Sie sind auf Seite 1von 20

n° 164

current
transformers
for HV protection

Michel Orlhac

Graduated from the Ecole Centrale


de Paris in 1977.
After one year's specialisation at the
university of Stuttgart (Germany), he
entered the overseas projects
department of Stein Heurtey (iron
and steel engineering). In 1980 he
joined Merlin Gerin, becoming part
of the technical section of the High
Voltage Prefabricated Switchgear
Department (P.S.H.T.) where he
completed a study on current
transformers. This Cahier Technique
publishes the results of this study.
At present he is the marketing
manager for France-Transfo, a
subsidiary of the Merlin Gerin
Group.

E/CT 164 first issued, march 1995


Cahier Technique Merlin Gerin n° 164 / p.2
current transformers Current transformers or CTs take up a
lot of space in HV cubicles. Thorough
for HV protection knowledge of how they work makes it
possible to:
c reduce their dimensions and thus
their cost,
c use standard CTs in a larger number
of configurations.
content The purpose of this study is to learn
more about CT operation in association
with protection relays and to lay down a
few rules for sizing them properly.
1. Theoretical review p. 4 After a brief theoretical review of CT
operation and current protection
Hysteresis - Saturation p. 5
devices, the behaviour of the CT-
Characterisation of CTs p. 6 protection relay combination is studied
2. General current protection Current transformers p. 7 in two particularly important cases
information Functional CTs p. 8 in HV:
Protection relays p. 8 c overcurrent relay supplied by a
heavily saturated CT,
Technological evolution p. 8
c protection relay connected to two
3. Response of a CT in saturated state Experiments - Wiring p. 9 CTs in parallel in duplex cubicles.
Testing with symmetrical p. 10 This study is completed by
constant currents experimental results.
Testing with asymmetrical p. 11
currents
Conclusions on CTs delivering p. 12
on an overcurrent relay
4. Parallel cubicle operation p. 14
5. General conclusions p. 16
Appendix: CT standards NF C 42-502 (Norme Française) p. 17
IEC 185 p. 19

Cahier Technique Merlin Gerin n° 164 / p.3


1. theoretical review

Current transformers consist of a di 2


magnetic circuit in toroid form. The e 2 = v 2 + R 2 i2 + l 2
dt i1
primary is made up of n1 turns or simply dϕ dϕ
a single conductor crossing the toroid e 1 = n1 and e 2 = − n 2
dt dt
(n1 = 1). The secondary is wound in n2 If all the functions described are →
regular turns around this toroid (see dI n
sinusoidal of pulsation ω, the following
fig. 1 and 2). can be written vectorially:
Ampere's theorem states that the sum → → →

of the ampere-turns is equal to the V1 = E1 + (R1 + jl1 ω ) I 1


→ → →
circulation of the magnetic field vector. E2 = V2 + R2 I 2
→ → → → → →
n1 i1 + n2 i2 = ∫ H n dI E1 = jn1 ω Φ E2 = − jn2 ω Φ

Toroid →
H = magnetic field I1 → →
→ + I2 = Ie i2
n = tangent unit vector n
A transformer is said to be perfect The wiring diagram in figure 3 and
when equations (1) result in the vectorial fig. 1.
→ →
representation in figure 4.

∫ Toroid
H n dI = 0 The exciting current I e is broken down
→ →
on the axes Φ and E into:
In the real transformer, this term refers → → →
to the error introduced by the magnetic I e = Ia + Im i1

circuit and defines the exciting current c where I a represents the part of this
ie formed at the secondary by: current lost in the magnetic circuit (iron
n1 i1 + n 2 i 2 = n 2 i e losses due to hysteresis and eddy
n2 currents).
If n = is the winding ratio, the →
n1 c and I m is the magnetising current
relationship is written as: which transfers power from one winding
i1 to the other by creation of a i2
+ i2 = ie magnetomotive force which induces the
n →
flux Φ . fig. 2.
The transformer can then be
represented (see fig. 3) as having two
parallel elements:
c a perfect transformer of ratio n
delivering a current i1/n at the
secondary, l1 l2
i1 R1 i1/ n R2 i2
c an impedance which consumes a
current ie.
Moreover, each winding, both primary ie
and secondary, creates a slight voltage n = n 2/ n 1
drop due to the resistance of the
winding (R1 and R2) and to the leakage
e1 n2 n1 e2
inductances ( l 1 and l 2 ). Since, in the V1 V2 Z
case of the CT, the secondary winding im ia
is tight and regular, l 2 need not be perfect transformer
considered.
If ϕ is the flux common to both
windings, the following can be written
between the emf e1, e2 and the
real transformer
difference in potential v1, v2:
di1 fig. 3: CT schematic diagram.
v 1 = e 1 + R 1 i1 + l 1
dt

