Beruflich Dokumente
Kultur Dokumente
current
transformers
for HV protection
Michel Orlhac
→ Φ→
B= n
S V2 I2
→ →
E2 = n2 jω Φ R2 I2
l 2 ω I2
→ → N.B.: the real proportions, between the representative vectors of primary and secondary
V ≈ E2 values, are not repected.
h represents the exciting current since fig. 4: vectorial representation of a CT.
→ →
n2 Ie = ∫ H n dI
Toroid
current transformers CT with cross primary Wound type CT with Wound type CT with
winding (cable) wound primary wound primary
Since relays cannot be connected 1 secondary - 600/1 winding winding
directly onto the MV network, the 1 secondary - 200/5 2 secondaries - 200/5 and 100/5
information they receive comes from
fig.7: different types of CTs.
current transformers or CTs (see fig. 7)
and from voltage transformers or VTs.
When primary current is high, the CTs
are of the cross bar type, and when it is from part of the network to be
low they are of the wound primary type. monitored (a motor, a transformer, a
CTs have a number of roles to play in busbar...) to quickly detect and isolate relay
electrical networks: any faults inside that part. I2 = I1/m
c supplying at their secondary a current Zero sequence protection
exactly mirroring the one flowing in the This monitors the zero sequence I1
HV conductor concerned, component Io of the three-phase
c providing galvanic insulation between current which appears during phase- fig. 8.
the HV and the measuring and earth faults. There are two possible
protection circuits, configurations:
c protecting the measuring and c a toroid transformer encircling the I1 I'1
protection circuits from damage when a three phase conductors (if possible).
fault occurs on the HV network. This configuration (see fig. 10a) I'1 - I1
Using this current image in the HV enables detection of small zero
relay
conductor, the relay generates in turn a sequence currents (1 to 100 A).
tripping order according to the type of c three CTs achieving in the neutral
protection it provides and the values at connection of their secondary the sum
fig. 9.
which it has been preset [threshold(s), of the three phase currents. This
time delay(s)....]. configuration (see fig. 10b) is the only
This order is transmitted to one or more one possible for large and numerous
cables or busbar ducts. It is not a)
breaking devices (circuit-breaker,
contactor, switch). recommended when the zero sequence
CT configurations vary according to the current to be detected is 5% less than
type of protection to be provided. ln (or even 12% for consumer
substations according to standard
Overcurrent protection (see fig. 8) NF C 13-100 (French Standard)). Io
relay
This directly uses the «current»
information supplied at the CT secondary
to detect short-circuit or overload functional CTs b)
currents or calculate the thermal status of In HV cubicles, the «current
a machine. Note that this configuration transformer» function takes on a new
type must also contain the protection dimension as a result of its content and
devices using in addition to VTs: shape.
c directional overcurrent protection, Thus:
c power protection (active or reactive). c a number of CTs can be moulded in Io
Earth leakage protection (see fig. 9) the same enclosure: one core for the relay
This measures the current difference measurement function, one core for the
between two CTs, one connected protection function and sometimes even fig. 10.
downstream and the other upstream a third core for earth leakage protection,
i2
i2
i2
v2 v2
v2
Î
≈ 2.3
Irms
i2 10 A/mm
These values are slightly less than
those in standard NF C 64-100 for
which
no saturation
Î
= 205 = 1.8 2 b)
Irms
scales:
i.e. 20% of asymmetry at 70 ms.
The secondary load is identical to that
of the main test at resistive rated load v1
comprising an electromechanical or
static relay.
i1 1,000 A/mm
c results
Both relays correctly respond in a
few ms and in the same manner as in
symmetrical testing throughout the i2 10 A/mm
range explored (up to Î1 = 140 kA peak
with Irms = 54 kA).
