Beruflich Dokumente
Kultur Dokumente
Temperature Transducer
Pt100, Cu10 and Resistance
Page 1/4
August 2008
Characteristics
Electronic transducer for mounting in panels or machines.
This transducer is properly designed for conversion of voltage or
ohmic resistance into a direct voltage or current signal. It can be
used also for temperature measuring by means of two-wire or three
wire thermocouples and thermo resistances.
The input signal is converted in a proportional, aligned or not
aligned output signal, which is independent of the load.
Galvanic isolation between input and output signals.
Sensor break protection device.
The output signal is compatible for connection of various
instruments, such as: analogical or digital indicators, graph records,
controllers, analogical digital converters and others.
Application
Industrial ovens
Engines
Heat treatment
Transformers
TAP position
When the sensor break, the output will be saturated in end of scale
(standard version).
Optional: Saturation in the beginning of scale.
Influence magnitudes
Error limit
Reference
conditions
Input
Ohmic resistance
Two-wire or three-wire thermo resistance
Teletransmitter with potentiometer
Current sensor
Pt100: 1mA.
Cu: 5mA.
Resistance; according field
Input:
0,5% (standard),
0,25% (optional)
0100%
Auxiliary power
supply:
Uax 2%
Ambient temperature:
Heat time:
25C 2K
20 min.
Linearity deviation
Temperature
Auxiliary
power supply
(Uax)
Output:
Universal.
85 265Vac / 90 300Vdc
consumption ~ 4VA.
2060Vac/Vdc
consumption ~ 4VA.
0 1mA RC 10 k
0 5mA RC 2 k
0 10mA RC 1k
0 20mA RC 500
4 20mA RC 500
0 10V RC 500
1 5V RC 500
0,2%
(included in error limit)
0,2%/10 K;
rated temperature 25C
(Optional 0,1%/10K for Pt100)
0,05% within the permitted
tolerance range for the supply
voltage
0,5% for field intensity of
0,4 kA/m
0,5% between 27460MHz
at a distance of 1 m power 1 W
Electrical test
Voltage test
ETT-15
Temperature Transducer
Pt100, Cu10 and Resistance
Page 2/4
August 2008
Input Signal
Housing
Fastening
Electrical
connection
Protection class
(NBR 6146)
IP 50 in housing
IP 20 at the connection terminals
Weight
0,3 kg
Climatic conditions
Operation temperature
Functioning temperature
Transport and storage temp.
Relative humidity
-20...+60C
-25...+70C
-40...+80C
75% of annual average with
light condensation.
(others on consult)
Mechanical test
Impact
Vibration
Connection three-wire
Dimensional Drawing
Dimension in mm
Output Signal
ETT-15
Temperature Transducer
Pt100, Cu10 and Resistance
Additional Information
Cautions
Mounting Instructions
Temperature
Sensor
Transformer
ETT-15
Indicators
Graph Records
Controllers
PLCs
Remotes
ETT-15
Temperature Transducer
Pt100, Cu10 and Resistance
Page 4/4
August 2008
Ordering information
Catalog number
TRANSDUCER ETT-15 Case
Input Signal
Thermoresistance Pt100 (temperature range to be informed)
between 200+850C.
Measuring Resistance 10 ohm10Kohm
Thermoresistance Cu10 (0-150C, or 0-180C or 0-200C)
Auxiliary power supply
2060 Vca/cc
85265Vac e 90300Vdc
Output Signal
01mAcc
05mAcc
010mAcc
020mAcc
420mAcc
010Vcc
Others (01mAcc up to 20mAcc and 01Vcc up to
015Vcc)
Option
Class 0,25% ( only for Pt100 and resistance)
Normal (Error limit 0,5%)
Additional Information
Complement (Inform temperature range)
Normal
Example:
Transducer ETT15 Case
Input signal:
Auxiliary power supply:
Output Signal:
Option:
Additional Information:
01
02
03
12
13
1
2
3
4
5
7
0
1
5
C
1