Introduction to PQView and PQWeb

Wieslaw Jerry Olechiw


Vice President of Sales Dranetz
General Manager - Electrotek Concepts

Who Uses PQView Today?


United States/Canada
American Electric Power
Alabama Power Company
Baltimore Gas and Electric
CMS Energy
CPS Energy San Antonio
Con Edison New York
Detroit Edison Company
Dominion Virginia Power
Duke Energy Corporation
EnerNex Corporation
Entergy Services
EPRI
FirstEnergy
Georgia Power Company
Hawaiian Electric Company
Hydro One Networks
Hydro Ottawa
Maui Electric Company
NIST
Nebraska Public Power District
Northeast Utilities
Public Service Electric and Gas
Company
Public Service of New Hampshire
Salt River Project
San Diego Gas and Electric

Southern California Edison


Southern Company
Tennessee Valley Authority
United Illuminating Company
Wisconsin Public Service
Wireless from AT&T
Asia-Pacific
Ausgrid Sydney
Companhia de Electricidade
de Macau (CEM)
Guangdong Power Grid
Guangxi Power Grid Company
Hebei Electric Power Company
Henan Power Company
North China Power Grid
Orion New Zealand
Provincial Electricity Authority
Shandong Provincial Electrical Power
Corporation
Shanghai Municipal Electric Power
Company
Shanghai Jiu Long Electric Power Science
& Technology Company
Shanxi Power Company
Yunnan Power Grid Corporation
Transpower New Zealand
Latin America
Central Hidroelctrica de Caldas
Operador Nacional do Sistema Elctrico
2

Europe
Agder Energi Nett AS
BKK Nett AS
CEE Energiteknikk AS
Central Networks (E.ON)
DEM Slovenia
Elektro Slovenia
Elektrobistand
Hlogaland Kraft AS
Helgelandskraft AS
Hydro Aluminium AS
Hrvatska Elektroprivreda (HEP)
Istad Nett AS
Lyse Nett AS
Nordmre Energiverk AS
Notodden Energi AS
PSE-Operator
Rdy-Lury Kraftverk AS
SFE Nett AS
Skagerak Nett AS
SINTEF
Statnett
StatoilHydro
Sunnfjord Energi AS
Sweco Grner AS
Tafjord Kraftnett AS
Tussa Nett AS
2012 Electrotek Concepts, Inc. All rights reserved.

What data is stored in a PQView Database?


Circuit
Breaker
Operations

Data Logs

RMS Samples

Waveform
Samples

Event Causes

PQView
Database

Geospatial
Attributes

2012 Electrotek Concepts, Inc. All rights reserved.

What are the data sources


for a PQView Database?
Digital Fault
Recorders

Energy
Meters

Microprocessor
Relays

Power Quality
Monitors

SCADA Logs

PQView
Database

System
Models

2012 Electrotek Concepts, Inc. All rights reserved.

What analysis functions are offered by


PQView?
Event
Analysis

Compliance
Summaries

Reports

PQView
Database

Notifications

Indices

Fault
Analysis and
Location

2012 Electrotek Concepts, Inc. All rights reserved.

Companies that Produce Power System Sensors or


Software Integrated by PQView Users Today
Advantech

Grounded Power

Arbiter Systems

HIOKI

Cooper Power Systems CYME

Landis+Gyr

Dranetz

Linbo

Edison Electric Institute

OSIsoft

EDMI

Power Monitors, Inc. (PMI)

Electro Industries

PSL Power Standards Labs

Electrotek Concepts

Qualitrol/LEM Instruments

E-MAX Instruments

SATEC

Fluke/Reliable Power Meters

Schneider Electric/Power Measurement

General Electric

Schweitzer Engineering Laboratories (SEL)

GL Industrial Group/Stoner Software


SynerGEE Electric

Siemens

Gossen Metrawatt

Unipower

GridSense

Utility Systems Inc. (USI)

SoftSwitching Technologies

2012 Electrotek Concepts, Inc. All rights reserved.

Power Quality
Monitors

Digital
Relays

PQView PQDA
for In-Depth
Analysis
PQWeb for Web
Browsers
& Mobile Browsers

PQView
PQDM

PQView
Databases
SCADA
Databases
Digital Fault
Recorders

Compliance Reports
EN 50160

Automatic
Fault Location

2012 Electrotek Concepts, Inc. All rights reserved.

Schweitzer Engineering Laboratories


Data Handler for Schweitzer Engineering Laboratories Reports:
The data handler can now import SEL event reports (EVE
files), compressed event reports (CEV files), and load profile
reports (LDP files).
Additionally, the PQView installation program installs
example SEL files and an example configuration file
demonstrating how to import SEL text reports.

