Design Guide

(abstract from AB-6536, AB-6656)

DC221-03E

(For Remote unit input/output table)

1. Point type
Analog
input
ID
0
1
AI
Analog
input
2

Analog
output
1

AO3
Analog
output

AO4
Analog
output

(SCP)
Running
monitoring

(OOAm)
ON-OFF
-AUT

OOAt
ON-OFF
-AUT

4 to 20mA

(Local command)

Digital input
2
SOP
Status
AOP
Alarm
SAP
Status
+Alarm

M/M

Digital input/output
Momentary
Maintained Transfer
3
4
5
COPm
COPl
S/S
S/S
(Momentary)

(Maintained)

CCPm
S/S+Status

CCPl
S/S+Status

(Momentary)

(Maintained)

CAPm
S/S+Status
+Alarm

CAPl
S/S+Status
+Alarm

(Momentary)

(Maintained)

(Momentary)

(Transfer)

AO5
Analog
output

HOLm
HI-OFF
-LO

HOLt
HI-OFF
-LO

(Voltage)

(Momentary)

(Transfer)

Totalizer
6
TTD
Pulse
TOT
TTA
Analog
TOT

CCPf
S/S+Status
(Momentary remote)

CAPf
S/S+Status
+Alarm
(Momentary remote)

HOLf
HI-OFF
-LO
(Momentary remote)

Note:

1. The point type ID number is a 2-digit number. Ex. AI: 01, CCPl: 42
2. The following point types are not available for Infilex GC/GD.
Point type: SCP, OOAm
3. If the point has no input/output, such as analog parameter, set pseudo (1).

Para
meter
7
PRD
Digital
parameter
PRA
Analog
parameter

2. Digital Input/Output Point


COP: Command Only Point
SOP: Status Only Point 52X
AOP: Alarm Only Point 51X (ex. Trip alarm)
SAP: SOP + AOP
CCP: COP + SOP + command fail +COS alarm
CCPf (momentary remote): COP + SOP + command fail
CAP: COP + SOP + AOP +command fail + COS alarm
CAPf (momentary remote): COP + SOP + AOP +command fail

Note:
Refer to the document, DC221-01E page 36
COS alarm: Only status changes, although ON/OFF point where receives no command.
Command fail: Status does not change, after ON/OFF point where receives the start and stop
command.
Period monitoring time inhibit command fail (default 2 seconds)

XXXf (momentary remote): detect command fail, not detect COS alarm

Which is better CCP or CAP?


Merit of CAP: CAP can monitor the reason of stop (trouble or remote)

Other digital input/output


OOA: 3 position control (ON/OFF/AUTO) + SOP + command fail + COS alarm
HOL: 3 position control (Hi/Lo/OFF) + status (Hi) + status (Lo) +command fail + COS alarm
Example:
Light: full, half, off
Fan speed: high, low, off

3. Relationship with input/output list

Parameter

Totalizer

Status

CCPl

CCPm or CCPf

Alarm

Output

Name

Point type

Analog

Input/output list table

CAPl
O

CAPm or CAPf
O

OOAm or HOLm or HOLf

O
O

SOP

SAP
O
O

AOP
O

AI
O

TTD
O

AO6
COPl (Usage: point interphone) (DIF-II only)

Symbol

Description

M:

Maintained/Latched output, 1a

C:

Momentary output, 1a+1a

A:

Maintained 3-position output, 1a+1a

4. Point parameter item list

Name displayed

Item name

SOP

SAP

SCP

AOP

COP
mlt

CCP
ml

CAP
mlf

OOA
mlt

HOL
mlt

CCPt

TYPE

Point type

A/D

A/D

IPD

IPD

SEG

Segregation

ABL

Rated power

DLAYs

On delay time

TIMEs

Timeout monitoring time

NRCV

Batch restoration disabled

DI1

I/O DI1

DI2

I/O DI2

DO1

I/O DO1

REC

LOG1

OI Command/COS log
(Not in use.)
Boolean calculation 1

LOG2

Boolean calculation 2

VLV

Switch valve

BCNT

NC contact changeover

TIMs

Alarm decision time

AI

AO3

AO4/5

TTD

TTA

PRD

PRA

TYPE

Name displayed

Point type

Item name

A/D

A/D

IPD

IPD

SEG

Segregation

DPOS

Decimal position

COEF

Coefficient

SCL

Prescale range

RTIO

Sampling ratio

MAXS

High limit

MINS

Low limit

MAX

Output high limit

MIN

Output low limit

FLG

Output

AIS

Linearization table No.