Cahier Technique Merlin Gerin n° 164 / p.4


hysteresis - saturation
Magnetic circuit quality is defined by l 1 ω I1 I1 «order of creation»
the relationship it imposes between the of values:
induction vector B and the magnetic R1 I1 I1, V1 I1, Ie
field vector H.
At a given moment and in a fixed point, V1 E1
these two vectors are linked by the
I 1/ n
relative permeability of the magnetic
ϕ1
material µr such that: E1
→ →
B = µ o µr H →
B
A magnetic circuit is thus characterised →
Im Φ
by the curve b = f (h) known as the
magnetising curve. α Ia Φ
Ie
According to the different material →
types, the curves in figure 5 are H
obtained, the results of sinusoidal ϕ2
I2
excitation (primary current). E2
V2
In sinusoidal state, b represents voltage
since: E2

→ Φ→
B= n
S V2 I2
→ →
E2 = n2 jω Φ R2 I2
l 2 ω I2
→ → N.B.: the real proportions, between the representative vectors of primary and secondary
V ≈ E2 values, are not repected.
h represents the exciting current since fig. 4: vectorial representation of a CT.
→ →
n2 Ie = ∫ H n dI
Toroid

assuming that hypotheses: magnetising curves ie and B as a function of time


b B, ie
→→
H n = H = constant
n 2 Ie = L H perfect
transformer
h t
Perfect transformer
Permeability of the medium is assumed
infinite

→ → → I1 linear
H = 0 hence I e = 0 and I 2 = transformer
n h t
This hypothesis approaches the real
situation with CTs since they normally
«work» far below saturation. I2 is then
saturable trans-
the mirror image of I1. former without
Linear transformer hysteresis h t
Permeability of the medium is constant
B = Cste x H hence ie and i2 are
sinusoidal functions. saturable
Saturable transformer without transformer
with hysteresis h t
hysteresis
Saturation is the sudden variation of µr
from a high value to a low value at the exciting current: ie
induction B
point known as the «saturation bend».
Induction b then increases only slowly fig. 5: magnetising curves and their incidence on ie.
and ie deforms to form a peak.

Cahier Technique Merlin Gerin n° 164 / p.5


Saturable transformer with c for measurement CTs Bear in mind that the less the CT is
hysteresis The module error loaded (the more it is below its accuracy
The magnetising curve is undoubled, I / n − I2 level power Y), the greater its accuracy.
thus indicating the resistance of the εM = 1 Its real accuracy level is therefore
I1 / n
magnetic circuit to the induction greater than its rated accuracy level Fp.
The phase error
variations. Curve ie then exhibits a This point is developed in chapter 3.
−2
characteristic «swing». ε ϕ = (I1, I2 ) 10 rd Admissible short term current
The magnetising curve of a CT can An accuracy class X is given (generally Expressed in kA it is the maximum
easily be observed using an 0.5 or 1) which expresses limit values current admissible Ith for one second
oscilloscope. A sinusoidal voltage V2 (t) of the module error εM and of the phase (the secondary being short-circuited). It
is applied to the secondary (the primary shift error εϕ as a function of the load represents CT thermal overcurrent
is not charged). The current ie (t) ratio N: withstand.
absorbed then represents the exciting (standard values are given in the
I
current and is proportional to the N = 1 (N var ies from 0.1 to 1. 2) standards in the appendix).
I1n
For times other than 1 second, the heat
magnetic field vector H. for N = 1 εM = X (in class 0.5 for I1 = I1n,
conservation law I2 t = cste can be
Integration of voltage V2 represents the εM = 0.5 %) applied:
flux ϕ2 which is proportional to the (for value details refer to the standards
→ for t < 1 sec. the calculation gives I > Ith,
magnetic induction vector B (see in the appendix).
thus increasing electrodynamic forces.
fig. 6a). c for protection CTs However, the limit guaranteed value is
Integration of a sinusoidal value causes The composite error εc Idyn = 2.5 Ith.
a rotation of π/2 (90°). It is thus 2
1 1 T i1 
∫o
sufficient on an oscilloscope: εc =  i2 − n  dt
c to sweep with ie, I1 / n T  
c to apply voltage V2 to the vertical Protection CTs are characterised by
amplifier. V2(t)
3 symbols: Y, P, Fp:
The magnetising curve of the material Y = error rate (5 or 10),
is thus obtained (see fig. 6b). P = protection,
Fp = accuracy limit factor which gives ie(t)
characterisation of CTs the limit values of errors εM, εϕ and εc
as a function of the load ratio N.
CTs are characterised in practice by
the following values (according to For N = Fp
standards NF C 42-502 and IEC 185).
εc = Y
(in class 10P5 for I1 = 5 l1n: εc = 10 %) a - scales: ie = 0.25 A per square
CT voltage
(for value details, refer to the standards V2 = 50 V per square.
This is the operating voltage applied to
in the appendix).
the CT primary. Note that the primary is
at the HV potential level and that one of For a CT working at a rated induction ϕ 2 = ∫ V2 dt (or B)
Bn, a saturation coefficient Ks such that:
the terminals of the secondary (which
must never be opened) is normally Bs
earthed. Ks =
Bn
Just as for all equipment, a maximum
where Bs is the saturation induction
1 min withstand voltage at standard
characterising the core material.
frequency and a maximum impulse
In practice K s ≈ Fp and they are often ie (or H)
withstand voltage are defined (refer to
treated as the same in calculations.
the standards in the appendix).
e.g. for a rated voltage of 24 kV, the CT Accuracy level power
must withstand 50 kV for 1 mn at 50 Hz Expressed in VA, it indicates the power
and 125 kV impulse voltage. that the secondary can supply while
respecting the rated accuracy class Y,
Rated winding ratio P, Fp.
Normally takes the form: l1/l2. 2 I a = constant
It represents the total consumption of
I2 is very generally 5 A or 1 A (for rated the secondary circuit (except for CT), b - scales: ie = 0.25 A per square
values of I1, refer to the standards in i.e. the power consumed by all the ϕ2 = 0.077 V.s per square.
the appendix). connected devices as well as the
fig. 6 : oscillographic reading of curves i(t)
Rated accuracy class connecting wires. V2(t) and h(b) of a CT, 50/5, 15 VA, 10P20
This depends on whether the CT is used (for rated values, refer to the standards where: V2 = 83 V and le = 0.26 A.
for measurement or protection: in the appendix).