2012 Electrotek Concepts, Inc. All rights reserved.

IEEE COMTRADE Files

SEL Relays

SEL 5045 acSELerator


Team Software
PQView
PQ Data Manager
GE
EnerVista

GE Relays

Qualitrol Relays

BEN32 Master
Station Software

COMTRADE
Folders
PQView Database

Other Relays

Softstuf Wavewin
Data Collection
SUBNET Solutions
SubSTATION Server
9

2012 Electrotek Concepts, Inc. All rights reserved.

Signature System/Encore Series

InfoNode Server

HTTP or Telephone
Modem Connection

PQView PQ
Data Manager

IEEE 1159.3 PQDIF Files

PQView Database
DataNodes

10

2012 Electrotek Concepts, Inc. All rights reserved.

Dranetz
PQNode 7100,
8010

Advantech
ADAM Module

Dranetz ES210,
ES220, ES230

Arbiter Power
Sentinel 1133A

Power
Standards Lab

General Electric
KV Meter

PQube

Dranetz
DataNode
5520, 5530,
5540, 5560,
5571, 61000

ESS/
InfoNode

Modbus
Compatible
Meters

PQView
PQView
Database

PQView Integration with ION Enterprise


or WinPM.Net Database
Requires installation of optional ION Enterprise Database Data
Handler
Telephone or
Ethernet
Connections

PQView PQ
Data Manager

ION Enterprise

ION and ACM


Meters

ION
Enterprise
Database
12

PQView
Database
2012 Electrotek Concepts, Inc. All rights reserved.

PQView Integration
with Unipower PQSecure Database
Requires installation of optional PQ Secure Database Data

Telephone or Ethernet
Connections

PQView PQ
Data Manager

PQ Secure
Software
Unipower
Meters

PQ Secure
Database Server

13

PQView Database

2012 Electrotek Concepts, Inc. All rights reserved.

OSIsoft PI System
Requires installation of optional OSIsoft PI SDK and Electrotek
PiSlicer Library
PI SDK

PiSlicer Library

PQView PQ Data
Manager

PiSlicer

PQView
Databases

PI Server

PI Server

PI Server

14

2012 Electrotek Concepts, Inc. All rights reserved.

PQView Integration
with Dranetz Portable Monitors
Power Xplorer
PQView PQ Data
Manager
Power Guide

DDB Files

Power Visa

PQView
Database
Energy Platform EP-1

15

2012 Electrotek Concepts, Inc. All rights reserved.

More Data Sources


Cooper Power Systems CYME
Dranetz PES Databases
Electro Industries/General Electric
Communicator Log EPM Files
Fluke/Reliable Power Meters
(RPM) Omega and Scenario
Databases
GL Industrial Group/Stoner
Software SynerGEE
Gossen Metrawatt Portable
Monitors

GridSense PowerView
GroundedPower Text Files
HIOKI Text Files
Landis+Gyr Text Files
PQView Text File Formats
PQView Databases
SATEC PAS Databases
Siemens SICARO PQ Manager Text
Files
SoftSwitching Technologies I-Grid
Web Site

www.pqview.com/data-sources/
16

2012 Electrotek Concepts, Inc. All rights reserved.

Custom Data Sources


Alabama Power Company SCADA Database
Con Edison AMR Databases
Ergon Energy Australia AMR Database
Progress Energy Feeder Management System Database
Provincial Electric Authority (PEA) Thailand AMR Database
Companhia de Electricidade de Macau (CEM) EDMI Meters

17

2012 Electrotek Concepts, Inc. All rights reserved.

Dranetz PQNode 8010


Monitors

Proprietary Dialup

PQNode
Data Files
InfoNode Servers

File Share

MMS via WAN


HTTP
via LAN

Dranetz DataNode 5530


Monitors

InfoNode Servers
PQView

HTTP via RAS


Dranetz DataNode 61000
Monitors

HTTP
via LAN
HTTP via Frame Relay

InfoNode Servers

Schneider Electric
ION Meters

HTTP
via LAN
ION Server

SEL and GE Relays

LAN

File
Share
Microsoft
SQL Server

Frame Relay
EnerVista Download Server

COMTRADE
Files
LAN

GE XA/21
PI SDK
SCADA RTU Sensors

ECC PI Server

PQView
Databases

PQView Event Analysis

Waveform Samples for Voltage Sag


Duration: 0.08333s Minimum: 50.29%
Va

Vb

Vc

Ia

Ib

Ic

In

Voltage (%)

