Power System Controller PSC 1000

! Microprocessor controlled System supervision with


simple menu system
! User configurable alarms and settings
! Liquid crystal display with background light and
plain text information in different languages
! Compatible with Ascom rectifiers of all sizes
! Advanced automatic battery test functions with
battery block voltage measurements
! Temperature compensated battery charging
! Remote monitoring function through serial RS232C
link and windows based software PSM magic
! Standards: EN 60 950, EN 55 022, IEC 1000-4
! Dimensions 180x116x30mm (HxWxD)
The Ascom PCS 1000 is a powerful microprocessor based Power System Controller ideally suited to
supervise and control modular power systems for telecom applications. It is compatible with all
rectifier modules from Ascom Energy Systems. The PSC 1000 meets the european safety standard EN
60 950 and the european EMC standard for Informaton Technology equipment EN 55 022.
The superior functions make the controller a prime choice for your telecom power system:
- System supervision with display of system- voltage and current, battery- voltage, current and temp.
- Alarms: major, minor, mains failure, alarm stop, battery failure and battery test indication.
- Rectifier supervision: all rectifiers ok, one rectifier not ok and more than one rectifier not ok.
- Battery supervison and charging control: temperature compensation, boost and equalize, advanced
automatic battery test with blockvoltage measurements (optional).
- Supervision of fuses, circuit breakers and the mains.
- Low battery voltage control: Battery and /or load disconnection at mains failure.
- Programmable charging voltage, user configurable alarms and settings through keypad.
- System activities are time stamped and stored in an event log. Monitoring history of essential system
parameters are stored for 3 years in weekly buckets.
- Remote monitoring functions with RS232C serial link and windows based software PSM magic.

Power System Controller PSC 1000 - Technical specifications


GENERAL
Nominal system voltages
Accuracy of system voltage measurement
Nominal system currents
Accuracy of system current measurement
User definable alarm / protection thresholds
Supply voltage
Supply current at 53.5 V
System reliability

24 VDC, 48 VDC, 60 VDC


0.2 %
Up to several 1000 A
2%
Yes
18 to 80 VDC
50 mA, typical
All rectifiers continue operating at their own preset
default values in case of controller failure, (automatic self
diagnosis)
0 to 50 EC
116 x 180 x 30 mm
0.4 kg
EN 60 950, class 1
EN 55 022, class B
IEC 1000-4-2, level 3
IEC 1000-4-3
PSM-Magic, Modem 1000

Ambient temperature range, operation


Dimensions (WxHxD)
Weight
Safety standard
EMC
ESD
Immunity
Remote monitoring options

BATTERY CONTROL
Accuracy of battery voltage measurement
Battery temperature compensated float charging
voltage
Automatic boost charging control
Periodic equalizing
Automatic periodic battery test
Battery block voltage measurement
System monitoring history

0.5 %
-0 mV / EC to -200 mV / EC with reference to the
nominal battery float charging voltage within programmable temperature limits
Yes
Yes
Yes
Option
Yes, up to 3 years

CONNECTIONS
Loads
Batteries
Rectifier modules
Alarms
Low battery / DC load disconnect / Temperature alarm /
/ External fan control
External alarms
Serial Line, RS 232C
Modem 1000 inbuilt power supply

3 independent DC load strings


2 independent battery strings
Option:8 input channels for block voltage measurements
Max. 24 rectifier modules
5 Alarm relays with potential free change over switch to
connect external alarm signalling equipment
2 programmable output relays with potential free change
over switch
2 programmable inputs for major or minor alarms
9 pole D-sub
Yes

OPERATION
Display
Local alarm display
Keypad
Mode of operation
Monitoring
Subject to change due to technical progress.

Liquid crystal display with 2 lines of 16 characters each


5 LED's
4 keys
Menu controlled
Local or Remote on line to PC
PSC1000.wpd, 2000-08-10/BJ

Ascom Energy Systems AB


Box 3096
S-350 33 Vxj
+46 470 70 68 00
Tel.
Fax.
+46 470 70 68 90
E-mail. aesse@ascom.se

ascom Energy Systems

Das könnte Ihnen auch gefallen