Circuit Breakers
Section C
Innovative, intelligent NEC and IEC solutions safely and efficiently control power and protect
circuits in explosive, wet, and corrosive environments worldwide.
Section
2C
2C
2C
5C
5C
6C
Engineered Solutions
7C
Section C of the Eaton's Crouse-Hinds Product Catalog lists motor control, circuit breakers, variable frequency drives, and engineered
solutions and switch racks. Information on application, features, standard materials, standard finishes, size ranges, compliances, options, and
accessories are presented for ease of product selection.
Information relating to product families in Section C is grouped as follows:
Section 1C
Section 5C
Combination magnetic line starters and enclosures for across-theline motor starting, motor disconnect, motor and line protection,
and start-stop operations.
For hazardous areas
EBMC
EPC
AFA / AFAX
D2X
EGF
XLC
DSD-TS
Section 2C
Section 6C
Motor Starters
Manual starters
EBMS
EPC
NMG
EFD
EDS
EMN
MC
EMN
GHG
NSSC
NFSC
NMN
GUSC
Section 7C
Engineered Solutions
(for hazardous and non-hazardous areas)
For motor control centers in outdoor and/or hazardous areas.
Section 3C
Circuit Breakers
EBMB
EFD
EPC
EIB
FLB
NCB
Section 4C
Traditional Control Stations
(for hazardous and non-hazardous areas)
For means of remote and local motor control, visual indicators and
circuit control and selection. Offers a selection of pushbuttons,
pilot lights, and selector switches.
For hazardous areas
FlexStation
GHG43
EDS / EDSC
N2SU / N2SCU
EDSCM
N2FA / N2FAC
DSD / DSD-SR
N2S / N2SC
EDS
EFS
MC / MCC
OAC
444
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
1C
Description
Page No.
Application/Selection
EPC Series
www.crouse-hinds.com
EBMC Series
EPC Series
US: 1-866-764-5454
CAN: 1-800-265-0502
445
1C
1C
Applications:
1C
NEMA/EEMAC
Enclosure Type
Single Speed
Non-Reversing
Starter
Breaker/Switch
Cover Type
EBMC
Cl.
Cl.
Cl.
Cl.
3, 4*, 7BCD,
9EFG, 12
05
Allen-Bradley
G.E.
Square D
Cutler-Hammer
G.E.
Square D
Cutler-Hammer
Bolted/Ground
Joint/Gasketed
EPC
Cl.
Cl.
Cl.
Cl.
3, 4, 7CD,
9EFG, 12
03
Allen-Bradley
G.E.
Square D
Cutler-Hammer
G.E.
Square D
Cutler-Hammer
Threaded
NMC
3, 4X, 12
04
Allen-Bradley
G.E.
Square D
Cutler-Hammer
G.E.
Square D
Cutler-Hammer
Gasketed
Enclosures
446
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
1C
Applications:
Features:
Rugged, corrosion resistant, cast copper-free aluminum
construction (less than 0.4 of 1%)
Component operating handles located through the right side wall
of the body permits visual confirmation of correct component
assembly and operation
Total compliance to the wiring end room requirements of the
National Electrical Code*/Canadian Electrical Code
Semi-clamshell enclosure design, with an external flanged ground
joint between body and cover makes interior components more
accessible
Minimum enclosure-to-enclosure spacing with little interference
between the opened cover and an adjacent enclosure
Stainless steel hinges allow the cover to swing well out of the way
Stainless steel, quick release, captive, hex head cover bolts.
Stainless steel springs provide clear indication cover bolts are fully
retracted from body
Versatile, internal operating mechanisms allow for field adjustment
to accommodate popular manufacturers' starters and breakers
Simple, straightforward installation of breaker and starter on predrilled mounting plate within enclosure. Mounting plate also field
removable.
Circuit breaker motor circuit protector external operating handle
can be padlocked in either "ON" or "OFF" positions
Neoprene cover gasket permanently attached to the cover seals
out moisture
Bodies have top and bottom drilled and tapped entrances for
power conduits plus one at the bottom for control conduit.
Removable reducers are supplied, as standard, to accommodate
smaller size conduits. All conduit entrances are plugged.
Tap-on mounting feet
Optional EMPS control devices may be added to enclosure cover
Steel bracket for lifting larger enclosures during installation
supplied as standard
*National Electrical Code is a Registered Trademark of the National Fire Protection
Association.
1C
Standard Materials:
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
447
1C
Options:
The following options are available from the factory by adding suffix
to catalog number suffixes are added alphanumerically.
Catalog Number System Example
EBMC1FB--DT30FAL36-W643-
Options in this position are additions to the enclosure itself and
should be listed alphanumerically.
1C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Position
Description
in Cat. #
Suffix
Ambient compensated circuit breaker trip
setting ........................................................................
AC
Less overload relays (lighting contactor)....................
CL
Less overload relays (motor contactor)......................
CM
Control Circuit Transformer, 100VA for
NEMA/EEMAC sizes 02, 600/480/240120,
50 / 60 Hertz, with provision for fusing both primary
leads and one secondary lead (fuses
not provided) ..............................................................
FTPS100
Control Circuit Transformer, 200VA for
NEMA/EEMAC size 3, 600/480/240120,
50 / 60 Hertz, with provision for fusing both primary
leads and one secondary lead (fuses
not provided) ..............................................................
FTPS200
Control Circuit Transformer, 300VA for
NEMA/EEMAC size 4, 5 600/480/240120,
50 / 60 Hertz, with provision for fusing both primary
leads and one secondary lead (fuses
not provided) ..............................................................
FTPS300
Pilot light, 120VAC, red jewel, w/blank
indicating plate ..........................................................
J1
Pilot light, 120VAC, green jewel, w/blank
indicating plate ..........................................................
J3
LED pilot lights (in place of standard
incandescent lamps) ..................................................
LED
Less heaters in starter overload relay...........................
0
Start-Stop pushbuttons (requires 2 spaces)................
PB23
On-Off selector switch ................................................
RR2
Hand-Off-Auto selector switch ...................................
RR3
Space heater, 120 Volt, 25 Watts ................................
R11
Space heater, 240 Volt, 25 Watts ................................
R22
Space heater, 480 Volt, 25 Watts ................................
R44
Automatic reset overload relay ....................................
S1
Insulated neutral w/2 connectors ................................
S146
Std. drain, Class I, B,C & D; Class II, E, F & G;
Class III ......................................................................
S756
Std. breather & drain, Class I, B,C & D; Class II,
E, F & G; Class III .....................................................
S756V
External epoxy finish ...................................................
S752
Internal and external epoxy finish ................................
S753
Additional control contacts, N.O. or N.C. for single
speed, non-reversing starters only (number limited
by design of starter. Details on specific makes and
sizes on request.)
Auxiliary contacts on starter 1 N.O. & 1 N.C................
S781
Auxiliary contacts on starter 2 N.O. & 2 N.C................
S782
Auxiliary contacts on starter 3 N.O. & 3 N.C................
S783
Auxiliary switch on Circuit Breaker 1A and 1B
S784
contacts .....................................................................
Auxiliary switch on Circuit Breaker 2A and 2B
contacts .....................................................................
S785
12 Point term. block 30 Amp, 300V............................
S786
General purpose control relay, 4 pole N.O., contacts
rated 10A@600V, coil 120VAC,
50 / 60 hertz ...............................................................
S787*
*Use of this option with NEMA/EEMAC Size 0, or 1 starters necessitates using the larger "D"
size enclosure.
Enclosure not suitable for NEMA 4 or 4X with cover mounted operators. Breather and drain
entries must be plugged for NEMA 4 rating.
With S752 or S753.
448
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
1C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Options:
If desired, markings on indicating plates may be added to catalog
number. Select from the list of standard markings below.
Insert Legend Plate(s) Catalog Number (i.e. DSL16) immediately
after optional device in the EBM Catalog Number.
Example:
EBMC1FB-J1-DSL14-J3-DSL09-DT30FAL36-W643
Use the charts below to select the appropriate legend plate(s) for your application. Markings shown in bold print are etched;
all others are stamped.
Single Function
Legend Plates
Two Function
Legend Plates
Cat. #
Marking
Cat. #
Automatic
Blank
Blank with single field
Close
Down
Emerg. Stop
DSL16
DSL01
DSL02
DSL21
DSL23
DSL17
DSL03
DSL30
DSL29
DSL35
DSL48
DSL32
Fast
Forward
Hand
In
Jog
Lower
DSL46
DSL18
DSL15
DSL24
DSL10
DSL27
Raise-Lower
Run-Jog
Safe-Run
Start-Stop
Slow-Fast
Up-Down
DSL36
DSL28
DSL86
DSL37
DSL65
DSL33
On
Off
Open
Out
Power On
Raise
DSL07
DSL08
DSL20
DSL25
DSL14
DSL26
Three Function
Legend Plates
Reset
Reverse
Run
Safe
Slow
Start
DSL12
DSL19
DSL09
DSL85
DSL47
DSL05
Stop
Test
Trip
Up
DSL06
DSL13
DSL11
DSL22
Marking
Cat. #
Auto-Off-Hand
Blank with 3 fields
Fast-Off-Slow
For-Off-Rev
Hand-Off-Auto
Run-Off-Jog
DSL49
DSL04
DSL41
DSL40
DSL39
DSL38
Open-Off-Close
Raise-Off-Lower
Slow-Off-Fast
Up-Off-Down
1-Off-2
DSL43
DSL87
DSL88
DSL44
DSL42
Marking
Start
Stop
Emerg. Stop
Plate Color
Green
Red
Red
1C
Marking
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
449
1C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Dimensions
1C
In Inches:
J**
Conduit Entry
Trade Size
D&T w/RE
Enclosure Enclosure
Only
Size
Cat. #
Symbol
A
B
C
D
Size 0, 1 FVNR combination line starter
EBMCFB
B
25.75 24.75 26.90 6.00
1.5"
22.00
2.5"
24.50
2.5"
2.5"
34.06
33.75
(2) 2.5"
(2) 3.5"
19.97
4.00 3.50 13.03 41.50 18.40 29.88
(2) 3.5"
450
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Motor Starter
1C
Circuit Breaker
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Line
Volts
NEMA
Size
Amp
Rating
Frame
Volts
Frame
Types
2
2
2
120
120
120
0
0
0
30
30
30
240
480
600
TEB
TED, EHD
TED, FDB
EBMCFB
EBMCFB
EBMCFB
3
3
3
240
240
240
0
0
0
20
20
20
240
480
600
TEB
TED, EHD
TED, FDB
EBMCFB
EBMCFB
EBMCFB
5
5
5
480
480
600
0
0
0
15
15
15
480
600
600
TED, EHD
TED, FDB
TED, FDB
EBMCFB
EBMCFB
EBMCFB
5
5
5
240
240
240
1
1
1
30
30
30
240
480
600
TEB
TED, EHD
TED, FDB
EBMCFB
EBMCFB
EBMCFB
71/ 2
71/ 2
71/ 2
240
240
240
1
1
1
50
50
50
240
480
600
TEB
TED, EHD
TED, FDB
EBMCFB
EBMCFB
EBMCFB
10
10
10
480
480
600
1
1
1
30
30
30
480
600
600
TED, EHD
TED, FDB
TED, FDB
EBMCFB
EBMCFB
EBMCFB
10
10
10
240
240
240
2
2
2
50
50
50
240
480
600
TEB
TED, EHD
TED, FDB
EBMCFD
EBMCFD
EBMCFD
15
15
15
240
240
240
2
2
2
70
70
70
240
480
600
TEB
TED, EHD
TED, FDB
EBMCFD
EBMCFD
EBMCFD
15
15
15
480
480
600
2
2
2
40
40
40
480
600
600
TED, EHD
TED, FDB
TED, FDB
EBMCFD
EBMCFD
EBMCFD
20
20
20
480
480
600
2
2
2
50
50
50
480
600
600
TED, EHD
TED, FDB
TED, FDB
EBMCFD
EBMCFD
EBMCFD
25
25
25
480
480
600
2
2
2
70
70
70
480
600
600
TED, EHD
TED, FDB
TED, FDB
EBMCFD
EBMCFD
EBMCFD
20
25
30
240
240
240
3
3
3
90
100
125
240
240
480
TEB
TEB
TED
EBMCFH
EBMCFH
EBMCFH
30
30
30
480
480
600
3
3
3
70
70
70
480
600
600
TED, EHD
TED, FDB
TED, FDB
EBMCFH
EBMCFH
EBMCFH
With
Breaker &
Starter
Cat. #
1C
Max. HP
Polyphase
Enclosure
Without
Breaker &
Starter
Cat. #
To include a 120V coil, insert a "1" between second to last and last character in catalog number. 120V coil standard with FTPS option.
Ex. EBMC0FB-3032-613 becomes EBMC0FB-3032-6113
Enclosure not suitable for NEMA 4 or 4X with cover mounted operators.
With S752 or S753.
Starters are furnished with 3 heaters, when heater ratings are fully specified.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
451
1C
1C
Motor Starter
Circuit Breaker
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Max. HP
Polyphase
Line
Volts
NEMA
Size
Amp
Rating
Frame
Volts
Frame
Types
Enclosure
Without
Breaker &
Starter
Cat. #
40
40
40
480
480
600
3
3
3
90
90
90
480
600
600
TED, EHD
TED, FDB
TED, FDB
EBMCFH
EBMCFH
EBMCFH
50
50
50
480
480
600
3
3
3
100
100
100
480
600
600
TED, EHD
TED, FDB
TED, FDB
EBMCFH
EBMCFH
EBMCFH
40
50
60
60
75
75
100
100
240
240
480
600
480
600
480
600
4
4
4
4
4
4
4
4
175
200
125
100
150
125
200
150
600
600
600
600
600
600
600
600
TFK
TFK
TFK
TFK
TFK
TFK
TFK
TFK
EBMCFL
EBMCFL
EBMCFL
EBMCFL
EBMCFL
EBMCFL
EBMCFL
EBMCFL
EBMC4FL
EBMC4FL
EBMC4FL
EBMC4FL
EBMC4FL
EBMC4FL
EBMC4FL
EBMC4FL
125
150
480
480
5
5
300
400
600
600
EBMCFM
EBMCFM
Motor Starter
/
/
/
/
/
/
/
/
JD,
JD,
JD,
JD,
JD,
JD,
JD,
JD,
TFJ,
TFJ,
TFJ,
TFJ,
TFJ,
TFJ,
TFJ,
TFJ,
JDB
JDB
JDB
JDB
JDB
JDB
JDB
JDB
With
Breaker &
Starter
Cat. #
17536
20036
12536
10036
15036
12536
20036
15036
Max. HP
Polyphase
Max.
Line
Volts
NEMA
Size
Amp
Rating
Max.
Volts
Switch
Type
5
10
25
30
600
600
600
600
0
1
2
3
30
30
60
100
600
600
600
600
DS161R
DS161R
DS262R
DS363R
EBMC0FD
EBMC1FD
EBMC2FD
EBMC3FH
Circuit Breakers:
Manufacturer
Cutler-Hammer
General Electric
NEMA
Size
Without Switch & Starter Cat. #
Symbol
0
1
2
3
WT
TT
EBMCFD
EBMCFD
EBMCFD
EBMCFH
FD
FD
FD
FD
600VAC
600VAC
KD Interchangeable Trip Unit
KDB Non-Interchangeable Trip Unit
TJK Interchangeable Trip Unit
TJJ Non-Interchangeable Trip Unit
Cutler-Hammer
EHD
FDB
General Electric
TEB
TED
TED
Motor Starters:
Manufacturer
Allen Bradley
Square D
General Electric
Cutler-Hammer
WFD30J36 W643
WFD30J36 W643
WFD60J36 W643
WFD100J36 W643
Symbol
AB
D
G
W
452
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
623
623
643
663
643
663
643
663
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
1C
Ordering Information:
Select the complete Catalog No. below and specify HP, voltage, frequency, RPM, type and full load ampere rating of
motors or specify ampere rating of heaters.