100
50
0
-50
-100

RMS Samples for Voltage Sag


Duration: 0.08333s Minimum: 50.29%
Va

-200

0.00

Vb

Vc

Ia

Ib

Ic

In

100

0.02

0.04

0.06

0.08

0.10
Time (s)

0.12

Voltage (%)

Current (A)

200

Electrotek/EPRI

90
80
70
0.14
60

0.16

0.18
PQView

Current (A)

50
200
150
100
50
0
0.00

19

Electrotek/EPRI

0.05

0.10

0.15

0.20
0.25
0.30
Time
(s)2012 Electrotek Concepts, Inc. All rights reserved.
PQView

Examples of PQView Event Derivations


Substation Bus - 1/12/2007 14:48:08.0060
Va

Vb

Vc

Ia

Ib

Ic

Voltage (V)

20000
10000
0
-10000

Substation Bus - 1/12/2007 14:48:08.0060

-20000

Reactance to Fault

Voltage (V)

2BC

0
Electrotek/EPRI

0.05

0.10
Time (s)

Vb

Vc

Vab

Vbc

Vca

Ib

Ic

Iab

Ibc

Ica

XTF

Ia

20000
15000
3ABC
10000

0.15
6000

Current (A)

-5000

Va
25000

4000

Reactance (O)

Current (A)

5000

20

0.20

0.25
PQView

2000
0
40

1.676

2BC

0
0

0.05

3ABC

0.10

0.15

1.686

0.20

0.25

Time (s)

20

2012 Electrotek Concepts, Inc. All rights reserved.

Examples of PQView Event Derivations


Substation ION 7700 - 2/1/2003 09:30:31.5377
Va

Vb

106

Substation ION
Qb 7700 - 2/1/2003 09:02:54.1855
Qc

Qa

105

-450

104

-500

1-Cycle FFT Va from -0.01735 to -0.0008137 s

Substation ION 7700 - 2/1/2003 09:02:54.1855


Total Harmonic Distortion

4.0
Va

-550

400

-0.10 380 -0.05


Electrotek/EPRI
-0.10

-600
-650
RMS
104.9
Fund
104.4
DC
0.04575
Max
108
Min
-113.6
CF
1.532
FF
1.110
THD Fund 9.73%
0.10
0.15
THD RMS 9.68%
HRMS Time10.16
(s)
Phase Jump 2.380

-700
-750
-800
-8500.05
-900

-950
-0.05
-1000

Vc

Ia

Ib

Ic

0.05

Electrotek/EPRI

-0.1

8
3.0
6

THD (%)
Voltage (%)

420

Vb

10
3.5

42.5
22.0

00.20
1.5
25

0.10 201.0 0.15


Time (s)
15
0.5
0
10
5 0

Electrotek/EPRI
Electrotek/EPRI

0.25

THD (%)

0
Current (A)

Current (A)

Ic

Reactive Power

103

-500

Ib

Vc
Ia
Ib
Ic
Substation
ION 7700
- 2/1/2003
09:30:31.5377

Vb

Reactive Power (kvar)

500

Va

107

-100

Ia

RMS

50

Voltage (%)

Voltage (%)

100

-50

Vc

Substation ION 7700 - 2/1/2003 09:02:54.1855

0
-0.10

0.30

0.20

0.35
PQView
0.30
0.35

0.25

0.1

0.2

PQView
0.3

Time (s)
10
-0.05

Electrotek/EPRI

20
0

30
40
Frequency (60 Hz Harmonic)
0.05
0.10
0.15
Time (s)

PQView
50
60
0.20

0.25

0.30
0.35
PQView
PQView

21

2012 Electrotek Concepts, Inc. All rights reserved.

Derivations from Waveform


and RMS Samples
Reactance-to-Fault
Radial Fault Location

Missing Voltage and Delta Current from First


Cycle or from Ideal Waveform

Spectrum Charts

Symmetrical Components

Delta Symmetrical Components

1, 2, 3, 4, 5, 6, 10, and 12 Cycle Windows

Phasors and Harmonic Phasors

Three-Phase Diode Rectifier Output

High-Pass Filter and Low-Pass Filter

Line Frequency during Event

First Derivative , Second Derivative, Third


Derivative, and Squared ValueTime

Total Harmonic Distortion (THD)


