Sie sind auf Seite 1von 6

Type Testing a 2000 MW Turbogenerator

K. Sedlazeck
C. Richter
S. Strack

S. Lindholm
J. Pipkin
F. Fu
B. Humphries
L. Montgomery

Siemens Energy
Mlheim, Germany

Siemens Energy
Orlando, FL USA

Abstract Type tests completed in August 2008 have validated all


electrical and mechanical design parameters of the 1992 MVA 4pole, 1500 RPM turbogenerator that Teollisuuden Voima Oy is
now installing in the Olkiluoto 3 nuclear power station. Olkiluoto
3 is the first European Pressurized Reactor (EPR) power station.
In response to TVOs requirement that the generator capability
be at least 10% above the 1992 MVA nameplate rating, Siemens
Energy designed the generator so that its capability is above 2222
MVA (2000 MW, 0.90 power factor). Besides being designed to
have this high capability, the generator is also designed to be very
efficient (tested generator efficiency is nearly 99% at the 1992
MVA nameplate rating), and it is designed to exhibit very low
mechanical vibration levels. In this paper the authors report the
following highlights of the electrical and mechanical
characteristics that were observed during recent type tests:
Confirmation of expected steady state MVA capability
Confirmation of expected dynamic stability parameters
Confirmation of expected acceptable mechanical vibration
Index Terms turbogenerator, nuclear power station,
hydrogen cooling, water cooling, type testing, MVA capability,
efficiency, vibration, stability parameters

I.

INTRODUCTION

The first EPR turbogenerator with its brushless exciter is


shown fully assembled on the test field in Figure 1 at the
conclusion of a 3 week type test that was completed in August
2008. A few days after this photograph was taken, the
generator was disassembled and shipped to the Olkiluoto 3
power station, where it is now being installed on the turbine
deck.
In this paper the authors outline design features that have
been previously described in more detail in References 2 and 3,
and we also describe the main electrical and mechanical
characteristics that were observed during the recent type test.
Successfully completing the type test of this 2000 MW
turbogenerator marks a major milestone in a journey that began
nearly 40 years ago with the initiation of nuclear
turbogenerator designs in this rating class. Some discussions
of the work of those earlier days are recorded in Reference 1.

Figure 1 - Olkiluoto 3 turbogenerator with its brushless exciter at the conclusion of the type test

978-1-4244-4252-2/09/$25.00 2009 IEEE

465

MAIN PERFORMANCE ATTRIBUTES

II.

Main performance attributes are summarized in Table 1


below.
TABLE 1 - ATTRIBUTES OF EPR TURBOGENERATOR

Applied Standard

IEC 60034

Class of Insulation

Class 155, with Class 130


temperatures

Apparent Power

2222 MVA

Power Factor

0.90

Frequency and Speed

50 Hz, 25 sec-1

Rated Voltage

27 kV

Rated Current

47.5 kA (50 kA at 95% voltage)

Excitation

Brushless Exciter

Figure 3 Axial flow hydrogen-cooled rotor winding and water-cooled


stator winding in EPR turbogenerator

III. MAIN DESIGN FEATURES


IV.

Evolutionary design: As discussed in References 2 and 3,


the 2222 MVA EPR turbogenerator design is based on the
1500-1700 MVA Siemens Konvoi turbogenerators that have
operated with high reliability and availability for decades in
nuclear power stations (see Ref 1). To meet requirements
specified for the EPR generator, well proven features from
other Siemens generators have been incorporated.

TYPE TEST OVERVIEW

The 3 week type test included the following activities:


Mechanical runs at rated speed (1500 rpm)
Balance and vibration (in air)
Ventilation test (in air)
Friction and windage losses (in hydrogen)
Steady-state short circuit tests
Short circuit heat runs with collector set
Short circuit losses and saturation curve
Short circuit heat runs with brushless exciter

Generator Cooling: As illustrated in Figures 2 and 3, this


hydrogen-cooled generator is equipped with an all watercooled stator winding. The rotor winding is axially hydrogencooled. The stator core is primarily axially hydrogen-cooled,
with radial ducts at each end for supplemental cooling.
Hydrogen is circulated with one multi-stage, axial flow blower
located at the turbine end of the generator, between two
vertical coolers.

Steady state open circuit tests


Open circuit heat runs at 27 kV
Open circuit saturation curve and core losses
Voltage wave shape analysis
Rotor moment of inertia (retardation test)
Sudden short circuit tests (with brushless exciter)
Accomplishing this extensive test program in only 3 weeks
was facilitated by the fact that all activities were controlled and
monitored by experienced test field personnel working in a
state of the art control room overlooking the test field. As
shown in Figure 4, throughout the test program key members
of the design team joined the test field colleagues in this
control room to compare test results with pre-calculated values
for key parameters (e.g. temperatures, reactances, vibration
levels) as those parameters were being measured.

