Sie sind auf Seite 1von 53

TECHNICAL DATA SHEET

M/S Zhongding International Engineering Co., Ltd and Hulas Steel Industries Ltd., P.R.China and Nepal
(Zhongding-Hulas JV)
ITEM No. 1 POWER TRANSFORMERS
ITEM No. 1.1:132/33 kV POWER TRANSFORMER
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of Origin ZHEJIANG Jiangshan Transformer
Co.,Ltd China
2.Years of Manufacturing experience Years 10 40
3. Service Outdoor Outdoor
4. Type (Core or Shell) Core Core
5. Applicable Standard IEC IEC
6. Number of winding per phase No. 2 2
7. Type of cooling ONAN/ONAF ONAN/ONAF
8. Rating
a) Rated capacity
- ONAN MVA 24 24
- ONAF 30 30
b) Rated voltage
- Primary kV 132 132
- Secondary 33 33
c) Rated frequency Hz 50 50
9. Noise level
a) On ONAN rating dB <73 <73
c) On ONAF- rating dB <75 <75
10. Temperature rise
a) Temperature rise above 40oC ambient
-In oil by thermometer
-In winding by resistance deg.C 50 50
deg.C 55 55
b) Hottest spot temperature in winding limited to deg.C 55 55
11. Connection
a) High voltage Star Star
b) Low voltage star star
c) Vector group reference in accordance with IEC 60076 YNyn0 YNyn0

12. Taps
a) Type of tap changer ON – Load ON – Load
b) Tap steps No. 17 17
c) Tap range % +/- 10% +/- 10%
13. On-load tap changing gear & control- system
a)    Manufacturer and type As specified in Tech. MR Germany
Specs.
b) Rating
-Rated voltage kV 72 72
-Step voltage V 1400
-Rated current (min.) A 150 150
-Number of steps Nos. 17 17
c) Control suitable for:
-Remote/local operation Remote & local Remote & local
-Auto/manual operation Auto & manual Auto & manual
-Parallel operation Yes/No Yes Yes
d) Rated voltage of drive motor V, AC 400/230 400/230
14. Cooling equipment (for ONAF)
a) Manufacturer and type Sanmen Erg,China DBF5Q-10
b) Number of Fans Nos. 2
c) Rated power kW 1.1
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
d) Rated voltage V, AC 230/400 230/400
e) Temperature range over which control is adjustable Deg. C (0-150)

15. Magnitude of IIIrd harmonics voltage as of % <2 <2


fundamental frequency
16. Guaranteed losses
a)       No-load loss at rated voltage and frequency on kW 22
maximum MVA base
b)      Load loss at rated current and 75 deg.C on kW 125
max.MVA base
c) Cooler loss for full load operation on maximum MVA kW 0.65
base
d) Total losses kW 147.65
17. Impedance at rated current and
frequency at 75 deg.C winding
temperature and normal tapping
a) on maximum MVA base in ONAN % >10% >10%
b) on maximum MVA base in ONAF % Around 12.5%
18. Reactance at rated current and frequency at 75 deg. C 12.47%
on max. MVA base at name plate %
19. Efficiency at 75 deg.C winding
Temperature at PF=0.9
a) At 100 % load % 99.45%
b) At 75 % load % 99.53%
c) At 50 % load % Above 99% 99.59%
20. No load current in % of rated current referred to HV
side & 50Hz
a) At 90 % rated voltage % 0.44
b) At 100 % rated voltage % 0.50
c) At 110 % rated voltage % 0.58
21. Load in % of full load and p.f. at which max. % Load in 50% of full load and p.f.
efficiency occures 0.9, max effiency 99.59% occures

22. Regulation at full load and at 75 °C % 5.6835%


23. Minimum clearance in air
HV/LV
-Between phases mm >1500/150 >1500/150
-Between phase and ground mm >1270/150 >1270/150
24. Insulation level
a) Power frequency withstand
voltage (1 min. rms)
-Primary kV 275 275
-Secondary kV 70 70
b) Impulse withstand
-Primary kV 650 (crest) 650 (crest)
-Secondary kV 170/75 (crest) 170/75 (crest)
25. Detail of oil preservation system
a) Type of oil preservation system furnished type Conservator type Conservator type
b) Urethane air cell provided Yes/No Yes Yes
c) Volume of Conservator litres 1570
26. Minimum pressure of pressure relief device set to kg/cm2 0.55
operate at
27. Details of bushings HV/LV/HV Neutral
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
a) Manufacturer / Model No. Nanjing Zhida Electric Co.,Ltd.,
H.V. :BRDLW-145/630-
3,H.V.Neutral:BRDLW-72.5/630-
3,L.V.:B/W-35/400,L.V
Neatral:BJW-35/400

b) Type H.V & L.V.Neutral:


Condenser,L.V&L.V.Neutral:Proce
lain
c) Voltage class kV 145/36 145/36
d) Creepage distance (min.) mm 3300/825 3906/900
e) Reference standard IEC IEC
f) Dry flash over voltage kV 275/70 275/95
g) Wet flash over voltage kV 275/70 275/85
h) Impulse withstand voltage kV peak 650/170 650/170
28. Insulating oil
a) Approximate volume of oil liter 17250
b) Whether first fill of oil with 10 % excess furnished Yes/No Yes Yes

29. Bushing current transformer


a) Type oil-immersed
b) Voltage class (HV/LV) kV/kV 132/33 132/33
c) Number of cores
-HV No. 1 1
-LV No. 1 1
d) Ratio
-HV A 100/1 100/1
-LV A 1200/1 1200/1
e) Accuracy class PS PS
f) Burden per core (HV/LV) VA 15/15 15/15
30. Approximate overall dimension (L * W * H) mm 6600x4100x6300
31. Approximate weight
a) Core and coils kg 25500
b) Tank and fittings kg 7500
c) Oil kg 15500
d) Total weight kg 550000
32.Delivery of equipment in month following award of months
contract (Allowing time for approval of drawings) 4

ITEM No. 1.2: 33/11 kV POWER TRANSFORMERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of Origin ZHEJIANG Jiangshan Transformer
Co.,Ltd China
2.Years of Manufacturing experience Years 10 40
3. Service Outdoor Outdoor
4. Type (Core or Shell) Core Core
5. Applicable Standard IEC IEC
6. Number of winding per phase No. 2 2
7. Type of cooling ONAN/ONAF ONAN/ONAF
8. Rating
a) Rated capacity
- ONAN MVA 6 6
- ONAF 8 8
b) Rated voltage
- Primary kV 33 33
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
- Secondary 11 11
c) Rated frequency Hz 50 50
9. Noise level
a) On ONAN rating dB <67 <65
c) On ONAF- rating dB <69 <67
10. Temperature rise
a) Temperature rise above 40oC ambient
-In oil by thermometer deg.C 50 50
-In winding by resistance deg.C 55 55
b) Hottest spot temperature in winding limited to deg.C 55 55
11. Connection
a) High voltage Delta Delta
b) Low voltage star star
c) Vector group reference in accordance with IEC 60076 Dyn11 Dyn11

12. Taps
a) Type of tap changer ON – Load ON – Load
b) Tap steps No. 17 17
c) Tap range % +/- 10% +/- 10%
13. On-load tap changing gear & control- system
b)   Manufacturer and type As specified in Tech. MR Germany
Specs.
b) Rating
-Rated voltage kV 76 76
-Step voltage V 1400
-Rated current (min.) A 150 200
-Number of steps Nos. 17 17
c) Control suitable for:
-Remote/local operation Remote & local Remote & local
-Auto/manual operation Auto & manual Auto & manual
-Parallel operation Yes/No Yes 400/230
d) Rated voltage of drive motor V, AC 400/230
14. Cooling equipment (for ONAF)
a) Manufacturer and type Sanmen Erg,China DBF5Q-10
b) Number of Fans Nos. 2
c) Rated power kW 0.55
d) Rated voltage V, AC 230/400 230/400
e) Temperature range over which control is Deg. C (0-150)
adjustable
15. Guaranteed losses
c)       No-load loss at rated voltage and frequency on kW 6
maximum MVA base
d)      Load loss at rated current and 75 deg.C on kW 40
max.MVA base
c) Cooler loss for full load operation on maximum MVA kW 0.35
base
d) Total losses kW 46.35
16. Impedance at rated current and frequency at 75 deg.C
winding temperature and normal tapping

a) on maximum MVA base in ONAN % 7% 7%


b) on maximum MVA base in ONAF % 9.30%
17. Reactance at rated current and frequency at 75 deg. C 9.27%
on max. MVA base at name plate %
18. Efficiency at 75 deg.C winding
Temperature at PF=0.9
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
a) At 100 % load % 99.37%
b) At 75 % load % 99.47%
c) At 50 % load % Above 99% 99.56%
19. No load current in % of rated
current referred to HV side & 50Hz
a) At 90 % rated voltage % 0.58
b) At 100 % rated voltage % 0.62
c) At 110 % rated voltage % 0.69
20. Load in % of full load and p.f. at which max. % Load in 45% of full load and p.f.
efficiency occures 0.9, max effiency 99.57% occures

21. Regulation at full load and at 75 °C % 3.978%


22. Minimum clearance in air >450/340
HV/LV >400/280
-Between phases mm >450/340
-Between phase and ground mm >400/280
23. Insulation level
a) Power frequency withstand
voltage (1 min. rms)
-Primary kV 70 70
-Secondary kV 28 28
b) Impulse withstand
-Primary kV 170 (crest) 170 (crest)
-Secondary kV 75 (crest) 75 (crest)
24. Detail of oil preservation system
a) Type of oil preservation type Conservator type Conservator type
system furnished
b) Urethane air cell provided Yes/No Yes Yes
c) Volume of Conservator litres 1125
25. Minimum pressure of pressure relief device set to kg/cm2 0.55
operate at
26. Details of bushings HV/LV/
HV Neutral
a) Manufacturer / Model No. Nanjing Zhinda Electric
Co.,Ltd,H.V.BJW-
35/400,L.V.:BJW-12/630,L.V
Neutral:BJW-12/630
b) Type Procelain
c) Voltage class kV 36/12 36/12
d) Creepage distance (min.) mm 825/275 900/225
e) Reference standard IEC IEC
f) Dry flash over voltage kV 70/28 95/42
g) Wet flash over voltage kV 70/28 80/30
h) Impulse withstand voltage kV peak 170/75 200/75
27. Insulating oil
a) Approximate volume of oil liter 4000
b) Whether first fill of oil with Yes/No Yes Yes
10 % excess furnished
28. Bushing current transformer
a) Type
b) Voltage class (HV/LV) kV/kV 33/11 33/11
c) Number of cores
-HV No. 1 1
-LV No. 1 1
d) Ratio
-HV A 200/1 200/1
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
-LV A 600/1 600/1
e) Accuracy class PS PS
f) Burden per core (HV/LV) VA 15/15 15/15
29. Approximate overall dimension mm 4000x2930x3270
(L * W * H)
30. Approximate weight
a) Core and coils kg 8400
b) Tank and fittings kg 3500
c) Oil kg 3600
d) Total weight kg 16800
31.Delivery of equipment in month months
following award of contract
(Allowing time for approval of 4
drawings)

ITEM No. 2: 132 kV SF6 CIRCUIT BREAKERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of Origin AREVA T & D Ltd., India

2. Years of manufacturing experience Years 10 14 years


3. Manufacturer's designation as per submitted catalogue/ To be furnished by the GL 312F1/4031P
Model No. bidder/manufacturer at
4. Applicable standard the timeIEC
of bidding IEC 62271-100
5. Type / Class SF6 / outdoor SF6 / outdoor
6. Poles No. 3 3
7. Local and remote operations Both Required Both provided
8. Rated voltage
a) Nominal kV 132 132
b) Maximum kV 145 145
9. Rated current
a) Normal current A 1250 1250
b) Short time for 3 sec kA 25 25
10. Frequency Hz 50 50
11. Insulation level
a) Impulse withstand voltage kV 650(crest) 650
c)     Power frequency withstand voltage (1 min, rms) kV 275 275
12. Rated short circuit breaking current kA 25 25
13.Rated short circuit making current kAp 62.5 62.5
14.Interrupting time at 100% capacity
a) Max. opening time ms 40 36
b) Total interrupting time ms 60 60
15. Closing time ms 100 72
16. Make Time ms 120 72(closing time)
17. Max. capacitive current breaking capacity (rms) A 400

18. First pole to clear factor 1.3 1.3


19. Temperature rise above 40°C ambient
a)       Contacts °C with in IEC limits
b)      Terminals °C with in IEC limits
20. Operating mechanism
a) Type Spring operated Spring operated
b) Number of mechanisms per breaker set 1; (3 for 132 kV line 1
breaker)
c) single/three phase auto reclosure Three; Single for 132 Three phase auto recloser
kV line
d) enclosure protection IP55W IP55
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
e) Nominal Operating voltage of Closing/ Tripping coil V, DC 110 110
f) Operating voltage range % of rated

- Closing voltage 85-110% 85-110%


- Tripping 70-110% 70-110%
g) Spring charging Motor rating

- Capacity kW 0.63
- Rated voltage V 110 V DC 110 V DC
h) Time required by motor to charge the spring
completely
Sec 30 <10 sec
21. Push button for local operation Yes/No Yes yes

