

SiteArchive

Follow Us

Newsletters

Search HPAC.com

ViewMobileSite

Mechanical Systems Sites


ContractingBusiness Contractor HVACTalk Comfortech2013Show HVACRDistributionBusiness RadiantLiving
FireProtectionEngineering

Copyright2015Penton

http://hpac.com/firesmoke/minimumsmokelayeratrium0309

11/11

Das könnte Ihnen auch gefallen