DATA SHEET - N00325

Temperature Transducer
Pt100, Cu10 and Resistance

Page 1/4
August 2008

Characteristics
Electronic transducer for mounting in panels or machines.
This transducer is properly designed for conversion of voltage or
ohmic resistance into a direct voltage or current signal. It can be
used also for temperature measuring by means of two-wire or three
wire thermocouples and thermo resistances.
The input signal is converted in a proportional, aligned or not
aligned output signal, which is independent of the load.
Galvanic isolation between input and output signals.
Sensor break protection device.
The output signal is compatible for connection of various
instruments, such as: analogical or digital indicators, graph records,
controllers, analogical digital converters and others.

Sensor break protection device:

Application
Industrial ovens
Engines
Heat treatment
Transformers
TAP position

When the sensor break, the output will be saturated in end of scale
(standard version).
Optional: Saturation in the beginning of scale.

Technical data (NBR 8145)

Influence magnitudes
Error limit

Reference
conditions

Input
Ohmic resistance
Two-wire or three-wire thermo resistance
Teletransmitter with potentiometer
Current sensor

Pt100: 1mA.
Cu: 5mA.
Resistance; according field

Input:

0,5% (standard),
0,25% (optional)
0100%

Auxiliary power
supply:

Uax 2%

Ambient temperature:
Heat time:

25C 2K
20 min.

Linearity deviation
Temperature

Auxiliary
power supply
(Uax)

Output:

Universal.
85 265Vac / 90 300Vdc
consumption ~ 4VA.
2060Vac/Vdc
consumption ~ 4VA.

0 1mA RC 10 k
0 5mA RC 2 k
0 10mA RC 1k
0 20mA RC 500
4 20mA RC 500
0 10V RC 500
1 5V RC 500

Auxiliary power supply


External magnetic fields
Radio frequency
interference

0,2%
(included in error limit)
0,2%/10 K;
rated temperature 25C
(Optional 0,1%/10K for Pt100)
0,05% within the permitted
tolerance range for the supply
voltage
0,5% for field intensity of
0,4 kA/m
0,5% between 27460MHz
at a distance of 1 m power 1 W

Electrical test
Voltage test

Uax. 85V : 2,5kV/1 min ; 60Hz


(for all circuits mutually).
Uax. 60V: 1,5kV/1 min ; 60Hz
(for all circuits mutually).

ETT-15

DATA SHEET - N00325

Temperature Transducer
Pt100, Cu10 and Resistance

Page 2/4
August 2008

Construction and mounting

Input Signal

Housing
Fastening

The sensor input signal is done by 51,52,53 and 54 born.

Electrical
connection

Base and cover of plastic.


Surface mounting with two screws M4, or
using DIN rail
Frontal terminals for eye and fork type
cable shoes.

Protection class
(NBR 6146)

IP 50 in housing
IP 20 at the connection terminals

Weight

0,3 kg

Connection two-wire Wire resistance.

Terminals 51,52 Place a compensation resistance with ohmic value


equal to the line resistance value.
Terminals 53,54 sensor.

Climatic conditions
Operation temperature
Functioning temperature
Transport and storage temp.
Relative humidity

-20...+60C
-25...+70C
-40...+80C
75% of annual average with
light condensation.
(others on consult)

Mechanical test
Impact
Vibration

Connection three-wire

Terminals 51,53 sensor common point,


Terminal 54 other common point.
Obs.: The 3 wires should have the same line resistance.

Acceleration 30g, during 11ms


Acceleration 2g, frequency 5..150Hz

Dimensional Drawing

Dimension in mm

Output Signal

Terminals 61 (+) e 62 (-)

Auxiliary power supply


Terminals 13 e 14.

ETT-15

Temperature Transducer
Pt100, Cu10 and Resistance

Additional Information

DATA SHEET - N00325


Page 3/4
August 2008

Example for measuring the transformer temperature:

The following items contain tips and cautions to be observed by the


user for a good functional performance, as well as the maintenance
of the instrument and the safety of the installation.

Cautions

Be sure the voltages and currents to be connected to the instrument


are compatible.
Loosen all connections from the instrument before removing it from
the installation.

Mounting Instructions

Observe the environment temperature range. At the place of


installation, values for vibration, dust, dirt and humidity, which
must remain between the limits, established by the protection class
of the housing and the climatic group, specified in this data sheet,
have to be observed.
For fastening on flat area use two M4 screws. For mounting on DIN
rail, use the snap-in device on the rear of the instrument.
The connections can be made with eye or fork type cable shoes

Temperature
Sensor

Instructions for Use


When connections have been made, switch on the power supply
and check at the output the functioning of the transducer.

Transformer

ETT-15

Indicators
Graph Records
Controllers
PLCs
Remotes

ETT-15

DATA SHEET - N00325

Temperature Transducer
Pt100, Cu10 and Resistance

Page 4/4
August 2008

Ordering information
Catalog number
TRANSDUCER ETT-15 Case

Input Signal
Thermoresistance Pt100 (temperature range to be informed)
between 200+850C.
Measuring Resistance 10 ohm10Kohm
Thermoresistance Cu10 (0-150C, or 0-180C or 0-200C)
Auxiliary power supply
2060 Vca/cc
85265Vac e 90300Vdc
Output Signal
01mAcc
05mAcc
010mAcc
020mAcc
420mAcc
010Vcc
Others (01mAcc up to 20mAcc and 01Vcc up to
015Vcc)
Option
Class 0,25% ( only for Pt100 and resistance)
Normal (Error limit 0,5%)
Additional Information
Complement (Inform temperature range)
Normal

Example:
Transducer ETT15 Case
Input signal:
Auxiliary power supply:
Output Signal:
Option:
Additional Information:

Thermoresistance Pt100 0-100C


85265Vca e 90300Vcc
420mAcc
Class 0,25%
Normal

Code number: N003250113511

ABB Ltda - ATLV/IE Instrumentation Electrical


Avenue Dos Autonomistas, 1496 - 06020-902 - Osasco - SP
Tel: +55 11 3688-8320 / 8323 / 8347 - Fax: +55 11 3688-8322