Motor Starter
Volts
NEMA
Size
MCP
Amp
Rating
Enclosure
without Starter
& MCP Cat. #
Enclosure
with Starter
& MCP Cat. #
240
480
600
480
600
0
0
0
0
0
15
7
7
15
15
EBMCFB
EBMCFB
EBMCFB
EBMCFB
EBMCFB
EBMC0FB
EBMC0FB
EBMC0FB
EBMC0FB
EBMC0FB
15A36 623
7A36 643
7A36 663
15A36 643
15A36 663
71/2
71/2
10
10
240
480
480
600
1
1
1
1
30
15
30
15
EBMCFB
EBMCFB
EBMCFB
EBMCFB
EBMC1FB
EBMC1FB
EBMC1FB
EBMC1FB
30A36
15A36
30A36
15A36
10
15
15
20
25
25
240
240
480
600
480
600
2
2
2
2
2
2
50
100
30
30
50
50
EBMCFD
EBMCFD
EBMCFD
EBMCFD
EBMCFD
EBMCFD
EBMC2FD
EBMC2FD
EBMC2FD
EBMC2FD
EBMC2FD
EBMC2FD
50A36 623
100A36 623
30A36 643
30A36 663
50A36 643
50A36 663
30
30
50
50
240
600
480
600
3
3
3
3
100
50
100
100
EBMCFH
EBMCFH
EBMCFH
EBMCFH
EBMC3FH
EBMC3FH
EBMC3FH
EBMC3FH
100A36 623
50A36 663
100A36 643
100A36 663
50
100
100
240
480
600
4
4
4
250*
250*
250*
EBMCFL
EBMCFL
EBMCFL
60
100
125
150
200
200
240
240
480
600
480
600
5
5
5
5
5
5
250*
400
250*
250*
400
400
EBMCFM
EBMCFM
EBMCFM
EBMCFM
EBMCFM
EBMCFM
EBMC5FM
EBMC5FM
EBMC5FM
EBMC5FM
EBMC5FM
EBMC5FM
Max. HP
Polyphase
3
3
3
5
5
WP
TP
DP
General Electric
Square D
HMCP
(F-Frame)
TEC
FAL
Motor Starters:
Manufacturer
Symbol
Allen Bradley
Square D
General Electric
Cutler-Hammer
AB
D
G
W
623
623
643
663
643
663
After the MCP amp rating the following character symbol must be
entered to designate the trip range. Consult factory for other trip
ranges available.
MCP Amp Rating
Symbol
Trip Range
Symbol
25036
40036
25036
25036
40036
40036
1C
623
643
643
663
HMCP
(J-Frame)
TFC
KAL
HMCP
(K-Frame)
TJC
LAL
www.crouse-hinds.com
US: 1-866-764-5454
Cutler-Hammer (WP)
7
15
30
50
100
250
400
A
A
A
B
B
J
G
21 to 70
45 to 150
90 to 300
150 to 500
300 to 1000
1250 to 2500
1250 to 2500
A
A
A
A
A
B
C
18 to 90
42 to 198
90 to 390
180 to 660
300 to 1308
1000 to 2250
1000 to 3300
Square D (DP)
7
15
30
50
100
250
400
A
A
A
A
A
H
E
18 to 70
50 to 180
100 to 350
150 to 580
300 to 1100
1250 to 2500
1250 to 2500
CAN: 1-800-265-0502
453
1C
Applications:
1C
Certifications and
Compliances:
NEC/CEC
Class I, Division 1 & 2, Groups C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA/EEMAC: 3, 4, 7CD, 9EFG, 12
UL Standard: 698
CSA Standards: C22.2 No. 30
Standard Materials:
Standard Finishes:
Features:
Quick-opening covers less than two turns
to remove or install
Three section design for ease of installation
Water-shedding construction with female
threads on top cover, male threads on
bottom cover, and top cover skirted
Specially located stops and locks insure
adequate thread engagement and prevent
overtightening
Separate replaceable mounting bracket
attached to the rear of the body provides
three-point suspension for quick
installation and leveling one keyhole slot
at top and two open slots at bottom
Bodies have two taper-tapped conduit
hubs with integral bushings on the top, and
two more directly below
Universal mounting plate and reset
mechanism will accommodate any of the
motor starters and circuit breakers in
catalog listing
When interior mounting plate is removed,
feeder and branch circuit conductors are
easily pulled into the wiring chamber. The
interior assembly, with breaker and starter
attached, is then replaced, final
connections made, and covers assembled
External handle, which operates breaker
can be padlocked in either "ON" or "OFF"
positions
Breaker is trip-free of the handle, therefore
it will open under short circuit or overload,
even if the external handle is locked in the
"ON" position
Furnished with third overload relay as
standard
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Assembled unit
Description
Options:
The following special options are available
from factory by adding suffix to Cat. No. and
many are available in kit form or for field
addition to existing units: See page 471 for
listing of kits
Description
Suffix
FT
FTPS
S781
S782
S783
S784
S785
S366
S367
PB3
Separated view
showing major
components
Suffix
454
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
1C
1C
EPC87FTPS or
EPC87FT
Int. Dia.
7"
7"
a
b
c
d
e
f
g
h
j
k
l
m
n
p
Dimensions
105/8
261/16
3511/16
1411/16
63/4
711/16
115/8
2
75/8
73/8
21/16
93/8
51/4
11/4
Dimensions
105/8
311/16
4711/16
1411/16
113/4
711/16
115/8
9
75/8
73/8
21/16
93/8
51/4
11/4
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
455
1C
Select the complete Cat. No. below and specify HP, voltage,
frequency, RPM, type and full load ampere rating of motor or
specify ampere rating of heaters.
Motor Starter
1C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Max. HP
Polyphase
Circuit Breaker
Volts
NEMA
Size
Amp
Rating
Frame
Enclosure
Hub
Size in.
Int.
Dia. in.
Without
Starter &
Circuit
Breaker
Cat. #
With
Starter &
Circuit
Breaker
Cat. #
120
30
EB
11/4
EPC87
3
3
3
3
240
480
480
600
0
0
0
0
20
15
15
15
EHD
EHD
FDB
FD
11/4
11/4
11/4
11/4
7
7
7
7
EPC87
EPC87
EPC87
EPC87
EPC870
EPC870
EPC870
EPC870
20EHD 623
15EHD 643
15FD 643
15FD 653
5
5
5
5
240
480
480
600
1
0
0
0
30
15
15
15
EHD
EHD
FDB
FDB
11/4
11/4
11/4
11/4
7
7
7
7
EPC87
EPC87
EPC87
EPC87
EPC871
EPC870
EPC870
EPC870
30EHD 623
15EHD 643
15FD 643
15FD 653
71/2
71/2
71/2
71/2
240
480
480
600
1
1
1
1
50
30
30
30
EHD
EHD
FDB
FDB
11/4
11/4
11/4
11/4
7
7
7
7
EPC87
EPC87
EPC87
EPC87
EPC871
EPC871
EPC871
EPC871
50EHD 623
30EHD 643
30FD 643
30FD 653
10
10
10
480
480
600
1
1
1
30
30
30
EHD
FDB
FDB
11/4
11/4
11/4
7
7
7
EPC87
EPC87
EPC87
Motor Starters:
Circuit Breakers:
Manufacturer
Symbol
Frames 100/150AMP
240V
480V
600V
General Electric
Cutler-Hammer
TT
WT
TEB
EHD
TED*
EHD
TED*
FB, FDB
*Specify Voltage
Manufacturer
Symbol
Allen-Bradley
General Electric
Square D
Cutler-Hammer
AB
G
D
W
Starters are furnished with three heaters when heater ratings are fully specified.
456
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Single-Speed Non-Reversing
with Motor Circuit Protectors
3-Pole 60 hertz, 600 VAC Maximum
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
1C
Ordering Information:
Select the complete Catalog No. below and specify HP, voltage,
frequency, RPM, type and full load ampere rating of motors or
specify ampere rating of heaters.
Current limiters may be ordered by specification*.
Enclosure with Motor Circuit
Protector and Starter
Amp
Rating
Cat. #
3
3
3
5
5
240
480
600
480
600
0
0
0
0
0
15
7
7
15
15
EPC870
EPC870
EPC870
EPC870
EPC870
15HMCP 623
7HMCP 643
7HMCP 653
15HMCP 643
15HMCP 653
71/2
71/2
10
10
240
480
600
480
1
1
1
1
30
15
15
30
EPC871
EPC871
EPC871
EPC871
30HMCP
15HMCP
15HMCP
30HMCP
TP
DP
WP
Motor Starters:
Manufacturer
Allen-Bradley
General Electric
Square D
Cutler-Hammer
AB
G
D
W
1C
Motor Starter
Max. HP
NEMA
Polyphase Volts Size
623
643
653
643
Symbol
Symbol
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
457
1C
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
1C
Features:
Enclosures are made of Krydon high
impact strength fiberglass-reinforced
polyester material having excellent
corrosion resistance and stability to
heat.
Unitized, strong and durable enclosure
construction provides longer service life
for equipment.
Provided with top and bottom
mounting feet.
Enclosure has hinged access door
which opens 160 for easy wiring and
maintenance. Three screws for door
frame are hidden behind access door.
Access door may be padlocked to
prevent unauthorized access.
Options:
Certifications and
Compliances:
NEMA/EEMAC: 3, 4X and 12
Description
Suffix
Control circuit transformer
480/240-120 volts, 50 or
60 hertz, (Sizes 0 and 1 50VA,
Size 2 100VA, Size 3 150VA,
Size 4 300VA)
Fusible
Secondary....................................
FT
Primary and secondary................ FTPS
Auxiliary Contact on Starter
or Contactor*
1NO/1NC..................................... S781
2 NO/2 NC................................... S782
3 NO/3 NC................................... S783
Auxiliary Switch on Circuit
Breaker or Motor
Circuit Protector*
1A/1B .......................................... S784
2A/2B .......................................... S785
Time delay low voltage release
for 3-wire control with 2, 4 or 6second adjustment. For singlespeed, non-reversing starters only.
Control circuit voltage:
120 volt, 60 hertz.............................. LVR1
240 volt, 60 hertz.............................. LVR2
480 volt, 60 hertz.............................. LVR4
NOTE ON HUBS: The following number and sizes of hubs (not mounted) are included when combination starters are
ordered complete. If enclosures only are ordered, hubs must be ordered separately (see "Options").
458
www.crouse-hinds.com
US: 1-866-764-5454
Starter Size
Number Included
Hub Size
1
2
/4
1
1
2
3
/4
11/2
1
2
3
/4
2
1
2
3
/4
21/2
CAN: 1-800-265-0502
/4
1C
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
Single-Speed, Non-Reversing
600VAC Heavy Duty
Ordering Information - With Circuit Breakers
To order an enclosure complete with starter and breaker, insert the manufacturers symbols in the designated positions of the catalog number.
Symbols are shown in the footnotes.
Select the complete Cat. No. below and specify HP, voltage, frequency, RPM, type and full load ampere rating of motor or specify ampere
rating of heaters. Starters are furnished with three heaters.
Enclosures only can be ordered. Select from listings below. Specific reference table is shown in the listings below. Instantaneous magnetic
trip circuit breakers (magnetic circuit interrupters) can be supplied.
Motor Starter
Circuit Breaker
Enclosure
Trip
With Starter &
Without Starter &
Max. HP
Volts
NEMA
Setting
Circuit Breaker
Circuit Breaker
Polyphase
(A-C)
Size
Amps
Frame
Cat. #
Cat. #
2
2
120
240
0
0
30
15
EB
EB
NMC1024B
NMC1024B
240
20
EB
NMC1024B
240
480
600
1
0
0
30
15
15
EB
EHD
FDB
NMC1024B
NMC1024B
NMC1024B
71/2
71/2
71/2
240
480
600
1
1
1
50
20
20
EB
EHD
FDB
NMC1024B
NMC1024B
NMC1024B
10
10
10
240
480
600
2
1
1
60
30
30
EB
EHD
FDB
NMC1024B2
NMC1024B
NMC1024B
15
15
15
240
480
600
2
2
1
80
40
40
EB
EHD
FDB
NMC1024B2
NMC1024B2
NMC1024B
20
20
20
240
480
600
3
2
2
80
60
50
EB
EHD
FDB
NMC1426B
NMC1024B2
NMC1024B2
25
25
25
240
480
600
3
2
2
80
70
60
EB
EHD
FDB
NMC1426B
NMC1024B2
NMC1024B2
30
30
30
240
480
600
4
3
3
125
80
60
JDB
EHD
FDB
NMC2426B
NMC1426B
NMC1426B
40
40
40
240
480
600
4
3
3
150
80
80
JDB
EHD
FDB
NMC2426B
NMC1426B
NMC1426B
50
50
50
240
480
600
4
3
3
200
100
100
JDB
EHD
FDB
NMC2426B
NMC1426B
NMC1426B
60
60
480
600
4
4
125
100
JDB
JDB
NMC2426B
NMC2426B
75
75
480
600
4
4
150
125
JDB
JDB
NMC2426B
NMC2426B
100
100
480
600
4
4
175
150
JDB
JDB
NMC2426B
NMC2426B
1C
3
5
5
5
Motor Starters:
Circuit Breakers:
Manufacturer
Frames
100/150A
Symbol 240V
480V
General Electric
Square D
Cutler-Hammer
TT
DT
WT
TEB
FAL
EB
600V
225/250A
600V
TED
TED
TFJ
FAL
FAL
KAL
EHB, EHD FB, FDB JB, JDB
Manufacturer
Symbol
Allen-Bradley
General Electric
Square D
Cutler-Hammer
AB
G
D
W
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
459
1C
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
1C
Volts
(AC)
NEMA
Size
MCP Trip
Setting Amps
Enclosure
With Starter &
MCP Cat. #
3
5
5
240
480
600
0
0
0
15
15
15
NMC1024B
NMC1024B
NMC1024B
71/2
10
10
240
480
600
1
1
1
30
30
30
NMC1024B
NMC1024B
NMC1024B
15
25
25
240
480
600
2
2
2
50
50
50
NMC1024B2
NMC1024B2
NMC1024B2
30
50
50
240
480
600
3
3
3
100
100
100
NMC1426B
NMC1426B
NMC1426B
50
100
100
240
480
600
4
4
4
150
150
150
NMC2426P
NMC2426P
NMC2426P
Motor Starters:
Manufacturer
Allen-Bradley
Square D
General Electric
Cutler-Hammer
Symbol
G
W
Symbol
AB
D
G
W
With motor circuit protector only. For motor circuit protector with
current limiter information on request.
Motor Starter
Max. HP
Polyphase
Volts
(AC)
NEMA
Size
Non-fusible
Disconnect
Switch
Switch
Size-Amps
3
5
5
240
480
600
0
0
0
30
30
30
NMC1024D 30 6230
NMC1024D 30 6430
NMC1024D 30 6530
NMC1024D
NMC1024D
NMC1024D
71/2
10
10
240
480
600
1
1
1
30
30
30
NMC1024D 30 6231
NMC1024D 30 6431
NMC1024D 30 6531
NMC1024D
NMC1024D
NMC1024D
15
25
25
240
480
600
2
2
2
60
60
60
NMC1426D 60 6232
NMC1426D 60 6432
NMC1426D 60 6532
NMC1426D
NMC1426D
NMC1426D
30
50
50
240
480
600
3
3
3
100
100
100
NMC2426D
NMC2426D
NMC2426D
Disconnect Switches:
Manufacturer
Symbol
General Electric
G
Square D
D
Cutler-Hammer
W
Enclosure
With Starter & Disconnect Switch
Cat. #
Switch Type
Type QMW
Class 9422
Type DS
460
www.crouse-hinds.com
US: 1-866-764-5454
Motor Starters:
Manufacturer
Symbol
Allen-Bradley
Square D
General Electric
Cutler-Hammer
AB
D
G
W
CAN: 1-800-265-0502
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
Single-Speed, Non-Reversing
600VAC Heavy Duty
1C
Enclosure
With Starter &
Disconnect Switch Cat. #
3
5
5
240
480
600
0
0
0
30
30
30
30
30
30
NMC1024D
NMC1024D
NMC1024D
71/2
71/2
10
10
10
10
240
240
480
480
600
600
1
1
1
1
1
1
30
30
30
30
30
30
30
60
30
60
30
60
NMC1024D
NMC1024D
NMC1024D
NMC1024D
NMC1024D
NMC1024D
3030
3060
3030
3060
3030
3060
6231
6231
6431
6431
6531
6531
NMC1024D
NMC1024D
NMC1024D
NMC1024D
NMC1024D
NMC1024D
15
15
25
25
25
25
240
240
480
480
600
600
2
2
2
2
2
2
60
60
60
60
60
60
60
100
60
100
60
100
NMC1426D
NMC1426D
NMC1426D
NMC1426D
NMC1426D
NMC1426D
6060
6010
6060
6010
6060
6010
6232
6232
6432
6432
6532
6532
NMC1426D
NMC1426D
NMC1426D
NMC1426D
NMC1426D
NMC1426D
30
50
50
50
240
480
480
600
3
3
3
3
100
100
100
100
100
100
200
100
NMC2426D
NMC2426D
NMC2426D
NMC2426D
1010
1010
1020
1010
6233
6433
6433
6533
NMC2426D
NMC2426D
NMC2426D
NMC2426D
Disconnect Switches:
Manufacturer
Switch Type
Symbol
General Electric
Square D
Cutler-Hammer
Type QMW
Class 9422
Type DS
G
D
W
Motor Starters:
Manufacturer
Allen-Bradley
Square D
General Electric
Cutler-Hammer
1C
Motor Starter
Max. HP
Volts
Polyphase
AC
Symbol
AB
D
G
W
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
461
1C
Dimensions
1C
In Inches:
NMC
Cat. #
Outside Dimensions
l
w
Mounting Dimensions
mw
ml
NMC1024
NMC1426
2513/32
2713/32
1113/32
1513/32
823/32
923/32
77/8
117/8
253/8
271/4
227/8
2311/16
511/16
911/16
NMC2426
2713/32
2513/32
923/32
213/4
271/4
2311/16
1911/16
462
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
2C
Description
Page No.