DC Component, Fundamental Component,
and Harmonic Trends during Event

Mean Values and RMS Values


Load Resistance, Load Reactance, Load
Impedance, and Load Impedance Angle

Links to Map Viewer and Trend Viewer

Real Power, Reactive Power, Apparent


Power, and Energy

IEEE P1159.2 Point-in Wave Characteristics

Delta Real Power, Reactive Power, Apparent


Power, and Energy

Dranetz Event Characteristics

IEEE P1159.2 RMS Characteristics


IEEE P1159.2 Missing Voltage Characteristics
Digital Status Changes

Characteristic Voltage

Operations Summary

Waveform Transformation
22

2012 Electrotek Concepts, Inc. All rights reserved.

Analysis of Data Logs


Substation - V RMS A, V RMS B, V RMS C
from 2/1/2003 to 3/1/2003

Substation
RMS
RMS
B,
Max[V RMS A] (kV)- VMin[V
RMS B] A,
(kV) V Avg[V
RMS B]
(kV) V RMS C

Min[V RMS A] (kV)

Avg[V RMS A] (kV)

Max[V RMS B] (kV)

Min[V RMS C] (kV)

Avg[V RMS C] (kV)

from
Max[V2/1/2003
RMS C] (kV)to 3/1/2003

Relative Frequency
30%

7.0

5.5

24183
6.785
7.105
7.299
0.5141
0.08452
6.826
6.931
7.068
7.121
7.162
7.215
7.244
0.04703

25%
Relative Frequency

6.0

Count
Min
Avg
Max
Range
St Dev
CP01
CP05
CP25
CP50
CP75
CP95
CP99
SI Range

80%

20%

60%

15%
40%
10%
20%

5%
1 Sat
Feb 2003
EPRI/Electrotek

8 Sat

100%

15 Sat
0%Time

22 Sat

Cumulative Frequency

6.5

Cumulative Frequency

1 Sat

0%
PQView 7.2
6.8
6.9
7.0
7.1
Avg[V RMS A] (kV), Avg[V RMS B] (kV), Avg[V RMS C] (kV)

EPRI/Electrotek

PQView
23

2012 Electrotek Concepts, Inc. All rights reserved.

RMS Voltage Variation Analysis


RMS Variation Magnitude-Duration Scatter Plot

Single Site, From 1/1/1996 To 1/1/2003


SARFI-90

SARFI-85

SARFI-70

50

1.4
1.2
1.0
0.8
0.6
0.4

40
30
20
10

0.2

0.0
10-3

10-2

10 -1
100
101
Duration (s)

10 2

1997

103

1998

1999

2000
Month

2001

SARFI Rates by Year

Selected Sites, From 2/1/2003 To 3/1/2003

Selected Sites, From 1/1/1996 To 1/1/2003

0.4
0.2

0.0
yc
< 11cccyyccc
23 cyyc
4 c cyc c
5 cy c
10 cy
6 toto 2 0 0 cycyc
10 0 to 3 60 c sec
2 0 to 2
c
3 1 to 5 se ec
o
2 t 10 s se c
o
5 t o 30 sec
t
0
c
Du
10 to 6
se
ra
0
c
30
tio
12
se
0
to
n
12
60
>

85
7850 toto 90
6750t toto78805
0 too 705
56
5
5 t 6
4 0t o6 5
)
4 5 t o 55 0
3 0 to o 5 0
(%
30 5 to 4 45
e
d
25 to 3 0
tu
5
2 0 to
ni
1 5 to 3 0
ag
M
10 to 2 25
0
to
5
ge
1
to
lta
0
10 5
to
Vo
5

SARFI-ITIC - Events per 365 Days

0.6

2003
PQView

Sag and Interruption Rate Magnitude-Duration Column Chart


Events per Site per 30 Days

2002

PQView Electrotek/EPRI

Electrotek/EPRI

10

0
1996

Electrotek/EPRI

SARFI-50

60

Events per 30 Days

Voltage Magnitude (pu)

Site Name
Service Entrance 3100
Service Entrance 5530
Service Entrance 5540
Service Entrance 5571
Service Entrance 7100
Service Entrance 7700
Substation 3720
Substation 5530
Substation 7700
Substation 8010
Substation DFR

SARFI Rates by Month

Selected Sites, From 2/1/2003 To 3/1/2003


2.0
Total Events: 47
1.8
Events Violating ITIC Lower Curve: 14
Events Violating ITIC Upper Curve: 0
1.6

PQView Electrotek/EPRI

24

1997

1998

1999
Year

2000

2001

2002

PQView
2012 Electrotek Concepts, Inc. All rights reserved.