Cahier Technique Merlin Gerin n° 164 / p.6


2. general current protection information

Protection devices have many functions


since they have to:
c protect equipment from destruction or
damage as a result of faults (short-
circuit, overload...),
c ensure normal operation of the
installation and its equipment (control,
load shedding...),
c guarantee safety of personnel.

current transformers CT with cross primary Wound type CT with Wound type CT with
winding (cable) wound primary wound primary
Since relays cannot be connected 1 secondary - 600/1 winding winding
directly onto the MV network, the 1 secondary - 200/5 2 secondaries - 200/5 and 100/5
information they receive comes from
fig.7: different types of CTs.
current transformers or CTs (see fig. 7)
and from voltage transformers or VTs.
When primary current is high, the CTs
are of the cross bar type, and when it is from part of the network to be
low they are of the wound primary type. monitored (a motor, a transformer, a
CTs have a number of roles to play in busbar...) to quickly detect and isolate relay
electrical networks: any faults inside that part. I2 = I1/m
c supplying at their secondary a current Zero sequence protection
exactly mirroring the one flowing in the This monitors the zero sequence I1
HV conductor concerned, component Io of the three-phase
c providing galvanic insulation between current which appears during phase- fig. 8.
the HV and the measuring and earth faults. There are two possible
protection circuits, configurations:
c protecting the measuring and c a toroid transformer encircling the I1 I'1
protection circuits from damage when a three phase conductors (if possible).
fault occurs on the HV network. This configuration (see fig. 10a) I'1 - I1
Using this current image in the HV enables detection of small zero
relay
conductor, the relay generates in turn a sequence currents (1 to 100 A).
tripping order according to the type of c three CTs achieving in the neutral
protection it provides and the values at connection of their secondary the sum
fig. 9.
which it has been preset [threshold(s), of the three phase currents. This
time delay(s)....]. configuration (see fig. 10b) is the only
This order is transmitted to one or more one possible for large and numerous
cables or busbar ducts. It is not a)
breaking devices (circuit-breaker,
contactor, switch). recommended when the zero sequence
CT configurations vary according to the current to be detected is 5% less than
type of protection to be provided. ln (or even 12% for consumer
substations according to standard
Overcurrent protection (see fig. 8) NF C 13-100 (French Standard)). Io
relay
This directly uses the «current»
information supplied at the CT secondary
to detect short-circuit or overload functional CTs b)
currents or calculate the thermal status of In HV cubicles, the «current
a machine. Note that this configuration transformer» function takes on a new
type must also contain the protection dimension as a result of its content and
devices using in addition to VTs: shape.
c directional overcurrent protection, Thus:
c power protection (active or reactive). c a number of CTs can be moulded in Io
Earth leakage protection (see fig. 9) the same enclosure: one core for the relay
This measures the current difference measurement function, one core for the
between two CTs, one connected protection function and sometimes even fig. 10.
downstream and the other upstream a third core for earth leakage protection,