Application/Selection
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
463
2C
Motor Starters
2C
Selection:
Options:
2C
Enclosures
MC
NEC/CEC Hazardous
Area Compliance
None
NEMA/
EEMAC
Enclosure
Type
3, 4, 12
Starter
Type
Manual
NEMA/EEMAC
Size Starters
Single Speed
Non-reversing
Motor
Phase
and Type
Single-AC
Manufacturers
Equipment
Enclosed
Starter
Cutler-Hammer
Cover Type
Gasketed
EPC
Cl.
Cl.
Cl.
Cl.
3, 4, 7CD,
9EFG, 12
Magnetic
0-2
Poly-AC
Allen-Bradley
Cutler-Hammer
G.E.
Square D
Threaded
EBMS
Cl.
Cl.
Cl.
Cl.
3, 4, 7BCD,
9EFG, 12
Magnetic
0-5
Poly-AC
Allen-Bradley
G.E.
Square D
Cutler-Hammer
Bolted/
Ground
Joint/
Gasketed
EMN
NEMA
3, 4, 4X,
7(CD),
9(EFG)
Manual
0-1P
DC and
Single and
Poly-AC
G.E.
Square D
Bolted
EMN IEC
3, 4, 4X,
7(CD),
9(EFG)
Manual
Single and
Poly-AC
Cutler-Hammer
Bolted
EMN
Cl.
Cl.
Cl.
Cl.
3, 7CD,
9EFG, 12
Manual
0-1P
Single and
Poly-AC
Allen-Bradley
Cutler-Hammer
G.E.
Square D
Bolted/
Ground
Joint
GUSC
Cl.
Cl.
Cl.
Cl.
3, 7CD,
9EFG, 12
Manual
3, 71/ 2, 15, 20
Single-AC
EDS,
EDSC
Cl.
Cl.
Cl.
Cl.
3, 7CD,
9EFG, 12
Manual
DC and
Single AC
Allen-Bradley
G.E.
Cutler-Hammer
Bolted/
Ground
Joint
EFD
Cl.
Cl.
Cl.
Cl.
3, 7BCD,
9EFG, 12
Manual
DC and
Single and
Poly-AC
G.E.
Square D
Bolted/
Ground
Joint
NSSC /
NFSC
None
3, 4X, 12
Manual
DC and
Single and
Poly-AC
Allen-Bradley
G.E.
Square D
Cutler-Hammer
Screw and
gasket
NMN
None
3, 4X, 12
Manual
0-1P
Single AC
Allen-Bradley
G.E.
Square D
Screw and
gasket
NMG
None
3, 4X, 12
Manual
0-4
Poly-AC
Allen-Bradley
G.E.
Square D
Cutler-Hammer
Westinghouse
Hinged,
screw and
gasket
464
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Threaded
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
2C
Applications:
Spectrum EBM hinged cover motor control enclosures are used:
For general motor control indoors or outdoors in damp, wet,
dirty, dusty hazardous locations, without the need for a protective
shelter.
In areas where frequent washdowns are necessary or where heavy
rain or water spray is prevalent.
For across-the-line starting, stopping, speed changing and
reversing of polyphase AC induction motors.
To provide motor overload and undervoltage protection.
On switchracks or other assemblies where it's desired that motor
control be centrally located.
Features:
2C
Standard Materials:
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
465
2C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Options:
The following options are available from the factory by adding suffix to catalog number. Suffixes are added alphanumerically.
Catalog Number System Example
EBMS1FB--W6413-
Options in this position are additions to the enclosures and should be listed alphanumerically.
2C
Options in this position are modifications to the motor starter and should be listed alphanumerically.
Description
Position in Cat. #
Less Overload Relays (lighting contactor) .........................................................................................................................
Less Overload Relays (motor contactor) .............................................................................................................................
Control Circuit Transformer, 100VA for NEMA/EEMAC sizes 02, 600/480/240120, 50 / 60 Hertz, with
provision for fusing both primary leads and one secondary lead (fuses not included) ....................................................
Control Circuit Transformer, 200VA for NEMA/EEMAC size 3, 600/480/240120, 50 / 60 Hertz, with
provision for fusing both primary leads and one secondary lead (fuses not included) ....................................................
Control Circuit Transformer, 300VA for NEMA/EEMAC size 4, 5 600/480/240120, 50 / 60 Hertz, with
provision for fusing both primary leads and one secondary lead (fuses not included) ....................................................
Pilot Light, 120VAC, Red Jewel, w/blank indicating plate ....................................................................................................
Pilot Light, 120VAC, Green Jewel, w/blank indicating plate .................................................................................................
Less Heaters in Starter Overload Relay ...............................................................................................................................
Start-Stop Pushbuttons (requires 2 spaces) .......................................................................................................................
On-Off Selector Switch .......................................................................................................................................................
Hand-Off-Auto Selector Switch ..........................................................................................................................................
Space Heater, 120 Volt, 25 Watts ........................................................................................................................................
Space Heater, 240 Volt, 25 Watts ........................................................................................................................................
Space Heater, 480 Volt, 25 Watts ........................................................................................................................................
Automatic Reset Overload Relay ........................................................................................................................................
Std. Drain, Class I, B, C&D; Class II, EF&G; Class III .............................................................................................................
Std. Breather & Drain, Class I, B, C&D; Class II, EF&G; Class III ...........................................................................................
External Epoxy Finish ..........................................................................................................................................................
Internal and External Epoxy Finish ......................................................................................................................................
Additional control contacts, N.O. or N.C. for single speed, non-reversing starters only (number limited by design of
starter. Details on specific makes and sizes on request.)
Aux. Contacts on starter 1 N.O. & 1 N.C..............................................................................................................................
Aux. Contacts on starter 2 N.O. & 2 C...............................................................................................................................
Aux. Contacts on starter 3 N.O. & 3 N.C............................................................................................................................
12 Point Term. Block 30 Amp, 300V ...............................................................................................................................
General Purpose Control Relay, 4 Pole N.O., contacts rated 10A @ 600V, coil 120VAC, 5060 Hz ...............................
Suffix
CL
CM
FTPS100
FTPS200
FTPS300
J1
J3
0
PB23
RR2
RR3
R11
R22
R44
S1
S756
S756V
S752
S753
Example:
Without
Starter
466
Enclosure
Enclosure for
Cat. #
EBMSFA
S787
EBMSFB
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
S781
S782
S783
S786
S787*
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
2C
Ordering Information:
To order an enclosure complete with motor starter, insert the manufacturer's symbol in the
designated position (see ) of the catalog number. Symbols are shown in the footnotes.
Also specify HP, voltage, frequency, RPM, type and full load ampere rating of motor or
specify ampere rating of heaters.
Enclosures without starters may be ordered. Select from the listings below.
Enclosure
Without
Starter
Cat. #
With
Starter
Cat. #
Volts
120
EBMSFA
EBMS0FA 613
3
3
120
240
1
0
EBMSFA
EBMSFA
EBMS1FA 613
EBMS0FA 623
5
5
480
600
0
0
EBMSFA
EBMSFA
EBMS0FA 643
EBMS0FA 663
71/2
71/2
120
240
2
1
EBMSFB
EBMSFA
EBMS2FB 613
EBMS1FA 623
10
10
480
600
1
1
EBMSFA
EBMSFA
EBMS1FA 643
EBMS1FA 663
15
15
120
240
3
2
EBMSFH
EBMSFB
EBMS3FH 613
EBMS2FB 623
25
25
480
600
2
2
EBMSFB
EBMSFB
EBMS2FB 643
EBMS2FB 663
30
240
EBMSFH
EBMS3FH 623
50
50
50
480
600
240
3
3
4
EBMSFH
EBMSFH
EBMSFH
EBMS3FH 643
EBMS3FH 663
EBMS4FH 623
100
100
100
480
600
240
4
4
5
EBMSFH
EBMSFH
EBMSFL
EBMS4FH 643
EBMS4FH 663
EBMS5FL 623
200
200
480
600
5
5
EBMSFL
EBMSFL
EBMS5FL 643
EBMS5FL 663
2C
Max. HP
Polyphase
Symbol
Allen Bradley
Square D
General Electric
Cutler-Hammer
AB
D
G
W
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
467
2C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
2C
J**
Conduit Entry
Trade Size
D&T w/RE
14.38
12.13
2"
1.5"
3.25
3.13
10.25
12.63
14.38
12.13
2"
1.5"
3.25
3.13
10.25
6.00
6.00
12.63
14.25
14.06
16.00
12.13
13.54
3"
3"
2.5"
2.5"
3.25
3.25
3.13
3.94
10.25
11.66
12.00
12.00
17.25
17.50
19.88
20.18
11.00
15.00
(2) 3"
(2) 4"
(2) 2.5"
(2) 3.5"
3.25
4.00
3.00
3.50
10.78
13.03
41.50
18.00
Enclosure
Enclosure
Only
Size
Cat. #
Symbol
Size 0,1 FVNR Starter
EBMSFA
A
18.25
17.25
19.00
6.00
12.63
25.75
24.75
26.50
6.00
28.25
37.50
27.25
36.50
29.00
38.25
43.12
53.25
41.50
51.50
42.25
52.88
Use EBMSFB enclosure when S787 option is ordered with size 0 or 1 starter.
*1" Drilled & Tapped conduit entry for control conductors supplied with PLG plug (top & bottom)
**Conduit entrance for power conductors (top and bottom). (All conduit entrances supplied with RE reducer and PLG plug.)
For Cutler-Hammer W200 Advantage starters.
Drilled & Tapped.
Enclosure not suitable for NEMA 4 or 4X with cover mounted operators.
With S752 or S753.
468
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Applications:
Standard Finishes:
Features:
Options:
NEC/CEC
Class I, Division 1 & 2, Groups C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA/EEMAC: 3, 4, 7CD, 9EFG, 12
UL Standard: 1203
CSA Standard: C22.2 No. 30
Standard Materials:
2C
2C
Certifications and
Compliances:
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Description
Suffix
Control circuit transformer 600/480/240120 volts, 50 or 60 hertz
(Sizes 0 and 1 50VA, 100VA) Fusible Secondary .....................................................
FT
Primary and secondary ............................................................................................. FTPS
Automatic reset overload relay .......................................................................................
S1
Less overload relays (lighting contactor) ........................................................................
CL
Less overload relays (motor contactor) ..........................................................................
CM
Auxiliary Contacts:*
1NO/1NC ................................................................................................................... S781
2NO/2NC ................................................................................................................... S782
3NO/3NC ................................................................................................................... S783
Pilot light holes drilled, tapped and plugged for future addition of pilot lights
one hole ..................................................................................................................... S541
two holes ................................................................................................................... S542
Side bosses drilled and tapped same size as standard hubs ....................................... S366
Back boss drilled and tapped same size as standard hubs .......................................... S367
Standard Breather (Cl. I, Groups C, D; Cl. II, Groups E, F, G; Cl. III) .............................. S219
Standard Drain (Cl. I, Groups C, D; Cl. II, Groups E, F, G; Cl. III) ........................................ S198
Standard Breather and Drain (Cl. I, Groups C, D; Cl. II, Groups E, F, G; Cl. III) ................... S198V
Universal Breather-Drain (Cl. I, Groups C, D; Cl. II, Groups F, G) ................................... S454
(2) Universal-Breather Drains (Cl. I, Groups C, D; Cl. II, Groups F, G) ............................S454V
Pushbuttons (heavy duty):
START-STOP ............................................................................................................. PB3
Selector switches (standard duty):
ON-OFF ..................................................................................................................... RR2
HAND-OFF-AUTO...................................................................................................... RR3
Pilot lights:
Red, 120 volt ..............................................................................................................
J1
Green, 120 volt ...........................................................................................................
J3
Pilot light transformers:
240 volt ....................................................................................................................
T2
480 volt ....................................................................................................................
T4
600 volt ....................................................................................................................
T5
Space heaters:
120 volt ......................................................................................................................
R11
240 volt ......................................................................................................................
R22
480 volt ......................................................................................................................
R44
*Application limited by starter or contactor design consult factory.
Required for pilot lights on other than 120 volt control circuits. One required for each lamp.
Not suitable for NEMA 4.
US: 1-866-764-5454
CAN: 1-800-265-0502
469
2C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Ordering Information:
To order an enclosure complete with starter, insert the manufacturer's symbol in the
designated position of the catalog number. Symbols are shown in the footnote at the
bottom of this page. Specify HP, voltage, frequency, RPM, type and full load ampere rating
of motor or specify ampere rating of heaters.
Enclosures only can be ordered. Select from listings.
Motor Starter
Enclosure
2C
Max. HP
NEMA/EEMAC Hub
Polyphase Volts Size
Size in.
2
3
3
5
5
71/2
10
10
120
120
240
480
600
240
480
600
0
1
0
0
0
1
1
1
11/4
11/4
11/4
11/4
11/4
11/4
11/4
11/4
Without With
Int.
Starter Starter
Dia. in. Cat. #
Cat. #
7
7
7
7
7
7
7
7
EPC97
EPC97
EPC97
EPC97
EPC97
EPC97
EPC97
EPC97
EPC970
EPC971
EPC970
EPC970
EPC970
EPC971
EPC971
EPC971
613
613
623
643
653
623
643
653
Motor Starters:
Manufacturer
Symbol
Allen-Bradley
General Electric
Square D
Cutler-Hammer
AB
G
D
W
Dimensions
In Inches*:
Single-Speed Non-Reversing Sizes 0, 1, Starters
Int. Dia.
a
b
c
d
e
f
g
h
j
k
l
m
n
p
EPC97
EPC97-FT
EPC97-FTPS
7"
7"
Dimensions
Dimensions
105/ 8
1913/ 16
2513/ 16
1411/ 16
63/ 4
711/ 16
53/ 8
2
4
73/ 8
21/ 16
93/ 8
51/ 4
11/ 4
105/ 8
2413/ 16
3713/ 16
1411/ 16
113/ 4
711/ 16
53/ 8
9
4
73/ 8
21/ 16
93/ 8
51/ 4
11/ 4
470
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
2C
16320 N
ESWP126
ESWP126
When EPC magnetic line starter and EPC combination line starter
enclosures have been ordered with pilot light holes drilled, tapped
and plugged (Cat. No. suffix S541 and S542), pilot lights can be
assembled in the field, using kits listed below.
Description
Pilot light assembly less
transformer
Applies to
7", 11" EPC
Cat. #
EMP015 KIT
EPC87 KIT
EPC813 KIT
2C
Description
START-STOP pushbutton station assembly
EPC87 KIT
EPC813 KIT
All units
15129 A
All units
15130 A
All units
15131 A
www.crouse-hinds.com
US: 1-866-764-5454
Symbol
Color
Symbol
J1
J3
J6
Clear
Blue
J10
J11
Voltage
Symbol
240
480
600
T2
T4
T5
CAN: 1-800-265-0502
471
2C
Explosionproof
Wet Locations
Applications:
Explosionproof compact across-the-line
manual NEMA starters for single and
polyphase VAC or VDC motors
Used on drilling rigs for mud agitators
and shakers where flammable or
explosive gases are present
Also used for fans and blowers, pumps,
compressors, and conveyors
2C
Features:
Built to protect from mud and hosedirected water - NEMA 4
Robust protection for start-stop buttons
Option for no top entries for further
protection from water ingress
Pushbutton can be locked in "OFF"
position
Versatile mounting footprint
accomodates field retrofit
STARTER
D31
OPTIONS
S198V
ENCLOSURE TYPE
25
Compact Pushbutton Enclosure pre-drilled for Square D starter
27
Compact Pushbutton Enclosure pre-drilled for GE starter
Certifications and
Compliances:
ENCLOSURE TYPE
25
STARTER
D31
NO. OF
POLES
NEMA
SIZE
0
1
1P
Standard Materials:
Enclosure copper-free aluminum
Shaft, bearing, and bolts stainless
steel
O-ring gasket Buna-N
0
3
1
0
2
DC
Electrical Ratings:
NEMA starter sizes 0, 1, and 1P
1 to 10 HP
OPTIONS
S752
S753
S198V
NTE
Dimensions
MOTOR
VOLTAGE
115
230
115
230
115
230
200-230
380-575
200-230
380-575
115
230
115
230
MAX. HORSEPOWER
SINGLE
POLYDC
PHASE
PHASE
1
2
2
3
3
5
3
5
7-12
10
1
1-12
1-12
2
CATALOG
NUMBER
EMN25 D20
EMN25 D21
EMN25 D21P
EMN25 D30
EMN25 D31
EMN25 D20DC
EMN25 D21DC
In Inches:
6.06
7.94
7.94
7.35
9.81
9.19
11.06
2.00
2.00
2X
3/4" CONDUIT ENTRIES
1.25
4.25
2.50
ACCEPTS 5/16" OR
3/8" MTG. BOLTS
ACCEPTS 1/4" OR
5/16" MTG. BOLTS
Top/Bottom View
Cover View
Side View
472
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Bottom View
No Top Entry Option
2C
Explosionproof
Wet Locations
Select heater elements based on motor nameplate listed Full Load Amps (FLA). Trip rating of elements is 125% of motor minimum FLA listed for the elements. One heater is furnished with
two-pole AC or DC starters and three heaters with three-pole starters.