ZERO

Zero adjustment

FBC

Fully-close raw data

Name displayed

Item name

AI

AO3

AO4/5

TTD

TTA

PRD

PRA

FBO

Fully-open raw data

GAP

Gap

HYS

Hysteresis

CLMP

Clamp delete/assign

AOCYs

Minimum output interval

COV

COV

RNG

Input type signal

HYC

AI1

Measuring cycle
Normal/increased interval
I/O

AO1

I/O

TO1

I/O

AIP

Related AI point No.

Note:
When the point is a central monitoring point, not write anything in the column of Central. And set SEG=
10000000.
When the point is not a central monitoring point, write [X] in the column of Central. And set SEG=
00000000.

5. Operation type (Digital Output point)


Point type

Operation type

Description

COPm, CCPm, CAPm

Non-voltage normally open (ON) + normally open (OFF)

Remote control relay output

COPl, CCPl, CAPl

Non-voltage normally open (ON/OFF)

(OOAm) HOLm, HOLf

Non-voltage normally open (ON) + normally open (OFF)

OOAt, HOLt

Non-voltage SPDT

CCPf, CAPf

Non-voltage normally open (ON) + normally open (OFF)

Remote control relay output

6. Analog linearization table (AIS No.)


Linearization
Table No.
Linearization

16, 814, 18
X

7
X

15
Y

16
Y

17

Table
00

0.000

0.000

37.002

7.824

-500

25.431

-200

01

0.000

10.002

100

39.878

50

16.651

-350

31.226

-100

02

0.000

20.000

200

42.754

100

25.413

-200

37.002

03

0.000

30.002

300

45.627

150

34.106

-50

42.754

100

04

0.000

40.000

400

48.480

200

42.754

100

48.480

200

05

0.000

50.002

500

51.333

250

51.333

250

54.183

300

06

0.000

60.000

600

54.183

300

59.863

400

59.863

400

07

0.000

70.002

700

57.032

350

68.327

550

65.520

500

08

0.000

80.000

800

59.863

400

76.746

700

71.139

600

09

0.000

90.002

900

62.693

450

85.085

850

76.746

700

10

0.000

100.00

1000

65.520

500

93.389

1000

82.319

800

Application

Reserve

Linear

Pt 100

Pt 100

Pt 100

Range

0.0 ~ 100.0

0.0 ~ 50.0

-50.0 ~ 100.0

-20.0 ~ 80.0

Unit

Linearization

19

Table No.
Linearization

20

21

22

23

24

Table
00

0.000

37.002

20.561

-30

20.561

150

25.413

-200

0.000

01

10.002

10

42.754

100

79.439

30

79.439

300

23.312

-150

15.258

500

02

20.000

20

48.480

200

0.000

0.000

31.226

-100

0.000

03

30.002

30

54.183

300

0.000

0.000

34.106

-50

0.000

04

40.000

40

59.863

400

0.000

0.000

37.002

0.000

05

50.002

50

65.520

500

0.000

0.000

39.878

50

0.000

06

60.000

60

71.139

600

0.000

0.000

42.754

100

0.000

07

70.002

70

76.746

700

0.000

0.000

45.627

150

0.000

08

80.000

80

82.319

800

0.000

0.000

48.480

200

0.000

09

90.002

90

87.866

900

0.000

0.000

51.333

250

0.000

10

100.00

100

93.389

1000

0.000

0.000

54.183

300

0.000

Inside Neopanel,
Application

Humidity (Linear)

Pt 100

Relative Value

Absolute Value

Neoplate

Neoplate

inside wireless
Pt 100

Neopanel, Wireless
sensors
(Temperature)

Ranges

0 ~ 100

0.0 ~ 100.0

-3.0 ~ 3.0

15.0 ~ 30.0

-20.0 ~ 30.0

0.0 ~ 50.0

Unit

Note: Set the number of Linearization Table in the column of AIS No for each AI point.

Linearization

25

Table No.
Linearization

26

27~99

Table
00

0.000

0.000

0.000

01

3.052

100

7.782

255

0.000

02

0.000

0.000

0.000

03

0.000

0.000

0.000

04

0.000

0.000

0.000

05

0.000

0.000

0.000

06

0.000

0.000

0.000

07

0.000

0.000

0.000

08

0.000

0.000

0.000

09

0.000

0.000

0.000

10

0.000

0.000

0.000

Buttery Shortage

Application

Humidity (Linear)

Ranges

0 ~ 100

0.0 ~ 255.0

Unit

For JOB

Notice

7. Signal type
Point type
AI

Input symbol
PT

Description

I/O Module model number

PT100ohms 0-50 C

RY5004P0000
RY5004J0000 (AIx2, PTx2)

