HALFAYA PROJECT
SURFACE FACILITY
Petrochina (Halfaya)

DETAIL DESIGN

PHASE THREE
DOC.NO.: HFY3-3125-ELE-SPC-0005

REV.: 0

PAGE 2 OF 6

CONTENT
1.0

SCOPE ..................................................................................................................... 3

2.0

CODES, REGULATIONS AND STANDARDS ......................................................... 3

3.0

ENVIRONMENTAL DATA ........................................................................................ 3

4.0

RATING & TECHNICAL DATA ................................................................................ 3

5.0

CONSTRUCTION ..................................................................................................... 3

6.0

INSPECTION AND TESTING ................................................................................... 5

7.0

VENDOR DATA REQUIREMENT ............................................................................ 5

8.0

PREPARATION FOR SHIPMENT ............................................................................ 6

HALFAYA PROJECT
SURFACE FACILITY
PHASE THREE

Petrochina (Halfaya)

DETAIL DESIGN
1.0

DOC.NO.: HFY3-3125-ELE-SPC-0005

REV.: 0

PAGE 3 OF 6

SCOPE
This Specification covers the minimum requirements for LV and control cables.

2.0

CODES, REGULATIONS AND STANDARDS


Vendor shall meet or exceed the requirements of the latest edition of the following codes,
regulations and standards, except as superseded herein. In cases where more than one
code, regulation or standard apply to the same condition, the most stringent shall be
followed. In the event of a conflict between this specification and other specifications or
correspondence, the OWNER shall be consulted and a ruling, in writing, shall be
obtained before any work is started.
IEC 61084

Cable trunking and ducting systems for electrical installations

IEC 60228

Conductors of insulated cables

IEC 60287

Calculation of the continuous current rating of cables

IEC 60331

Fire resisting characteristics of electric cables

IEC 60332

Tests on electric cables under fire conditions

BS 5467

Specifications for cables with thermosetting insulation for electricity


supply for rated voltages up to and including 600/1000V and up to and
including 1900/3300V

Some requirements in this specification may be modified by specific requirements in the


Purchase Specification. In case of conflict, the specific requirements supersede this
specification.
Any deviation from this specification must be approved, in writing, by OWNER. Such
written approval must be obtained prior to the commencement of any work which would
constitute such a deviation.
3.0

ENVIRONMENTAL DATA
For the details of environmental conditions please refer to the data sheet.

4.0

RATING & TECHNICAL DATA


Rated for continuous operation in a 50Hz, 400 V system with solidly earthed neutral.

5.0

CONSTRUCTION
The cable shall be of the following specifications:

Conductor: Annealed, stranded copper, preferably circular in shape with maximum


conductor temperature limited to 90 .

HALFAYA PROJECT
SURFACE FACILITY
PHASE THREE

Petrochina (Halfaya)

DETAIL DESIGN

DOC.NO.: HFY3-3125-ELE-SPC-0005

REV.: 0

Insulation: XLPE, 600/1000V Grade, for LV power and control.

Code identification:

PAGE 4 OF 6

Two Cores: Red & Black


Three Cores: Red, Yellow and Blue
Four Cores: Red, Yellow, Blue and Black
Five Cores: Red, Yellow, Blue, Black and Green&Yellow
Above mentioned cores used for power cables, coded numbers are also acceptable.
Control Cores: Black coded numbers in white

Conductor lay: Cores laid up with fillers

Inner sheath: Plastic tape wrapping & PVC Bedding

Bedding: Extruded PVC.

Armouring: Galvanized steel wire (lay in a direction opposite to conductor) and


aluminum wire for single core only.

Outer sheath: Extruded, moisture-proof, black colored, polyethylene, grade ST7 with
additive to make it withstand solvents & aliphatic hydrocarbon, resistant to corrosion
due to hydrocarbon, organic solvent etc. Also this shall be flame retardant.

Marker: Embossing or print type shall be provided on the outer sheath to depict the
voltage rating, manufactures name, year of manufacture, number of cores and size.

Note:
If cable will be laid underground directly, the armoring is needed.

The cables shall conform to the attached data sheet. All the missing details and
parameters in the data sheet shall be filled by the vendor. The cables shall be
supplied and installed in such a way that:

Maximum possible length is provided per drum.

No less than four pieces of tight fitting PVC/Rubber end caps per drum length shall
be provided with each drum for use during the cable cutting / installation.

The cable drum shall:

Be of wood or steel provided with wooden batons to protect the cable from
damage.

Have either ends of the cable wound on it properly plumbed / sealed with
water proof sealing caps, immediately after the factory tests.

Be arranged to take round spindle.

Have clear markings on outside faces of both the flanges as follows:

HALFAYA PROJECT
SURFACE FACILITY
PHASE THREE

Petrochina (Halfaya)

DETAIL DESIGN

6.0

DOC.NO.: HFY3-3125-ELE-SPC-0005

Ultimate users name.

Project name.

Purchase order number.

Year of manufacture.

Voltage rating.

Type of cable.

Number of cores and size.

Drum length.

Drum number.

Drum weight.

Direction of rotation.

REV.: 0

PAGE 5 OF 6

INSPECTION AND TESTING


Inspection and testing of the material shall meet the requirements as per the Owners
Standards and Specifications listed as Item2.

7.0

VENDOR DATA REQUIREMENT


This section describes the Vendor Data Requirements applicable to a Vendor's scope.
The Vendor Data Requirements Form is provided as a separate document.
Within this section the following definitions apply:
Buyer

Purchaser

Vendor

Manufacturer/Supplier of the material items.

Vendor shall submit, as a condition of this Purchase Order or Contract, all data
requirements specified as following at least:
-

Equipment data sheet.

Supporting documents

Certificate reports

Listing of Each and All Exceptions to the Specification

Each document submitted for review must be clear, legible, complete and properly
identified. Failure to provide adequate documents may result in them being returned
without review at Vendors expense. In that event, Vendor will be considered not to have
formerly submitted the documents so returned.

HALFAYA PROJECT
SURFACE FACILITY
Petrochina (Halfaya)

DETAIL DESIGN

PHASE THREE
DOC.NO.: HFY3-3125-ELE-SPC-0005

REV.: 0

PAGE 6 OF 6

Drawings and data approval does not relieve Vendor of his responsibility to meet
Purchase Order or Contract conditions relating to specifications, material and delivery
requirements, nor relieve Vendor of responsibility for compliance with laws, codes and
regulations.
8.0

PREPARATION FOR SHIPMENT


Vendor shall be responsible for preparing the materials for shipment.
Adoption of suitable packing methods and materials is at the sole discretion of the
Vendor, and should any loss, damage and/or deterioration be caused due to improper
packing, the consequences shall be responsibility of the Vendor.
The maximum dimensions of any package should not exceed 3.9 meters in width, 4.32
meters in height, and 20 meters in length, and total weight should not exceed 56 tonnes.
Packages larger or heavier than this will require approval from the owner.