Cahier Technique Merlin Gerin n° 164 / p.7


c the enclosure is used to ensure c replace relays (automation) in the
insulation between two compartments cubicle,
and plugging-in of the breaking device: c provide operators with measurement
the CT is then said to be «functional». of electrical parameters.
An application example is given in the These units, with their increased
metalclad cubicles for withdrawable vocation, are:
switchgear (see fig. 11 and 12). c flexible (protections are chosen
Overall dimensions are thus reduced by simply by programming),
using one insulating enclosure (the most c parameterisable (large choice of
appropriate), thus also reducing costs. settings),
c reliable (they are fitted with self-
monitoring or with watchdog and
the protection relays self-test),
The equipment currently available is c economic (reduced wiring and
based on the three technologies: implementation time).
electromechanical, analog and digital.
Their digital communication and
The oldest of these is powerful algorithms also enable
electromechanical technology: relays additional functions such as logic
are simple and specialised (current, discrimination to be performed. fig. 11: functional CT for HV metalclad
voltage, frequency, ... monitoring) but This communication capacity means cubicles (Merlin Gerin).
their accuracy is poor as their settings that genuine network operation (similar
may be altered over time. to technical management of industrial
The last two technologies benefit from installations) is now possible.
the advantages provided by electronics Finally, their ability to acquire and
(see fig. 13): process the information provided by
c compact dimensions of the device, sensors allows them to make full use of
c low power required for acquisition of the performances of the new non-
«current» information (a few fractions of magnetic sensors.
VA),
c response time not dependent on the
current received by the relay, technological evolution
c reliability increased by lack of In this current sensor field, sensors with
mechanical parts (no dirt accumulation wide measuring bands are being
or corrosion, not affected by impacts), increasingly used instead of current
c low cost since they use mass produced transformers (1 or 5 A). These sensors
non-specific electronic components. based on Rogowski's principle (non-
Finally, in the nineteen eighties, digital magnetic sensors) are currently on the
technology made it possible, thanks to market and provide distributors with
microprocessor processing power, to optimised solutions (fewer alternative
produce information processing units versions and simplified choice) which fig. 12: installation example of functional
able to: are far more efficient (improved CTs in a Fluair 200 12 kV HV metalclad
c globally provide the various response curve linearity) than cubicle (Merlin Gerin).
protections, traditional transformers.

fig. 13: Vigirack static relays (Merlin Gerin).

Cahier Technique Merlin Gerin n° 164 / p.8


3. response of a CT in saturated state

The emergence of static relays leads to


revision of protection behaviour as a
i2
whole in the case of strong currents: as
i1
the CT saturates beyond a certain
threshold, the first reaction is often to i2
avoid this by raising the threshold.
However, this results in both additional resistance
relay
costs (more efficient, larger, more
tested CT R
space consuming CT) and in the risk of
excessive temperature rise of the
relays. measuring
oscilloscope
On the contrary, saturation plays a
useful role for the «measurement»
function since primary current image
accuracy is only useful up to the value
u2
of the rated current I1n. Beyond this standard CT
point, the measurement ceases to be of i1
any use and saturation must occur for a u1
low current (2 to 3 I1n) in order to limit
the secondary current and protect the fig. 14: diagram for checking proper relay operation.
measuring instruments.
It is thus necessary to know the
I2
response of the CT in saturated state to (A)
ensure the protection device works
properly when the primary current 500 1
exceeds rated current strength,
particularly for the high values which
appear if a short-circuit occurs.
In theory, induction in the core reaches
a plateau at the saturation bend, thus 2
100
limiting current strength at the 3
secondary. In actual fact the
experiment performed will show that
current strength at the secondary
slightly increases and that protection
relay operation is quite satisfactory.
10
experiments - wiring
A current i1 is injected in the CT
primary, and the current supplied by the
secondary in a load Z containing a
relay R and a resistance is analysed
(see fig. 14).
10 100 500 N = I1/I1n
The currents at the secondary l2 are
given, according to the current supplied Fig. 15: I2 = f(N) for 1 CT only (15 VA 10P5 100/5).
at the primary (represented by the Load Z at the secondary:
I 1. relay only,
parameter N = 1 ) for various loads Z 2. Z = rated Z of CT, i.e. 0.6 Ω and cos ϕ = 1,
I1n 3. Z = rated Z of CT, i.e. 0.6 Ω and cos ϕ = 0.8.
and various CTs (see fig. 15).