22. Selection switch for local/ remote control Yes/No Yes yes
23. Anti pumping device provided Yes/No Yes yes
24. Trip-free feature provided Yes/No Yes yes
25. Gas density detector provided Yes/No Yes yes
26. Operation counter provided Yes/No Yes yes
27. Space heater provided for cubicle Yes/No Yes yes
28. Operating duty cycle O-0.3 sec-CO-3 min- O-0.3 sec-CO-3 min-CO
CO
29.Thickness of sheet steel of cubicle mm min 2 2mm
30. Number of Auxiliary Contacts No. 8NO, 8 NC 8NO, 8 NC
31. Number of possible operations without maintenance :
for contacts
- Rated short circuit breaking current No. Not less than 10 40
- Rated normal current No. Not less than 2,000 2500
for mechanism No. Not less than 2,000 2500(at rated current)
32. Rated SF6 gas pressure kgf/cm2 0.64NPa (rel) at 20 deg.C

33. Guaranteed SF6 gas loss per annum % / annum <0.1 <0.1

34. Porcelain insulator

a) Manufacturer Abil/MIL/WSI/IEC/BHEL/SARA
VANA/LHT/GAOKE/REPUTED
b) Creepage distance mm 3,300 3650
35. Padlocking provision for local cubicle Yes/No Yes yes
36. Gas pressure gauge provided Yes/No Yes densimeter provided
37. Total weight of circuit breaker kg 1390kgs
38. Mechanical dimension (LxWxH) mm As per catalouge
39. Delivery of equipment in months following award of month 4 months from the approval of
contract. (Allowing time for approval of drawing) drawing

ITEM No. 3: 33 kV VACUUM CIRCUIT BREAKERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of Origin AREVA T & D Ltd., India

2. Years of manufacturing experience Years 10 14 years


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
3. Manufacturer's designation as per submitted catalogue/ To be furnished by the PCOB 36
Model No. bidder/manufacturer at
the time of bidding

4. Applicable standard IEC IEC-56/IS13118

5. Type / Class Vacuum / outdoor Vaccum


6. Poles No. 3 3
7. Local and remote operations Both Required Both provided
8. Rated voltage
a) Nominal kV 33 33
b) Maximum kV 36 36
9. Rated current
a) Normal current A 1250 1250
b) Short time for 3 sec kA 25 25

10. Frequency Hz 50 50
11. Insulation level
a) Impulse withstand voltage kV 170(crest) 170

d)    Power frequency withstand voltage (1 min, rms) kV 75 75

12. Rated short circuit breaking current kA 25 25

13.Rated short circuit making current kAp 62.5 63

14.Interrupting time at 100% capacity

a) Max. opening time ms 40 40

b) Total interrupting time ms 60 60

15. Closing time ms 100 100


16. Make Time ms 120 120
17. Max. capacitive current breaking capacity (rms) A

18. First pole to clear factor 1.5

19. Temperature rise above 40°C ambient

c)       Contacts °C 65
d)      Terminals °C 65
20. Operating mechanism

a) Type Spring operated Spring operated


b) Number of mechanisms per 1

breaker set 1
c) single/three phase auto reclosure Three Three

d) enclosure protection IP55W


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
e) Nominal Operating voltage of Closing/ Tripping coil V, DC 110 110

f) Operating voltage range % of rated

- Closing voltage 85-110% 85-110%


- Tripping 70-110% 70-110%
g) Spring charging Motor rating
- Capacity kW 0.5
- Rated voltage V 110 V DC 110 V DC
h) Time required by motor to charge the spring
completely
Sec 30 15sec
21. Push button for local operation Yes/No Yes Yes

22. Selection switch for local/ remote control Yes/No Yes Yes
23. Anti pumping device provided Yes/No Yes Yes
24. Trip-free feature provided Yes/No Yes Yes
25. Gas density detector provided Yes/No Yes Yes
26. Operation counter provided Yes/No Yes Yes
27. Space heater provided for cubicle Yes/No Yes Yes
28. Operating duty cycle O-0.3 sec-CO-3 min- O-0.3 sec-CO-3 min-CO
CO
29.Thickness of sheet steel of cubicle mm min 2
30. Number of Auxiliary Contacts No. 8NO, 8 NC 8NO, 8 NC
31. Number of possible operations without maintenance :

for contacts
- Rated short circuit breaking current No. Not less than 10 100
- Rated normal current No. Not less than 5,000 10000
for mechanism No. Not less than 2,000
32. Porcelain insulator AREVA approved
a) Manufacturer
b) Creepage distance mm 825 900
33. Padlocking provision for local cubicle Yes/No Yes
34. Total weight of circuit breaker kg 400
35. Mechanical dimension (LxWxH) mm As per catalouge
36. Delivery of equipment in months following award of month not mentined
contract. (Allowing time for approval of drawing)
DESCRIPTION UNIT REQUIREMENT OFFERED DATA

ITEM No.4: 12 kV SWITCHGEARS

DESCRIPTION UNIT REQUIREMENT OFFERED DATA

INCOMER
A. Switchgear manufacturer CGL India
Years of manufacturing experience Years 10 >25Years
Manufacture's designation as per submitted catalogue/ To be furnished by the 12VE26/1250
Model No. bidder/manufacturer at
the time of bidding

B. Bus-bars
1. Material Copper copper
2. Size
a) main bus mm2 12 x 50, 4-nos per phase
b) ground bus mm2 5 x 50, 1 nos
3. Minimum clearance
a) Phase to phase mm 120 +/- 10mm
b) Phase to ground mm 90 +/- 10mm
4. Rated current
a) Continuous at 40 °C ambient A 2500 2500
b) Short time current for 3 sec. kA 25 25
5. Rated voltage kV 12 12
6. Bus support insulators
a) Manufacturer CGL/Reputed make
b) Type Epoxy resin cast/Polycrete
c)Impulse withstand voltage kV 75 75
d) Power frequency withstand 28
voltage (1 min. rms) kV 28
7. Busbar joint silver-plated? Yes/No Yes yes
C. Circuit breakers
1. Manufacturer CGL
2. Type vacuum, with vacuum with moving carriage
moving carriage
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
3. Manufacture's designation as per submitted To be furnished by the As per standard design supplied to
catalogue/ Model No. bidder/manufacturer at NEA
the time of bidding

4. Rated voltage kV 12 12
5. Number of possible operations without maintenance:

for contacts
- Rated short circuit breaking current No. 100 100
- Rated normal current No. 10,000 10000
for mechanism No. 2,000 10000
6. Frequency Hz 50 50
DESCRIPTION UNIT REQUIREMENT OFFERED DATA

INCOMER
7. Rated current
a) normal current A 1250 1250
b) short circuit current for 3 sec. kA 25 25
8. Vacuum Interrupter
a) Make CGL
b) Rating A 12kV
9. Interrupting current (rms. sym.) kA 25 25
10. Interrupting time ms 60 </= 60
11. Making current peak kA 62.5 63
12. Closing time, max ms 120 </=120
13. Insulation level
a) Impulse withstand voltage kV 75 75
b) Power frequency withstand kV 28 28
voltage (1 min. rms.)
14. Operating mechanism
a) Type Spring with motor Spring with motor charging
charging
b) Operating voltage range
- closing % of 110V 85-110% 85-110%

- tripping % of 110V 70-110% 70-110%

c) Closing and tripping coils current A As per standard design supplied to


d) Duty cycle CO-15sec-CO NEA
CO-15sec-CO
15. Spring charging motor
a) Type and manufacturer Reputed make
b) Voltage V 110 DC 110V DC
c) Rating kW spring operated
d) Spring charging time sec 15 <30
16. Total no of auxiliary contacts
a) Normally open No. 8 8
b) Normally closed No. 8 8
c) Contact ratings (make and Siemens/L & T / EQ. make
continuous current)
-AC at 230 volt A 1 1
-DC inductive at 110 volt A 0.5 0.5
18. Overall dimensions (L* W * H) mm Shall be furnished during detail
engg.
D. Current transformers
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer CGL/Silkans/JSL/SG
Electrical/ECS

2. Type cubicle cubicle mounted, expoxy resin


mounted, epoxy resin

3. Manufacture's designation as per submitted catalogue/ To be furnished by the Indoor resin cast
Model No. bidder/manufacturer at
the time of bidding

4. Frequency Hz 50 50
5. Voltage class kV 12 12
6. Reference standard IEC IEC
7. Current transformer rating 800-400/1 1200/2400/5A
8. Insulation level
a) Impulse withstand (BIL) kV, crest 75 75
b) Power frequency withstand kV 28 28
(1 min. rms.)
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
INCOMER
9. Burden per phase VA 15 15
10. No. of cores No. 3 2
11. Accuracy class 5P20 (PS) for 0.5
protection & 0.5 for
metering

E. Voltage transformer
1.    Manufacturer CGL/Silkans/KAPPA/ECS
2. Type Incomor cubical mounted
3. Manufacture's designation as per submitted catalogue/ To be furnished by the Indoor resin cast
Model No. bidder/manufacturer at
the time of bidding

4. Frequency Hz 50 50
5. Voltage class kV 12 12
6. Reference standard IEC IEC
7. Rated voltage
a) Primary V 11000 11000
b) Secondary V 110 110
8. Rated burden VA 100 100
9. Accuracy class 0.5 0.5
10. Insulation level
a) Impulse withstand voltage (BIL) kV 75 75

crest
b) Power frequency withstand voltage (1 min. rms.) kV 28 28

11. Overall dimensions (L* W* H) mm shall be furnished during detail


engg.
12. Weight kg
13. Fuses (HV/LV)
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
a) Type
b) Continuous rating A as per requirement
c) Symmetrical fault rating kA
F. Switchgear assembly
1. Type of switchgear Indoor metal clad

2. Enclosure
a) Type MS
b) Thickness of metal sheet (min) mm 2 2
c) Degree of protection provided by the enclosure IP43 IP 4X

3. Breaker assembly
a) Breaker provided with service test and withdrawn Yes/No Yes yes
position
b) Type of indication provided for breaker position LED LED

c) Cubicle door can be closed with breaker in service or Yes/No yes


test position
4. Space heater
a) Thermostat controlled space heater furnished for each Yes/No Yes yes
cubicle?
b) Rating
- Voltage V, AC 230 230
- Watts W
5. Overall dimension (L * W * H) (of complete panel) mm As per design

6. Approximate weight (complete panel) kg 1000Kg


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
INCOMER
7. Shipping dimension (L *W * H) (of complete panel) mm 2140 x 650 x 2220

G. Relays
1. Manufacturer & country of origin EASUN
REYROLLE/EQ.Make,India
2. Manufacture's designation as per submitted catalogue/ To be furnished by the MIT 114
Model No. bidder/manufacturer at
the time of bidding

3. Years of manufacturing service Years 10 >10 year


4. Applicable standard IEC IEC
5. Type Numeric Numeric
6. Current setting
a)       Over Current % of rated 20 - 250 20 - 250

current
b)      High set (Instanteneous) 200-2500 yes
c)       Earth Fault % of rated 10 – 100 10-100

d)      High set (Instanteneous) current 50-500 yes


7. Characteristics IDMT (SI) IDMT(Inverse)
8. Reset time ms
9. Insulation test according to IEC Yes/No Yes yes
10. Indication
- light emitting diodes provided? Yes/No Yes yes
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
H. Annunciator type as per requirement
I. Delivery of equipment in months month not mentioned
following award of contract.
(allowing time for approval of
drawings)

Item No. 5: 145 kV CENTER BREAK DISCONNECTING SWITCHES


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of origin CGL,India
2. Years of manufacturing experience Years 10 More than 10 years
3. Manufacturer's designation as per submitted To be furnished by the HDB
catalogue / Model no. bidder/manufacturer at
the time of bidding

4. Applicable standard IEC IEC 62271-102/IEC129


5. Type Two column; Three column,Centre rotating
Center break
6. Operations Local & Manual
7. Frequency Hz 50 50
8. Rated voltage kV 145 145
9. Rated current
a) Normal current A 1250 1250
b) Short time for 1 sec kA 25 25
10. Insulation level
a) Impulse withstand voltage kV crest 650 650
b) Power frequency withstand voltage (1 min, rms) kV 275 275

11. Maximum current the switch can safely interrupt

a. Bus/line charging current A 0.5 min 0.7@0.15pf


b. Potential transformer magnetizing current A 0.5 min 0.7@0.15pf
12. Clearance
a. Between live parts and ground mm 3000
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
b. Between fixed contact and blade in open position mm 1300

13. Main contacts


- Material of contacts copper alloy E.T.P Copper
- Coating of contacts Silver plated E.T.P Copper
- Material of the contacts of the copper alloy E.T.P Copper
earthing switch
- Coating of the contacts of the Silver plated E.T.P Copper
earthing switch
14. Material of terminals As per IEC 60694
15. Coating of terminals As per IEC
16. Operating mechanism Motor operated Motor operated (Electrical) &
(Electrical) & Manual Manual
17. Local operating device provided Yes/No Yes Yes
18. Auxiliary contacts
a) Type (convertible or fixed) convertible convertible
b) Continuous current rating at 110V DC A 0.5 0.5
c) Material Copper Copper
d) Contacts silver-plated? Yes/No Yes Yes
19. No of operations switch can withstand without Nos.
deterioration of contacts
20. Type of interlocks furnished: Electrical & Electrical & Mechanical
Mechanical
21. Are the disconnectors and the earthing switches Yes/No Yes Yes
mechanically interlocked to each other

22. Auxiliary power supply


a) DS operating motor supply voltage V/ Phase 400V / 3Ph 400V / 3Ph
b) DS operating motor power W 0.5 HP
c) Space heater and cubicle V/ Phase 230V / 1Ph 230V / 1Ph
d) Control circuit V 110V, DC 110V, DC
23. Insulator
a) Manufacturer IEC/Birla NGK/Morden/Sarvana

b) Creepage distance in air mm 3300 3625


24. Number of NC. Contacts (minimum) No. 8 8
25. Number of NO. contacts (minimum) No. 8 8
26. Enclosure protection IP-55W
27. Weight of disconnecting switch kg
28. Thickness of sheet (minimum) mm 2 2
29. Earthing switch
a) Operating mechanism Manual Manual
b) Type of interlocks furnished Electrical & Electrical &
Mechanical Mechanical
c) Number of NC. Contacts (min.) No. 4 4
d) Number of NO. contacts (min.) No. 4 4
30. Weight of earthing switch kg not mentined
31. Delivery of equipment in months following award of month not mentined
contract. (Allowing time for approval of drawing.)