PT100ohms 0-100 C
PT100ohms -20-80 C
PT100ohms -20-30 C
PT100ohms -50-100 C
AIA

Current input 4-20 mA DC

AIV1

Voltage input 1-5 V DC

AIV2

Voltage input 0-5 V DC

AIV4

Voltage input 0-10 V DC

RY5004A0000
RY5004J0000 (AIx2, PTx2)

AIV5

Voltage input 2-10 V DC

AO3

MM

Modutrol motor drive

RY5001F0000 (For 1 pt)


RY5003F0000 (For 3 pts)

AO4

AOA

Current output 4-20 mA DC

AO5

AOV1

Voltage output 1-5 V DC

RY5002M0000 (For 2 pts)


RY5004M0000 (For 4 pts)

AOV2

Voltage output 2-10 V DC

AOV3

Voltage output 0-5 V DC

AOV4

Voltage output 0-10 V DC

Note: Set the input symbol in the column of Signal Type for each AI/AO point.

8. RNG (Analog input signal type)


Parameter

Analog input signal type

4~20 mA

0~5 V

1~5 V

0~10 V

2~10 V

11

0~50 (C)

12

0~100 (C)

13

-20~30 (C)

14

-20~80 (C)

16

-50~100 (C)

None

Note: Set the value of parameter in the column of RNG for each AI point.

9. I/O module list table


Model Selection Table
Abbr. of
modules

Connection to
Infilex AC

Model number

Description

Object points and I/O points to be used

RY50

Base model number

I/O module for 8 digital input


points
I/O module for 16 digital input
points
I/O module for 8 relay output
points (N.O. (normally open)
contacts)
I/O module for 16 relay output
points (N.O. contacts)
I/O module for 8 relay output
points (N.O. contacts) +
8 digital input points

For SOP, AOP: DI 1 point


For SAP, SCP: DI 2 points
For CCP, OOA inputs: DI 1 point
For CAP, HOL inputs: DI 2 points

DI

No

For COP maintained, CCP maintained, CAP


maintained: DO 1 point*1
For COP momentary/local, CCP momentary/local,
CAP momentary/local: DO 2 points

DO

No

DO+DI

Yes*5,*7

DOC

No

RRD

No

TOT

No

08 S

0000

16 S

0000

08 D

0000

16 D

0000

16 R

0000

08 C

I/O module for 8 relay output


0000 points (N.O./N.C. (normally
open/normally close) contacts)

04 Y

0000

04 T

0000

16 T

0000

02 M

0000

04 M

0000

04 A

0000

04 P

0000

04 J

0000

01 F

0000

03 F

0000

01 U

0000 User terminal (UT) module

01 Q

0000

I/O module for 4 remote control


relay output points
I/O module for 4 totalizer pulse
input points
I/O module for 16 totalizer pulse
input points
I/O module for 2 voltage/current
output points
I/O module for 4 voltage/current
output points
I/O module for 4 voltage/current
input points

Combination of modules

(For relay output, see DO. For digital input, see


DI.)
For OOA transfer/HOL transfer: NO/NC contact DO
2 points*2
When using HOL momentary/local => <See Note
4 >
For limited to CCP local: RRD 1 point
(DI is not necessary.)
For limited to TTD: Pulse input 1 point

For limited to AO4 or AO5: AO 1 point


AO4 (4-20 mA) or AO5 (2-10 V/0-10 V/1-5 V/0-5 V)

For limited to AI: AI 1 point


(4-20 mA/2-10 V/0-10 V/1-5 V/0-5 V)
For limited to AI: Pt 1 point
I/O module for 4 temperature
(0 to 100 C/0 to 50 C /-20 to 80 C /-20 to 30 C
input points
/-50 to 100 C)
I/O module for 2 voltage /current
Combination of modules

input points +
(For voltage/current input, see AI. For
2 temperature input points
temperature input, see Pt.)
I/O module for 1 Modutrol Motor Output is limited to AO3.
output point
Input (measurement of actual opening)
MM
3
I/O module for 3 Modutrol Motor 1 point*
is limited to AI.
output points

Operator Panel
(integral type)

SOP: Status Only Point


SAP: Status Alarm Point
CCP: Command with COS Point
CAP: Command witn SAP
TTD: Totalizer Digital Point

Yes*6,*7
AO
No
AI

No

Pt

No

AI+Pt

Yes*7

MM

No

For Neopanel, Neoplate, Operator Panel (panel


mount type)