Remarks:
c the first peak seen at the secondary
by the relays is enough to make them
trip, if its energy is sufficient: this is the
case for Irms greater than 2 kA but
c)
below this value (see fig. 17a) the third
peak is required; scales:
c the CT does not saturate during the
first negative peak of the primary
current for Î1 = 4 k ;
c the response delivered by the CT on
the first negative peak of the primary
v1
(or even secondary) is normally shorter
than the responses in steady state
(which is reached as from the sixth
peak);
choice of Ks Icc
I1n ITIn I1r = β I1n Ith = Icc θ ∞
∞
I2n I2max θ I2 max
Ir min Ir max Ithr
Power supplies with double busbars encountered in this system is highly provide insulation between
are frequently used in HV network complex lockings: compartments and to plug in the
configurations. c cubicles connected in duplex (see breaking device. This arrangement
fig. 20). Using standard elements, this makes it necessary to connect the
There are currently two solutions for relays (which are not backed up) on
most cubicles: solution can advantageously replace
each CT secondary. This has resulted
c the double busbar cubicle: the circuit- the double busbar, as it is more
in the study below concerning
breaker may be connected to either reliable.
operation of two identical CTs
busbar without discontinuity of service. As on the new cubicle generations, the connected in parallel on the same
One of the drawbacks often CTs are standard elements used to load.
relay
1800
1060
fig. 20: connection of 2 cubicles in duplex relay
Wiring diagram I1
Connection of two cubicles in duplex, standard CT
as shown in figure 18, results in the
diagram in figure 21 for protection.
resistance relay
One of the CTs (said to be «live») is tested «live» CT R
supplied at the primary by the
shunt i2 ir shunt Ir
HV network; its secondary supplies a
current i2 broken down into a current im
im
on the secondary of the other CT (said recorder
to be «dead») and a current ir on the Im
rated load of 15 VA made up of an
electromagnetic or static relay and a
pure resistance. I2 tested «dead» CT
The tests were performed on two
identical CTs of the same series (15 VA fig. 21: wiring diagram for study of a parallel-connected CT.
50/5 10P5 as in the above paragraphs).
Conclusion
The connection of two CTs in parallel
presents no problem:
c for low currents: hardly any current 1
1 10 100 N = I1/I1n
flows into the «dead» CT,
c for high currents: sufficient current fig. 23: rms currents and tripping times of the relays connected to 2 CTs in parallel (10P5 50/5 15 VA).
flows into the relay to trip it.
Note: after agreement between manufacturer and user, guarantees can be provided for
accuracy and phase shift, between 120% and 200% of In n.
fig. 25: error limits (table III).
Accuracy class
c measurement CT
Current errors in module and phase are fig. 29: rated insulation voltages set for the U.S.A (table II B).
the same in class 3 and 5. For classes
0.1 - 0.2 - 0.5 and 1, the errors are the
same, except for the 10% of I1n column
which is replaced by 5% of I1n with the
errors listed in table IV A in figure 30. accuracy error εM error εϕ
Moreover, the IEC standard defines two class for I1 = 5 % of I1n for I1 = 5 % of I1n
additional classes, 0.2 S and 0.5 S for minutes centiradians
CTs with special applications 0.1 0.4 15 0.45
(connection with special electrical energy 0.2 0.75 30 0.9
meters). In this table, the module and
phase errors are given for I2n = 5 A only. 0.5 1.5 90 2.7
c protection CT 1 3 180 5.4
The IEC gives the same limit errors.
The only difference is that the accuracy accuracy error εM for error εϕ for values as a %
limit factor, Fp = 40, does not exist. class values as a % of of rated current I1n
Accuracy level power rated current
The IEC only gives the same normal I1n minutes centiradians
values up to 30 VA. Beyond this point, % l1n 1 5 20 100 120 1 5 20 100 120 1 5 20 100 120
power can be chosen to meet needs. 0.2S 0.75 0.35 0.2 0.2 0.2 30 15 10 10 10 0.9 0.45 0.3 0.3 0.3
Peak current and short term current 0.5S 1.5 0.75 0.5 0.5 0.5 90 45 30 30 30 2.7 1.35 0.9 0.9 0.9
Unlike the NF C standard, the IEC
standard does not define preferential
values of Ith for each network voltage.
However, application of the law i2 t = Cste fig. 30: accuracy class (table IV A).
to define the Ith is limited to: 0.5 < t < 5 s.