PQWeb Analysis via Internet

25

2012 Electrotek Concepts, Inc. All rights reserved.

PQWeb Analysis via Internet

26

2012 Electrotek Concepts, Inc. All rights reserved.

PQWeb Analysis via Internet

27

2012 Electrotek Concepts, Inc. All rights reserved.

PQView Application Study


Guangdong Power, Guangzhou, China
Provides transmission service for
38GW of load to Guangdong
Province in Southeast China
Monitors network with DranetzBMI DataNodes and Power
Measurement ION meters
Measurements available on
intranet with Chinese user
interface
Measurements record DC
transmission line performance
during monopole ground return
mode

28

2012 Electrotek Concepts, Inc. All rights reserved.

PQView Application Examples


Fault Location
System Performance
Integration of Power System Measurements with GIS
Standards Compliance

29

2012 Electrotek Concepts, Inc. All rights reserved.

Fault Location Systems with PQView


Hydro-Qubec
Detroit Edison

San Diego
Gas & Electric

Wisconsin
Public Service

United
Illuminating

American Electric Power

Con Edison

Georgia Power
Company

30

2012 Electrotek Concepts, Inc. All rights reserved.

Example Single-Phase Fault

I0 = 2kA
Total Current
I0 = 4x2 kA = 8kA

I0 = 2kA
I0 = 8kA
IA

I0 = 2kA

I0 = 2kA

VA
Voltage Drop
31

2012 Electrotek Concepts, Inc. All rights reserved.

Fault Locating Process at Con Edison


PQ Meter
Captures
Waveforms

Feeder Trips
due to Fault

PQView
Calculates
Reactance

Match Reactance
To Feeder Model

Single-Phase Fault Evolves


Single-Phase
into Two-Phase
Fault Evolves into Two-Phase
Vb
Voltage (kV)

20
0

Va Ia

Vb

Ib

Vc

Ic Ia

Ib

Ic

15.0

Visual
Fault
Locator

12.5

-5
0.00

0.05

Current (kA)

-20

XTF

17.5

10.0

5
Current (kA)

Vc

Reactance (ohms)

Voltage (kV)

Va

10.0

2
1

7.5

Dispatch
Crews

5.0
2.5

1B

0.10
Time (s)

2.195

2AB

2.216

0.15
0.05

EPRI/Electrotek

32

0.10
Time
PQView
(s)

0.15

2012 Electrotek Concepts, Inc. All rights reserved.

Summary of Estimated Fault Location versus


Actual Fault Location for Faults in Manhattan
On average, use of the Reactance-to-Fault for fault location
saves one hour per feeder restoration job because it saves use
of capacitive discharge thumpers and DC hi-pot
Recent Results:
Year

0-1 MH

1-3 MH

3-5 MH

5-10 MH

> 10 MH

2009

64%

24%

5%

2%

6%

2010

67%

14%

5%

3%

11%

2011

64%

20%

8%

3%

5%

Summer 2012

76%

14%

4%

4%

1%

33

2012 Electrotek Concepts, Inc. All rights reserved.

One-Line Diagram with Aerial Map


of Estimated and Actual Location

Distance between estimated and actual location:200 meters


34

2012 Electrotek Concepts, Inc. All rights reserved.

Fault Location View with Street View

35

2012 Electrotek Concepts, Inc. All rights reserved.

Demo

36

2012 Electrotek Concepts, Inc. All rights reserved.

Example Correlation of Feeder Fault Event


with PI Event from SCADA Operation
50THST - 2/25/2010 08:56:10.0650
Va

Vb

Vc

Ia

Ib

Ic

Voltage (kV)

20

0
-10

50BX13E.DX
2/25/2010 08:56:12.0233
W50ST BKR 13E 39M54
CLOSE-TRIP

5000
Current (A)

Operation
Point Name
Time Stamp
Value
Description

10

-5000

1C

0
Electrotek/EPRI

Reference Cycle = 131


37

6
Time (c)

10
PQView
2012 Electrotek Concepts, Inc. All rights reserved.

Example Correlation of Feeder Reclose


Event with PI Event from SCADA Operation
50THST - 12/24/2010 22:25:48.3130
Va

Vb

Vc

Ia

Ib

Ic

Voltage (kV)

10

50BX41W.DX
12/24/2010 22:25:52.0059
W50ST BKR 41W5M90
TRIP-CLOSE

0
-5
-10
2000

Current (A)