1 PH
3 PH
Suffix
1 PH
3 PH
B44
0.33-0.36
0.29-0.32
B51
0.37-0.40
0.33-0.36
B57
0.41-0.45
0.37-0.39
B63
0.46-0.52
0.40-0.47
B71
0.53-0.59
0.48-0.56
B81
0.60-0.66
0.57-0.63
B92
0.67-0.73
0.64-0.69
B103
0.74-0.81
0.70-0.77
B116
0.82-0.91
0.78-0.86
B130
0.92-1.02
0.87-0.96
B145
1.03-1.14
0.97-1.11
B167
1.15-1.29
1.12-1.23
B188
1.20-1.42
1.24-1.37
B210
1.43-1.64
1.38-1.55
B240
1.65-1.80
1.56-1.75
B265
1.81-2.10
1.76-1.92
B300
2.11-3.20
1.93-2.16
B330
2.31-2.61
2.17-2.50
B370
2.62-2.99
2.51-2.81
B415
3.00-3.37
2.82-3.16
B485
3.38-3.94
3.17-3.40
B550
3.95-4.24
3.41-3.76
B625
4.25-4.54
3.77-4.00
B690
4.55-5.29
4.01-4.68
B770
5.30-5.73
4.69-5.18
B820
5.74-6.35
5.19-5.51
B910
6.36-7.08
5.52-6.19
B102
7.09-7.83
6.20-7.12
B115
7.84-8.47
7.13-8.15
B128
8.48-9.83
8.16-8.60
B140
9.84-10.50
8.61-9.21
B155
10.60-11.40
9.22-10.10
B175
11.50-12.80
10.20-11.20
B195
12.90-13.90
11.30-12.00
B220
14.00-16.10
B250
16.20-18.00
Following Selections for Size M-1 and M-1P Only
36A
39A
43A
48A
54A
60A
66A
71A
78A
87A
97A
109A
118A
131A
148A
163A
184A
196A
220A
239A
268A
301A
326A
356A
379A
419A
466A
526A
592A
630A
695A
778A
867A
955A
104B
113B
125B
137B
151B
163B
180B
198B
214B
B360
B400
B450
B500
11.30-12.10
12.20-13.60
13.70-15.30
15.40-17.30
17.40-19.10
19.20-21.70
21.80-24.20
24.30-26.00
19.80
21.10
23.10
25.20
19.40
20.60
22.00
25.30
23.20-27.10
27.20-29.20
29.30-33.00
33.10-36.00
778A
867A
955A
104B
113B
125B
137B
151B
163B
180B
198B
214B
228B
250B
273B
303B
330B
www.crouse-hinds.com
0.29
0.31
0.34
0.40
0.44
0.48
0.52
0.58
0.64
0.71
0.81
0.89
0.98
1.12
1.22
1.38
1.48
1.66
1.80
2.03
2.28
2.47
2.71
2.87
3.18
3.54
3.89
4.51
4.90
5.30
5.94
6.70
7.36
7.98
8.59
9.46
10.30
11.70
12.60
13.80
15.40
16.60
17.40
2C
B195
B220
B250
16.20-17.60
B280
17.70-20.60
B320
20.70-23.10
B360
23.20-26.00
B400
B450
Following Selections for Size M-1P Only
0.34
0.37
0.42
0.47
0.52
0.57
0.63
0.69
0.77
0.87
0.97
1.06
1.18
1.33
1.47
1.66
1.78
2.00
2.18
2.45
2.76
3.00
3.27
3.49
3.86
4.30
4.88
5.49
5.85
6.45
7.22
8.05
8.88
9.66
10.50
11.60
12.70
13.20
15.10
16.60
17.60
US: 1-866-764-5454
CAN: 1-800-265-0502
8.56
9.43
10.30
11.00
12.10
13.20
15.00
16.20
17.70
19.70
21.20
22.20
24.90
26.40
30.00
32.70
34.00
473
2C
Explosionproof
Wet Locations
Applications:
Explosionproof compact across-the-line
starting and stopping for small single
and polyphase AC motors
Used for small machine tools, turbines,
fans and blowers, pumps, compressors,
and conveyors where ignitable dusts,
fibers, or filings accumulate
IEC starters are more precisely rated
and, as a result, save users money
during operation
Sophisticated IEC design reduces risk of
motor damage during a fault
2C
Features:
Built to protect from mud and hosedirected water - NEMA 4 and robust
protection of buttons
Option for no top entries for further
protection from water ingress
Pushbutton can be locked in "OFF"
position
Versatile mounting footprint
accomodates field retrofit
SERIES
EMN
STARTER
WP16
OPTIONS
S198V
ENCLOSURE TYPE
26
Compact Pushbutton Enclosure pre-drilled for Cutler-Hammer Starter
STARTER
WP16
Certifications and
Compliances:
ENCLOSURE TYPE
26
RATED
ADJUSTMENT
UNINTERRUPTED
RANGE FLA
CURRENT
MAXIMUM HORSEPOWER
Single Phase
115V
230V
0.1
0.16
0.12
0.33
0.25
0.5
0.5
1.5
0.5
2
1
2
1.5
3
2
3
Standard Materials:
Enclosure copper-free aluminum
Shaft, bearing, and bolts stainless
steel
O-ring gasket Buna-N
Electrical Ratings:
200-208V
*
*
*
*
*
*
0.5
0.75
1
2
3
3
5
5
Three Phase
230V
480V
*
*
*
*
*
*
*
*
*
0.5
*
0.75
0.5
1
0.75
2
1
3
3
5
3
7.5
5
10
5
10
7.5
15
600V
*
*
*
*
0.5
0.75
1.5
3
5
7.5
10
10
15
20
0.1-0.16
0.16-0.25
0.25-0.4
0.4-0.63
0.63-1
1-1.6
1.6-2.5
2.5-4
4-6.3
6.3-10
8-12
10-16
16-20
20-25
CATALOG
NUMBER
0.16
0.25
0.4
0.63
1
1.6
2.5
4
6.3
10
12
16
20
25
EMN26 WP16
EMN26 WP25
EMN26 WP40
EMN26 WP63
EMN26 W001
EMN26 W1P6
EMN26 W2P5
EMN26 W004
EMN26 W6P3
EMN26 W010
EMN26 W012
EMN26 W016
EMN26 W020
EMN26 W025
*In this range, calculate motor rating according to rated current. Speci ed values to NEC Table 430.250.
OPTIONS
S752
S753
S198V
NTE
Dimensions
In Inches:
6.06
7.94
7.35
7.94
9.81
9.19
11.06
2.00
2.00
4.25
ACCEPTS 5/16" OR
3/8" MTG. BOLTS
2X
3/4" CONDUIT ENTRIES
1.25
ACCEPTS 1/4" OR
5/16" MTG. BOLTS
Top/Bottom View
Cover View
2.50
Side View
474
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Bottom View
No Top Entry Option
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
600VAC Maximum
Applications:
Options:
2C
2C
Ordering Information:
Features:
Motor Starter
Certifications and
Compliances:
NEC/CEC
Class I, Division 1 & 2, Groups C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA/EEMAC: 3, 7CD, 9EFG, 12
UL Standard: 1203
CSA Standard: C22.2 No. 14
NEMA
Size
Poles
(Phase)
Max. AC HP Ratings
208/
115V
240V
M-0
M-1
M-1P
M-0
2
2
2
3
3
3
1
2
3
2
2
3
M-1
(1PH)
(1PH)
(1PH)
(3PH)
(1PH)
(3PH)
2
3
5
3
3
71/2
480/
600V
5
10
EMN24 W30
EMN24 W31
Enclosure Cat. #
Standard Materials:
Cutler-Hammer
EMN24
Dimensions*
In Inches:
Standard Finishes:
Copper-free aluminum natural
Stainless steel natural
Sheet steel electrogalvanized with
chromate finish
Enclosures are furnished with two 11/ 4" drilled and tapped openings with 11/4" to 1" reducers.
*Dimensions are approximate, not for construction purposes.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
475
2C
GUSC Enclosures
2C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Applications:
Size Ranges:
Features:
Cat. #
Style
GUSC2013-MS*
3-Pole 30A
Ordering Information:
Rating/Horsepower
120VAC /
3 HP
240VAC /
71/2 HP
480VAC /
15 HP
600VAC /
15 HP
30A
30A
20A
Hub Size
/4"
Rating/Horsepower
Cat. #
Style
120VAC /
3 HP
GUSC2036-MS
3-Pole
40A
240VAC /
71/2 HP
480VAC /
15 HP
600VAC /
20 HP
40A
40A
40A
Hub Size
/4"
Dimensions
In Inches:
Certifications and
Compliances:
NEC/CEC:
Class I, Div. 1 & 2, Groups C, D
Class II, Div. 1, Groups E, F, G
Class II, Div. 2, Groups F, G
Class III
NEMA/EEMAC: 3, 7CD, 9EFG, 12
UL Standard: 1203
CSA Standard: C22.2, No. 30
Standard Materials:
Standard Finishes:
Type
Size
Through Feed Hubs Fig. 1
3-Pole
63/16
61/16
47/8
41/8
53/8
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
2C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Applications:
EFD manual motor starting and stopping
switch enclosures are used:
For manual starting of small AC or DC
motors
In locations made hazardous due to the
presence of flammable vapors, gases or
highly combustible dusts
For installation at petroleum refineries,
chemical and petrochemical plants and
in other process industry facilities where
similar hazards exist
Features:
EFD dead end
NEC/CEC
Class I, Division 1 & 2, Groups B*, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA: 3, 7B*CD, 9EFG, 12
UL Standard: 1203
CSA Standard: C22.2 No. 30
Electrical Ratings
Without Overload Protection
With Switches
Poles Cat. #
Certifications and
Compliances:
2C
HP
Square D
Class 2510
Type KO-1
250VAC
30
115VAC
1
GE TC2368S
600VAC
20
230VAC
2
460575VAC
3
Ordering Information
Through feed
Dead end
Poles Hub Size in. With Switch Cat. #
2
EFD218 T8
EFD318 T8
/4
1
EFD2419
EFD3419
Standard Materials:
Dimensions
/4
1
/4
1
EFDC218 T8
EFDC318 T8
/4
1
EFDC2419
EFDC3419
In Inches:
Standard Finishes:
Feraloy iron alloy electrogalvanized and
aluminum acrylic paint
Type 6 / 6 nylon natural (black)
Stainless steel natural
Options:
The following special options are available
from factory by adding suffix to Cat. #:
Description
Suffix
For use in Group B hazardous areas GB*
Dim. "h"
Dim."a"
/8
1
13
/16
/16
15
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
477
2C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
2C
Applications:
Factory sealed enclosures are installed in a
rigid metallic conduit system for surface
mounting adjacent to or remote from
equipment being controlled and are used:
To prevent arcing of enclosed device
from causing ignition of a specific
hazardous atmosphere or atmospheres
external to the enclosure
In industrial areas such as chemical
plants, oil and gas refineries, paint and
varnish manufacturing plants, gasoline
bulk loading terminals, grain elevators,
grain processing industries, coal
processing or handling areas, or metal
handling or finishing areas where
atmosphere may contain hazardous
gases and/or dust
In non-hazardous areas where sturdy,
durable enclosures are required
In conjunction with magnetic starters or
contactors for remote control of motors
Manual motor starting switch enclosures
are used:
For manual starting of small AC or DC
motors
To provide manual starting and stopping
and, in the case of units with heaters,
motor running protection
EDSC2199
Standard Materials:
Standard Finishes:
Dimensions
Options:
In Inches:
Description
Suffix
For use in Group B hazardous
areas
GB*
Bodies and covers (single and two
gang units) copper-free aluminum
SA
Side View
Features:
Factory sealed devices have many distinct
advantages:
Reduce installation problems
Eliminate external seals
Lower installation costs
Improve safety
Mounting lugs and taper tapped hubs
with integral bushings
Large machine screws for fastening
covers to bodies
Lockout hole for padlock having 1/ 4"
hasp is provided
Close tolerances in machining of wide,
mating flanges and journalled shafts and
bearings produce flametightness of
enclosure joints
Dead end (EDS) or through feed (EDSC)
hubs 3/4" or 1" sizes
EDS2299
Hub
Size
3
/4
1
Dim.
"h"
Dim.
"i"
/8
1
13
/16
/16
15
Front View
Single gang
Two gang
Certifications and
Compliances:
NEC/CEC
Class I, Division 1 & 2, Groups B*, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA/EEMAC: 3, 7B*CD, 9EFG
UL Standard: 1203
CSA Standard: C22.2 No. 30
478
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
2C
Ordering Information
With Allen-Bradley Bulletin 600 Switches
Maximum HP Ratings
115230
Poles
Volts AC
230
Volts DC
Cat. #
/4 hp
1 hp
GE CR101 Y
GE CR101 H
1
2
1 hp
1 hp
115230
Volts DC
Cat. #
Maximum HP Ratings
115230
115
Poles Volts AC
Volts DC
/4 hp
1
2
Hub
Poles
Size in.
Single Gang
3
/4
1
1
EDS2199
EDS3199
EDSC2199
EDSC3199
3
/4
1
EDS21100
EDS31100
EDSC21100
EDSC31100
/4
1
EDS2299
EDS3299
EDSC2299
EDSC3299
3
/4
1
EDS22100
EDS32100
EDSC22100
EDSC32100
2
Two Gang
1 hp
1 hp
Hub Size
Poles
in.
Single Gang
3
/4
1
1
EDS21093
EDS31093
EDSC21093
EDSC31093
/4
1
EDS21094
EDS31094
EDSC21094
EDSC31094
/4
1
EDS22093
EDS32093
EDSC22093
EDSC32093
/4
1
EDS22094
EDS32094
EDSC22094
EDSC32094
2C
1 hp
1 hp
Two Gang
3
Eaton's
Crouse-Hinds
Symbol Number
Max. Motor
Full-Load
Amps
Eaton's
Crouse-Hinds
Symbol Number
Max. Motor
Full-Load
Amps
Eaton's
Crouse-Hinds
Symbol Number
Max. Motor
Full-Load
Amps
Eaton's
Crouse-Hinds
Symbol Number
0.17
0.21
0.25
0.32
0.39
0.46
0.57
0.71
0.79
0.87
0.98
1.08
1.19
1.30
1.43
1.58
1.75
1.88
2.13
2.40
2.58
P1
P2
P3
P4
P5
P6
P7
P8
P9
P10
P11
P12
P13
P14
P15
P16
P17
P18
P19
P20
P21
2.92
3.09
3.32
3.77
4.16
4.51
4.93
5.43
6.03
6.83
7.72
8.24
8.9
9.6
10.8
12.0
13.5
15.2
P22
P23
P24
P25
P26
P27
P28
P29
P30
P31
P32
P33
P34
P35
P36
P37
P38
P39
.48
.53
.58
.65
.71
.78
.86
.95
1.04
1.14
1.25
1.37
1.49
1.63
1.78
1.95
2.13
2.32
2.53
2.76
G2
G3
G4
G5
G6
G7
G8
G9
G10
G11
G12
G13
G14
G15
G16
G17
G18
G19
G20
G21
3.01
3.27
3.56
3.88
4.22
4.60
5.00
5.43
5.90
6.41
6.98
7.60
8.25
8.95
9.75
10.6
11.4
12.5
13.6
14.8
16.0
G22
G23
G24
G25
G26
G27
G28
G29
G30
G31
G32
G33
G34
G35
G36
G37
G38
G39
G40
G41
G42
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
479
2C
/4 hp
/4 hp
1 hp
1 hp
1
1
2C
Two Gang
3
/4
1
1
/4
1
120
Volts DC
240
Volts DC Cat. #
/4 hp
1 hp
/4 hp
/4 hp
WEST MST01
WEST MST02
EDS21101
EDS31101
EDSC21101
EDSC31101
EDS21102
EDS31102
EDSC21102
EDSC31102
EDS22101
EDS32101
EDSC22101
EDSC32101
EDS22102
EDS32102
EDSC22102
EDSC32102
Eaton's
Crouse-Hinds
Symbol Number
Max. Motor
Full-Load
Amps
Eaton's
Crouse-Hinds
Symbol Number
.43
.48
.53
.58
.64
.71
.78
.87
.95
1.03
1.15
1.27
1.35
1.51
1.67
1.83
1.99
2.23
2.47
2.71
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
W11
W12
W13
W14
W15
W16
W17
W18
W19
W20
2.95
3.27
3.59
3.99
4.39
4.79
5.26
5.83
6.39
7.03
7.74
8.46
9.35
10.30
11.35
12.47
13.67
15.12
16.00
W21
W22
W23
W24
W25
W26
W27
W28
W29
W30
W31
W32
W33
W34
W35
W36
W37
W38
W39
480
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
UL/cUL Listed
Cl. I, Div. 2, Groups A, B, C, D
Cl. I, Zones 1 and 2, AEx de
IIB + H2, T5, T6
25 Amp, 690 VAC Non-metallic Enclosure Cl. II, Div. 1, Groups E, F, G (cUL)
CENELEC - PTB 99
ATEX 1162 Certified
Ex de IIC, T6, Zones 1 and 2
Ex de IIC, T6 Zones 21 and 22
IP66, NEMA 4X
2C
Applications:
Explosion protected manual motor
starters are used in a metallic conduit or
cable system for surface mounting to
protect motors against overload and
phase failure.