ITEM No 6 .1: 132 kV CURRENT TRANSFORMERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of Origin Aereva T&D, India
2. Years of manufacturing experience Years 10 30
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
3. Manufacturer's designation as per submitted catalogue / To be furnished by the OSKF-145
Model No. bidder/manufacturer at
the time of bidding

4. Applicable standard IEC IEC-60044-1


5. Type Outdoor,oil immersed Outdoor,oil immersed, Live Tank,
Hermetically sealed

6. Number of phases No. single single


7. Number of cores in each CT No. 3 3
8. Frequency Hz 50 50
9. Rated Primary Voltage kV 132 132
10. Insulation level
a) Impulse withstand voltage kV,(crest) 650 650
b) Power frequency withstand voltage (1 min. kV 275 275
rms)
11. Rated peak withstand current kA 62.5 62.5
12. Creepage distance mm 3,300 3625
13. Short time thermal rating (1 Sec) kA 25 25
14. Ratings
15. Current ratio A 800-400-200/1 A 800-400-200/1 A

16. Rated VA burden for each core VA 30 30


17. Accurancy class 5P20 for protection & 5P20 for protection & 0.2 for
0.2 for metering metering
18. Dimension (L x W x H ) mm As per inclose drawing
19. Weight kg As per inclose drawing
20. Delivery of equipment in months following award month
of contract (Allowing time for approval of drawings.) not mentioned

ITEM No 6.2: 132 kV CAPACITOR VOLTAGE TRANSFORMERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of origin Aereva T&D, India
2. Years of manufacturing experience Years 10 30
3. Manufacturer's designation as per submitted CCV-145
catalogue /Model No.
To be furnished by the
bidder/manufacturer at
the time of bidding
4. Applicable standard IEC IEC-60044-5
5. Type Outdoor, oil immersed Outdoor, oil immersed

6. Frequency Hz 50 50
7. Rated primary voltage
a) Nominal kV 132/Ö3 132/Ö3
b) Maximum voltage kV 145/Ö3 145/Ö3
8. Insulation level
a) Impulse withstand voltage (primary) kV 650 650
b) Power frequency withstand (1 min. rms) kV 275 275
(primary)
9. Crepage distance mm 3300 3625
10. High voltage capacitor
a) Number of capacitor 1
b) Capacitance of each stack pF 10461
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
c) Manufacturing tolerance (+/-%) +10%-5%
d) Total value of the high voltage capacitor pF 10461
11. Intermediate voltage capacitor
a. Number of stacks 1
b. Capacitance of each stack pF 58740
c. Manufacturing tolerance +/-%) +10%-5%
d. Total value of intermediate volt. capacitor pF 58740
e. Equivalent capacitance for carrier coupling pF 8800,+10%-5%

f.      Capacitance of CCVT pF 8800 8800


12. Value of the equivalent capacitance pF > 4400 > 4400
13. Open circuit intermediate voltage V 20kV/Ö3
14. Rating
a) Voltage ratio kV 132/Ö3:0.11/Ö3 132/Ö3:0.11/Ö3
b) Rated burden VA 50 50
c) Accuracy class 3P & 0.2for metering 3P & 0.2for metering

d) Overvoltage factor
- Continuous 1.1 1.2
- 30 seconds 1.5 1.5
e) Connection star
f) Secondary fuse cartridge type
- Type
- Manufacturer Reputed Make
- Amp rating A
g) Power factor (min) 0.8 0.8
h) Number of secondary windings 2 2
15. Dimension (LxWxH) mm As per inclose drawing
16. Weight kg As per inclose drawing
17. Delivery of equipment in months following award of month
contract (allowing time for approval of drawing) not mentioned

ITEM No.7.1: 120 kV LIGHTNING ARRESTERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of origin CGL, India
2. Years of manufacturing service Years 10 More than 10 years

3. Manufacturer's designation as per submitted To be furnished by the ZLAX25C


catalogue / Model No. bidder/manufacturer at
the time of bidding

4. Applicable standard IEC IEC 99-4.1991


5. Type Gap less metal – Stationclass, Heavy duty, Class 3
oxide / Outdoor
6. Rated voltage rating of L.A. kV 120 120
7. Impulse withstand voltage, (crest) kV 650 650
8. Power frequency withstand voltage kV 275 275
9. Rated frequency Hz 50 50
10. Nominal discharge current kA 10 10
11. Surge counter with insulating base furnished? Yes/No Yes for transmission Yes for transmission line
line
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
12. Leakage current measuring instrument furnished? Yes/No Yes for transmission Yes for transmission line
line
13. Porcelain creepage distance mm 3300 3625
14. Line terminal with accessories provided Yes/No Yes Yes
15. Earth terminal with accessories provided Yes/No Yes Yes
16. Has manufacturer exported such units? Yes/No Yes Yes

Item No. 6: 36 kV CENTER ROTATING DISCONNECTING SWITCHES


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of origin CGL,India
2. Years of manufacturing experience Years 10 More than 10 years
3. Manufacturer's designation as per submitted To be furnished by the HDB
catalogue / Model no. bidder/manufacturer at
the time of bidding

4. Applicable standard IEC IEC 62271-102, IEC 129


5. Type Three column; Three column;
Center Rotating Center Rotating
6. Operations Local & Remote Local
7. Frequency Hz 50 50
8. Rated voltage kV 36 36
9. Rated current
a) Normal current A 800 800
b) Short time for 1 sec kA 25 25
10. Insulation level
a) Impulse withstand voltage kV crest 170 170
b) Power frequency withstand voltage (1 min, rms) kV 75 75

11. Maximum current the switch can safely interrupt

a. Bus/line charging current A 0.5 min 0.7 @ 0.15pf


b. Potential transformer magnetizing current A 0.5 min 0.7 @ 0.15pf
12. Clearance
a. Between live parts and ground mm 1200
b. Between fixed contact and blade in open position mm 600

13. Main contacts


- Material of contacts copper alloy HDEC ETP Copper
- Coating of contacts Silver plated HDEC ETP Copper
- Material of the contacts of the copper alloy HDEC ETP Copper
earthing switch
- Coating of the contacts of the Silver plated HDEC ETP Copper
earthing switch
14. Material of terminals
15. Coating of terminals
16. Operating mechanism Motor operated Motor operated (Electrical) &
(Electrical) & Manual Manual
17. Local operating device provided Yes/No Yes Yes
18. Auxiliary contacts
a) Type (convertible or fixed) convertible convertible
b) Continuous current rating at 110V DC A 0.5 0.5
c) Material Copper Copper
d) Contacts silver-plated? Yes/No Yes Yes
19. No of operations switch can withstand without Nos.
deterioration of contacts
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
20. Type of interlocks furnished: Electrical & Electrical & Mechanical
Mechanical
21. Are the disconnectors and the earthing switches Yes/No Yes Yes
mechanically interlocked to each other

22. Auxiliary power supply


a) DS operating motor supply voltage V/ Phase 400V / 3Ph 400V / 3Ph
b) DS operating motor power W
c) Space heater and cubicle V/ Phase 230V / 1Ph 230V / 1Ph
d) Control circuit V 110V, DC 110V, DC
23. Insulator
a) Manufacturer
b) Creepage distance in air mm 825 825
24. Number of NC. Contacts (minimum) No. 8 8
25. Number of NO. contacts (minimum) No. 8 8
26. Enclosure protection IP-55W
27. Weight of disconnecting switch kg
28. Thickness of sheet (minimum) mm 2 2
29. Earthing switch
a) Operating mechanism Manual Manual
b) Type of interlocks furnished Electrical & Electrical &
Mechanical Mechanical
c) Number of NC. Contacts (min.) No. 4 4
d) Number of NO. contacts (min.) No. 4 4
30. Weight of earthing switch kg not mentioned
31. Delivery of equipment in months following award of month not mentioned
contract. (Allowing time for approval of drawing.)

ITEM No 7 .1: 36 kV CURRENT TRANSFORMERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of Origin CGL,India
2. Years of manufacturing experience Years 10 More than 10 years
3. Manufacturer's designation as per submitted catalogue / To be furnished by the Outdoor, Dry Type
Model No. bidder/manufacturer at
the time of bidding

4. Applicable standard IEC IS 2705


5. Type Outdoor, Outdoor,
Epoxy resin Polycrete Type
encapsulated
6. Number of phases No. single single
7. Number of cores in each CT
a) for 12 nos. No. 2 2
b) for 3 nos No. 3 3
8. Frequency Hz 50 50
9. Rated Primary Voltage kV 36 36
10. Insulation level
a) Impulse withstand voltage kV,(crest) 170 170
b) Power frequency withstand voltage (1 min. kV 75 75
rms)
11. Rated peak withstand current kA 62.5 62.5
12. Creepage distance mm 825 900
13. Short time thermal rating (1 Sec) kA 25 25
14. Ratings
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
15. Current ratio
For Incomer A 800-400/1 A As required
For outgoing A 400-200/1 A As required
16. Rated VA burden for each core VA 30 30
17. Accurancy class 5P20 for protection & 5P20 for protection & 0.2 for
0.2 for metering metering
18. Dimension (L x W x H ) mm 350 x 350 x580
19. Weight kg 60 kg approx.
20. Delivery of equipment in months following award month not mentined
of contract (Allowing time for approval of drawings.)

ITEM No 6.2: 36 kV CAPACITOR VOLTAGE TRANSFORMERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of origin CGL,India
2. Years of manufacturing experience Years 10 More than 10 years
3. Manufacturer's designation as per submitted Outdoor, Dry Type
catalogue /Model No.
To be furnished by the
bidder/manufacturer at
the time of bidding
4. Applicable standard IEC IS 3156
5. Type Outdoor, Outdoor,
Epoxy resin Polycrete Type
encapsulated
6. Frequency Hz 50 single
7. Rated primary voltage
a) Nominal kV 33/Ö3 33/Ö3
b) Maximum voltage kV 36/Ö3 36/Ö3
8. Insulation level
a) Impulse withstand voltage (primary) kV 170 170
b) Power frequency withstand (1 min. rms) kV 75 75
(primary)
9. Crepage distance mm 850 900
10. Rating
a) Voltage ratio kV 33/Ö3:0.11/Ö3 33/Ö3:0.11/Ö3
b) Rated burden VA 50 50
c) Accuracy class 3P & 0.2for metering 3P & 0.5for metering

d) Overvoltage factor
- Continuous 1.1 As per IS
- 30 seconds 1.5 As per IS
e) Connection Asrequired
f) Secondary fuse
- Type
- Manufacturer
- Amp rating A
g) Power factor (min) 0.85 0.85
h) Number of secondary windings 2 2
15. Dimension (LxWxH) mm 350 x 350 x580
16. Weight kg 60 approx
17. Delivery of equipment in months following award of month Not mentined
contract (allowing time for approval of drawing)

ITEM No.7.1: 30 kV LIGHTNING ARRESTERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of origin CGL
2. Years of manufacturing service Years 10 More than 10 Years
3. Manufacturer's designation as per submitted To be furnished by the
catalogue / Model No. bidder/manufacturer at
the time of bidding

4. Applicable standard IEC IEC -99-4


5. Type Gap less metal – Station class, Heavy Duty, Gapless
oxide / Outdoor
6. Rated voltage rating of L.A. kV 30 30
7. Impulse withstand voltage, (crest) kV 140 140
8. Power frequency withstand voltage kV 75 75
9. Rated frequency Hz 50 50
10. Nominal discharge current kA 10 10
11. Surge counter with insulating base furnished? Yes/No Yes for transmission Yes for transmission line
line
12. Leakage current measuring instrument furnished? Yes/No Yes for transmission Yes for transmission line
line
13. Porcelain creepage distance mm 825 750
14. Line terminal with accessories provided Yes/No Yes Yes
15. Earth terminal with accessories provided Yes/No Yes Yes
16. Has manufacturer exported such units? Yes/No Yes Yes

ITEM No.7.3: 9 kV LIGHTNING ARRESTERS


DESCRIPTION UNIT REQUIREMENT OFFERED DATA
1. Manufacturer and Country of origin CGL, India
2. Years of manufacturing service Years 10 more than 10 years
3. Manufacturer's designation as per submitted To be furnished by the Distribution class ZYPD31
catalogue / Model No. bidder/manufacturer at
the time of bidding

4. Applicable standard IEC IEC 99-4


5. Type Gap less metal – outdoor
oxide / Outdoor
6. Rated voltage rating of L.A. kV 9 9
7. Impulse withstand voltage, (crest) kV 75 75
8. Power frequency withstand voltage kV 28 28
9. Rated frequency Hz 50 50
10. Nominal discharge current kA 10 10
11. Porcelain creepage distance mm 275 300
12. Line terminal with accessories provided Yes/No Yes Yes
13. Earth terminal with accessories provided Yes/No Yes Yes
14. Has manufacturer exported such units? Yes/No Yes Yes
DESCRIPTION UNIT REQUIREMENT OFFERED DATA