Cahier Technique Merlin Gerin n° 164 / p.9


testing with symmetrical Nevertheless, the rms current I2 v both relays trip from their threshold ß
continues to increase as is shown in right up to Nmax.
constant currents
line 2 in figure 15. Testing at reduced load
Testing at resistive rated load
As I2 increases, the power supplied at The secondary load only comprises the
The test was carried out using a CT with
the secondary P2 = Z l22 and the power relay and the connecting wires.
low performance: 10P5, 50/5 with a
delivered at each relay Pr = R l22 also Compared with the rated load of 15 VA,
rated load Z of 15 VA (at 5 A) made up
increase. This accounts for the this represents a load of roughly 9%.
of an overcurrent relay and a resistance.
tripping of both relay types as from
Two relays were used: c results
threshold ß to which they were set right
v a Vigirack static relay, Curves i2 (t) (see fig. 16c) and i2 (N)
up to Nmax.
v an electromechanical relay. (see line 1 in figure 15) show that the
Testing at rated partly inductive load saturation bend is far higher than at
As both these relays have a low
This test resembles the previous one. rated load.
internal resistance, a resistance was
However, a choke is placed in the This bend follows the law:
added to reach roughly 0.6 Ω, i.e.
K s (P2 + R 2 I2 ) = constant
secondary circuit to represent the case 2
15 VA at 5 A (connecting wiring
of an electromechanical relay
included). Because the inductance of with P2 = Z l 22 is the total power
connected by itself to the secondary
the electromechanical relay was low supplied at the secondary (consumed
which would consume the rated power
(15 µH, i.e. cos ϕ = 0.95 for the relay by the relay and the connecting wires).
of the CT. In practice, these relays
only), the load can be considered to be R2 = internal resistance of the CT
never fall below cos = 0.8.
purely resistive in both cases. secondary winding,
In this test, the current I1 explored the
The test consisted in making current l1 Ks = saturation coefficient (real or rated).
range I1n = 50 A to I1 max = 16,400 A,
vary in the range I1n = 50 A Thus, in practice, when a CT delivers into
at I1max = 54 kA N max
i.e. N max = 328 and η = = 65.6 a load less than its rated accuracy level
Fp power (in VA), saturation occurs at a far
54,000
I.e. N max = = 1,080 and c results higher overcurrent level than the rated
50
Current i2 (t) assumes the curve given saturation coefficient Ks.
N max 1,080
η= = = 216 in figure 16b. The presence of a choke This phenomenon must be taken into
Fp 5 spreads out the peak, hence the lower .
consideration and calculated for each
(the latter value indicates the level of value I2 (see line 3 in figure 15). application since it may generate
saturation to which the CT was With respect to testing at pure resistive overcurrents in the secondary which
subjected). load: are incompatible with the thermal and
c results v I2 is multiplied by a factor of 0.65, dynamic withstands of the relays
The current i2 (t) collected at the v the total power supplied at the connected to the CT secondary (for
secondary takes the form of a peak secondary is multipled by a factor calculation, refer to the conclusions
above: N = 10 (see fig. 16a). of 0.4, given below).

i2
i2
i2
v2 v2
v2

fig. 16 a - CT 15 VA 10P5 50/5 fig. 16 b - CT 15 VA 10P5 50/5 fig. 16 c - CT 15 VA 10P5 50/5


testing at purely resistive rated load testing at rated load with cos ϕ = 0.8 testing at reduced rated load
I1 = 16,400 A I1 = 16,400 A relays + connecting wires - I1 = 14,200 A
scale: i2 = 100 A/square; v2 = 100 V/square. scale: i2 = 25 A/square; v2 = 50 V/square. scale: i2 = 100 A/square; v2 = 5 V/square.

Cahier Technique Merlin Gerin n° 164 / p.10


testing with asymmetrical
currents
a)
The test was performed using an
asymmetrical current, i.e. the sum of a scales:
symmetrical sinusoidal current and a v1
DC component with the following
characteristics: i1 500 A/mm

Î
≈ 2.3
Irms
i2 10 A/mm
These values are slightly less than
those in standard NF C 64-100 for
which
no saturation
Î
= 205 = 1.8 2 b)
Irms
scales:
i.e. 20% of asymmetry at 70 ms.
The secondary load is identical to that
of the main test at resistive rated load v1
comprising an electromechanical or
static relay.
i1 1,000 A/mm
c results
Both relays correctly respond in a
few ms and in the same manner as in
symmetrical testing throughout the i2 10 A/mm
range explored (up to Î1 = 140 kA peak
with Irms = 54 kA).
Remarks:
c the first peak seen at the secondary
by the relays is enough to make them
trip, if its energy is sufficient: this is the
case for Irms greater than 2 kA but
c)
below this value (see fig. 17a) the third
peak is required; scales:
c the CT does not saturate during the
first negative peak of the primary
current for Î1 = 4 k ;
c the response delivered by the CT on
the first negative peak of the primary
v1
(or even secondary) is normally shorter
than the responses in steady state
(which is reached as from the sixth
peak);

c the above points show that for higher


peak factors (case of off-load i1 2,000 A/mm
energising of transformers with an
i2 20 A/mm
Î
= 3.7 ), there is a risk of the
Irms
response at the secondary disappearing
during the first peaks. If, in addition, the
time constant of the primary current DC
component is high (t = 80 ms in the
case quoted), this disappearance fig. 17: CT secondary responses on an asymmetrical primary current for:
continues until the primary current a) lrms. ≈ 1.4 kA,
crosses the 0 axis. This phenomenon is b) lrms. ≈ for 14 kA and Î1 ≈ 32 kA,
shown on the curves in figure 17 c) lrms. ≈ 54 kA and Î1 ≈ 140 kA.
(tripping time moves to 68 ms).