Features:
Certifications and
Compliances:
UL/cUL Listed
Class I, Division 2, Groups A, B, C, D
Class I, Zones 1 and 2, Ex de IIB+H2, T6
Class II, Division 1, Groups E, F, G (cUL)
CENELEC - PTB 99-ATEX 1162
Ex de IIC, T6, Zones 1 and 2
IP66, NEMA 4X
2C
Technical Data
Type of Protection
Rated Voltage
Rated Current
Rated Current, Aux. Contact
Short Circuit
Under Voltage Trip
Connection Terminals
Connection Terminals, Aux. Contact
Conduit or Cable Entries
Weight
Up to 10mm2
2 x 2.5 mm2
2 x 3/4" Myers hubs
5.5 Ibs./2.5 Kg.
Standard Materials:
Enclosure - Fiberglass-reinforced
polyester
Nonmetallic, corrosion resistant
Increased safety Ex-e protection
Impact Resistant
NEMA 4X, IP66 Protection
Enclosure meets UL 94-VO
UV rated
Enclosure Gasket - Silicon
Handle - Impact-resistant thermoplastic
Cover Screws - Stainless steel
Conduit Entries - Zinc Myers Hubs
Brass Mounting plate - Ground continuity
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
481
2C
UL/cUL Listed
Cl. I, Div. 2, Groups A, B, C, D
Cl. I, Zones 1 and 2, AEx de
IIB + H2, T5, T6
Cl. II, Div. 1, Groups E, F, G (cUL)
CENELEC - PTB 99
ATEX 1162 Certified
Ex de IIC, T6, Zones 1 and 2
Ex de IIC, T6 Zones 21 and 22
IP66, NEMA 4X
0.1 A 1.6 A
1.6 A 2.5 A
2.5 A 4.0 A
4.0 A 6.3 A
6.3 A 9.0 A
9.0 A 12.5 A
12.5 A 16.0 A
16.0 A 20.0 A
20.0 A 25.0 A
N/A*
N/A*
N/A*
N/A*
N/A*
75
60
55
50
N/A*
N/A*
60
40
30
27
25
22
20
N/A*
40
10
7
5
4.5
4
3.5
3
2C
Ordering Information
Setting Range or rated current
Cat. #
0.1 0.16 A
0.16 0.25 A
0.25 0.40 A
0.40 0.63 A
0.63 1.0 A
1.0 1.6 A
1.6 2.5 A
2.5 4.0 A
4.0 6.3 A
6.3 9.0 A
9.0 12.5 A
12.5 16 A
16 20 A
20 25 A
GHG
GHG
GHG
GHG
GHG
GHG
GHG
GHG
GHG
GHG
GHG
GHG
GHG
GHG
635
635
635
635
635
635
635
635
635
635
635
635
635
635
1101
1101
1101
1101
1101
1101
1101
1101
1101
1101
1101
1101
1101
1101
L0101
L0102
L0103
L0104
L0105
L0106
L0107
L0108
L0109
L0110
L0111
L0112
L0113
L0114
Accessory Options
1 = without aux. contact
2 = with aux. contact 1 NO + 1NC
3 = with aux. contact 2 NO
Catalog numbers on this page are shown without auxiliary contacts. To add aux. contacts, change last number in "1101" to a 2 or 3. Ex. 1102.
Wiring Diagram
Dimensions
In Inches:
482
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
NEMA 3, 4, 12
Raintight
Wet Locations
2C
Applications:
MC manual motor starting switches and
enclosures are used:
For manual starting of small AC and DC
motors of one horsepower or less (see
next page for ratings)
In damp, wet or corrosive locations such
as dairies, meat packing plants, chemical
plants and outdoor locations
To provide motor running protection and
manual starting and stopping
Features:
MC dead end
2C
Dimensions
In Inches*:
Certifications and
Compliances:
NEMA/EEMAC: 3, 4, 12
UL Standard: 508
CSA Standard: C22.2 No. 14
Standard Materials:
Body and cover Feraloy iron alloy
Operating handle copper-free
aluminum
Operating shaft stainless steel
Standard Finishes:
Feraloy electrogalvanized and
aluminum acrylic paint
Copper-free aluminum natural
Stainless steel natural
Hub Size
a
b
www.crouse-hinds.com
US: 1-866-764-5454
/2
/8
5
/8
/4
/8
/4
CAN: 1-800-265-0502
483
2C
Heater Table
Manufacturer
Poles
Cat. #
Cutler-Hammer
Cutler-Hammer
1
2
MST01
MST02
Full Load
Motor
Current
.40 .43
.44 .48
.49 .53
.54 .58
.59 .64
.65 .71
.72 .78
.79 .87
.88 .95
.96 1.03
1.04 1.15
1.16 1.27
1.28 1.35
1.36 1.51
1.52 1.67
1.68 1.83
1.84 1.99
2.00 2.23
2.24 2.47
2.48 2.71
2.72 2.95
2.96 3.27
3.28 3.59
3.60 3.99
4.00 4.39
4.40 4.79
4.80 5.26
5.27 5.83
5.84 6.39
6.40 7.03
7.04 7.74
7.75 8.46
8.47 9.35
9.36 10.30
10.31 11.35
11.36 12.47
12.48 13.67
13.68 15.12
15.13 16.00
1-Pole
2-Pole
120 / 240 AC
32 DC
120 / 240 DC
240 DC
1
1
/4
1
1
/4
1
/4
Ordering Information - MC
2C
NEMA 3, 4, 12
Raintight
Wet Locations
Poles
Enclosure
With
Switch
Cat. #
1
1
2
2
/2
/4
/2
3
/4
MC1211
MC2211
MC1212
MC2212
3
1
Without
Switch
Cat. #
MC1212B
MC2212B
MC1212B
MC2212B
Poles
Enclosure
With
Switch
Cat. #
1
1
2
2
/2
/4
/2
3
/4
MCC1211
MCC2211
MCC1212
MCC2212
3
1
Without
Switch
Cat. #
MCC1212B
MCC2212B
MCC1212B
MCC2212B
Heater
Rating
Eaton's Crouse-Hinds
Symbol Number
.50
.55
.61
.67
.74
.81
.89
.98
1.10
1.20
1.30
1.45
1.60
1.70
1.90
2.10
2.30
2.50
2.80
3.10
3.40
3.70
4.10
4.50
5.00
5.50
6.00
6.60
7.30
8.00
8.80
9.70
10.60
11.70
12.90
14.20
15.60
17.10
18.60
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
W11
W12
W13
W14
W15
W16
W17
W18
W19
W20
W21
W22
W23
W24
W25
W26
W27
W28
W29
W30
W31
W32
W33
W34
W35
W36
W37
W38
W39
Includes one interchangeable heater. Select heater from table above and use symbol
number as second section of the Cat. No. Example: MC1211-W5. Symbol 0 (zero) may be
used to indicate heater omitted.
These heaters are for motors rated 40C continuously. For motors rated 50C or 55C,
multiply full load motor current by 0.9 and use this value to select heaters.
484
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
2C
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
Features:
Certifications and
Compliances:
2C
Ordering Information
NSSC Series Manual Motor Starting Switch Without
Overload Protection
With Square D Switches
Poles
Max. HP Rating
115 VAC
200230 VAC 460575 VAC
2
3
1
2
30
30
Poles
Grounding plate or bushing
see page 677
3
10
20
20
Options:
2
71/2
/2
/4
NSSC D12
NSSC D22
/2
/4
NSSC D13
NSSC D23
3
1
Enclosures Only
Enclosure
Type
Hub
Size
Through
Feed Cat. #
Manual Motor
Starting Switch
/2
NSSC1
/4
NSSC2
/2
NFSC1
/4
NFSC2
Fractional HP
Starter
1
3
Dimensions*
In Inches:
*Dimensions are approximate. Not to be used for construction purposes unless approved.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
485
2C
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
Ordering Information
NFSC Series Fractional HP Starters With Overload Protection
With Allen-Bradley Bulletin 600 Switches
Maximum HP Ratings
115230
Poles
Volts AC
1
1 hp
2
1 hp
115230
Volts DC
Maximum HP Ratings
115230
Poles
VAC
/4 hp
1
2
Poles
2C
Poles
NFSC AB11
NFSC AB21
/2
3
/4
1
1 hp
1 hp
115
VDC
230
VDC
/4 hp
/4 hp
1 hp
1 hp
1
/4 hp
1 hp
1
1
32
VDC
NFSC G11
NFSC G21
/2
NFSC AB12
/4
NFSC AB22
Heater Table (see pages 479480)
/2
NFSC G12
/4
NFSC G22
Heater Table (see pages 479480)
Maximum HP Ratings
115230
Poles
Volts AC
1
1 hp
2
1 hp
Poles
1 hp
Poles
/2
3
/4
NFSC C11
NFSC C21
/2
/4
NFSC C12
NFSC C22
Maximum HP Ratings
115230
Poles
Volts AC
1
1 hp
2
1 hp
115230
Volts DC
/2
/4
NFSC D11
NFSC D21
/2
/4
NFSC D12
NFSC D22
3
1
3
Max.
Motor
Full-Load
Amps
Eaton's
Crouse-Hinds
Symbol
Number
Max.
Motor
Full-Load
Amps
Eaton's
Crouse-Hinds
Symbol
Number
.43
.48
.53
.58
.64
.71
.78
.87
.95
1.03
1.15
1.27
1.35
1.51
1.67
1.83
1.99
2.23
2.47
2.71
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
W11
W12
W13
W14
W15
W16
W17
W18
W19
W20
2.95
3.27
3.59
3.99
4.39
4.79
5.26
5.83
6.39
7.03
7.74
8.46
9.35
10.30
11.35
12.47
13.67
15.12
16.00
W21
W22
W23
W24
W25
W26
W27
W28
W29
W30
W31
W32
W33
W34
W35
W36
W37
W38
W39
Full-Load
Motor
Current
Eaton's
Crouse-Hinds
Symbol
Number
0.410.44
0.450.49
0.500.53
0.540.58
0.590.65
0.660.71
0.720.78
0.790.85
0.860.96
0.971.04
1.051.16
1.171.29
1.301.37
1.381.47
1.481.56
1.571.65
1.661.79
1.801.95
1.962.15
2.162.38
2.392.75
2.762.84
A.49
A.54
A.59
A.65
A.71
A.78
A.86
A.95
A1.02
A1.16
A1.25
A1.39
A1.54
A1.63
A1.75
A1.86
A1.99
A2.15
A2.31
A2.57
A2.81
A3.61
Includes one interchangeable heater. Select heater suffix from table and add to catalog
number. Example: NFSC-D11A.49
486
www.crouse-hinds.com
US: 1-866-764-5454
/4 hp
115230
Volts DC
CAN: 1-800-265-0502
Full-Load
Motor
Current
Eaton's
Crouse-Hinds
Symbol
Number
2.853.06
3.073.45
3.463.70
3.714.07
4.084.32
4.334.90
4.915.35
5.365.85
5.866.41
6.426.79
6.807.57
7.588.15
8.168.98
8.999.67
9.689.95
9.9610.8
10.912.1
12.213.1
13.213.9
14.015.0
15.116.0
A3.95
A4.32
A4.79
A5.30
A5.78
A6.20
A6.99
A7.65
A8.38
A9.25
A9.85
A11.0
A11.9
A13.2
A14.1
A14.8
A16.2
A17.9
A19.8
A21.3
A25.2
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
Starter sizes 0, 1, 1P
Features:
Undervoltage protection.
Available with toggle operator
only ................................................
U
Grounding plate see page 677.
Insulated, groundable type
terminal block for grounded or
ungrounded neutral can be
supplied ......................................... S618
2C
Options:
Description
Suffix
2C
Certifications and
Compliances:
NEMA/EEMAC 3, 4X and 12
Ordering Information
Enclosure with Starter
3
/4" Hubs
Starter
NEMA
Size
Poles
Max. HP
115V 230V
M-0
M-1
M-1P
M-0
M-1
2
2
2
3
3
3
1
2
3
2
2
3
(1
(1
(1
(3
(1
(3
PH)
PH)
PH)
PH)
PH)
PH)
2
3
5
3
3
71/2
460/575V
Dead End
Cat #
NMN
NMN
NMN
NMN
10
NMN 231
220
221
221P
230
1" Hubs
Through Feed
Cat #
NMNC
NMNC
NMNC
NMNC
220
221
221P
230
Dead End
Cat #
NMN
NMN
NMN
NMN
320
321
321P
330
Through Feed
Cat #
NMNC
NMNC
NMNC
NMNC
320
321
321P
330
NMNC 231
NMN 331
NMNC 300
Enclosure Only*
NMN 200
NMNC 200
NMN 300
NMNC 300
AB
G
D
Dimensions
In Inches:
NMN
*Furnished with mounting plate and operator installed.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
487
2C
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
Applications:
NMG magnetic line starters are used:
For magnetic across-the-line starting of
motors and remote starting and
stopping
For across-the-line starting of polyphase
AC induction motors
To provide motor running protection,
undervoltage protection and remote
starting and stopping
2C
Features:
Enclosures are made of Eaton's CrouseHinds high-impact strength Krydon
fiberglass-reinforced polyester material
which has excellent corrosion resistance
and stability to heat.
Unitized, strong and durable enclosure
construction provides longer service life
for equipment.
Exterior parts of RESET button made of
Krydon material.
Certifications and
Compliances:
NEMA/EEMAC: 3, 4X and 12
Magnetic line starter with optional hinged cover with START-STOP pushbuttons.
Options:
Description
Hinged cover.....................................
Pilot lights, 120 V primary specify
other primary voltages as required:
Red pilot light...............................
Green pilot light............................
LED pilot lights in place of standard
incandescent pilot lamps.................
Pushbutton (heavy duty, uses two
device holes):
START-STOP..............................
Selector switches (heavy duty):
ON-OFF........................................
HAND-OFF-AUTO........................
JOG-RUN-OFF.............................
Padlock attachment for:
Pushbutton..................................
Control circuit transformer 480 /
240-120 volts, 50 or 60 hertz, (sizes
0 and 150VA, size 2100VA, size
3150VA, size 4300VA):
Fusible
Secondary...................................
Primary and Secondary...............
Automatic reset overload relay..........
Less overload relays (contactor)........
Auxiliary Contact on Starter or
Contactor:
1NO/1NC.....................................
2NO/2NC.....................................
3NO/3NC.....................................
Suffix
NH
J1*
J3*
LED
PB13*
RR17*
RR18*
RR19*
S708
Description
Suffix
Time delay low voltage release for
3-wire control with 2, 4 or 6-second
adjustment. For single-speed, nonreversing starters only. Control
circuit voltage:
120 volt, 60 hertz............................ LVR1
240 volt, 60 hertz............................ LVR2
480 volt, 60 hertz............................ LVR3
Hubs (see "Note on Hubs")
see page 677
Grounding plate or bushing
see page 677
Insulated, groundable type terminal
block for a grounded or ungrounded
neutral can be supplied..................... S618
Information on other options or
combination of options for a specific
enclosure size is available on request.
FT
FTPS
S1
C
S781
S782
S783
488
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
Dimensions
In Inches:
2C
0
1
0
0
0
2
1
1
1
3
2
2
2
3
4
3
3
4
4
NMG0710
NMG0710
NMG0710
NMG0710
NMG0710
NMG0714
NMG0710
NMG0710
NMG0710
NMG1018
NMG0714
NMG0714
NMG0714
NMG1018
NMG1024
NMG1018
NMG1018
NMG1024
NMG1024
6130
6131
6230
6430
6530
6132
6231
6431
6531
6133
6232
6432
6532
6233
6234*
6433
6533
6434*
6534*
NMG0710
NMG0710
NMG0710
NMG0710
NMG0710
NMG0714
NMG0710
NMG0710
NMG0710
NMG1018
NMG0714
NMG0714
NMG0714
NMG1018
NMG1024
NMG1018
NMG1018
NMG1024
NMG1024
2C
2
3
3
5
5
71/2
71/2
10
10
15
15
25
25
30
50
50
50
100
100
Without
Starter Cat. #
Motor Starters:
Manufacturer
Allen-Bradley
Square D
Cutler-Hammer
General Electric
Westinghouse
Enclosure Cat. #
Outside Dimensions
l
w
d
Mounting
Dimensions
ml
mw
NMG0710
NMG0714
NMG1018
NMG1024
101/2
141/2
1913/32
2513/32
93/8
133/8
193/8
253/8
Symbol
AB
D
C
G
W
71/2
71/2
1113/32
1113/32
7
7
823/32
823/32
63/8
63/8
77/8
77/8
Starter Size
1
2
/4
1
1
2
3
/4
11/2
1
2
3
/4
2
1
2
3
/4
21/2
/4
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
489
2C
2C
490
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Circuit Breakers
Hazardous
3C
Description
Page No.