ITEM No. 7.1: 132 kV LINE, BUS-COUPLER & 33/11 kV TRANSFORMER CONTROL & RELAY PANELS
DESCRIPTION UNIT REQD. Offered
Line/ Bus Coupler Line / Bus Coupler Panel
Panel
CONSTRUCTION OF CONTROL AND RELAY PANELS
1. Manufacturer and country of origin Easun Reyrolle Ltd., India

2. Manufacturing experience years 10 more than 25 years


3. Type (simplex/duplex) Duplex** Duplex for 132 kV simplex for 33
kV
4. Applicable standard IEC IEC
5. Control panels furnished as per specification? Yes/No Yes yes

6. Enclosure protection class IP IP 43 IP 43


7. Thickness of sheet metal used
a) Front and rear portion mm >=3 3
b) Side, top & bottom covers mm >=2 2
c) Doors mm >=3 3
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
8. All instruments, meters, relays and control switches flush flush
flush or semi‑flush type? type
9. Ground bus
a) Material copper copper
b) Size mm x mm 25 x 6 25x6
10. Overall dimension of control boards (LxWxH) mm 1000mm(L) X 610mm (W) X
2300mm(H) for simplex panel
maximum
11. Shipping data

a) Size of the large package (LxWxH) mm 2200mm(L) X 810mm (W) X


2500mm(H)
b) Weight of the heaviest package Kg 500 kg
12. Delivery of equipment in months following award of month 3-4 months from the date of recepit
contract. (Allowing time for approval of drawing) of final approved drawinds

13.Indicating Instruments
a) Ammeter
Manufacturer's designation / Model No. AE/MECO MAKE - India
Type Digital
Accuracy class 0.5 0.5
Scale
- Type of scale linear / NA
non-linear

‑ Range of indication (...../1 A CT operated) A 800-400-200/1A 0-800 or as per your requirement

DESCRIPTION UNIT REQD. Offered


Line/ Bus Coupler Line / Bus Coupler Panel
Panel
b) Voltmeter
Manufacturer's designation / Model No. AE/MECO MAKE - India
Type Digital
Accuracy class 0.5 0.5
Scale
‑ Range of indication kV 0-150 0-150 or as per your requirement

- Linear / non-linear
c) Active power meter
Manufacturer's designation / Model No. AE/MECO MAKE - India
Type Digital
Manufacturer's type designation
Applicable standard IEC IEC
Rated voltage kV 132/Ö3: 110V (PT secondary)

0.11/Ö3
Rated current A 800-400-200/1A 1A(or)5A(CT SEC)

Current range mA To be supplied as part of the


(Transducer operation) instrument
Accuracy class 0.5
Scale
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
- Type of scale log Center zero yes
‑ Range of indication MW 100-0-100 as per specification
200-0-200
- Linear / non-linear linear
d) Frequency meter AE/MECO MAKE - India
Manufacturer's designation / Model No. Digital
Range of indication Hz 47-53
e) Energy Meter
Manufacturer's designation / Model No. Elster
Type electronic electronic 3-phase 4- wire
3- ph, 4 wire

Applicable standard IEC IEC


Class of accuracy 0.2 0.2
Import and export meter provided Yes/No Yes yes
Rated voltage kV 132/Ö3: 132/Ö3:
0.11/Ö3 0.11/Ö3
Rated current A 800-400-200/1A 0-800 or as per your requirement

VA burden VA 0.1 VA
f) Annunciators
Manufacturer's designation / Model No. ALAN/BHARANI MAKE-INDIA

Type Numeric Microprocessor

Number of inputs (annunciator /event)


Number of active points No. 18 18
Number of rows No. 3 3
Number of columns No. 6 6
Type of mounting flush flush
DESCRIPTION UNIT REQD. Offered
Line/ Bus Coupler Line / Bus Coupler Panel
Panel
Replacement of individual inscription plates and lamps Yes/No Yes Yes
from front panel possible?
Sequence of operation as per specifications Yes/No Yes Yes
g) Phase Over-current Relays: (Directional & Non-
directional)
Manufacturer's designation / Model No.
Type numeric numeric
Applicable standards IEC IEC
Triple pole or single pole Triple pole Four pole(3O/C & 1E/F)

Continuous overload capacity x In 3.0 x In continous phase/earth

Current setting range % of rated 20 - 200% 5 - 250%


current
Operating time at 10 times current setting (max.) sec 3 3
Reset time ms
Characteristics
- IDMT(standard inverse) IDMT IDMT
- IDMT(very inverse) (standard (standard
- IDMT(extremely inverse) inverse) inverse)
- Definite time
Instantaneous unit provided Yes/No Yes yes
- Current setting range % of rated 500-2000% for directional
50-5250% for non directional
- Current setting range
DESCRIPTION UNIT REQUIREMENT 500-2000% for directional
OFFERED DATA
current 50-5250% for non directional
-     Operating time ms
h) Ground Over-current Relays: (Directional & Non- In built in phase overcurrent relay
directional)
Manufacturer's designation / Model No.
Type numeric
Applicable standards IEC
Single pole/Triple pole three pole

Continuous overload capacity x In


Current setting range % of rated 10 - 80%
current
Operating time at 10 times current setting (max.) sec 3
Reset time ms
Characteristics
- IDMT(standard inverse) IDMT
- IDMT(very inverse) (standard inverse)

- IDMT(extremely inverse)
-           Definite time
Instantaneous unit provided Yes/No Yes
- Current setting range % of rated
current
-           Operating time ms
DESCRIPTION UNIT REQD. Offered
Line/ Bus Coupler Line / Bus Coupler Panel
Panel

i) Bus / Transformer Differential Relay


Manufacturer's designation / Model No.

Applied standards IEC


Type numeric
Current magnitude difference setting range % of
rated
secondary

current
j) SYNCHRO-CHECK RELAY In built in distance relay relay
Manufacturer's designation / Model No.
Applied standards IEC
Type Numeric
Rated input measuring voltage V
Voltage magnitude difference setting range % of 5%-30%
Vn of Vn
Phase angle difference Degrees 50 - 300
setting range
Frequency difference setting range Hz 0.05 - 0.5
Operating time ms
Reset time ms
Specify whether each relay incorporate with the following
options of reclosing on:
- Dead bus - live line Yes/No Yes
- Dead line - live bus Yes/No Yes
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
If the options of reclosing on dead bus- live line and dead
line- live bus are separately furnished and mounted,
specify:
- Type.
-Voltage rating V
k) Auxiliary Tripping & Lockout Relays
Manufacturer's designation / Model No. Easun Reyrolle make -AR/TR
Series
Applicable standards IEC IEC
Type static/ numeric Electromecamical

Operating time ms 10ms


l) BREAKER FAILURE RELAY
Manufacturer's designation / Model No. Easun Reyrolle make -ARGUS-1

Applicable standards IEC IEC


Type numeric numeric communicable
Setting range A 0.10 to 2.50 x In step of 0.05 for
phase fault 0.10 to 2.50 xIn step of
0.05 for earthfaults

Trip steps 2, 0.01 - 20sec, 0.01-20sec


- number of trip steps No.
- adjustable time of 1st step ms
- adjustable time of 2nd step ms
- both in steps ms
Operating times >= 30msec
- maximum operating time ms 60sec step 1 sec
- reset time ms
DESCRIPTION UNIT REQD. Offered
Line/ Bus Coupler Line / Bus Coupler Panel
Panel
m) Distance Relay
Manufacturer's designation / Model No. SEL, USA,SEL 311C
Applicable standards IEC IEC
Type numeric numeric communicable
No of zones
- forward direction 3 3
- reverse direction 1 1
- Zone reach setting ranges including steps
- Zone 1 W/phase 0.25-320ohms
- Zone 2 W/phase
- Zone3 W/phase
- Reverse Zone W/phase
Zone timer setting ranges including steps
- Zone 2 sec 0-320s
- Zone 3 sec
- Reverse Zone sec
Directional sensitivity
- Single phase and phase to phase faults yes
- Three phase faults yes
Are the following features incorporated in each
distance relay?
Instantaneous tripping when closing on three phase Yes/No Yes yes
zero volt bolted fault
Carrier auxiliary relays for additional following carrier/ yes, provided
optical transfer trip schemes
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
- Zone acceleration Yes/No Yes Yes
- Permissive under reaching Yes/No Yes Yes
- Permissive overreaching Yes/No Yes Yes
Auxiliary tripping relays Yes/No Yes Yes
Single pole tripping and reclosing scheme Yes/No Yes Yes
Operation indicators for each function Yes/No Yes
Alarm for auxiliary DC voltage failure Yes/No Yes
Built-in test facilities Yes/No Yes
Power swing blocking facility Yes/No Yes Yes
VT supply supervision facility Yes/No Yes Yes
Specify whether the distance relay is insensitive to:
-Frequency changes Yes/No Yes
-Power swing (Hunting) Yes/No Yes
-Capacitive loading Yes/No Yes
Fault Locator Inbuilt in distance relay Inbuilt in distance relay
(inbuilt / separate)
DESCRIPTION UNIT REQD. Offered
Line/ Bus Coupler Line / Bus Coupler Panel
Panel
Accuracy % <3% <3%
Calculating time ms < 20 20ms
Does the fault locator incorporate following features:

- Independent of the fault type Yes/No Yes Yes


- phase selection indication Yes/No Yes Yes
Mis-operation protection for loss-of-potential due to short Yes/No Yes Yes
circuit in the secondary of CVT

OPTION B for Distance relay


Manufacturer's designation / Model No. EASUN Reyrolle Ltd., India -
OHMEGA
Applicable standards IEC IEC
Type numeric numeric communicable
No of zones
- forward direction 3 3
- reverse direction 1 1
- Zone reach setting ranges including steps
- Zone 1 W/phase 0.1-250ohms for 1A 0.1 : 500ohms
- Zone 2 W/phase for 5A
- Zone3 W/phase
- Reverse Zone W/phase
Zone timer setting ranges including steps
- Zone 2 sec 10-10sec in step of 10 msec
- Zone 3 sec
- Reverse Zone sec
Directional sensitivity
- Single phase and phase to phase faults cross polarization for single phase
& phase to phase
- Three phase faults memory polarization for 3 -phase
fault
Are the following features incorporated in each
distance relay?
Instantaneous tripping when closing on three phase Yes/No Yes yes
zero volt bolted fault
Carrier auxiliary relays for additional following carrier/ yes
optical transfer trip schemes
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
- Zone acceleration Yes/No Yes Yes
- Permissive under reaching Yes/No Yes Yes
- Permissive overreaching Yes/No Yes Yes
Auxiliary tripping relays Yes/No Yes Yes
Single pole tripping and reclosing scheme Yes/No Yes Yes
Operation indicators for each function Yes/No Yes
Alarm for auxiliary DC voltage failure Yes/No Yes
Built-in test facilities Yes/No Yes
Power swing blocking facility Yes/No Yes Yes
VT supply supervision facility Yes/No Yes Yes
Specify whether the distance relay is insensitive to:
-Frequency changes Yes/No Yes
-Power swing (Hunting) Yes/No Yes
-Capacitive loading Yes/No Yes
Fault Locator Inbuilt in distance relay Inbuilt in distance relay
(inbuilt / separate)
DESCRIPTION UNIT REQD. Offered
Line/ Bus Coupler Line / Bus Coupler Panel
Panel
Accuracy % <3% <3%
Calculating time ms < 20 20ms
Does the fault locator incorporate following features:

- Independent of the fault type Yes/No Yes Yes


- phase selection indication Yes/No Yes Yes
Mis-operation protection for loss-of-potential due to short Yes/No Yes Yes
circuit in the secondary of CVT

ITEM No 8.1: 110 V & 48 V BATTERY


DESCRIPTION UNIT REQD.110 V OFFERED DATA 110 V

1. Manufacturer and Country of Origin HBL Power Systems Ltd., India

2. Manufacturing experience years 10 20


3. Type of battery Maintenance Maintenance
free valve regulated free valve regulated lead Acid
lead Acid

4. Applicable standards IEC IEC 60896 - 21 & 22 2004

5. Number of cells No. 56


6. Number of units No. 14
7. Number of cells in a unit No. 4
8. Nominal voltage rating V 110 110
9. Nominal capacity at 270C at 10 h discharge time to AH 400 400
cell end voltage 1.75
10. Ampere capacity at 270C at 15 min discharge time A >300 421
to cell end voltage 1.75
11. Battery construction (type) MAS.S. Mounting Frame with acid
resistance powder coating

12. Type of plates


a) Positive ( flat or tubular ) Flat plasted
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
b) Negative Flat plasted
13. Type of rack 2610±15 x 445 ±1189±12mm
-           Rack dimensions
14. Float charging voltage V 2.25±0.005V/ceel at 25 deg. C

15. Equalizing charging voltage V 2.30±0.005V/ceel at 25 deg. C

16. Internal resistance of one cell ohm 0.37


17. Short circuit current withstand capacity A
18. Float charging current A 10
19. Charging current of a fully discharged battery at 8 Catalouge provided
hour charging rate A
20. End voltage of each cell V 1.75
21. Charging efficiency of the battery %
22. Max. duration in month, the battery can be kept month <0.5% per week at 25 deg C
without charging
23. Battery life (guaranteed value) years 20
24. Rack interconnection furnished? Yes Yes
25. Delivery of equipment in months following month not menyioned
award of contract (allowing time for approval of
drawings)
ITEM No 8.2: 110 V & 48 V BATTERY CHARGERS