Cahier Technique Merlin Gerin n° 164 / p.11


conclusions on CTs current value, even if the CT is strongly
saturated.
delivering on an
Thus, the CT saturation coefficient Ks
overcurrent relay must be calculated not according to the
The above tests show that for both short-circuit current lcc but according to
electromagnetic and static relays, the maximum setting threshold of the
tripping is obtained whatever the associated relay (see fig. 18 and 19).

choice of Ks Icc
I1n ITIn I1r = β I1n Ith = Icc θ ∞


I2n I2max θ I2 max
Ir min Ir max Ithr

of the I1n = rated current


network I1r = β I1n setting current
Icc = short-circuit current
θ = maximum short-circuit time

of the relay Ir min to Ir max = setting range


Ithr = admissible short term current (1s)

of the CT ITIn = rated primary rating


I2n = rated secondary current
I2 max = CT response to Icc

fig. 18: characteristics to be considered for defining a CT.

Cahier Technique Merlin Gerin n° 164 / p.12


1. the saturation threshold Ks
must correspond to the maximum
setting value of the relay.
2. the CT must thermally withstand
3. this CT must the current Icc for a time θ at least
electrodynamically equal to the breaking time of the
withstand the peak short-circuit by the circuit-breaker.
value 2.5 Icc.

4. the secondary circuit must


thermally withstand the maximum
secondary rms current I2 max
created by Icc at a primary for the
time θ. 5. the relay setting range
(Ir mini, Ir maxi) must be large
enough to cover the CT
response at the setting
current of network B I1n.

fig. 19: general rules for sizing a CT.

Cahier Technique Merlin Gerin n° 164 / p.13


4. parallel cubicle operation

Power supplies with double busbars encountered in this system is highly provide insulation between
are frequently used in HV network complex lockings: compartments and to plug in the
configurations. c cubicles connected in duplex (see breaking device. This arrangement
fig. 20). Using standard elements, this makes it necessary to connect the
There are currently two solutions for relays (which are not backed up) on
most cubicles: solution can advantageously replace
each CT secondary. This has resulted
c the double busbar cubicle: the circuit- the double busbar, as it is more
in the study below concerning
breaker may be connected to either reliable.
operation of two identical CTs
busbar without discontinuity of service. As on the new cubicle generations, the connected in parallel on the same
One of the drawbacks often CTs are standard elements used to load.

1455 1300 1455

relay

1800

1060
fig. 20: connection of 2 cubicles in duplex relay

Wiring diagram I1
Connection of two cubicles in duplex, standard CT
as shown in figure 18, results in the
diagram in figure 21 for protection.
resistance relay
One of the CTs (said to be «live») is tested «live» CT R
supplied at the primary by the
shunt i2 ir shunt Ir
HV network; its secondary supplies a
current i2 broken down into a current im
im
on the secondary of the other CT (said recorder
to be «dead») and a current ir on the Im
rated load of 15 VA made up of an
electromagnetic or static relay and a
pure resistance. I2 tested «dead» CT
The tests were performed on two
identical CTs of the same series (15 VA fig. 21: wiring diagram for study of a parallel-connected CT.
50/5 10P5 as in the above paragraphs).

Cahier Technique Merlin Gerin n° 164 / p.14


Results
These are given in the curves of scales:
figures 22 (currents as a function of
time) and figure 23 (root mean square im 9.4 A/mm
currents and tripping times). The
following observations are made:
c both relays quickly respond from their ir 9.55 A/mm
tripping threshold ß to η = 72,
c the static relay trips in a constant time
T ≈ 20 ms, whereas the i2 19 A/mm
electromagnetic relay reacts as a
function of I2 (T ≈ 80 ms at the tripping
i1 955 A/mm
threshold to T ≈ a few ms at η = 72);
c the secondary current I2 continues to
increase but two separate zones
appear:
Vigirack relay
v before η = 10, Ir ≈ I2 and lm << lr
the secondary current flows entirely into
the relays since the «dead» CT acts as fig. 22: currents at the secondary of 2 parallel-connected CTs. I1 = 12,500 A.
an infinite impedance,
v after η = 10 Im → I2, which means
that the secondary current mostly I(A)
flows into the «dead» CT but, T(ms)
I2 (total secondary current)
however, Ir continues to grow, thus Im (current flowing in the «dead» CT)
causing the relays to trip (do not forget 100
π
that ir is dephased by with respect Ir (current flowing in the relay)
2
to im);
c the current lr flowing in the relays T: static relay tripping
during testing with two CTs is lower
than for testing with one CT (at 10
N = 300, roughly - 40%). T: electromagnetic relay tripping

Conclusion
The connection of two CTs in parallel
presents no problem:
c for low currents: hardly any current 1
1 10 100 N = I1/I1n
flows into the «dead» CT,
c for high currents: sufficient current fig. 23: rms currents and tripping times of the relays connected to 2 CTs in parallel (10P5 50/5 15 VA).
flows into the relay to trip it.