Figure 2 - General assembly of EPR turbogenerator

Figure 5 shows the generator with the test field collector


set, and Figure 6 shows the generator with its brushless exciter.

466

Figure 7 - Summary of test results for steady state thermal capability

Details of the winding temperatures are described in


Figures 8 and 9. As shown in Figures 7 and 8, temperatures in
the rotor winding are well below IEC and IEEE Class 130
limits.

Figure 4 - Control room of test field

Figure 5 - EPR generator and test field collector set on the test field at the
beginning of the test program

Figure 8 - Temperatures in rotor winding of EPR turbogenerator

As shown in Figures 7 and 9, stator winding temperatures


are well below limits for water-cooled stator windings.

Figure 6 - EPR generator and its brushless exciter on the test field at the
end of the test program

V.

TEST CONFIRMATION OF THERMAL CAPABILITY

As outlined in Figure 7, tested generator winding


temperatures were well below IEC 60034-1 and IEEE C50.13
Class 130 limits. As can also be seen in this figure, tested
temperatures closely matched calculated temperatures.

467

Figure 9 - Stator winding temperatures in EPR turbogenerator

As shown in Figures 7, 8 and 9, from the point of view of


IEC Class 130 thermal limits for the windings, the tested
capability exceeds the target maximum apparent power, 2222
MVA, by over 20%.
All additionally measured temperatures (e.g. core, frame,
bearing brackets, terminal box) were lower than calculated and
lower than any temperatures that would prove injurious to
generator components during operation of the generator at the
design target maximum apparent power, 2222 MVA.
One of the major design challenges to achieving this 2222
MVA rating is in the design of the terminals. As noted in
Figure 7, at this rating, the terminal current approaches 50 kA.
Indeed, the numbers recorded in Table 1 in Section II of this
paper show that at the lower extreme of the 5% voltage range
specified in IEC and IEEE standards the required terminal
current slightly exceeds 50 kA. Designing the terminals
needed for so high a current was a major challenge in
developing the EPR turbogenerator design. Confirming the
proper functioning of these conductors was an important
objective of the type test. Results from the short circuit factory
tests at 40kA (refer to Figure 7) revealed that temperatures of
outlet water leaving the high voltage bushings would be less
than 60oC when the generator current reaches 50KA. This
temperature is well below the 90oC limit specified by IEC and
IEEE standards.

Figure 11 Dodecagon flexible connector assemblies between main leads


and bushings

A very important step in validating the design of the 50 kA


terminals of the EPR generator was to verify the effectiveness
of thermal conduction cooling of the braided copper flexible
conductors which are used to electrically connect the 6 water
cooled main leads to the 6 water cooled bushings. These
connector assemblies, shown in Figures 10 and 11, are used to
facilitate connecting the bushings to the main leads during
assembly of the terminal box to the generator frame in the
power station. They also serve to isolate bushing vibration
from main lead vibration. Cooling of these flexible conductors
is by thermal conduction to the water-cooled bushings and
main leads to which the flexible conductors are bolted.

Because each assembly of 12 flexible connectors must


carry 50kA, and because cooling is by thermal conduction to
adjacent water-cooled components, even distribution of current
among the flexible connectors is important. Designing this
assembly for even distribution of the connector currents around
the circle of conductors shown in Figure 11 included three
dimensional electromagnetic finite element analyses. As
shown in Figures 10 and 11, the 6 connector assemblies are
much larger than a depth of penetration, and the 6 assemblies
are close to each other. Consequent electromagnetic coupling
induces uneven current distribution. By working with 3D FEA
models (and by experimentally confirming these models by
favorable comparisons of calculations with tests on a smaller
generator with similar flexible connector assemblies) the
design team achieved a calculated 5% variation among the 12
flexible conductors. As reported in Reference 4, observations
made with Rogowski coils wrapped around each connector
during the type tests showed good agreement between
calculations and tests. Comparing calculated distributions of
currents in the flexible connectors (the 12 white bars in Figure
12) with results from two separate tests (the blue and red bars.)
shows this good agreement and confirms the 5% variation
design goal.

Figure 10 - Terminals of EPR turbogenerator, showing 6 main leads, 6


flexible connector assemblies and 6 bushings

Figure 12 - Comparison of tested and calculated current distributions in


flexible connector assemblies between main leads and bushings

468

Validating calculated magnetic saturation and calculated


synchronous reactances was an important aspect of the test
program. As shown in Figures 13 and 14, the tested saturation
curves closely matched the curves calculated by finite element
analysis (FEA) of the generator electromagnetic performance.

VI.

CONFIRMATION OF DYNAMIC CHARACTERISTICS

As shown in Figures 15 and 16, all tested reactances were


within the calculated min/max range, thus validating grid
stability studies completed with reactances calculated during
the development of this generator design.