DESCRIPTION UNIT REQD.110 V OFFERED DATA 110 V

1. Manufacturer and Country of Origin HBL Power Systems Ltd., India

2. Manufacturing experience years 10 20


3. Type of charger constant voltage Constant Voltage with current limit

4. Applicable standard IEC IEC 60146


5. Manufacturer’s designation as per submitted To be Furnished by the 110 TP 80 Main and standby
catalogue bidder/manufacturer at FCBC, with DVR
the time of bidding

6. Output rating A 80 80
7. Range of DC voltage variation ±V 99V to 126.5V

8. Maximum AC input kVA 16.86 KVA


9. Input Voltage / phase V 400 V, 3 ph 400 V, 3 ph
10. Ripple % < 2% < 2%
11. Efficiency of charger at 100 % output % 75% at full load
12. Temperature rise above ambient of 40 degree C

a) Solid state elements 0


C 90 deg C
b) Wound elements 0
C 90 deg C
13.Voltage regulation % +3% to -2% max +3% to -2%
14. Float voltage adjustment 123.75V (adj)
15. Equalizing voltage adjustment Boost 126.5V
16. Auto equalizing charge provided? Yes/No Yes Yes
17. Timer for equalizing charge Yes/No Yes Yes
provided?
18. End switching to limit equipment type
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
19. Manual over-ride switch for selection of Yes/No Yes Yes
float/equalizing charge provided?
20. Delivery of equipment in months following month 2.5
award of contract (allowing time for approval of
drawings)

ITEM No 14 : STATION GROUNDING SYSTEM


DESCRIPTION UNIT REQD. DATA
1.    Main ground grid conductor material Copper Copper
2. Main ground grid conductor size mm x mm 25 x 4 25 x 4

3. Cross section of riser conductors sq. mm. > 100 > 100

4. Ground electrodes

- Material Copper clad steel Copper clad steel

- Diameter mm 16 16

- Length meter 2 or 3 2 or 3

5. Material of risers Copper Copper

6. Earthing system designed for ohm £ 1 £1

ITEM No. 9.1 LINE TRAP / LINE MATCHING UNIT


DESCRIPTION UNIT REQ. OFFERED DATA
LINE TRAP
Manufacturer and Country of Origin see specs. Areva T & D ,India
Type Outdoor, Air cored, dry type
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
Applicable standard IEC IEC-603563
Manufacturer’s designation as per submitted catalogue / To be Furnished by the 1.0/800
Model No. bidder/manufacturer at
the time of bidding

Operating temperature range 0


C -40o to +40o
Nominal system voltage kV 132 132
Highest system voltage kV 145 145
Nominal frequency Hz 50 50
Rated continuous current A 800 800
Rated short time current for one second kA 25 25
Asymmetrical peak value of the first half wave of rated kA 51
short current
current carrying material Aluminum Aluminum
Rated inductance mH 1 1
Frequency range kHz 50-500 50-90kHz & 90 - 500kHz
Means of tuning Variable broad band
Type of tuning Variable broad band
Impedance within the bandwidth ohm 600 600
Nominal discharge current of protective device kA 10 10
Impedance at tuned frequency ohm 600
Attenuation in the tuned frequency band dB 1.6(max)
Type of mounting suitable for hanging suitable for hanging

Technical literature submitted Yes/No Yes Yes


COUPLING UNIT
Manufacturer and Country of Origin Areva T & D ,India
Type LMU500
Applicable standard IEC 60481 IEC 60481
Manufacturer’s designation as per submitted catalogue / To be Furnished by the …
Model No. bidder/manufacturer at
the time of bidding

Operating temperature range 0


C -45deg C + 70deg c
Insulation voltage on H.V. side (50 Hz) (lighting V As per standard
conductor and drain disconnected)
Nominal earth breaker current (50 Hz) A As per standard
Impedance of drainage coil (50 Hz) ohm < 20 < 20
Impedance of the coaxial input ohm 75 75
Impedance of the coupling ohm 400-600 400-600
AC sparkover voltage of arrestor kV 1 - 1.15 kV 1 - 1.15 kV
AC withstand voltage
-Primary - Secondary kV 5 5
-Primary - Earth kV 5 5
-Secondary- Earth kV 3 3
Admissible power without distortion W >400 watts
Inductance compensation Inductance of drain coil IS 0.5 mH
to 1mH with tolarance ( at 50HZ)

Max composite loss dB <2 <2


Frequency range Hz 50-500 50-500
Technical literature submitted Yes/No Yes Yes
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
ITEM No. 10. RTU
DESCRIPTION UNIT REQ. OFFERED DATA
Remote Terminal Unit
Name of manufacturer RTU 560,ABB Ltd.
Type of transmission system Serial communication
Transmission speed Bit/s 50-19200 ≤ 19200 Bit/s over RS458
Max. system capacity Max. 500 IO points in total
-Single –point commands
-Set-point commands (4 decades)
-Single-state indications
-Continuously measured values
-Meter readings (6 decades)
Transmission time
-Single –point commands Sec @ 9600 bd 2
-Single-state indications Sec 1
-Measured value correction sec 2
Data priority facility Yes yes
Permissible signal distortion for safe operation %
Accuracy of the entire measuring loop
-Metering transducers o.2/0.3/0.5/1.0
-Transmission equipment 0.1
-Indicators NA
Measured Value-input Max. % 1
-Output mA
-at 1 Ohm mA 4-20mA
-Load impedance 50Ω at 40 and 20 mA 150 Ω at 10
to 2 mA 110 kΩ at 2 V and 20
VDC
-Digital output
Power supply voltage V DC. 24-60 24-60 VDC
Power consumption W 44.3 W
Mode of operation Parallel operation
-Commands Yes Yes
-Indications Yes Yes
-measured values Yes Yes
Pulse train code IEC 870-5-101 or IEC 870-5-101
equivalent
-Address – block Yes Yes
-Information – block, indications Yes Yes
-measured values Yes Yes
-commands Yes Yes
-metering (readings) Yes Yes
-Check bits Yes Yes
Remote terminal capacity: Max. 5000 IO s including all
-Total number of analog inputs DI/DO/AI/AO, MWH & MVARH
-Total number of status inputs (one/switch) accumulator inputs and pulse out
puts
-Total number of status with memory inputs
-Total number of alarm inputs
-Total number of MWH and MVARH accumulator inputs

-Total number of control outputs


-Total number of pulse outputs
(Output is defined as : one output/switch or breaker)

Dimension of cabinets (packs) completely equipped and


wired
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
-height cm 200
-width cm 80
-depth cm 80
Voltage transducer
Manufacturer Securemeters/equivalent
Type DU 124/equivalent
Accuracy (at ambient temp. 0-500C) % 0.1 0.2 as per the IEC 688 standard

Ripple (peak to peak) % 1% P-P


Response time to 99 % of final value Sec. < 300ms
Input voltage V 110/415 V
Output current mA DC. 0-10 mA/ ± 100 mA/ 4-20mA
Auxiliary voltage V DC. 18-80 V AC/DC
Test voltage (input to earth) kV For input voltage < 300V the test
voltage is 3.7kV & for input
voltage of 300-600 is 5.5kV as per
the IEC 688 standard

Power consumption VA 2 <1.2 VA for upto 60 Volts, & for


60-600 V it is 1 mA * Vn (Voltage
nominal) as per the IEC 688
standards
Module dimension cmXcm 11.4 X 7.7
Transducer for active power
Manufacturer Securemeters/equivalent
Type DP 234/equivalent
Accuracy (at ambient temp. 0-500C) % 0.1 o.2
Ripple (peak to peak) % 1% P-P
Response time to 99 % of final value Sec. < 300ms
Frequency Hz 50 45-60Hz
Input voltage V 110-500V L-L
Input current A 1A/5A
Output current mA DC. 0-10 mA/ ± 10 mA/ 4-20mA
Test voltage (input to earth) kV For input voltage < 300V the test
voltage is 3.7kV & for input
voltage of 300-600 is 5.5kV as per
the IEC 688 standard
Power consumption VA 2 <0.1 VA per phase for current ,
1mA per phase for voltage
Auxiliary voltage V 110 18-80V AC/DC
Module dimension cmXcm 12 X 7.7
Frequency transducer Securemeters/equivalent
Manufacturer
Type DF 03,04/equivalent
Accuracy (at ambient temp. 0-500C) % 0.1
Ripple (peak to peak) % 1% of full rated O/P
Response time to 99 % of final value Sec. <300ms
Input voltage V 60 - 500V
Output current mA DC. 0-10/0-20/4-20mA
Auxiliary voltage V DC. 18-58 V AC/DC
Test voltage (input to earth) kV For input voltage < 300V it is
3.7kV & input voltage of 300-
600V it is 5.5kV
Power consumption VA < 0.6Vn(voltage nominal) which
conforms to the requirement
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
Module dimension cmXcm 11.4 X 7.7
DESCRIPTION UNIT REQUIREMENT OFFERED DATA

ITEM No. 15: 132 kV BUS, FITTINGS AND INSULATORS


DESCRIPTION UNIT REQ. OFFERED DATA
132 KV
1. ACSR CONDUCTOR
Manufacturer and Country of Origin
Type BEAR BEAR
Applicable standard
No. of wires
a) Aluminum No. 30 30
b) Steel No. 7 7
Cross section
a) Aluminum sq mm 264.4 264.4
b) Steel sq mm 61.7 61.7
c) Complete conductor sq mm 326.1 326.1
Overall diameter
a) Steel core mm 10.05 10.05
b) Complete conductor mm 23.45 23.45
Ultimate tensile strength Kg 11320 11320
Weight kg/km 1,216 1,216
2. SHIELD WIRE
Manufacturer and Country of Origin
Type
Applicable standard IEC IEC
No. of wires No. 7 7
Nominal cross sectional area sq mm 61.7 61.7
Overall diameter mm 10.05 10.05
Ultimate tensile strength kg 7,400 7,400
Zinc coating g/sq.m
Equivalent modulus of elasticity kg/mm2 19,000 19,000
Weight kg/km 483 483
3. ALUMINUM TUBULAR BUS
Manufacturer and Country of Origin
Applicable standard
Cross-section mm2
Diameter inner / outer mm
Material
4. Fittings
Manufacturer and Country of Origin
Applicable standards
Material
5. Suspension/ TENSION Insulator STRING
Manufacturer and Country of Origin
Applicable standards
Size of disc
- Diameter mm 254 254
- Height mm 146 146
Number of units per string No 11 11

Combined mechanical and electrical kN 120 120


failing load
Creepage distance per unit mm 292 292
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
Impulse withstand voltage kV, crest 120 120
Dry power frequency withstand voltage kV 70 70
Wet power frequency withstand voltage kV 40 40
Puncture voltage kV 120 120
6. Post insulator
Manufacturer
Applicable standards IEC IEC
Rated system voltage kV
Max. rated voltage kV
Unit size (Diameter) mm
Unit size (length) mm
Creepage distance mm
Insulation level
a) Impulse withstand voltage kV, crest
b) Power frequency withstand kV
voltage (1 min rms)
Failing load (bending) kg
Failing load (torsion) kg-m
DESCRIPTION UNIT REQUIREMENT OFFERED DATA

ITEM No. 11C: 11kV POWER CABLE


DESCRIPTION REQD. for REQD. for Outgoing feeders

11 kV
UNIT incomer
1. Manufacturer & country of origin
2.Years of manufacturing experience Years 10
3. Type
4. Reference standard IEC
5. Number of cores Single/
three Single core Single core
6. Voltage rating
a) Nominal System Voltage kV 11 11
b) Max. system voltage kV 12 12
c) Voltage grade of cable (U0 /U)
d) Rated voltage between conductor and screen
kV 12/Ö3 12/Ö3
e) Rated voltage between two conductors kV 12 12
7. Maximum conductor temperature
a) Continuous 0
C 90 90
b) Short time 0
C
8. Conductor material Copper Aluminum
9. Conductor
a) Cross section of conductor Suitable for 1500 A
continuous current
mm2 rating ³240
b) No. of Runs or Loops proposed, if any
c) Cross section of each wire mm2 400 240
d) No. & diameter of wire in each conductor
No./ mm
e) Class of stranding
f) Insulation
- Material XLPE XLPE
- Thickness mm
g) Overall jacket
- Material PVC PVC
- Thickness mm
h) Approximate overall diameter mm
i) Standard drum length meter
j) Net weight of cable in drum kg
k) Continuous current rating at 40 deg. C ambient
A
-In ground A >1500
-In duct A >1500
l) Short circuit current
- 0.1 sec. kA
- 1.0 sec. (Minimum kA) kA 25 25
m) Electrical parameter
- Resistance / km ohm
DESCRIPTION UNIT REQUIREMENT OFFERED DATA
- Reactance / km ohm
- Capacitance / km micro F
10. Armor sheath provided? Yes/No Yes
10. Armor sheath provided? Yes/No Yes
12. Delivery of equipment in months following award of
contract (allowing time for approval of drawing)
month

ITEM No 12: LOW VOLTAGE POWER CABLE


DESCRIPTION UNIT REQUIRED DATA GUARANTEED DATA
1. Manufacturer and Country of Origin Lumbini Vidyut Udog Pvt Ltd.,
Nepal
2. Type
3. Applicable standard IEC IS 1554 Part : 1988
4. Voltage rating
a) Suitable for max.system voltage V 600 1100
b) Voltage grade of the cable( Uo/U) V 600/1100
c) Rated voltage between each conductor and screen V 600

d) Rated voltage between two conductors V 1100


5. Conductor material Copper Copper
6. Insulation material Polyethylene Polyethylene
7. Overall jacket material PVC PVC
8. Net weight of cable kg/m Depends upon No. of Cores and
cross-sectional area
9. Technical literature submitted Yes/No Yes Yes
10.Type test certificate submitted Yes/No Yes Yes
11. Delivery of equipment in months following award of not mentioned
contract. (Allowing time for approval of drawing.)