UT

Yes

For Neopanel , Neoplate

OP

Yes

AOP: Alarm Only Point


SCP: Status and COS (Change of Status) Point
OOA: ON/OFF/Auto Point
HOL: HI (high)/OFF/LO (low) Command with COS Point

Notes:
1 Since the DO module does not have any N.C. (normally close) contact, the DOC module is used for the OOA or
HOL.
2 In the OOA transfer, ON/OFF is assigned to the first N.O./N.C. contact, and AUTO is assigned to the second
N.O./N.C. contact.
In the HOL transfer, HI/OFF is assigned to the first N.O./N.C. contact, and LO is assigned to N.O. of the second
N.O./N.C. contact.
3 Two points, AO3 and AI, are assigned to one MM point in the point file.
The following shows the points correnponsing to IO numbers.
IO number
Point type
MM1:
(1, 2)
(AO3, AI)
MM2:
(3, 4)
(AO3, AI)
MM3:
(5, 6)
(AO3, AI)
4 For the HOL momentary/local, 3 points of N.O./N.C. contact DO of the DOC module are required.
HI: N.O. contact of DO, OFF: NC contact of DO2, and LO: NO contact of DO3
5 For DO+DI module connected to Infilex AC (Model WY5117C1400), I/O points are limited to DI 4 points and DO 4
points.
6 For AO module connected to Infilex AC (Model WY5117C1400), voltage output (0-5 V, 0-10 V, 1-5 V, 2-10 V) is
only available.
7 For DO+DI module, AO module, and AI+Pt module, connectabe Infilex AC is Model WY5117C1400 only.

10

Model No. RY5008S

Model No. RY5016S

Model No. RY5008D

Model No. RY5016D

Model No. RY5016R

Module ID = 1

Module ID = 2

Module ID = 3

Module ID = 4

Module ID = 5

DI 8

DI 16

DO 8

DO 16

DIO

I/O No.

Termial No.

I/O No.

Termial No.

I/O No.

Termial No.

I/O No.

Termial No.

Termial No.

DI 1

DI 1

DO 1

DO 1

DO 1

DI 2

DI 2

DO 2

DO 2

DO 2

DI 3

DI 3

DO 3

DO 3

DO 3

DI 4

DI 4

DO 4

DO 4

DO 4

DI 5

DI 5

DO 5

DO 5

DO 5

DI 6

DI 6

DO 6

DO 6

DO 6

DI 7

DI 7

DO 7

DO 7

DO 7

DI 8

DI 8

DO 8

DO 8

DO 8

I/O No.
1

COM

COM

COM

COM

DO COM

COM

10

COM

10

COM

10

COM

10

DO COM

10

DI 9

11

DO 9

11

DI 1

11

10

DI 10

12

10

DO 10

12

10

DI 2

12

11

DI 11

13

11

DO 11

13

11

DI 3

13

12

DI 12

14

12

DO 12

14

12

DI 4

14

13

DI 13

15

13

DO 13

15

13

DI 5

15

14

DI 14

16

14

DO 14

16

14

DI 6

16

15

DI 15

17

15

DO 15

17

15

DI 7

17

16

DI 16

18

16

DO 16

18

16

DI 8

18

COM

19

COM

19

DI COM

19

COM

20

COM

20

DI COM

20

11

Model No. RY5008C

Model No. RY5004Y

Model No. RY5004T

Model No. RY5016T

Module ID = 6

Module ID = 7

Module ID = 8

Module ID = 9

DOC 8

RRD 4

TOT 4

TOT 16

I/O No.

COM 1

RRD 1 (White)

DO 1b

(Virtual DI 1)

DO 2a

RRD 2 (Red)

COM 2

RRD 2 (White)

DO 2b

(Virtual DI 2)

TOT 1

Termial No.

Termial No.
RRD 1 (Red)

I/O No.

I/O No.
1

Termial No.

Termial No.
1

I/O No.
DO 1a

TOT 1

TOT 2

TOT 2

TOT 3

TOT 3

TOT 4

TOT 4

NC

TOT 5

NC

TOT 6

DO 3a

RRD 3 (Red)

NC

TOT 7

COM 3

RRD 3 (White)

NC

TOT 8

DO 3b

(Virtual DI 3)

COM

COM

COM

10

COM

10

11

DO 4a

10

10

RRD 4 (Red)

COM 4

11

11

RRD (White)

DO 4b

12

12

(Virtual DI 4)

