Up to 29 I/O
Drops per LAN Genius LAN “B” (Optional) • Analog Input Out of Range
• CPU Off-line
B
GENIUS • Loss of I/O Block
• System Bus Fault
BIU S
M
GG
BB • CPU Configuration Mismatch
• I/O Bus Failure
CC
Max-ON Lite - this 90-30 Hot Standby Redundancy Max-ON Extended- Designed with the advanced user
(Max-ON) package has been specially configured to in mind, Max-ON 302-EX provides configuration
provide the basic PLC user with many off-the-shelf flexibility while maintaining ease of use. Coupled with
redundancy features found in higher level systems. the power and functionality of Ethernet data
Max-ON 30 Lite provides the most cost effective synchronization, Max-ON 302-EX offers advanced
redundancy platform providing a simple plug and play features for over 5000 I/O points. The standard utility
environment. Preconfiguration of all input and output provides dialog boxes for selection system
addresses and mapping of automatically transferred configuration details as well as on-line diagnostics
system variables simplifies the task of system reporting, communication status and I/O fault
configuration. In addition, the user friendly Windows reporting. Special Functions preformed by the Max-ON
based programming environment allows the system include Analog input scaling, program equivalence
engineer to get the application into operation fast. testing , selection of master CPU and synchronization
of application program variables. Diagnostics
Max-ON Standard - features include extended I/O monitored by the Max-ON software include: analog
capability, configurable synchronized data, status and input out of range, CPU off line, bus fault, invalid
diagnostic flags, selectable master and Dual Genius checksum and loss of I/O. Faults and alarms are logged
LAN, all in a cost effective package. Max-ON automatically in to the fault history table where
Standard is the workhorse of the 90-30 hot standby reference address, fault description and date and time
redundancy suite providing I/O capacities of up to 1500 stamp recorded for up to 32 records. A variety of
points. As with all other Max-ON versions, I/O in the communication interface modules allow for easy access
system can be distributed to one or more Genius LANs by HMI and other MIS functions.
which operate at distances of up to 7500 feet over
twisted pair cable or self healing fiber optic rings for For additional information please reference the
longer distances. Max-ON User Manual # GFK-1862 (7/2000)
8/00
GE Fanuc Critical Control Solutions
Introduction
Not every customer has the same requirements for high availability and safety protection systems .
That is why GE Fanuc offers a wide range of critical control solutions, from hot backup to Genius
Modular Redundancy systems that meet the most stringent standards for high availability and human
life safety.
These solutions are based on GE Fanuc PLC and I/O technologies, which can be readily integrated for
outstanding performance and reliability. GE Fanuc’s Series 90-30 PLC and I/O products provide a
cost effective platform for applications requiring moderate levels of critical control, while the Series
90-70 PLC and Genius product lines offer the higher levels of on-line diagnostics required in human
life and environmental protection systems. These controllers can be interfaced to any I/O product to
form system configurations meeting the global requirements for Safety Integrity Levels 0-3 as defined
by ISA S84.01 and IEC 61508.
No matter what level of critical control you need, you can count on GE Fanuc’s standards-based
approach. GE Fanuc critical control products have been certified by United Laboratories (UL);
European CE Mark; Canadian Standards Association (CSA), Factory Mutual Research Corporation
(FM Class 1 Div. 2 hazardous equipment ratings), National Fire Protection Agency, American Bureau
of Shipping (ABS), and TÜV.
Simplex 1oo1D X X
GMR Human Life
Protection Systems Dual CPU 1oo2D X
Certified to SIL 3
X
2oo3 - TMR X X
8/00