Cahier Technique Merlin Gerin n° 164 / p.15


5. general conclusions

The conclusions in chapters 4 and 5 Nevertheless, CT saturation, as shown


show that: in this experiment, should not be
c the relays operate correctly in both considered a handicap:
cases studied: c when a CT «supplies» one or more
v high CT saturation, measuring instruments, saturation, by
v parallel-connection of two CTs;
limiting rms current at the secondary,
c static relays give the most reliable
protects the devices which, moreover,
response (constant operating time for
do not generally need to be very
all currents greater than the setting
threshold). accurate above l1n.
Moreover, static relays generally have c when a CT «supplies» a protection
a very small acquisition time, thus device, operation is ensured even if
meaning operation is more reliable saturation occurs. The idea of sizing
when the CT is strongly saturated and a CT according to the highest current it
supplies a very short current impulse. may have to withstand at the primary
Do not forget, however, that the must therefore be rejected. Moreover,
transient phenomena considered were this oversizing is risky for the relay and
limited to the asymmetrical current less cabling which could be seriously
than: damaged.
Î = 2.5
Irms

Cahier Technique Merlin Gerin n° 164 / p.16


appendix: CT standards

NF C 42-502 (French Standard) Normal rated current values


Rated insulation levels c at the primary (in A): 10 - 12.5 - 15 -
The insulation levels recommended by the standard are given in table II A presented 20 - 25 - 30 - 40 - 50 - 60 - 75
in figure 24. and their decimal multiples or
submultiples.
Preferential values are given in bold.
highest voltage for withstand voltage c at the secondary (in A): 1 - 5
equipment (kV) 1 minute at standard frequency to impulse voltage Accuracy class
(rms value) (kV) (peak value) (kV)
c measurement CTs
0.6 3
The normal accuracy classes are:
1.2 6
0.1 - 0.2 - 0.5 - 1 - 3 - 5.
2.4 11
The rated frequency operating range is
3.6 16 45
96% to 102% of rated frequency.
7.2 22 60
For transformers of accuracy classes
12 28 75
0.1 - 0.2 - 0.5 and 1, the current error
17.5 38 95 and phase shift in the rated frequency
23 45 95 range must not exceed the values in
24 50 125 table III (see fig. 25) when the
36 70 170 secondary load is between 25% and
52 95 250 100% of accuracy load.
72.5 140 325 For transformers of accuracy classes 3
and 5, the current error in the rated
fig. 24: insulation levels (table II A). frequency range must not exceed the
values in table IV (see fig. 26) when the
secondary load is between 50% and
accuracy current error phase shift, ±
class (ratio error) for current values
100% of accuracy load.
as a percentage, ±, given as a percentage In all cases, the load used must be
for current values of rated current inductive with a power factor of 0.8,
given as a percentage unless the corrresponding power is less
of rated current minutes centiradians
than 5 VA, in which case its power factor
% I1n 10 20 100 120 10 20 100 120 10 20 100 120 is the unit. On no account must the load
0.1 0.25 0.20 0.1 0.1 10 8 5 5 0.30 0.24 0.15 0.15 be less than 1 VA.
0.2 0.5 0.35 0.2 0.2 20 15 10 10 0.60 0.45 0.3 0.3
0.5 1.0 0.75 0.5 0.5 60 45 30 30 1.8 1.35 0.9 0.9
1 2.0 1.5 1.0 1.0 120 90 60 60 3.6 2.7 1.8 1.8

Note: after agreement between manufacturer and user, guarantees can be provided for
accuracy and phase shift, between 120% and 200% of In n.
fig. 25: error limits (table III).

accuracy current error


class (ratio error) as a percentage, ±, for current values given
as a percentage of rated current
% I1n 50 120
3 3 3
5 5 5

There is no phase shift limit for classes 3 and 5.


fig. 26: error limits (table IV).