Operation
Point Name
Time Stamp
Value
Description

-2000

0
Electrotek/EPRI

Reference Cycle = 4669


38

6
Time (c)

10
PQView
2012 Electrotek Concepts, Inc. All rights reserved.

Con Edison PQMS Module:


Correlation of Fault Events with SCADA Events
Multiple Breaker Trips due to Substation Fault
PKCHEST1 - 3/2/2009 02:18:28.1250
Va

Point NamePKBX33E.DX
Time Stamp3/2/2009 02:18:31.0241
Value
PARK_CH1 BKR 33E 7X81
Description CLOSE-TRIP

Vc

Ia

Ib

Ic

10000
Voltage (V)

Operations
Point NamePKBX32E.DX
Time Stamp3/2/2009 02:18:31.0241
Value
PARK_CH1 BKR 32E 7X78
Description CLOSE-TRIP

Vb

15000

5000
0
-5000
-10000

Point NamePKBX3BT.DX
Time Stamp3/2/2009 02:18:31.0241
Value
PARK_CH1 BKR 3BT
Description CLOSE-TRIP

Point NamePKBX7TR.DX
Time Stamp3/2/2009 02:18:31.0242
Value
PARK_CH1 BKR 7TR 7X24
Description CLOSE-TRIP

Current (A)

Point NamePKBX3TR.DX
Time Stamp3/2/2009 02:18:31.0242
Value
PARK_CH1 BKR 3TR 38X03
Description CLOSE-TRIP

-15000
10000
5000
0
-5000
-10000
0

Electrotek/EPRI

Event ID = 460896
39

6
Time (c)

10
PQView
2012 Electrotek Concepts, Inc. All rights reserved.

Reactive Power Change


Qa

Qb

Qc

5.4
5.2
5.0

Reactive Power (Mvar)

4.8
4.6
4.4
4.2
4.0
3.8
3.6
3.4
0

6
Time (c)
40

10

11

2012 Electrotek Concepts, Inc. All rights reserved.

Voltage THD Change


Va

3.0

Vb

Vc

2.5

THD (%)

2.0

1.5

1.0

0.5

0
0

6
Time (c)
41

10

11

2012 Electrotek Concepts, Inc. All rights reserved.

Examples Voltage Disturbances-3


Transformed waveforms
6 6k V M ea su re d - 5 /0 9/2 010 04 :3 1:2 9.5006
Vab

V bc

Vca

70 0 00

65 0 00

Voltage (V)

60 0 00

55 0 00

50 0 00

45 0 00

40 0 00
0

0 .5

1 .0

1. 5

2. 0

2. 5

Tim e ( s)
P o we r Q u a lity S o lu tio n s

P Q Vie w

42

2012 Electrotek Concepts, Inc. All rights reserved.

Examples Voltage
Disturbances-3
Transformed waveforms
6 6k V M ea su re d - 5 /0 9/2 010 04 :3 1:2 9.5006
Vab

V bc

Vca

70 0 00

65 0 00

Voltage (V)

60 0 00

55 0 00

50 0 00

45 0 00

40 0 00
0

0 .5

1 .0

1. 5

2. 0

2. 5

Tim e ( s)

22kV Transformed L-L Load - 5/09/2010 04:31:29.5006

P o we r Q u a lity S o lu tio n s

Vab

Vbc

Vca

21000

1 delta-star
1 delta-star
L-L
L-L

20000

Voltage (V)

P Q Vie w

19000
18000
17000
16000
15000
0.0

0.2

0.4

0.6

0.8

1.0

Time (s)
Event Description:
Power Quality Solutions

PQView

43

2012 Electrotek Concepts, Inc. All rights reserved.

Examples Voltage Disturbances-3


Transformed waveforms

6 6k V M ea su re d - 5 /0 9/2 010 04 :3 1:2 9.5006


Vab

V bc

Vca

70 0 00

65 0 00

Voltage (V)

60 0 00

55 0 00

50 0 00

45 0 00

40 0 00
0

0 .5

1 .0

1. 5

2. 0

2. 5

Tim e ( s)

3.3kV Transformed 2Tx L-L Load - 5/09/2010 04:31:29.5006 P Q Vie w

P o we r Q u a lity S o lu tio n s

Vab

Vbc

Vca

3200
3100

2 delta-star

3000

Voltage (V)