Application/Selection
Non-Interchangeable Trip
EPC Series
FLB Series
EBMB Series
EIB Series
NCB Series
Interchangeable Trip
225 / 250 ampere frame
FLB Series
EBMB Series
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
491
3C
Circuit Breakers
3C
Considerations for
Selection:
Options:
3C
NEMA/
EEMAC
Encl.
Type
3, 7BCD,
9EFG
3R, 4,
7BCD,
9EFG, 12
3, 4,
7CD,
9EFG
3, 7CD,
9EFG
EIB
3, 3R, 4,
7BCD,
9EFG
Magnetic
15100
NCB
N/A
3, 4X, 12
ThermalMagnetic
15-400
Encl.
EFD,
EFDC
EBMB
EPC
FLB
492
www.crouse-hinds.com
Type
ThermalMagnetic
ThermalMagnetic
Ampere
Rating
Range
1530
15800
Voltage
Range
120AC
Manufacturer and
Frame Size
Sq. D QOU
No. of
Poles
1
Interchangeable
Trip
No
120AC to
600AC
1, 2, 3
Yes
Bolted/
Ground
Joint/
Gasketed
1, 2, 3
Yes
Threaded
1, 2, 3
Yes
Threaded
480AC to
600AC
Cut. Ham. EG
No
Bolted/
Ground
Joint
240AC to
600VAC
250DC
2, 3
Yes
Hinged,
screw and
gasket
125DC to
250DC
ThermalMagnetic
15150
120AC to
600AC
125DC to
250DC
ThermalMagnetic
15225
120AC to
600AC
125DC to
250DC
US: 1-866-764-5454
CAN: 1-800-265-0502
Enclosure
Cover
Construction
Bolted/
Ground
Joint
EIB Series
Compact Circuit Breaker
Assemblies With Covers
The EIB Series Compact Circuit Breaker
Assemblies are an innovative line of
explosionproof motor control now being
offered by Eaton's Crouse-Hinds. The EIB
series utilizes the EJB style D enclosure with
its bolted construction, NEMA 4
environmental protection and Class I,
Division 1, Group B, C and D hazardous
area ratings. The EIB series is a costeffective solution for circuit breaker
protection and utilizes the Cutler-Hammer
Type EG circuit breakers. Circuit breaker
protection is available from 15 to 100 amps.
Features:
Options:
Description
Suffix
Insulated Neutral Lug ....................... S146
Grounded Neutral Lug Kit with
Connectors for 50, 100 & 225
Amps ................................................ S178
External Ground Stud ...................... S214
Breather and Drain .......................... S756V
Epoxy Powder Coat Finish
(exterior only) ................................... S752
Epoxy Powder Coat Finish
(exterior and interior) ........................ S753
Ordering Information
Electrical Ratings:
Circuit
Breaker
Rating
(amps)
15
20
25
30
35
40
45
50
60
70
80
90
100
EIBA
EIBA
EIBA
EIBA
EIBA
EIBB
EIBB
EIBB
EIBB
EIBB
EIBB
EIBB
EIBB
600V maximum
3 poles
Ampere Interrupting Capacity:
- All EIB enclosures are rated to
10k AIC
- Eaton Type EG Breaker AIC ratings:
- 240V: 35k AIC
- 480V: 25k AIC
- 600V: 18k AIC
EIBA3015
EIBA3020
EIBA3025
EIBA3030
EIBA3035
EIBB3040
EIBB3045
EIBB3050
EIBB3060
EIBB3070
EIBB3080
EIBB3090
EIBB3100
Weights:
EIBA
EIBB
39 lbs.
58 lbs.
Dimensions
In Inches:
Certifications and
Compliances:
Standard Materials:
Dimension
Size A
Size B
aa
bb
xx
yy
zz
Mounting Holes
10.47"
12.47"
11.13"
5.0"
9.6"
7
/16"
12.53"
16.53"
15.13"
7.0"
11.66"
7
/16"
Finishes:
Copper-free Aluminum Natural
Steel Electrogalvanized
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
493
3C
3C
3C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Applications:
Spectrum EBM hinged cover motor control enclosures are used:
For general motor control and circuit protection indoors and
outdoors in damp, wet, dirty, dusty hazardous locations without
the need for a protective shelter.
In areas where frequent washdowns are necessary or where heavy
rain or water spray is prevalent.
To provide line disconnect means and short circuit protection.
For service entrance, feeder or branch circuit protection for
lighting, heating, appliance and motor circuits.
On switchracks or other assemblies where its desired that motor
control be centrally located.
3C
Features:
Rugged, corrosion resistant, cast copper-free aluminum
construction (less than 0.4 of 1%).
Circuit breaker operating handle located through the right side wall
of the body permits visual confirmation of correct component
assembly and operation.
Total compliance to the wiring end room requirements of the
National Electrical Code.
Semi-clamshell enclosure design, with an external flanged ground
joint between body and cover makes interior components more
accessible.
Minimum enclosure-to-enclosure spacing with little interference
between the opened cover and an adjacent enclosure.
Copper-free aluminum hinges allow the cover to swing well out of
the way.
Stainless steel, quick release, captive, hex head cover bolts.
Stainless steel springs provide clear indication cover bolts are fully
retracted from body.
Versatile, internal operating mechanisms allow for field adjustment
to accommodate popular manufacturers' breakers.
Simple, straightforward installation of breaker on pre-drilled
mounting plate within enclosure. Mounting plate also field
removable.
Circuit breaker external operating handle can be padlocked in
either "ON" or "OFF" positions.
Neoprene cover gasket permanently attached to the cover seals
out moisture.
Bodies have top and bottom drilled and tapped entrances for
power conduits and control conduits. Removable reducers are
supplied, as standard, to accommodate smaller size conduits. All
conduit entrances are plugged.
Tap-on mounting feet.
Optional EMPS control devices may be added to enclosure cover.
Steel bracket for lifting larger enclosures during installation
supplied as standard.
Standard Materials:
Body and cover copper-free aluminum
Operating handle copper-free aluminum
Operating shaft and bushing
stainless steel
Interior parts sheet steel, electrogalvanized
Cover bolts, washers and retractile springs stainless steel
494
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
3C
Options:
The following options are available from factory by adding suffix to
catalog number. Suffixes are added alphanumerically.
Catalog Number System
EBMBB--WT30FDB36-
Options in this position are additions to the enclosure and should
be listed alphanumerically.
Options in this position are modifications to the circuit breaker and
should be listed alphanumerically.
Description
Position
in Cat. #
Suffix
AC
J1
J3
LED
PB23
R11
R22
R44
S146
S178
S756
S756V
S752
S753
S784
S785
S786
S787
3C
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
495
3C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Ordering Information:
To order an enclosure complete with circuit breaker, insert the manufacturer's symbols in the designated positions of the catalog number.
Symbols are shown below.
Enclosures can be ordered without circuit breakers. Select from listings below.
3C
Circuit Breaker
Enclosures
Poles
Voltage Rating
Circuit Breaker
Frame Size
3
3
3
3
3
3
3
3
3
3
3
3
3
3
240VAC
240VAC
480VAC
480VAC
600VAC
240VAC
240VAC
480VAC
480VAC
600VAC
600VAC
600VAC
600VAC
600VAC
100
150
100
150
150
100
150
100
150
150
250
400
600
800
or
or
or
or
125250VDC
125250VDC
250VDC
250VDC
or
or
or
or
125250VDC
125250VDC
250VDC
250VDC
or 250VDC
or 250VDC
or 250VDC
Circuit Breakers:
Manufacturer
Symbol
Cutler-Hammer
General Electric
WT
TT
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Frame
Frame
Frame
Frame
Frame
Frame
Frame
Frame
Frame
Frame
Frame
Frame
Frame
Frame
Without Circuit
Breaker Cat. #
EBMBA
EBMBA
EBMBA
EBMBA
EBMBA
EBMBB
EBMBB
EBMBB
EBMBB
EBMBB
EBMBG
EBMBK
EBMBL
EBMBL
*
*
*
*
Circuit Breaker
Amp Rating
With Circuit
Breaker Cat. #
EBMBA TTTEB32
EBMBA TTTEB32
EBMBA 34
EBMBA TTTED34
EBMBA 36
EBMBB TTTEB32
EBMBB TTTEB32
EBMBB 34
EBMBB TTTED34
EBMBB 36
EBMBG 36
EBMBK 36
EBMBL WT36
EBMBL WT36
100
150
225
400
600
800
Amp Frame (EHD)* 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
Amp. Frame (TDB, TEB, TED) 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150
/ 250 Amp Frame (JD, JDB, TFJ, TFK) 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
Amp. Frame (KD, KDB, TJJ, TJK) 100, 125, 150, 175, 200, 225, 250, 300, 350, 400
Amp. Frame (LD, TJK) 250, 300, 350, 400, 450, 500, 600
Amp Frame (MD, TKMA) 300, 350, 400, 450, 500, 600, 700, 800
Select Circuit Breaker Frame Type based on frame size, voltage, and manufacturer desired:
Manufacturer
Cutler-Hammer
General Electric
TEB
600 Amp.
Frame
600VAC
800 Amp.
Frame
600VAC
FDB
JD
JDB
KD
KDB
LD
MD
TED
TFK
TFJ
TJK
TJJ
TJK
TKMA
600VAC
600VAC
EHD
TED
496
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
3C
Dimensions
In Inches:
3C
Enclosure
Only
Cat. #
Enclosure
Size
Symbol
Dimensions
A
B
J** Conduit
Entry Trade
Size
D&T w/RE
Dimensions
K
L
M
18.25
17.25
19.40
6.00
13.03
14.78
10.25
2"
1.5"
14.50
24.75
26.90
6.00
13.03
14.78
10.25
2"
1.5"
22.00
36.50
39.28
6.00
13.03
14.78
10.25
3.0"
2.5"
34.06
41.50
42.65
12.00
17.65
20.28
10.92
(2)3"
(2)2.5"
29.23
53.28
12.00
17.90
20.58
13.03
(2)4"
(2)3.5"
41.50
18.40
29.88
43.12
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
497
3C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Applications:
EPC Circuit Breakers and Enclosures are used:
For service entrance*, feeder or branch circuit protection for
lighting, heating, appliance and motor circuits
In areas made hazardous due to the presence of flammable
vapors, gases or combustible dusts
In damp, wet or corrosive locations
Indoors or outdoors at petroleum refineries, chemical or
petrochemical plants and other process industry facilities where
similar hazards exist
To provide disconnect means, short circuit protection and thermal
time delay overload protection
3C
Features:
Quick-opening covers less than two turns to remove or install
Three section design for ease of installation
Water-shedding construction with female threads on top cover,
male threads on bottom cover, and top cover skirted
Specially located stops and locks insure adequate thread
engagement and prevent overtightening
Separate replaceable mounting bracket attached to the rear of the
body provides three-point suspension for quick installation and
leveling one keyhole slot at top and two open slots at bottom
Bodies have two taper-tapped conduit hubs with integral bushings
on the top, and two more directly below
Mounting plates are supplied with all necessary holes and
hardware to attach any of the circuit breakers shown in the
catalog listings. Breaker and interior mounting frames are easily
removed as a unit, providing free access to the wiring chamber
Breaker is operated by an external handle which can be
padlocked in either "ON" or "OFF" positions by as many as three
padlocks. Breaker is trip-free of the handle and will open under
short circuit or overload, even if the handle is locked in the "ON"
position
Standard Materials:
Options:
The following special options are available from factory by adding
suffix to Cat. #:
Description
Suffix
Auxiliary Switch
1A/1B (1P2T)..........................................................................
S784
2A/2B (2P2T)..........................................................................
S785
Insulated neutral with 2 connectors (100, 150 and 225 amp.)
S146
Grounded neutral stud with 3 connectors (100, 150 and 225
amp.)........................................................................................
S178
Side bosses drilled and tapped same size as standard hubs.
S366
Back boss drilled and tapped same size as standard hubs...
S367
Standard Breather (Class I, Groups C, D; Class II, Groups E,
F, G; Class III)...........................................................................
S219
Standard Drain (Class I, Groups C, D; Class II, Groups E, F,
G; Class III)...............................................................................
S198
Standard Breather and Drain (Class I, Groups C, D; Class II,
Groups E, F, G; Class III)......................................................... S198V
Universal Breather-Drain (Class I, Groups C, D; Class II,
Groups F, G)............................................................................. S454
(2) Universal Breather-Drains (Class I, Groups C, D; Class II,
Groups F, G)............................................................................. S454V
Standard Finishes:
Copper-free aluminum natural
Stainless steel natural
Sheet steel electrogalvanized
*Suffix S146 insulated material must be used to comply with NEC requirements for service entrance.
Application is limited by circuit breaker design Consult Factory.
Not suitable for NEMA 4.
498
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
3C
Dimensions
In Inches*
3C
Int. Dia.
a
b
c
d
e
f
g
h
j
k
l
m
n
p
EPC377
7"
105/ 8
1913/ 16
2313/ 16
143/ 8
63/ 4
711/ 16
53/ 8
2
2
73/ 8
21/ 16
93/ 8
51/ 4
11/ 4
EPC387
7"W
1213/ 16
1913/ 16
2313/ 16
143/ 8
63/ 4
711/ 16
53/ 8
2
2
91/ 4
21/ 16
93/ 8
51/ 4
2
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
499
3C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Ordering Information:
To order an enclosure complete with circuit breaker where there is a choice of manufacturer, insert the manufacturer's symbol in the
designated position of the catalog number.
Enclosures only can be ordered. Select from listings.
Non-Interchangeable Trip
Circuit Breaker
3C
Poles
Voltage
Rating
Enclosure
Int.
Dia.
Hub
Size
Circuit Bkr.
Amp
Rating
Without Circuit
Bkr. Cat. #
With Circuit
Bkr. Cat. #
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC387
EPC387 70EB 2
EPC387 90EB 2
EPC387 100EB 2
11/4
7W
70
90
100
11/4
15
20
30
40
50
70
90
100
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
7W
70
90
100
EPC387
EPC387 70EB 3
EPC387 90EB 3
EPC387 100EB 3
240VAC
or
125-250VDC
240VAC*
*Square D 240VAC/125250VDC
Circuit Breakers
Manufacturer
General Electric
Cutler-Hammer
500
www.crouse-hinds.com
15EB 2
20EB 2
30EB 2
40EB 2
50EB 2
70EB 2
90EB 2
100EB 2
15
20
30
40
50
70
90
100
Frame
Symbol
TEB
ED
TT
WT
US: 1-866-764-5454
CAN: 1-800-265-0502
15EB 3
20EB 3
30EB 3
40EB 3
50EB 3
70EB 3
99EB 3
100EB 3
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
3C
Non-Interchangeable Trip
Circuit Breaker
Poles
Voltage
Rating
Int.
Dia.
Hub
Size
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC387
EPC387 70EHD 2
EPC387 90EHD 2
EPC387 100EHD 2
15EHD 2
20EHD 2
30EHD 2
40EHD 2
50EHD 2
70EHD 2
90EHD 2
100EHD 2
11/ 4
7W
70
90
100
11/ 4
15
20
30
40
50
70
90
100
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
7W
70
90
100
EPC387
EPC387 70EHD 3
EPC387 90EHD 3
EPC387 100EHD 3
11/ 4
15
20
30
40
50
70
90
100
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
15FDB 2
20FDB 2
30FDB 2
40FDB 2
50FDB 2
70FDB 2
90FDB 2
100FDB 2
70
90
100
110
125
150
EPC387
EPC387
EPC387
EPC387
EPC387
EPC387
EPC387
70FDB 2
90FDB 2
100FDB 2
110FDB 2
125FDB 2
150FDB 2
11/ 4
15
20
30
40
50
70
90
100
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
EPC377
15FDB 3
20FDB 3
30FDB 3
40FDB 3
50FDB 3
70FDB 3
90FDB 3
100FDB 3
70
90
100
100
125
150
EPC387
EPC387
EPC387
EPC387
EPC387
EPC387
EPC387
70FDB 3
90FDB 3
100FDB 3
110FDB 3
125FDB 3
150FDB 3
480VAC
600VAC
or
250VDC
600VAC
7W
Circuit Breakers
Manufacturer
General Electric
Cutler-Hammer
With Circuit
Bkr. Cat. #
7
480VAC
or
250VDC
7W
Without Circuit
Bkr. Cat. #
15
20
30
40
50
70
90
100
Circuit Bkr.