ITEM No 13: CONTROL CABLE

DESCRIPTION UNIT REQUIRED DATA GUARANTEED DATA


1. Manufacturer and Country of Origin Lumbini Vidyut Udog Pvt Ltd.,
Nepal
2. Type
3. Applicable standard IEC IS 1554 Part : 1988
4. Voltage rating
a) Suitable for max. system voltage V 600 1100
b) Voltage grade of the cable( Uo/U) V 600/1100
c) Rated voltage between each conductor and screen V 600

d) Rated voltage between two conductors V 1100


5.Conductor material Copper Copper
6. Conductor
7. Insulation material Polyethylene Polyethylene
8. Overall jacket material PVC PVC
9. Net weight of cable kg/m Depends upon No. of Cores and
cross-sectional area
10. Technical literature submitted Yes/No Yes Yes
11. Type test certificate submitted Yes/No Yes Yes
12. Delivery of equipment in months following month not mentioned
award of contract. (Allowing time for approval of
drawing.)
DATA SHEET
M/S Zhongding International Engineering Co., Ltd and Hulas Steel Industries Ltd., P.R.China and Nepal
(Zhongding-Hulas JV)

ITEM No.4: 12 kV SWITCHGEARS

DESCRIPTION UNIT REQUIREMENT OFFERED DATA REQUIREMEN OFFERED DATA


T
INCOMER FEEDER
A. Switchgear manufacturer CGL India CGL India
Years of manufacturing experience Years 10 >25Years 10 >25Years
Manufacture's designation as per submitted catalogue/ To be furnished by the 12VE26/1250 To be furnished by 12VE26/1250
Model No. bidder/manufacturer at the
the time of bidding bidder/manufactur
er at the time of
bidding

B. Bus-bars
1. Material Copper copper Copper copper
2. Size
a) main bus mm2 12 x 50, 4-nos per phase 12 x 50, 4-nos per phase
b) ground bus mm2 5 x 50, 1 nos 5 x 50, 1 nos
3. Minimum clearance
a) Phase to phase mm 120 +/- 10mm 120 +/- 10mm
b) Phase to ground mm 90 +/- 10mm 90 +/- 10mm
4. Rated current
a) Continuous at 40 °C ambient A 2500 2500 1250 2500
b) Short time current for 3 sec. kA 25 25 25 25
5. Rated voltage kV 12 12 12 12
6. Bus support insulators
a) Manufacturer CGL/Reputed make CGL/Reputed make
b) Type Epoxy resin cast/Polycrete Epoxy resin cast/Polycrete
c)Impulse withstand voltage kV 75 75 75 75
d) Power frequency withstand 28 28
voltage (1 min. rms) kV 28 28
7. Busbar joint silver-plated? Yes/No Yes yes Yes yes
C. Circuit breakers
1. Manufacturer CGL CGL
2. Type vacuum, with vacuum with moving carriage vacuum , with vacuum with moving carriage
moving carriage moving carriage
3. Manufacture's designation as per submitted To be furnished by the As per standard design supplied to To be furnished by As per standard design supplied
catalogue/ Model No. bidder/manufacturer at NEA the to NEA
the time of bidding bidder/manufactur
er at the time of
bidding

4. Rated voltage kV 12 12 12 12
5. Number of possible operations without maintenance:

for contacts
- Rated short circuit breaking current No. 100 100 100 100
- Rated normal current No. 10,000 10000 10,000 10000
for mechanism No. 2,000 10000 2,000 10000
6. Frequency Hz 50 50 50 50
7. Rated current
a) normal current A 1250 1250 800 1600
b) short circuit current for 3 sec. kA 25 25 25 25
8. Vacuum Interrupter
a) Make CGL
b) Rating A 12kV 12kV
9. Interrupting current (rms. sym.) kA 25 25 25 25
10. Interrupting time ms 60 </= 60 60 </= 60
11. Making current peak kA 62.5 63 62.5 63
12. Closing time, max ms 120 </=120 120 </=120
13. Insulation level
a) Impulse withstand voltage kV 75 75 75 75
b) Power frequency withstand kV 28 28 28 28
voltage (1 min. rms.)
14. Operating mechanism
a) Type Spring with motor Spring with motor charging Spring with motor Spring with motor charging
charging charging
b) Operating voltage range
- closing % of 110V 85-110% 85-110% 85-110% 85-110%

- tripping % of 110V 70-110% 70-110% 70-110% 70-110%

c) Closing and tripping coils current A As per standard design supplied to As per standard design supplied
d) Duty cycle CO-15sec-CO NEA
CO-15sec-CO CO-15sec-CO to NEA
CO-15sec-CO
15. Spring charging motor
a) Type and manufacturer Reputed make Reputed make
b) Voltage V 110 DC 110V DC 110 DC 110V DC
c) Rating kW spring operated spring operated
d) Spring charging time sec 15 <30 15 <30
16. Total no of auxiliary contacts
a) Normally open No. 8 8 8 8
b) Normally closed No. 8 8 8 8
c) Contact ratings (make and Siemens/L & T / EQ. make Siemens/L & T / EQ. make
continuous current)
-AC at 230 volt A 1 1 1 1
-DC inductive at 110 volt A 0.5 0.5 0.5 0.5
18. Overall dimensions (L* W * H) mm Shall be furnished during detail Shall be furnished during detail
engg. engg.
D. Current transformers
1. Manufacturer CGL/Silkans/JSL/SG CGL/Silkans/JSL/SG
Electrical/ECS Electrical/ECS

2. Type cubicle cubicle mounted, expoxy resin cubicle cubicle mounted, expoxy resin
mounted, epoxy resin mounted, epoxy
resin
3. Manufacture's designation as per submitted catalogue/ To be furnished by the Indoor resin cast To be furnished by Indoor resin cast
Model No. bidder/manufacturer at the
the time of bidding bidder/manufactur
er at the time of
bidding
4. Frequency Hz 50 50 50 50
5. Voltage class kV 12 12 12 12
6. Reference standard IEC IEC IEC IEC
7. Current transformer rating 800-400/1 1200/2400/5A 200-100/1 200-400/5A
8. Insulation level
a) Impulse withstand (BIL) kV, crest 75 75 75 75
b) Power frequency withstand (1 min. rms.) kV 28 28 28 28
9. Burden per phase VA 15 15 15 15
10. No. of cores No. 3 2 2 2
11. Accuracy class 5P20 (PS) for 0.5 5P20 for 0.5
protection & 0.5 for protection & 0.5
metering for metering
E. Voltage transformer
1.    Manufacturer CGL/Silkans/KAPPA/ECS -
2. Type Incomor cubical mounted -
3. Manufacture's designation as per submitted catalogue/ To be furnished by the Indoor resin cast
Model No. bidder/manufacturer at
the time of bidding

4. Frequency Hz 50 50 -
5. Voltage class kV 12 12 -
6. Reference standard IEC IEC -
7. Rated voltage
a) Primary V 11000 11000 -
b) Secondary V 110 110 -
8. Rated burden VA 100 100 -
9. Accuracy class 0.5 0.5 -
10. Insulation level
a) Impulse withstand voltage (BIL) kV 75 75 -

crest
b) Power frequency withstand voltage (1 min. rms.) kV 28 28 -

11. Overall dimensions (L* W* H) mm shall be furnished during detail -


engg.
12. Weight kg -
13. Fuses (HV/LV)
a) Type -
b) Continuous rating A as per requirement -
c) Symmetrical fault rating kA -
F. Switchgear assembly
1. Type of switchgear Indoor metal clad Indoor metal clad
2. Enclosure
a) Type MS MS
b) Thickness of metal sheet (min) mm 2 2 2 2
c) Degree of protection provided by the enclosure IP43 IP 4X IP43 IP 4X

3. Breaker assembly
a) Breaker provided with service test and withdrawn Yes/No Yes yes Yes yes
position
b) Type of indication provided for breaker position LED LED LED LED

c) Cubicle door can be closed with breaker in service or Yes/No yes yes
test position
4. Space heater
a) Thermostat controlled space heater furnished for each Yes/No Yes yes Yes yes
cubicle?
b) Rating
- Voltage V, AC 230 230 230 230
- Watts W
5. Overall dimension (L * W * H) (of complete panel) mm As per design As per design

6. Approximate weight (complete panel) kg 1000Kg 1000Kg


7. Shipping dimension (L *W * H) (of complete panel) mm 2140 x 650 x 2220 2140 x 650 x 2220

G. Relays
1. Manufacturer & country of origin EASUN EASUN
REYROLLE/EQ.Make,India REYROLLE/EQ.Make,India
2. Manufacture's designation as per submitted catalogue/ To be furnished by the MIT 114 MIT 114
Model No. bidder/manufacturer at
the time of bidding

3. Years of manufacturing service Years 10 >10 year 10 >10 year


4. Applicable standard IEC IEC IEC IEC
5. Type Numeric Numeric Numeric Numeric
6. Current setting
a)       Over Current % of rated 20 - 250 20 - 250 20 - 250 20 - 250

current
b)      High set (Instanteneous) 200-2500 yes 200-2500 yes
c)       Earth Fault % of rated 10 – 100 10-100 10 – 100 10-100

d)      High set (Instanteneous) current 50-500 yes 50-500 yes


7. Characteristics IDMT (SI) IDMT(Inverse) IDMT (SI) IDMT(Inverse)
8. Reset time ms
9. Insulation test according to IEC Yes/No Yes yes Yes yes
10. Indication Yes yes
- light emitting diodes provided? Yes/No Yes yes
H. Annunciator type as per requirement as per requirement
I. Delivery of equipment in months month not mentioned not mentioned
following award of contract.
(allowing time for approval of
drawings)
ITEM No 8.1: 110 V & 48 V BATTERY
DESCRIPTION UNIT REQD.110 V OFFERED DATA 110 V REQD. 48 V OFFERED DATA 48 V

1. Manufacturer and Country of Origin HBL Power Systems Ltd., India HBL Power Systems Ltd., India
2. Manufacturing experience years 10 20 10 20
3. Type of battery Maintenance Maintenance Maintenance Maintenance
free valve regulated free valve regulated lead Acid free valve free valve regulated lead Acid
lead Acid regulated lead
Acid
4. Applicable standards IEC IEC 60896 - 21 & 22 2004 IEC IEC 60896 - 21 & 22 2004
5. Number of cells No. 56 24
6. Number of units No. 14 6
7. Number of cells in a unit No. 4 4
8. Nominal voltage rating V 110 110 48 48
9. Nominal capacity at 270C at 10 h discharge time to AH 400 400 400 400
cell end voltage 1.75
10. Ampere capacity at 270C at 15 min discharge time A >300 421 >80 >80
to cell end voltage 1.75
11. Battery construction (type) MAS.S. Mounting Frame with acid MAS.S. Mounting Frame with
resistance powder coating acid resistance powder coating

12. Type of plates


a) Positive ( flat or tubular ) Flat plasted Flat plasted
b) Negative Flat plasted Flat plasted
13. Type of rack 2610±15 x 445 ±1189±12mm 770±15 x 445 ±5 x 1376±8mm
-           Rack dimensions
14. Float charging voltage V 2.25±0.005V/ceel at 25 deg. C 2.25±0.005V/ceel at 25 deg. C
15. Equalizing charging voltage V 2.30±0.005V/ceel at 25 deg. C 2.30±0.005V/ceel at 25 deg. C
16. Internal resistance of one cell ohm 0.37 0.37
17. Short circuit current withstand capacity A
18. Float charging current A 10 10
19. Charging current of a fully discharged battery at 8 Catalouge provided Catalouge provided
hour charging rate A
20. End voltage of each cell V 1.75 1.75
21. Charging efficiency of the battery %
22. Max. duration in month, the battery can be kept month <0.5% per week at 25 deg C <0.5% per week at 25 deg C
without charging
23. Battery life (guaranteed value) years 20 20
24. Rack interconnection furnished? Yes Yes Yes Yes
25. Delivery of equipment in months following month not menyioned not mentioned
award of contract (allowing time for approval of
drawings)
ITEM No 8.2: 110 V & 48 V BATTERY CHARGERS
DESCRIPTION UNIT REQD.110 V OFFERED DATA 110 V REQD. 48 V OFFERED DATA 48 V

1. Manufacturer and Country of Origin HBL Power Systems Ltd., India HBL Power Systems Ltd., India

2. Manufacturing experience years 10 20 10 20


3. Type of charger constant voltage Constant Voltage with current limit constant voltage constant voltage

4. Applicable standard IEC IEC 60146 IEC IEC


5. Manufacturer’s designation as per submitted To be Furnished by the 110 TP 80 Main and standby To be Furnished 48 TP 80 Main and standby
catalogue bidder/manufacturer at FCBC, with DVR by the FCBC, with DVR
the time of bidding bidder/manufactur
er at the time of
bidding