DO 5a

13

TOT 9

COM 5

14

10

TOT 10

12

DO 5b

15

11

TOT 11

13

DO 6a

16

12

TOT 12

14

COM 6

17

13

TOT 13

15

DO 6b

18

14

TOT 14

16

DO 7a

19

15

TOT 15

17

COM 7

20

16

TOT 16

18

DO 7b

21

COM

19

DO 8a

22

COM

20

COM 8

23

DO 8b

24

12

Model No. RY5002M

Model No. RY5004M

Model No. RY5004A

Model No. RY5004P

Model No. RY5004J

Module ID = 10

Module ID = 11

Module ID = 12

Module ID = 13

Module ID = 14

AO 2

AO 4

AI 4

Pt 4

AI/Pt

AOI 1 +

AOI 1 -

AOI 1 -

AOV 2 +

AOV 2 +

AOV 2 -

AOV 2 -

AOI 2 +

AOI 2 -

AOI 2 +

AOI 2 -

AOV3 +

AOV3 -

10

AOI3 +

11

AOI3 -

12

AOV4 +

13

AOV4 -

14

AOI4 +

15

AOI4 -

16

13

Pt 1B

Pt 1B

Pt 2A

Pt 2B

AII 1

COM 1

AIV 2

AII 2

COM 2

Pt 2B

AIV 3

Pt 3A

AII 3

COM 3

AIV 4

10

AII 4

11

COM 4

12

Termial No.

AOV 1 1

Pt 1A

I/O No.

Termial No.

AOI 1 +

AIV 1

I/O No.

Termial No.

AOV 1 +

I/O No.

AOV 1 -

Termial No.

I/O No.

Termial No.

I/O No.
1

AOV 1 +

AIV 1

AII 1

COM 1

AIV 2

AII 2

COM 2

Pt 1A

Pt 3B

Pt 3B

Pt 4A

10

Pt 4B

11

Pt 4B

12

Pt 1B

Pt 1B

Pt 2A

10

Pt 2B

11

Pt 2B

12

Model No. RY5001F

Model No. RY5003F

Module ID = 15

Module ID = 16

MM1

MM3
Termial No.

I/O No.

Termial No.

I/O No.
1

MM1 Close

MM1 Close

MM1 Open

MM1 Open

MM1 COM

MM1 COM

MM1 COM

MM1 COM

MM1 POT G

MM1 POT G

MM1 POT Y

MM1 POT Y

MM1 POT T

MM1 POT T

(Virtual AI 1)

(Virtual AI 1)

MM2 Close

MM2 Open

10

MM2 COM

11

MM2 COM

12

MM2 POT G

13

MM2 POT Y

14

MM2 POT T

15

(Virtual AI 2)

16

MM3 Close

17

MM3 Open

18

MM3 COM

19

MM3 COM

20

MM3 POT G

21

MM3 POT Y

22

MM3 POT T

23

(Virtual AI 3)

24

14

Model No. RY5001U


Module ID=17
UT
I/O No.
Terminal
No.
1
2
3
4
5
6
7
8
9
10
11
12

(Pseudo
AI1)
(Pseudo
AI2)
(Pseudo
AI3)
(Pseudo
AI4)
(Pseudo
AI5)
(Pseudo
AI6)
(Pseudo
AI7)
(Pseudo
AI8)
(Pseudo
AI9)
(Pseudo
AI10)
(Pseudo
AI11)
(Pseudo
AI12)

Linearization table No.


used
Neopanel built-in sensor

24

Input value of Neoplate POT

21/22

Battery shortage notice

26

Neosensor wireless transmitter address 1 temperature *1

24

Neosensor wireless transmitter address 1 humidity

25

Neosensor wireless transmitter address 2 temperature *2

24

Neosensor wireless transmitter address 2 humidity

25

Reserved
Reserved
Reserved
Reserved
Reserved
Linearization table No. used
No.21: Neoplate fine-adjustment type (-3.0 to 3.0C)
No.22: Neoplate absolute value type (15.0 to 3.0C)
No.24: Neopanel built-in sensor/Neopanel wireless built-in sensor/
Neosensor wireless temperature (0.0 to 50.0C)
No.25: Neosensor wireless humidity (for 0 to 100%)
No.26: For Neosensor wireless/Neopanel wireless battery shortage notice
Point data for battery shortage notice information is as follows:
0: Both transmitters normal
1: Battery shortage notice included for
transmitter address 1
2: Battery shortage notice included for
transmitter address 2
3: Battery shortage notice included for both
transmitters
*1 Neopanel wireless (transmitter address 1) built-in sensor is pseudo AI4.
*2 Neopanel wireless (transmitter address 2) built-in sensor is pseudo AI6.

15

CAPl (maintained/latched)

CAPm (momentary)