SGen5-4000W for Olkiluoto 3


Open Circuit Saturation Curve

SGen5-4000W Generator
Unsaturated Reactances

Reactances P.U. at 1992 MVA

40

line to line voltage [kV]

35
30
25
20
Rated Voltage
Calculated by FEA
Test Points

15
10
5
0
0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

test unsat
2.5

1.5
1.0
0.5
0.0

xd

SGen5-4000W for Olkiluoto 3


Short Circuit Saturation Curve

Reactances P.U. at 1992 MVA

stator phase current [kA]

45
40
35
30
25
20
Rated Current
Calculated
Test Points
Test Based If(rated current)

0
0.0

0.2

0.4

0.6

0.8

1.0

xd

SGen5-4000W Generator
Saturated Reactances

50

xd

Figure 15 Calculated and tested unsaturated reactances

Figure 13 - Calculated and tested open circuit saturation curves

10

calc unsat min

2.0

field current normalized by


27 kV open circuit field current

15

calc unsat max

3.0

1.2

field current normalized by


42.6 kA short circuit field current

3.5
3.0

calc sat max


test sat

2.5

calc sat min

2.0
1.5
1.0
0.5
0.0

xd

xd

xd

Figure 16 Calculated and tested saturated reactances

Figure 14 - Calculated and tested short circuit saturation curves

469

VII.

TEST CONFIRMATION OF ACCEPTABLE VIBRATION

During the type test the stator was extensively instrumented


with vibration sensors. These sensors included fiberoptic
vibration sensors on the high voltage windings, piezoelectric
sensors on the core and frame and bearing brackets, and
standard sensors to measure rotor shaft vibration. All sensors
were monitored and recorded with computer data acquisition
systems that provided both real time output for immediate
inspection by the engineers monitoring the test and also orderly
storage of the data for post processing. As shown in Figure 17,
all tested stator and rotor vibrations were less than specified
limits. The Rigi-Flex stator winding vibration levels were
quite low, less than 60% of allowable levels. Nearly all
vibration levels were less than 80% of specified limits.

VIII.

CONCLUSIONS

Results from the August 2008 type test of the 2222 MVA,
2000 MW turbogenerator designed and manufactured for the
first EPR nuclear power station showed excellent agreement
between design values and tested values of the generator
parameters. All results met or exceeded requirements set by
Siemens and by IEC standards.
Successfully completing the type test of this 2000 MW
turbogenerator has marked a major milestone in a journey that
began over 40 years ago with the initiation of nuclear
turbogenerator designs in the rating class above 1200 MW.
All people who conducted and supported this type test, all
people who contributed to the previous years of development
of the generator design, and all people who contributed to
manufacturing the generator have good reason to be pleased
with the excellent results after this years-long and very difficult
work.

Figure 17 - Summary of vibration test results

In regard to the fact shown in Figure 17 that vibration of


the rotor shaft approached its permissible limit, two points are
REFERENCES
important to note. First, the shaft vibration limit for the
Olkiluoto 3 generator rotor was specified to be very low, about [1] A. Abolins, H. Achenbach, D. Lambrecht, Design and
performance of large four-pole turbogenerators with semi75% of previously acceptable limits. Second, the bearing
conductor excitation for nuclear power stations, CIGRE
bracket and rotor shaft vibration levels reflect the nature of the
Report 11-04, 1972 Session
foundation support for the generator in the test field. As can
be seen in Figures 1, 5 and 6, in the test field the generator was
supported on steel parallels that were nearly 2m tall. Because [2] K. Sedlazeck, W. Adelmann, H. Bailly, I. Gahbler, H.
Harders, U.Kainka, U. Schuberth, H. Spiess, R. Chianese,
that support is different from (and less stiff than) the support
P. Hugh Sam, R. Ward, L. Montgomery, Influence of
that is to be provided by the power station foundation, the
customers specifications upon design features of the EPR
generator rotor was balanced only to the extent needed to get
turbogenerator, CIGR Report 11-106, 2002 Session.
vibration levels to be acceptable for the type test. When the
generator is installed in the power station and connected to the
steam turbines, rotor balance can be refined further and the [3] R. Gray, R. Nelson, L. Montgomery, J. Pipkin, S. JokiKorpella, F. Caguiat, Designing the worlds most
rotor shaft and bearing bracket vibrations can be reduced
powerful turbogenerator Olkiluoto Unit 3, Conference
further below the limits specified for Olkiluoto 3.
Paper no. 0167, IEEE PES, Montreal, 2006
All generator vibration levels observed during the test were
below specified limits, and it is anticipated that generator [4] K. Sedlazeck, L. Montgomery, Generators > 1200 MW,
Giga-Watt Generation Panel Session, CIGR Group A1
vibration levels in the power plant will be less than observed
(Rotating Electrical Machines), 2008 Session
during the factory test.

470

Das könnte Ihnen auch gefallen