6. Output rating A 80 80 20 80
7. Range of DC voltage variation ±V 99V to 126.5V 43.2 V to 55.2 VV to 126.5
8. Maximum AC input kVA 16.86 KVA 7.3 KVA
9. Input Voltage / phase V 400 V, 3 ph 400 V, 3 ph 400 V, 3 ph 400 V, 3 ph
10. Ripple % < 2% < 2% < 2% < 2%
11. Efficiency of charger at 100 % output % 75% at full load 75% at full load
12. Temperature rise above ambient of 40 degree C

a) Solid state elements 0


C 90 deg C 90 deg C
b) Wound elements 0
C 90 deg C 90 deg C
13.Voltage regulation % +3% to -2% max +3% to -2% +3% to -2% max +3% to -2%
14. Float voltage adjustment 123.75V (adj) 54V
15. Equalizing voltage adjustment Boost 126.5V Boost 55.2V
16. Auto equalizing charge provided? Yes/No Yes Yes Yes Yes
17. Timer for equalizing charge provided? Yes/No Yes Yes Yes Yes
18. End switching to limit equipment type
19. Manual over-ride switch for selection of Yes/No Yes Yes Yes Yes
float/equalizing charge provided?
20. Delivery of equipment in months following award of month 2.5 2.5
contract (allowing time for approval of drawings)

ITEM No. 11C: 11kV POWER CABLE


DESCRIPTION REQD. for REQD. for Outgoing feeders DATA for DATA for
11 kV incomer Outgoing feeders
11 kV
UNIT incomer
1. Manufacturer & country of origin Zhengzhou Yifang Cable Co., Ltd
2.Years of manufacturing experience Years 10 10 10
3. Type 400MM2 240MM2
4. Reference standard IEC IEC 60502 IEC 60502
5. Number of cores Single/
three Single core Single core Single core Single core
6. Voltage rating
a) Nominal System Voltage kV 11 11 11 11
b) Max. system voltage kV 12 12 12 12
c) Voltage grade of cable (U0 /U)
d) Rated voltage between conductor and screen
kV 12/Ö 3 12/Ö3 12/Ö3 12/Ö3
e) Rated voltage between two conductors kV 12 12 12 12
7. Maximum conductor temperature
a) Continuous 0
C 90 90 90 90
b) Short time 0
C 250 250
8. Conductor material Copper Aluminum Copper Aluminum
9. Conductor
a) Cross section of conductor Suitable for 1500 A 400 240
continuous current
mm2 rating ³240
b) No. of Runs or Loops proposed, if any
c) Cross section of each wire mm2 400 240 400 240
d) No. & diameter of wire in each conductor 60/2.97 36/2.97
No./ mm (Compacted) (Compacted)
e) Class of stranding B B
f) Insulation
- Material XLPE XLPE XLPE XLPE
- Thickness mm
g) Overall jacket 3.4 3.4
- Material PVC PVC PVC PVC
- Thickness mm 1.2 1.2
h) Approximate overall diameter mm 45 40
i) Standard drum length meter 600 1200
j) Net weight of cable in drum kg 3324 2763
k) Continuous current rating at 40 deg. C ambient
A
-In ground A >1500 700 43
-In duct A >1500 685 415
l) Short circuit current
- 0.1 sec. kA 180 69
- 1.0 sec. (Minimum kA) kA 25 25 57 22
m) Electrical parameter
- Resistance / km ohm 0.047 0.125
- Reactance / km ohm 0.1477 0.1536
- Capacitance / km micro F 0.5331 0.429
10. Armor sheath provided? Yes/No Yes Yes(AI tape) Yes(AI tape)
10. Armor sheath provided? Yes/No Yes Yes(AI tape) Yes(AI tape)
12. Delivery of equipment in months following award of 1 1
contract (allowing time for approval of drawing)
month

ITEM No 12: LOW VOLTAGE POWER CABLE


DESCRIPTION UNIT REQUIRED DATA GUARANTEED DATA
1. Manufacturer and Country of Origin Lumbini Vidyut Udog Pvt Ltd.,
Nepal
2. Type
3. Applicable standard IEC IS 1554 Part : 1988
4. Voltage rating
a) Suitable for max.system voltage V 600 1100
b) Voltage grade of the cable( Uo/U) V 600/1100
c) Rated voltage between each conductor and screen V 600

d) Rated voltage between two conductors V 1100


5. Conductor material Copper Copper
6. Insulation material Polyethylene Polyethylene
7. Overall jacket material PVC PVC
8. Net weight of cable kg/m Depends upon No. of Cores and
cross-sectional area
9. Technical literature submitted Yes/No Yes Yes
10.Type test certificate submitted Yes/No Yes Yes
11. Delivery of equipment in months following award of not mentioned
contract. (Allowing time for approval of drawing.)

ITEM No 13: CONTROL CABLE

DESCRIPTION UNIT REQUIRED DATA GUARANTEED DATA


1. Manufacturer and Country of Origin Lumbini Vidyut Udog Pvt Ltd.,
Nepal
2. Type
3. Applicable standard IEC IS 1554 Part : 1988
4. Voltage rating
a) Suitable for max. system voltage V 600 1100
b) Voltage grade of the cable( Uo/U) V 600/1100
c) Rated voltage between each conductor and screen V 600

d) Rated voltage between two conductors V 1100


5.Conductor material Copper Copper
6. Conductor
7. Insulation material Polyethylene Polyethylene
8. Overall jacket material PVC PVC
9. Net weight of cable kg/m Depends upon No. of Cores and
cross-sectional area
10. Technical literature submitted Yes/No Yes Yes
11. Type test certificate submitted Yes/No Yes Yes
12. Delivery of equipment in months following month not mentioned
award of contract. (Allowing time for approval of
drawing.)
7.1: 132 kV LINE, BUS-COUPLER & 33/11 kV TRANSFORMER CONTROL & RELAY PANELS
DESCRIPTION UNIT REQD. Offered Offered
Line/ Bus Coupler Line / Bus Coupler Panel (offer Line / Bus Coupler Panel(offer 2)
Panel 1)

CONSTRUCTION OF CONTROL AND RELAY PANELS


1. Manufacturer and country of origin Easun Reyrolle Ltd., India AREVA T&D Ltd.,India

2. Manufacturing experience years 10 more than 25 years more than 10 years


3. Type (simplex/duplex) Duplex** Duplex for 132 kV simplex for 33 Duplex/simplex
kV
4. Applicable standard IEC IEC IEC 61850
5. Control panels furnished as per specification? Yes/No Yes yes yes

6. Enclosure protection class IP IP 43 IP 43 IP 52


7. Thickness of sheet metal used
a) Front and rear portion mm >=3 3 >=3
b) Side, top & bottom covers mm >=2 2 >=2
c) Doors mm >=3 3 >=3
8. All instruments, meters, relays and control switches flush flush flush
flush or semi‑flush type? type type
9. Ground bus
a) Material copper copper copper
b) Size mm x mm 25 x 6 25x6 2 x25 x 3mm
10. Overall dimension of control boards (LxWxH) mm 1000mm(L) X 610mm (W) X 2312mm(H) x 600mm(D) x
2300mm(H) for simplex panel 800/1000mm(W)
maximum
11. Shipping data 2312mm(H) x 600mm(D) x
800/1000mm(W)

a) Size of the large package (LxWxH) mm 2200mm(L) X 810mm (W) X


2500mm(H)
b) Weight of the heaviest package Kg 500 kg ˜300kg
12. Delivery of equipment in months following award of month 3-4 months from the date of recepit 6 weeks from the date of recepit of
contract. (Allowing time for approval of drawing) of final approved drawinds final approved drawinds

13.Indicating Instruments
a) Ammeter
Manufacturer's designation / Model No. AE/MECO MAKE - India AE
Type Digital Digital
Accuracy class 0.5 0.5 0.5
Scale
- Type of scale linear / NA Linear
non-linear

‑ Range of indication (...../1 A CT operated) A 800-400-200/1A 0-800 or as per your requirement 800/600/300/1A

DESCRIPTION UNIT REQD. Offered


Line/ Bus Coupler Line / Bus Coupler Panel
Panel
b) Voltmeter
Manufacturer's designation / Model No. AE/MECO MAKE - India AE
Type Digital Digital
Accuracy class 0.5 0.5 0.5
Scale
‑ Range of indication kV 0-150 0-150 or as per your requirement 0-150

- Linear / non-linear Linear


c) Active power meter
Manufacturer's designation / Model No. AE/MECO MAKE - India AE
Type Digital Analogue
Manufacturer's type designation
Applicable standard IEC IEC IEC
Rated voltage kV 132/Ö 3: 110V (PT secondary) As per your requirement

0.11/Ö3
Rated current A 800-400-200/1A 1A(or)5A(CT SEC) As per your requirement
Current range mA To be supplied as part of the As per your requirement
(Transducer operation) instrument
Accuracy class 0.5 IS 1248,classI
Scale
- Type of scale log Center zero yes Center zero
‑ Range of indication MW 100-0-100 as per specification 100-0-100
200-0-200 200-0-20
- Linear / non-linear linear Linear
d) Frequency meter AE/MECO MAKE - India AE
Manufacturer's designation / Model No. Digital
DESCRIPTION UNIT REQD. Offered Offered
Line/ Bus Coupler Line / Bus Coupler Panel (offer Line / Bus Coupler Panel(offer 2)
Panel 1)
Digital
Range of indication Hz 47-53 47-53
e) Energy Meter
Manufacturer's designation / Model No. Elster L & T/Elster/Secure
Type electronic electronic 3-phase 4- wire electronic 3-phase 4- wire
3- ph, 4 wire
Applicable standard IEC IEC IEC
Class of accuracy 0.2 0.2 0.2
Import and export meter provided Yes/No Yes yes yes
Rated voltage kV 132/Ö3: 132/Ö3: As per your requirement
0.11/Ö3 0.11/Ö3
Rated current A 800-400-200/1A 0-800 or as per your requirement

VA burden VA 0.1 VA
f) Annunciators
Manufacturer's designation / Model No. ALAN/BHARANI MAKE-INDIA ALAN/MINILAC/INSTALAM

Type Numeric Microprocessor Static/Microprocessor based

Number of inputs (annunciator /event)


Number of active points No. 18 18 18
Number of rows No. 3 3 3
Number of columns No. 6 6 6
Type of mounting flush flush flush
DESCRIPTION UNIT REQD. Offered
Line/ Bus Coupler Line / Bus Coupler Panel
Panel
Replacement of individual inscription plates and lamps Yes/No Yes Yes no
from front panel possible?
Sequence of operation as per specifications Yes/No Yes Yes yes
g) Phase Over-current Relays: (Directional & Non-
directional)
Manufacturer's designation / Model No. MICOMP 141
Type numeric numeric numeric
Applicable standards IEC IEC IEC 61850
Triple pole or single pole Triple pole Four pole(3O/C & 1E/F) Triple pole
Continuous overload capacity x In 3.0 x In continous phase/earth 4 In

Current setting range % of rated 20 - 200% 5 - 250% 50-200%


current
Operating time at 10 times current setting (max.) sec 3 3 3
Reset time ms <50 ms
Characteristics
- IDMT(standard inverse) IDMT IDMT IDMT
- IDMT(very inverse) (standard (standard (standard
- IDMT(extremely inverse) inverse) inverse) inverse)
- Definite time
Instantaneous unit provided Yes/No Yes yes yes
- Current setting range % of rated 500-2000% for directional 1a/5A
current 50-5250% for non directional
-     Operating time ms <30
h) Ground Over-current Relays: (Directional & Non- In built in phase overcurrent relay In built in phase overcurrent relay
directional)
Manufacturer's designation / Model No. MICOMP 141
Type numeric numeric
Applicable standards IEC IEC 61850
Single pole/Triple pole three pole Triple pole

Continuous overload capacity x In 4 In


Current setting range % of rated 10 - 80% 10-80%
current
Operating time at 10 times current setting (max.) sec 3 3
Reset time ms <50ms
Characteristics
- IDMT(standard inverse) IDMT IDMT (standard inverce)
- IDMT(very inverse) (standard inverse)
- IDMT(extremely inverse)
-           Definite time
Instantaneous unit provided Yes/No Yes Yes
- Current setting range % of rated 10-80%
current
-           Operating time ms <30

i) Bus / Transformer Differential Relay


Manufacturer's designation / Model No. MICOMP 632
Applied standards IEC IEC
DESCRIPTION UNIT REQD. Offered Offered
Line/ Bus Coupler Line / Bus Coupler Panel (offer Line / Bus Coupler Panel(offer 2)
Panel 1)

Type numeric numeric


Current magnitude difference setting range % of
rated as per requirement
secondary

current
j) SYNCHRO-CHECK RELAY In built in distance relay relay
Manufacturer's designation / Model No. In built in MICOMP 442
Applied standards IEC IEC
Type Numeric Numeric
Rated input measuring voltage V
Voltage magnitude difference setting range % of 5%-30% 2% to 10%
Vn of Vn
Phase angle difference Degrees 50 - 300 35o
setting range
Frequency difference setting range Hz 0.05 - 0.5 0.04-0.19
Operating time ms 200ms
Reset time ms as per requirement
Specify whether each relay incorporate with the following
options of reclosing on:
- Dead bus - live line Yes/No Yes
- Dead line - live bus Yes/No Yes
If the options of reclosing on dead bus- live line and dead
line- live bus are separately furnished and mounted,
specify:
- Type.
-Voltage rating V
k) Auxiliary Tripping & Lockout Relays
Manufacturer's designation / Model No. Easun Reyrolle make -AR/TR VAJHM23
Series
Applicable standards IEC IEC IEC
Type static/ numeric Electromecamical static
Operating time ms 10ms 10ms
l) BREAKER FAILURE RELAY
Manufacturer's designation / Model No. Easun Reyrolle make -ARGUS-1 Built in P441