Cahier Technique Merlin Gerin n° 164 / p.17


c Protection CTs
The normal accuracy limit factor values
are: 5 - 10 - 15 - 20 - 30 - 40.
The rated frequency operating range is accuracy ratio error phase shift composite error
90% to 110% of rated frequency. class for currents for rated current for accuracy
between In limit current
The normal accuracy classes are 5P and 2 In (as a %)
and 10P. (as a %) minutes centiradians
For accuracy level power and in the 5P ±1 ± 60 ± 1.8 5
rated frequency range, the current 10P ±3 10
error, phase shift and composite error
must not exceed the values in table V
(see fig. 27).
fig. 27: error limits (table V) .
To determine the current error and
phase shift, the load must be inductive
and equal to the accuracy load with a c the admissible times for the
power factor of 0.8, unless the admissible short term current are set
corresponding power is less than from the cold state. However, at the
10 VA; in this case the load could be user's request, the manufacturer is
resistive (unit power factor). To obliged to indicate, for a given type of
determine the composite error, the load device, the admissible short term
power factor may be between 0.8 current based on a state corresponding
(inductive circuit) and the unit, the value to operation, the heating current and
being set by mutual agreement maximum ambient temperature.
between manufacturer and user.
However, in the latter case, verification
Accuracy level power of admissible short term current cannot
The normal accuracy level power be made mandatory as an acceptance
values are: 2.5 - 5.0 - 10 - 15 - 30 - 75 - test.
100 VA. Admissible current peak value (Idyn).
Admissible peak current and short The admissible current peak value is
term current 2.5 Ith. However, another value can be
Admissible peak current and short term accepted provided it is stated on the
current (Ith). The short term current (Ith) identification plate.
must be specified for each transformer.
Their preferential values are given in
paragraph 10.1 (see fig. 28).
Notes
highest Ith
c for the highest network voltage less
network (kA)
than or equal to 36 kV, the admissible voltage
short term current value is (kV)
constructively linked to rated current 3.6 10 16 25 40
value. It is thus frequently expressed as 7.2 8 12.5 16 25 40
a multiple of rated current, for which the 12 8 12.5 16 25 40
preferential values are: 40 - 80 - 100 -
17.5 8 12.5 16 25 40
200 and 300.
23 8 12.5 16 25 40
c if no admissible values as a function 24 8 12.5 16 25 40
of time are given, it is accepted that the
36 8 12.5 16 25 40
transformer can withstand for a time t,
72.5 20 25
expressed in seconds, a current with a
root mean square value given by the 100 20
formula: 245 20 31.5
420 40
I th
I' th =
t2
fig. 28: preferential values of Ith
where t2 > t1 bearing in mind that Ith is (paragraph 10.1).
given for t1 (= 1s).

Cahier Technique Merlin Gerin n° 164 / p.18


IEC 185
This is the reference standard. The
NF C 42-502 (Norme Française) differs
only slightly from it. The differences are highest rated lightning impulse rated short term
as follows: voltage withstand voltage withstand voltage
for equipment Um (peak value) at standard frequency
Rated insulation levels (rms value) network power (rms value)
The IEC standard gives two tables: ≤ 500 kVA > 500 kVA
c the same table as the NF C standard kV kV kV kV
for European countries, 4.40 60 75 19
c another table as per USA practice
with slightly more stringent values: refer 13.20 95 110 34
13.97
to table II B (see fig. 29).
14.52
Normal rated current values
26.4 150 50
Same preferential values at the primary.
At the secondary possibility of a I2n = 2 A. 36.5 200 70

Accuracy class
c measurement CT
Current errors in module and phase are fig. 29: rated insulation voltages set for the U.S.A (table II B).
the same in class 3 and 5. For classes
0.1 - 0.2 - 0.5 and 1, the errors are the
same, except for the 10% of I1n column
which is replaced by 5% of I1n with the
errors listed in table IV A in figure 30. accuracy error εM error εϕ
Moreover, the IEC standard defines two class for I1 = 5 % of I1n for I1 = 5 % of I1n
additional classes, 0.2 S and 0.5 S for minutes centiradians
CTs with special applications 0.1 0.4 15 0.45
(connection with special electrical energy 0.2 0.75 30 0.9
meters). In this table, the module and
phase errors are given for I2n = 5 A only. 0.5 1.5 90 2.7
c protection CT 1 3 180 5.4
The IEC gives the same limit errors.
The only difference is that the accuracy accuracy error εM for error εϕ for values as a %
limit factor, Fp = 40, does not exist. class values as a % of of rated current I1n
Accuracy level power rated current
The IEC only gives the same normal I1n minutes centiradians
values up to 30 VA. Beyond this point, % l1n 1 5 20 100 120 1 5 20 100 120 1 5 20 100 120
power can be chosen to meet needs. 0.2S 0.75 0.35 0.2 0.2 0.2 30 15 10 10 10 0.9 0.45 0.3 0.3 0.3
Peak current and short term current 0.5S 1.5 0.75 0.5 0.5 0.5 90 45 30 30 30 2.7 1.35 0.9 0.9 0.9
Unlike the NF C standard, the IEC
standard does not define preferential
values of Ith for each network voltage.
However, application of the law i2 t = Cste fig. 30: accuracy class (table IV A).
to define the Ith is limited to: 0.5 < t < 5 s.

Cahier Technique Merlin Gerin n° 164 / p.19


Réal.: Sodipe - Valence - Photo.: IPV
Edition: DTE - Grenoble
Cahier Technique Merlin Gerin n° 164 / p.20 03-95 - 2500 - Printing.: Clerc

Das könnte Ihnen auch gefallen