2900
2800

L-L

2700
2600
2500
2400
2300
2200
2100
0.0

0.2

0.4
Time (s)
Event Description:

Power Quality Solutions

0.6

0.8

1.0

44
PQView

2012 Electrotek Concepts, Inc. All rights reserved.

2. Examples Voltage DisturbancesTransformed


3 waveforms
6 6k V M ea su re d - 5 /0 9/2 010 04 :3 1:2 9.5006
Vab

V bc

Vca

70 0 00

65 0 00

Voltage (V)

60 0 00

55 0 00

50 0 00

45 0 00

40 0 00
0

0 .5

1 .0

1. 5

2. 0

2. 5

Tim e ( s)
P o we r Q u a lity S o lu tio n s

P Q Vie w

415V Transformed 2Tx L-N Load - 5/09/2010 04:31:29.5006


Va

Vb

Vc

230

22 delta-star
delta-star

220

L-N
L-N

Voltage (V)

210
200
190
180
170
-0.1

0.0

0.1

Power Quality Solutions

0.2

0.3

0.4

0.5
0.6
Time (s)
Event Description:

0.7

0.8

0.9

1.0

45

PQView

2012 Electrotek Concepts, Inc. All rights reserved.

Examples Voltage Disturbances-3


Transformed waveforms
2 delta-star

6 6k V M ea su re d - 5 /0 9/2 010 04 :3 1:2 9.5006

3.3kV Transformed 2Tx L-L Load - 5/09/2010 04:31:29.5006


Vab

V bc

Vca

Vab
70 0 00

Vbc

Vca

3200

L-L

3100
3000

65 0 00

Voltage (V)

2900

Voltage (V)

60 0 00

55 0 00

2800
2700
2600
2500
2400
2300

50 0 00

2200
2100
45 0 00

0.0

0.2

0.4
0.6
Time (s)
Event Description:

40 0 00
0

0 .5

1 .0

1. 5

2. 0

Power Quality Solutions

2. 5

0.8

1.0

PQView

Tim e ( s)

22kV Transformed L-L Load - 5/09/2010 04:31:29.5006

P o we r Q u a lity S o lu tio n s

Vab

Vbc

Va

Vca

21000

Vc

2 delta-star

220

L-N

210
Voltage (V)

19000

Vb

230

1 delta-star
1 delta-star
L-L
L-L

20000

Voltage (V)

415V Transformed 2Tx L-N Load - 5/09/2010 04:31:29.5006

P Q Vie w

18000

200
190

17000

180
16000

170
15000
0.0

0.2

0.4

0.6

0.8

1.0

-0.1

Time (s)
Event Description:
Power Quality Solutions

PQView

0.0

0.1

46Power Quality Solutions

0.2

0.3

0.4

0.5
0.6
0.7
0.8
0.9
1.0
Time (s)
Event Description:
2012 Electrotek Concepts, Inc. All rights reserved.
PQView

Power monitoring solutions

www.adabel.com

Automatic Reporting System


(ARS) for PQView

Why ARS?
Motivation
Users have many specific
requirements for power quality reports.
PQView provides powerfull tools to analyse
data and to create complex reports, but:
That task is often complicated
It is time consuming.
Requires lots of manual work

Report format that will satisfy all existing


and future requirements is impossible.

48

2012 Electrotek Concepts, Inc. All rights reserved.

Automatic reporting system - overview


ARS uses PQView databases as data sources
Automatically creates customized power quality or other types of reports (submetering)

49

2012 Electrotek Concepts, Inc. All rights reserved.

Automatic reporting system: Main goals


Modular - many different report components are available as
plug-ins:

tables
trends
statistical analysis
histograms...

User defines report template:

components (pages)
databases / sites
time interval (last year, last month)
parameters and custom settings

Reports are
available as

Mechanism for automatic report generation


creates actual report documents from
templates without user intervention.
50

PDF
Word
2012 Electrotek Concepts, Inc. All rights reserved.

HTML files

Easy usage simple user interface


Complex part of
setup is done only
once
Databases
Sites and virtual
feeders
Compliance
criteria
Report visual
template

Report templates setup is very easy point and click

51

2012 Electrotek Concepts, Inc. All rights reserved.

ARS
Automatic reporting system key features

Automatic report generation ARS simplifies otherwise


complicated and time-consuming process of creating
complex reports.
Reports for one measurement site, or multi-site
(comparative) reports are available. Even multiple
databases can be used in single report
Reports: statistic-basic, compliance (using standardized or
custom compliance limits), custom

52

2012 Electrotek Concepts, Inc. All rights reserved.

ARS
Automatic reporting system key features

Large level of customization is offered: users can customize


various report parameters to their needs:

Components plugin modules


Display formats, colors
report template designs
Language

Report creation scheduler: user can define number of


automatic report generation schedules.
Created reports are automatically archived and can be sent
via e-mail to defined recipients.
53

2012 Electrotek Concepts, Inc. All rights reserved.

ARS
Automatic reporting system key features
Easy software localization translation of user interface and
report templates to different languages is very easy

54

2012 Electrotek Concepts, Inc. All rights reserved.

Automatic reporting system architecture


Modular structure software can be upgraded with new
modules for creating custom user-defined reports.