Amp
Rating
Frame
Symbol
TED
EHD
TT
WT
www.crouse-hinds.com
Circuit Breakers
Manufacturer
General Electric
Cutler-Hammer
US: 1-866-764-5454
Frame
Symbol
TED
FD, FDB
TT
WT
CAN: 1-800-265-0502
3C
Enclosure
15EHD 3
20EHD 3
30EHD 3
40EHD 3
50EHD 3
70EHD 3
90EHD 3
100EHD 3
501
3C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
3C
Applications:
FLB circuit breakers and enclosures are
used:
For service entrance, feeder or branch
circuit protection for lighting, heating,
appliance and motor circuits
In areas made hazardous due to the
presence of flammable vapors, gases or
combustible dusts
In damp, wet or corrosive locations
Indoors or outdoors at petroleum
refineries, chemical and petrochemical
plants and other process industry
facilities where similar hazards exist
To provide disconnect means, short
circuit protection and thermal time delay
overload protection
Features:
Options:
Description
Suffix
2 lugs for neutral connections (50, 100 and 225 amp.) ...............................................
S146
Ground neutral stud with 3 connectors (50, 100 and 225 amp.) .................................
S168
Standard Breather (Class I, Groups C, D; Class II, Groups E, F, G; Class III) ............
S219
Standard Drain (Class I, Groups C, D; Class II, Groups E, F, G; Class III) ..................
S198
Standard Breather and Drain (Class I, Groups C, D; Class II, Groups E, F, G; Class III) ... S198V
Universal Breather Drain (Class I, Groups C, D; Class II, Groups F, G) ...................
S454*
(2) Universal Breather Drains (Class I, Groups C, D; Class II, Groups F, G) ............ S454V*
Specify Auxiliary Switch
1A/1B (1P2T) ...........................................................................................................
S784
2A/2B (2P2T) ...........................................................................................................
S785
The following special options are available from factory by adding suffix to Cat. #:
Dimensions
Certifications and
Compliances:
In Inches:
NEC/CEC
Class I, Division 1 & 2, Groups C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA/EEMAC: 3, 4, 7CD, 9EFG
UL Standard: 698
CSA Standard: C22.2 No. 30
Standard Materials:
Bodies, covers and operating handles
copper-free aluminum
Operating shafts stainless steel
Interior parts sheet steel
Standard Finishes:
Copper-free aluminum natural
Stainless steel natural
Sheet steel zinc electroplate with
chromate finish
Cat. #
FLB140, 220, 221
FLB115, 141, 147, 148, 171, 172, 173,
175, 222, 361, 116, 142, 149, 174,
177, 223, 362
FLB224, 225, 264, 265, 267, 346
502
CAN: 1-800-265-0502
www.crouse-hinds.com
US: 1-866-764-5454
10 /4
6 /4
7 /4 7
5 /4
/16
11/8
71/2
133/8
81/2
93/4 91/8
/16
13/4
133/4
221/2
161/4
97/8 151/2
21
/32 27/16
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
3C
Ordering Information:
To order an enclosure complete with circuit breaker where there is a choice of manufacturer, insert the manufacturer's symbol in the
designated position of the catalog number.
Enclosures only can be ordered. Select from listings.
120VAC
or
125VDC
Hub
Size
Circuit Bkr.
Amp
Rating
Without Circuit
Bkr. Cat. #
/4
15
20
30
40
50
15
20
30
40
50
FLB221
FLB221
FLB221
FLB221
FLB221
FLB221
11/2
70
90
100
FLB223
FLB223 TT70 2
FLB223 TT90 2
FLB223 TT100 2
11/4
15
20
30
40
50
FLB222
FLB222
FLB222
FLB222
FLB222
FLB222
11/2
70
90
100
FLB223
FLB223 TT70 3
FLB223 TT90 3
FLB223 TT100 3
240VAC
or
125250VDC
240VAC
www.crouse-hinds.com
US: 1-866-764-5454
FLB220
FLB220
FLB220
FLB220
FLB220
FLB220
TT15
TT20
TT30
TT40
TT50
1
1
1
1
1
TT15
TT20
TT30
TT40
TT50
2
2
2
2
2
CAN: 1-800-265-0502
TT15
TT20
TT30
TT40
TT50
3C
Voltage
Rating
Enclosure
3
3
3
3
3
503
3C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
504
Hub
Size
Circuit Bkr.
Amp
Rating
Without Circuit
Bkr. Cat. #
15
20
30
40
50
FLB140
FLB140
FLB140
FLB140
FLB140
FLB140
11/ 2
70
90
100
FLB142
FLB142 WT70 2
FLB142 WT90 2
FLB142 WT100 2
FLB142 TT70 2
FLB142 TT90 2
FLB142 TT100 2
11/ 4
15
20
30
40
50
FLB141
FLB141
FLB141
FLB141
FLB141
FLB141
FLB141
FLB141
FLB141
FLB141
FLB141
11/ 2
70
90
100
FLB142
FLB142 WT70 3
FLB142 WT90 3
FLB142 WT100 3
480VAC
or
250VDC
3C
Voltage
Rating
Enclosure
480VAC
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
WT15
WT20
WT30
WT40
WT50
WT15
WT20
WT30
WT40
WT50
2
2
2
2
2
3
3
3
3
3
TT15
TT20
TT30
TT40
TT50
TT15
TT20
TT30
TT40
TT50
2
2
2
2
2
3
3
3
3
3
FLB142 TT70 3
FLB142 TT90 3
FLB142 TT100 3
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
3C
11/4
FLB115
11/2
70
90
100
FLB116
FLB116 WT70 2
FLB116 WT90 2
FLB116 WT100 2
11/4
15
20
30
40
50
FLB115
FLB115
FLB115
FLB115
FLB115
FLB115
11/2
70
90
100
FLB116
FLB116 WT70 3
FLB116 WT90 3
FLB116 WT100 3
WT15
WT20
WT30
WT40
WT50
Without Circuit
Bkr. Cat. #
1 /4
15
20
30
40
50
FLB361
FLB361
FLB361
FLB361
FLB361
FLB361
11/2
70
90
100
FLB362
FLB362 TT70 3
FLB362 TT90 3
FLB362 TT100 3
WT15
WT20
WT30
WT40
WT50
2
2
2
2
2
3
3
3
3
3
Enclosure
Hub
Size
Without Circuit
Bkr. Cat. #
FLB115
FLB115
FLB115
FLB115
FLB115
600VAC
Voltage
Rating
Circuit Bkr.
Amp
Rating
15
20
30
40
50
600VAC
or
250VDC
Circuit Breaker
Poles
Hub
Size
3C
Voltage
Rating
Enclosure
600VAC
Circuit Bkr.
Amp
Rating
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
TT15
TT20
TT30
TT40
TT50
3
3
3
3
3
505
3C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Voltage
Rating
600VAC
or
250VDC
Enclosure
Circuit Bkr.
Amp
Rating
Hub
Size
21/ 2
125
150
175
200
225
125
150
175
200
225
600VAC
21/ 2
Poles
Voltage
Rating
Hub
Size
600VAC
2 /2
3C
Circuit Bkr.
Amp
Rating
125
150
175
200
225
Without Circuit
Bkr. Cat. #
FLB264
FLB264
FLB264
FLB264
FLB264
FLB264
WT125
WT150
WT175
WT200
WT225
2
2
2
2
2
FLB264
FLB264
FLB264
FLB264
FLB264
FLB264
WT125
WT150
WT175
WT200
WT225
3
3
3
3
3
Without Circuit
Bkr. Cat. #
FLB224 or FLB346
TT125
TT150
TT175
TT200
TT225
3
3
3
3
3
Voltage
Rating
600VAC
or
250VDC
600VAC
Enclosure
Hub
Size
Circuit Bkr.
Amp
Rating
125
150
175
200
225
125
150
175
200
225
Without Circuit
Bkr. Cat. #
FLB267
FLB267
FLB267
FLB267
FLB267
FLB267
WT125
WT150
WT175
WT200
WT225
2
2
2
2
2
FLB267 or FLB225
FLB267
FLB267
FLB267
FLB267
FLB267
WT125
WT150
WT175
WT200
WT225
3
3
3
3
3
*Formerly "KB"
Formerly "JB"
506
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
FLB225
FLB225
FLB225
FLB225
FLB225
TT125
TT150
TT175
TT200
TT225
3
3
3
3
3
3C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Applications:
EFD circuit breakers and enclosures are used:
For branch circuit protection for lighting, appliance, and
motor circuits
In areas made hazardous due to the presence of flammable
vapors, gases or combustible dusts
In corrosive locations
For installation at petroleum refineries, chemical and petrochemical
plants and other process industry facilities where similar
hazards exist
To provide disconnect means, short circuit protection and thermal
time delay overload protection
Features:
3C
Electrical Ratings:
Single pole 120 / 240 VAC max.
Trip ratings 15, 20 and 30 amp.
Options:
Description
For use in Group B hazardous areas*
NEC:
Class I, Division 1 & 2, Groups B*, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA 3, 7B*CD, 9EFG, 12
Suffix
GB
Ordering Information
With Square D Type
"QOU" Circuit Breakers
Standard Materials:
Standard Finishes:
20 Amp Cat. #
30 Amp Cat. #
EFD21105
EFD31105
EFD21106
EFD31106
EFDC21106
EFDC31106
EFD22106
EFD32106
EFD22105
EFD32105
EFDC22106
EFDC32106
Dimensions
In Inches:
Hub Size
3
/4
1
Dim. "h"
/8
1
Dim. "l"
/16
/16
13
15
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
507
3C
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
Certifications and
Compliances:
3C
NEMA: 3, 4X and 12
CSA Standard: C22.2 No. 94
UL Standard: 489
Features:
Options:
Description
Suffix
S618
Circuit breaker enclosure with built-in
Krydon material handle
Ordering Information
To order an enclosure complete with circuit breaker, insert the manufacturers symbol in the designated position of the catalog number.
Enclosures only can be ordered. Select from listings.
Circuit Breaker
Voltage
Poles
Rating
Amps
100A Frame (Non-Interchangeable Trip)
15
20
25
30
35
40
240 VAC/
2
50
250 VDC
60
70
80
90
100
15
20
25
30
35
40
50
60
70
80
90
100
480 VAC/
250 VDC
Enclosure
With Circuit
Breaker Cat. #
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
15EB 22
20EB 22
25EB 22
30EB 22
35EB 22
40EB 22
50EB 22
60EB 22
70EB 22
80EB 22
90EB 22
100EB 22
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
15EHB 24
20EHB 24
25EHB 24
30EHB 24
35EHB 24
40EHB 24
50EHB 24
60EHB 24
70EHB 24
80EHB 24
90EHB 24
100EHB 24
NCB1018F
Circuit Breakers:
NOTE ON HUBS: The following number and sizes of hubs (not mounted) are included when
circuit breakers are ordered complete. If enclosures only are ordered, hubs must be ordered
separately (see "Options")
Frames
600V
225/
250A
600V
Manufacturer
General Electric
Symbol
100/ 150A
240V 480V
TT
TEB
TED
TED
TFJ
Square D
DT
FAL
FAL
FAL
KAL
WT
EB
EHB,
EHD
FB,
FDB
JB,
JDB
Cutler-Hammer
400A
600V
Circuit Breaker
Frame
Ampere
Rating
Number
Included
Hub
Size
LAL
1550
60100
110225
250400
2
2
2
2
11/4
2
21/2
3
Specify voltage.
508
www.crouse-hinds.com
Without Circuit
Breaker Cat. #
US: 1-866-764-5454
CAN: 1-800-265-0502
*Formerly EHB.
Formerly FB.
Formerly LB.
Formerly JB.
Copyright 2013 Eatons Crouse-Hinds Business
Circuit Breaker
Enclosure
With
Circuit
Breaker
Amps Cat. #
Without
Circuit
Breaker
Cat. #
240 VDC
480 VAC
600 VAC
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
15EB 32
20EB 32
25EB 32
30EB 32
35EB 32
40EB 32
50EB 32
70EB 32
80EB 32
90EB 32
100EB 32
15
20
25
30
35
40
50
70
80
90
100
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
15EHB 34
20EHB 34
25EHB 34
30EHB 34
35EHB 34
40EHB 34
50EHB 34
70EHB 34
80EHB 34
90EHB 34
100EHB 34
15
20
25
30
35
40
50
70
80
90
100
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
NCB1018F
15FB 36
20FB 36
25FB 36
30FB 36
35FB 36
40FB 36
50FB 36
70FB 36
80FB 36
90FB 36
100FB 36
NCB1018F
Voltage
Poles Rating
Enclosure
With
Circuit
Breaker
Amps Cat. #
Without
Circuit
Breaker
Cat. #
26
26
26
26
26
26
NCB1024F
NCB1024F
NCB1024F
NCB1024F
NCB1024F
NCB1024F
NCB1024F
110JB
125JB
150JB
175JB
200JB
225JB
36
36
36
36
36
36
NCB1024F
250LB
300LB
350LB
400LB
26
26
26
26
NCB1426F
250LB
300LB
350LB
400LB
36
36
36
36
NCB1426F
600 VDC
600
VAC
110
125
150
175
200
225
250
300
350
400
NCB1426F
NCB1426F
NCB1426F
NCB1426F
3C
3C
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
Circuit Breakers:
NCB1018F
Manufacturer
General Electric
Symbol
Frames
100/
150A
240V 480V
TT
TEB
TED
TED
TFJ
Square D
DT
FAL
FAL
FAL
KAL
EB
EHB,
EHD
FB,
FDB
JB,
JDB
Cutler-Hammer
WT
600V
225/
250A
600V
400A
600V
LAL
Note on Hubs: The following number and sizes of hubs (not mounted) are included when
circuit breakers are ordered complete. If enclosures only are ordered, hubs must be
ordered separately (see "Options").
NCB1018F
Circuit Breaker
Frame
Ampere
Rating
Number
Included
Hub
Size
1550
60100
110225
2
2
2
11/4
2
21/2
Specify voltage.
2-pole, 600 VAC/250 VDC for Square D circuit breakers only.
*For Square D circuit breakers only.
Also available with interchangeable trip breakers. Specify on order.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
509
3C
Corrosion-Resistant
Dust-tight
Watertight
Weatherproof
NEMA 3, 4X, 12
3C
In Inches*
Outside Dimensions
Cat. #
NCB1018
19 /32
NCB1024
NCB1426
25 /32
2713/32
Mounting Dimensions
mw
ml
dl
11 /32
8 /32
7 /8
11 /32
1513/32
8 /32
923/32
7 /8
117/8
w
13
13
13
13
23
23
7
7
19 /8
16 /8
511/16
25 /8
271/4
22 /8
2311/16
511/16
911/16
510
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
dw
7
4C
Control Stations
Hazardous and Non-hazardous
Description
Page No.
Application/Selection
page
page
page
page
514
519
521
524
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
511
4C
4C
Control Stations
Application and Selection
Quick Selector Chart
Applications:
4C
Options:
Considerations for
Selection:
The environment of the control station
location and requirements for
construction in terms of NEC/CEC
compliances and NEMA/EEMAC type
Function to be performed
Desirability of factory sealing as
compared to field sealing
Factory sealing has distinct advantages:
Less installation problems
Less time consuming
Less change of error
Lower installed cost
Accommodates future changes to
circuitry
Greater reliability
The number of controls required, and
the space available for installation.
Where space is limited, panel or junction
box mounting with many combinations
are available
See "Quick Selector Chart" for guidance
NEMA/EEMAC
Type
3, 4
Factory
Sealed
EDS, EDSC
Cl.
Cl.
Cl.
Cl.
Cl.
I, Div. 1, Groups C, D
I, Div. 2, Groups B, C, D
II, Div. 1, Groups E, F, G
II, Div. 2, Groups F, G
III
3, 7B
(Div. 2) CD,
9EFG
Pilot light
Pushbutton
Selector switch
Pilot light
Pushbutton
Selector switch
DSD Covers
and Device
Sub-assemblies
Cl.
Cl.
Cl.
Cl.
3, 7B,
9EFG
Pilot light
Pushbutton
Selector switch
Pilot light
Pushbutton
Selector switch
DSD-SR
Cl.
Cl.
Cl.
Cl.
3, 5, 7CD,
9EFG, 12
EDSCM
Cl.
Cl.
Cl.
Cl.
Cl.
I, Div. 1, Groups C, D
I, Div. 2, Groups B, C, D
II, Div. 1, Groups E, F, G
II, Div. 2, Groups F, G
III
EFS
Cl.
Cl.
Cl.
Cl.