Applicable standards IEC IEC IEC


Type numeric numeric communicable numeric
Setting range A 0.10 to 2.50 x In step of 0.05 for
phase fault 0.10 to 2.50 xIn step of
0.05 for earthfaults
Trip steps 2, 0.01 - 20sec, 0.01-20sec
- number of trip steps No.
- adjustable time of 1st step ms
- adjustable time of 2nd step ms
- both in steps ms
Operating times >= 30msec
- maximum operating time ms 60sec step 1 sec
- reset time ms
m) Distance Relay
Manufacturer's designation / Model No. SEL, USA,SEL 311C MiCOMP P441
Applicable standards IEC IEC 103/MODBUS
Type numeric numeric communicable numeric
No of zones 3
- forward direction 3 3
- reverse direction 1 1
- Zone reach setting ranges including steps -
- Zone 1 W/phase 0.25-320ohms 0.1-500 in steps of 0.01ohm
- Zone 2 W/phase
- Zone3 W/phase
- Reverse Zone W/phase
Zone timer setting ranges including steps
- Zone 2 sec 0-320s 0-10sec in steps 2 msec
- Zone 3 sec
- Reverse Zone sec
Directional sensitivity
- Single phase and phase to phase faults yes as per requirement
- Three phase faults yes as per requirement
Are the following features incorporated in each
distance relay?
Instantaneous tripping when closing on three phase Yes/No Yes yes yes
zero volt bolted fault
Carrier auxiliary relays for additional following carrier/ yes, provided yes
optical transfer trip schemes
- Zone acceleration Yes/No Yes Yes yes
- Permissive under reaching Yes/No Yes Yes yes
DESCRIPTION UNIT REQD. Offered Offered
Line/ Bus Coupler Line / Bus Coupler Panel (offer Line / Bus Coupler Panel(offer 2)
Panel 1)

- Permissive overreaching Yes/No Yes Yes yes


Auxiliary tripping relays Yes/No Yes Yes yes
Single pole tripping and reclosing scheme Yes/No Yes Yes yes
Operation indicators for each function Yes/No Yes yes
Alarm for auxiliary DC voltage failure Yes/No Yes yes
Built-in test facilities Yes/No Yes yes
Power swing blocking facility Yes/No Yes Yes yes
VT supply supervision facility Yes/No Yes Yes yes
Specify whether the distance relay is insensitive to: yes
-Frequency changes Yes/No Yes yes
-Power swing (Hunting) Yes/No Yes yes
-Capacitive loading Yes/No Yes yes
Fault Locator Inbuilt in distance relay Inbuilt in distance relay yes
(inbuilt / separate)
Accuracy % <3% <3% as the time of details engineering
Calculating time ms < 20 20ms
Does the fault locator incorporate following features:

- Independent of the fault type Yes/No Yes Yes yes


- phase selection indication Yes/No Yes Yes yes
Mis-operation protection for loss-of-potential due to short Yes/No Yes Yes yes
circuit in the secondary of CVT

OPTION B for Distance relay ( Easun Reyrolle Panel

Manufacturer's designation / Model No. EASUN Reyrolle Ltd., India -


OHMEGA
Applicable standards IEC IEC
Type numeric numeric communicable
No of zones
- forward direction 3 3
- reverse direction 1 1
- Zone reach setting ranges including steps
- Zone 1 W/phase 0.1-250ohms for 1A 0.1 : 500ohms
- Zone 2 W/phase for 5A
- Zone3 W/phase
- Reverse Zone W/phase
Zone timer setting ranges including steps
- Zone 2 sec 10-10sec in step of 10 msec
- Zone 3 sec
- Reverse Zone sec
Directional sensitivity
- Single phase and phase to phase faults cross polarization for single phase
& phase to phase
- Three phase faults memory polarization for 3 -phase
fault
Are the following features incorporated in each
distance relay?
Instantaneous tripping when closing on three phase Yes/No Yes yes
zero volt bolted fault
Carrier auxiliary relays for additional following carrier/ yes
optical transfer trip schemes
- Zone acceleration Yes/No Yes Yes
- Permissive under reaching Yes/No Yes Yes
- Permissive overreaching Yes/No Yes Yes
Auxiliary tripping relays Yes/No Yes Yes
Single pole tripping and reclosing scheme Yes/No Yes Yes
Operation indicators for each function Yes/No Yes
Alarm for auxiliary DC voltage failure Yes/No Yes
Built-in test facilities Yes/No Yes
Power swing blocking facility Yes/No Yes Yes
VT supply supervision facility Yes/No Yes Yes
Specify whether the distance relay is insensitive to:
-Frequency changes Yes/No Yes
-Power swing (Hunting) Yes/No Yes
-Capacitive loading Yes/No Yes
Fault Locator Inbuilt in distance relay Inbuilt in distance relay
(inbuilt / separate)
DESCRIPTION UNIT REQD. Offered
Line/ Bus Coupler Line / Bus Coupler Panel
Panel
Accuracy % <3% <3%
Calculating time ms < 20 20ms
Does the fault locator incorporate following features:
DESCRIPTION UNIT REQD. Offered Offered
Line/ Bus Coupler Line / Bus Coupler Panel (offer Line / Bus Coupler Panel(offer 2)
Panel 1)

- Independent of the fault type Yes/No Yes Yes


- phase selection indication Yes/No Yes Yes
Mis-operation protection for loss-of-potential due to short Yes/No Yes Yes
circuit in the secondary of CVT
INE, BUS-COUPLER & 33/11 kV TRANSFORMER CONTROL & RELAY PANELS
DESCRIPTION UNIT REQD. Offered Transformer Panel Offered Transformer
Transformer Panel (offer 1) Panel (offer 2)

CONSTRUCTION OF CONTROL AND RELAY PANELS


1. Manufacturer and country of origin Easun Reyrolle Ltd., India AREVA T&D
Ltd.,India
2. Manufacturing experience years 10 more than 25 years more than 10 years
3. Type (simplex/duplex) Duplex Duplex for 132 kV simplex for 33 Duplex/simplex
kV
4. Applicable standard IEC IEC IEC 61850
5. Control panels furnished as per specification? Yes/No Yes Yes
yes
6. Enclosure protection class IP IP 43 IP 43 IP 52
7. Thickness of sheet metal used
a) Front and rear portion mm >=3 3 >=3
b) Side, top & bottom covers mm >=2 2 >=2
c) Doors mm >=3 3 >=3
8. All instruments, meters, relays and control switches flush fluse flush
flush or semi‑flush type? type type
9. Ground bus
a) Material copper copper copper
b) Size mm x mm 25 x 6 25 x 6
10. Overall dimension of control boards (LxWxH) mm 1000mm(L) X 610mm (W) X 2312mm(H) x
2300mm(H) for simplex panel 600mm(D) x
maximum 800/1000mm(W)
11. Shipping data 2312mm(H) x
a) Size of the large package (LxWxH) mm 2200mm(L) X 810mm (W) X 600mm(D) x
2500mm(H) 800/1000mm(W)
b) Weight of the heaviest package Kg 500 kg ˜300kg
12. Delivery of equipment in months following award of month 3-4 months from the date of 6 weeks from the date
contract. (Allowing time for approval of drawing) recepit of final approved drawinds of recepit of final
approved drawinds
13.Indicating Instruments
a) Ammeter
Manufacturer's designation / Model No. AE/MECO MAKE - India AE
Type Digital Digital
Accuracy class 0.5 0.5 0.5
Scale
- Type of scale linear / NA Linear
non-linear

‑ Range of indication (...../1 A CT operated) A 400-200/1A 0-400 or as per your requirement 200/100/1A

b) Voltmeter
Manufacturer's designation / Model No. AE/MECO MAKE - India AE
Type Digital Digital
Accuracy class 0.5 0.5
Scale
‑ Range of indication kV 0-150 or as per your requirement 0-150

- Linear / non-linear Linear


c) Active power meter
Manufacturer's designation / Model No. AE/MECO MAKE - India AE
Type Analogue
Manufacturer's type designation
Applicable standard IEC IEC IEC
Rated voltage kV 132/Ö 3: 110V (PT secondary) As per your
requirement
0.11/Ö3
Rated current A 400-200/1A 1A(or)5A(CT SEC) As per your
Current range mA To be supplied as part of the requirement
As per your
(Transducer operation) instrument requirement
Accuracy class 0.5 IS 1248,classI
Scale
- Type of scale log yes Center zero
DESCRIPTION UNIT REQD. Offered Transformer Panel Offered Transformer
Transformer Panel (offer 1) Panel (offer 2)

‑ Range of indication MW 0-25 as per specification 100-0-100


0-50 200-0-20
- Linear / non-linear linear Linear
d) Frequency meter - AE
Manufacturer's designation / Model No. -
Range of indication Hz - 47-53
e) Energy Meter
Manufacturer's designation / Model No. Elster L & T/Elster/Secure
Type electronic electronic 3-phase 4- wire electronic 3-phase 4-
3- ph, 4 wire wire
Applicable standard IEC IEC IEC
Class of accuracy 0.2 0.2 0.2
Import and export meter provided Yes/No Yes yes yes
Rated voltage kV 132/Ö3: 132/Ö3: As per your
0.11/Ö3 0.11/Ö3 requirement
Rated current A 400-200/1A 0-400 or as per your requirement

VA burden VA 0.1 VA
f) Annunciators
Manufacturer's designation / Model No. ALAN/BHARANI MAKE- ALAN/MINILAC/INS
INDIA TALAM
Type Numeric Microprocessor Static/Microprocessor
based
Number of inputs (annunciator /event)
Number of active points No. 24 24 18
Number of rows No. 3 3 3
Number of columns No. 8 8 6
Type of mounting flush flush flush
Replacement of individual inscription plates and lamps Yes/No Yes Yes no
from front panel possible?
Sequence of operation as per specifications Yes/No Yes Yes yes
g) Phase Over-current Relays: (Directional & Non-
directional)
Manufacturer's designation / Model No. MICOMP 141
Type numeric numeric numeric
Applicable standards IEC IEC IEC 61850
Triple pole or single pole Triple pole Four pole(3O/C & 1E/F) Triple pole
Continuous overload capacity x In 3.0 x In continous phase/earth 4 In

Current setting range % of rated 20 - 200% 5 - 250% 50-200%


current
Operating time at 10 times current setting (max.) sec 3 3 3
Reset time ms <50 ms
Characteristics
- IDMT(standard inverse) IDMT IDMT IDMT
- IDMT(very inverse) (standard (standard (standard
- IDMT(extremely inverse) inverse) inverse) inverse)
- Definite time
Instantaneous unit provided Yes/No Yes yes yes
- Current setting range % of rated 50-25250% 1a/5A
current
-     Operating time ms <30
h) Ground Over-current Relays: (Directional & Non- In built in phase overcurrent relay In built in phase
directional) overcurrent relay
Manufacturer's designation / Model No. MICOMP 141
Type numeric numeric
Applicable standards IEC IEC 61850
Single pole/Triple pole three pole Triple pole

Continuous overload capacity x In 4 In


Current setting range % of rated 10 - 80% 10-80%
current
DESCRIPTION UNIT REQD. Offered Transformer Panel Offered Transformer
Transformer Panel (offer 1) Panel (offer 2)

Operating time at 10 times current setting (max.) sec 3 3


Reset time ms <50ms
Characteristics
- IDMT(standard inverse) IDMT IDMT (standard
- IDMT(very inverse) (standard inverse) inverce)
- IDMT(extremely inverse)
-           Definite time
Instantaneous unit provided Yes/No Yes Yes
- Current setting range % of rated 10-80%
current
-           Operating time ms <30

i) Bus / Transformer Differential Relay


Manufacturer's designation / Model No. Easun Reyrolle make DUOBUAS
M MICOMP 632
Applied standards IEC IEC IEC
Type numeric numeric communicable numeric
Current magnitude difference setting range % of Initial setting: 10% to 200% step
rated 5% Bias slope : o% to 70% step as per requirement
secondary 5% Bias slope limit : 1 to 20 x In
step 1
current
j) SYNCHRO-CHECK RELAY
Manufacturer's designation / Model No. In built in MICOMP
Applied standards 442
IEC
Type Numeric
Rated input measuring voltage V
Voltage magnitude difference setting range % of 2% to 10%
Vn
Phase angle difference Degrees 35o
setting range
Frequency difference setting range Hz 0.04-0.19
Operating time ms as per requirement
Reset time ms
Specify whether each relay incorporate with the following
options of reclosing on:
- Dead bus - live line Yes/No
- Dead line - live bus Yes/No
If the options of reclosing on dead bus- live line and dead
line- live bus are separately furnished and mounted,
specify:
- Type.
-Voltage rating V
k) Auxiliary Tripping & Lockout Relays
Manufacturer's designation / Model No. Easun Reyrolle make -AR/TR VAJHM23
Series
Applicable standards IEC IEC IEC
Type static/ numeric Electromecamical static
Operating time ms 10ms 10ms
l) BREAKER FAILURE RELAY
Manufacturer's designation / Model No. Easun Reyrolle make -ARGUS-1 Built in P632

Applicable standards IEC IEC IEC


Type numeric numeric communicable numeric
Setting range A 0.10 to 2.50 x In step of 0.05 for
phase fault 0.10 to 2.50 xIn step
of 0.05 for earthfaults

Trip steps 2, 0.01 - 20sec, 0.01-20sec


- number of trip steps No.
- adjustable time of 1st step ms
- adjustable time of 2nd step ms
- both in steps ms
DESCRIPTION UNIT REQD. Offered Transformer Panel Offered Transformer
Transformer Panel (offer 1) Panel (offer 2)

Operating times >= 30msec


- maximum operating time ms 60sec step 1 sec
- reset time ms

Das könnte Ihnen auch gefallen