55

2012 Electrotek Concepts, Inc. All rights reserved.

Data source flexibility


Support for various PQ monitor dana format
Different instruments can store
information in different formats

Frequency compliance measurements?

Trend data
Compliance counters

PQView channel map files can be


defined for different instrument
types in ARS:
PQView channels
Record format

Counters of
compliant 10
second intervals

Counters of non
compliant 10
second intervals

10 minute
min/average/max
trends

Unified reports can


be created using
data from different
instrument types

56

2012 Electrotek Concepts, Inc. All rights reserved.

Compliance criteria
Support for various compliance requirements
ARS supports unlimited number of different
compliance criteria sets.
Predefined compliance criteria files are available
at ARS:

EN 50160
NVE 1557
IEEE 519
IEEE 1559
IEC 61000-3-7

Custom compliance criteria files


can be defined

Internal utility regulation


Contracts
National and regional standards

Compliance of

Steady state parameters


RMS Events
Rapid voltage changes
57

2012 Electrotek Concepts, Inc. All rights reserved.

Compliance criteria
Steady-state measurements
Custom compliance criteria can be applied to any
measured steady-state parameter:

Valid range (90-110% Un)

Evaluation period (week, year)

Compliance time (95%, 100%...)

Different criteria can be defined for single parameter

Frequency should be 501Hz for 95% of a week

Frequency should be 507.5Hz for 100% of the time

Different criteria can be defined for different voltage


levels
Different criteria can be defined for various site
properties

Short circuit ratio

Location (rural / urban)

Generation / transmission / distribution

58

2012 Electrotek Concepts, Inc. All rights reserved.

Compliance criteria
Events
ARS offers many event classifications like:

Specification of event types by magnitude and duration


Long and short interruptions

UNIPEDE DISDIP tables (custom limits)

Different event severity criteria are available

CBEMA

ITIC

SEMI47

User defined sensitivity curves

Different compliance criteria can be applied to event


count in some period (year,month)

Total count of events

SARFI: CBEMA, ITIC, 70, 80, 90

Reliability indices: long interruption count duration, CAIDI,


SAIDI, CAIFI
59

2012 Electrotek Concepts, Inc. All rights reserved.

Measurement flagging
Support for various measurement flagging types

Flagging: excluding of

faulty measurements from


compliance statistics

Automatic flagging

criteria are activated when


choosed parameter value
falls into choosen limits

Manual flagging intervals


are entered by user or can
be imported from external
data source (maintinence,
storms, faults...)

60

2012 Electrotek Concepts, Inc. All rights reserved.

Advanced algorithms
Example: virtual feeder - grouping multiple
measurement sites into single virtual site

ARS allows to group two or more sites (instruments)


into virtual feeder virtual site
Usually used when two parallel transformers power
single bus

One of transformers can be disconnected for some time

Voltage at the point of measurement is not compliant


when transformer is off

Customers dont expirience interruption other


transformer is powering them.

Virtual feeder algorithm automatically detects and


calculates bus voltage
Can be used for

different instruments in same database,

different or identical instruments in separate databases

61

2012 Electrotek Concepts, Inc. All rights reserved.

Visual structure of report templates


Report templates are stored in HTML format, and easily changed to satisfy users
visual requirements.

62

2012 Electrotek Concepts, Inc. All rights reserved.

Visual structure of report templates

63

2012 Electrotek Concepts, Inc. All rights reserved.

Summary
PQView can import, manage and analyze data from a many
different types of devices from many manufacturers using
PQDIF, Comtrade, Modbus or proprietary data formats.
PQView can be used to present PQ event information and
reports from single sites to the complete system for short or
very long durations.
Advanced correlations and derivations can be to expand the
information available.
All departments within a utility organization.
PQView is an integral part of developing a Smart Grid Program

64

2012 Electrotek Concepts, Inc. All rights reserved.