Type of
Mounting
Surface
1-5 gang
Cover
Style
Gasketed
1-2*
Surface
1-2 gang
Ground
joint
Surface
1 gang
Ground
joint
Selector Switch
Surface
1 gang
Ground
joint
3, 7CD,
9EFG
Pilot light
Pushbutton
Selector switch
1-15*
Surface
1-15 gang
Ground
joint
3, 7BCD,
9EFG
Pilot light
Pushbutton
Selector switch
1-2*
Surface
1 gang
Ground
joint
Function
Pushbutton
Pilot light
Selector switch
Pilot light
Pushbutton
Selector switch
512
www.crouse-hinds.com
US: 1-866-764-5454
No. of
Devices
or Units
1-5*
CAN: 1-800-265-0502
Control Stations
4C
NEMA/EEMAC
Type
3, 7B
(Div. 2) CD,
9EFG
Function
Pilot light
Pushbutton
Pushbutton
Signal Lamp
Potentiometer
Ammeter
Selector Switch
Terminal Blocks
N2FA,
N2FAC
3, 7BCD, 12
Fire Alarm
N2S,
N2SC
N2SU,
N2SCU
3, 4X, 7BCD, 12
OAC
3, 7ABCD,
9EFG, 12
No. of
Devices Type of
Cover
or Units Mounting Style
1-2-3
Surface
Ground joint
1-2 gang
1-4*
Surface
1 gang
Screw and
Gasket
Pushbutton
Selector switch
Surface
1 gang
Screw and
Gasket
Pilot light
Pushbutton
Selector switch
Combination
Pilot light
Pushbutton
Selector switch
Combination
1-4*
Surface
1 gang
Screw and
Gasket
Pushbutton
Selector switch
Pushbutton
Selector switch
1-2*
Surface
1 gang
Threaded
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
513
4C
GHG43
Factory
Sealed
Pilot light
Pushbutton
4C
4C
Applications:
Five modular components operators,
contact blocks, covers, legend plates, and
bodies are combined to provide a variety
of control stations which are:
For use indoors or outdoors, in areas
which are hazardous due to the
presence of flammable gases and
vapors, or combustible dust.
Used in conjunction with magnetic
starters or contactors for remote control
of motors and other electrical apparatus.
For installation in petroleum refineries,
chemical, petrochemical, and other
industrial process facilities; grain
processing and storage facilities; and
other heavy industrial applications where
Class I, Class II, or Class III hazards are
present.
Features:
Momentary contact pushbuttons,
maintained contact pushbuttons, and
pilots lights offer a choice of functions.
Selector switches in 2 or 3 position
configurations including keyed and
spring return options.
Single-hole, two-hole, and three-hole
covers for one, two, or three devices
respectively per station.
Rugged control devices for safe, reliable
operation in industrial applications.
Bodies, with extra room for wire pulling
and termination, also include two
integral mounting feet for fast, secure
installation.
Bodies have 1/2", 3/4", or 1" dead-end or
through-feed conduit hubs with integral
bushing for protection of wire insulation.
Covers and bodies are available in
Feraloy or copper-free aluminum for
light weight and corrosion resistance.
DL legend plates have large lettering to
give clear indication of device function.
Space is available for field markings.
Standard Materials:
Options:
Description
Suffix
Copper-free aluminum bodies and
covers
SA
Corro-free epoxy finish for use in
severely corrosive environments.
FlexStation covers and bodies.
S752
Standard Finishes:
Feraloy iron alloy electrogalvanized
and aluminum acrylic paint.
Copper-free aluminum natural.
Stainless steel natural.
Electrical Ratings:
Pushbuttons and selector switches
600 VAC heavy duty (NEMA A600).
Pilot lights 120 VAC.
Dimensions
In Inches:
Certifications and
Compliances:
NEC
Class I, Division 1 & 2, Groups B*
(Div. 2), C, D
Class II, Division 1 & 2, Groups E, F, G
Class III
Zone 1 & 2 Group IIB*
NEMA: 3R, 7B (Div. 2) CD, 9EFG, 12
UL Standard: 1203
514
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
Cat. #
DEV11
DEV12
DEV22
Options
Suffix
light
light
light
light
light
with
with
with
with
with
Cat. #
red jewel
green jewel
amber jewel
clear jewel
blue LED and clear jewel
DEV30
DEV30
DEV30
DEV30
DEV30
Options
Suffix
LED
S300
T2
T4
T5
J1
J3
J6
J10
J11 LED
Cat. #
2-position (pos. 1 N.O., pos. 2 N.C.) for use with 1 or 2 contact blocks
3-position (pos. 1 N.O., pos. 2 Open, pos. 3 N.C.) for use with 1 or 2 contact blocks
3-position (pos. 1 N.C., pos. 2 N.O., pos. 3 N.O. for Switch A)
(pos. 1 N.O., pos. 2 N.O., pos. 3 N.C. for Switch B) for use with 2 contact blocks
DEV42
DEV43
Options
Suffix
S634
S635
S842
S847
S847
S847
S847
DEV44
K1
K2
K3
K4
STEP 2 Select Contact Block (if required). For product details see page 571.
Contact Block
Description
Cat. #
ESWP126
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
515
4C
Specify color for each pushbutton button (ex: DEV11G, DEV22GR). Color is black if unspecified.
Green button - unmarked
G
Red button - unmarked
R
Momentary red mushroom head style (not available with lockout or with DEV22)
S111
Lockout with bar and chain (available on DEV11 and DEV12)
S153
Maintained red mushroom head style (lockout comes standard, do not specify S153; not available
S769
on DEV22) (Push to stop only)
4C
4C
Cat. #
Inscription
Cat. #
Inscription
Cat. #
Inscription
DL101
DL128
DL129
DL130
DL132
DL133
DL135
DL136
DL137
DL138
DL139
DL140
DL141
DL142
DL143
DL144
DL148
DL149
DL165
DL186
DL187
DL188
DL189
DL190
DL191
DL192
DL193
DL194
DL195
DL196
DL197
DL198
DL199
Blank
Run-Jog
Hand-Auto
Forward-Reverse
Open-Close
Up-Down
In-Out
Raise-Lower
Start-Stop
Run-Off-Jog
Hand-Off-Auto
For-Off-Rev
Fast-Off-Slow
1-Off-2
Open-Off-Close
Up-Off-Down
Off-On
Auto-Off-Hand
Slow-Fast
Safe-Run
Raise-Off-Lower
Slow-Off-Fast
Odd-Off-Even
Stop-Start
On-Off
Fast-Slow
Local-Remote
Trip-Reset
Auto-Manual
Start-Emer Stop
Alarm-Silence
Maint-Manual
Test-Reset
DL01
DL02
DL03
DL05
DL06
DL07
DL08
DL09
DL10
DL11
DL12
DL13
DL14
DL15
DL16
DL17
DL18
DL19
DL20
DL21
DL22
DL23
DL24
DL25
DL26
DL27
DL28
DL29
DL30
DL32
DL33
DL35
DL36
DL37
DL38
DL39
DL40
DL41
DL42
DL43
DL44
DL46
DL47
DL48
DL49
DL65
DL85
DL86
DL87
DL88
DL89
DL90
DL91
DL92
DL93
DL94
DL95
DL96
DL97
DL98
DL99
Open-Close
Up-Down
In-Out
Raise-Lower
Start-Stop
Run-Off-Jog
Hand-Off-Auto
For-Off-Rev
Fast-Off-Slow
1-Off-2
Open-Off-Close
Up-Off-Down
Fast
Slow
Off-On
Auto-Off-Hand
Slow-Fast
Safe
Safe-Run
Raise-Off-Lower
Slow-Off-Fast
Odd-Off-Even
Stop-Start
On-Off
Fast-Slow
Local-Remote
Trip-Reset
Auto-Manual
Start-Emer Stop
Alarm-Silence
Maint-Manual
Test-Reset
Note:
516
Description
Cat. #
DS441
DS442
DS443 SA
206765
Options:
Suffix
SA
S752
S753
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
Through Feed
Hub Size
EDS171
EDS271
EDS371
EFS172
EFS272
EFS372
EDSC171
EDSC271
EDSC371
EFSC172
EFSC272
EFSC372
/2"
3
/4"
1"
1
/2"
3
/4"
1"
Suffix
Aluminum body
Exterior epoxy powder coat finish
Interior & exterior epoxy powder coat finish
SA
S752
S753
4C
Options:
Back Boxes for use with DS443-SA cover or with 11/2 gang DS511 (3-operator) Series covers
Dead End
Through Feed
Hub Size
EFD1491 SA
EFD2491 SA
EFD3491 SA
EFDC1491 SA
EFDC2491 SA
EFDC3491 SA
/2"
3
/4"
1"
Options
Suffix
S752
S753
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
517
4C
FlexStation Control
Station Components
Back Boxes for use with DS441 and DS442 covers
Through Feed
Hub Size
EDSC378
1"
3 gang tandem
4C
Cat. #
DS455
DS476
DS456
DS429
DS454
DS510
Add color symbol for each pilot light from table below.
Color
Symbol
Color
Symbol
Color
Symbol
Red
Green
J6
J10
Blue
J11
J1
J3
Amber
Clear
Suffix
220 / 110
440 / 110
550 / 110
220240
440480
550600
T2
T4
T5
If desired, markings on indicating plates may be added to catalog number. Select from the list of standard markings below:
OFF
RESET
START
RUN
TRIP
STOP
JOG
TEST
ON
OPEN
DOWN
EMERGENCY
CLOSE
IN
FORWARD
UP
OUT
REVERSE
518
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
LIGHT ON
HAND
AUTOMATIC
RAISE
LOWER
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
4C
For use with DSD device cover sub-assemblies see page 521.
Applications:
4C
Features:
EDSCM Modular Control Stations have many distinct advantages
over multiple individual units:
Reduce installation costs. A multi-gang device assembly can be
installed in less time than several single-gang units.
Seals not required between gangs.
Improved appearance. No exposed conduit runs between devices.
Lightweight. Fifteen-gang aluminum device body can be installed
by one person.
Mounting feet are provided on the top and bottom of every gang to
facilitate installation.
Two and three gang tandem bodies have 11/4" through feed inward
horizontal hubs and 1" or 2" vertical through feed hubs. Pipe plugs
are installed in one horizontal hub and both vertical hubs.
Single-gang device bodies have 1" through feed inward horizontal
hubs and 3/4" through feed vertical hubs. Pipe plugs are installed in
one horizontal hub and both vertical hubs.
All hubs are taper tapped and have integral bushings.
Close nipples, which are used to join two or more device bodies
together, are furnished with EDSCM 21, 32, 33, 62 and 63 units.
Any combination of bodies can be joined together horizontally.
Ordering Information
Description
Single Gang
Tandem Two Gang
Tandem Two Gang
Tandem Three Gang
Tandem Three Gang
Through Feed
Hub Size
Cat. #
/4"
1"
2"
1"
2"
EDSCM21
EDSCM32
EDSCM62
EDSCM33
EDSCM63
* When a CPS receptacle cover device is used, the assembly meets requirements for Class
I, Groups C and D areas only.
EDSCM32 and EDSCM62 will not accept covers with S697 or S701 suffixes.
Bottom gang opening will accept covers with S697 or S701 suffixes.
Standard Materials:
Copper-free aluminum
In Class I areas all conduit runs entering bodies must be sealed. As many as five bodies
can be joined horizontally without an intervening seal.
Finish:
Natural
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
519
4C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Dimensions
4C
In Inches:
EDSCM21
EDSCM32
EDSCM62
EDSCM33
EDSCM63
* When a CPS receptacle cover device is used, the assembly meets requirements for Class I,
Groups C and D areas only.
Dimensions are approximate. Not for construction purposes.
520
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
4C
Standard Finishes:
Feraloy electrogalvanized and
aluminum acrylic paint
Copper-free aluminum natural
Features:
Certifications and
Compliances:
(When used with EDSCM & EDS bodies):
NEC/CEC:
Class I, Division 1 & 2, Groups C, D
Class I, Division 2, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA/EEMAC: 3, 7B (Div. 2) CD, 9EFG
UL Standards: 894, 698
CSA Standard: C22.2 No. 30
Pushbuttons, Pilot Lights & Selector
Switches (when used with EFS bodies):
NEC/CEC:
Class I, Division 1 & 2, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA/EEMAC: 3, 7BCD, 9EFG
UL Standard: 1203
CSA Standard: C22.2 No. 30
Standard Materials:
Covers, front operated Feraloy iron
alloy and copper-free aluminum
Covers, side operated copper-free
aluminum
Shafts and shaft bushings stainless
steel
Rocker handles, pushbuttons and
guards type 6 / 6 nylon
Sealing enclosures copper-free
aluminum
CPS delayed action receptacle cover:
Receptacle housing copper-free
aluminum
Insulation diallyl phthalate (DAP)
Contacts brass
Options:
The following special options are available by adding suffix to Cat. #:
Description
Suffix
Lockout provision on front operated pushbutton cover (standard on buttons
marked "STOP" and "OFF").......................................................................................
S153
Three-position selector switches with modified operation:
Momentary contact clockwise operation, spring return to center, maintained
contact counter-clockwise operation.......................................................................
S634
Momentary contact counter-clockwise operation, spring return to center,
maintained contact clockwise operation..................................................................
S635
Emergency "STOP" button momentary front operated mushroom button breaks
normally closed contacts (DL02 legend plate included - must specify legend text)
S111
Bodies and covers copper-free aluminum..............................................................
SA
For 24 VDC operation on pilot lights.........................................................................
S300
Maintained contact mushroom head with lockout and guard (Will not fit with a
pilot light if transformer is required) (Push to stop only)............................................
S769
Spring return to center from right and left (For DEV43 or DEV44 only)....................
S842
Key Operated removable from all positions........................................................... S847 K1
Key Operated removable from left position for DEV42 or from center for DEV43
and DEV44................................................................................................................. S847 K2
Key Operated removable from right position for DEV42 or from left for DEV43
and DEV44................................................................................................................. S847 K3
Key Operated removable from right position for DEV43 and DEV44..................... S847 K4
Ordering Information
Manual Motor Starters
Poles
Max. H.P.
Max. Volts A.C.
With Allen-Bradley Bulletin 600 Switches
1
1
115230
2
1
115230
DSD910
DSD911
115230
115230
DSD912
DSD913
115230
115230
DSD914
DSD915
250
600
250
600
DSD916
DSD916
DSD917
DSD917
www.crouse-hinds.com
(30A)
(30A)
(30A)
(20A)
Cat. #
When a CPS receptacle cover device is used, the assembly meets requirements for Class
I, Groups C and D areas only.
* For pushbuttons, pilot lights, & selector switches, use EFS back box with required external
conduit seal for 1 inch hub size, within 5 feet for Class I, Division 1, Group B applications.
A comparable factory sealed cover will fit on the EDSCM21 body, EDS and EDSC bodies
and in bottom gang of EDSCM33 and EDSCM63 bodies. To order, add suffix S701 to
catalog number.
US: 1-866-764-5454
CAN: 1-800-265-0502
521
4C
4C
DSD918
DSD922
DSD933
DSD962
DSD970
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
CPS152R
ENR5201
For use with EDSCM modular control device bodies see page 519 & EFS/EDS back boxes.
4C
Ordering Information
Front Operated Pushbutton Stations
Factory Sealed
Number of
Normal
Cover Buttons Position
Diagram
Cat. #
Rating
Cat. #
CPS152R
(2 wire, 3 pole)
1 Circuit
Universal
DSD918
2 Circuits
Universal
DSD919
CPS532R
(2 wire, 3 pole)
2 Circuits
DSD920
CPS732R
(3 wire, 4 pole)
2 Circuits
Universal
DSD921
2 Circuits
Start-Stop
unless
otherwise
specified
DSD922
2 Circuits
Universal
Mushroom Head
DSD970
3 (2-operator)
3 Circuits
Universal
DSD962
3 (3-operator)
3 Circuits
Universal
DS511 SA
3 (3-operator)
3 Circuits
Universal
Double pilot light single pushbutton
combo
DS513 SA
START
STOP
ON
EMERGENCY
FORWARD
REVERSE
3 (3-operator)
3 Circuits
Universal
Double pushbutton single pilot light
combo
DS514 SA
1-Pole
2-Pole
3-Pole
3-Way
4-Way
1-Pole
2-Pole
3-Way
522
277 VAC
Cat. #
20
20
20
20
DSD933
DSD934
DSD935
DSD936
DSD937
DSD939
DSD940
DSD941
www.crouse-hinds.com
Rating
Cat. #
20 A, 125 VAC
ENR5201
Diagram
ENR6202
20 A, 250 VAC
6-20R
Amperes
120 VAC
20
20
30
30
30
Factory Sealed
5-20R
20
20
30
30
30
US: 1-866-764-5454
CAN: 1-800-265-0502
OFF
RUN
JOG
OPEN
CLOSE
UP
RESET
TRIP
TEST
DOWN
IN
OUT
LIGHT ON
HAND
AUTOMATIC
RAISE
LOWER
* For pushbuttons, pilot lights, & selector switches, use EFS back box with required external
conduit seal for 1 inch hub size, within 5 feet for Class I, Division 1, Group B applications.
When a CPS receptacle cover device is used, the assembly meets requirements for Class
I, Groups C and D areas only.
Two universal contact blocks, must be wired as two circuits with one normally open and
one normally closed. 1 green button, 1 red button, and lockout provision provided as
standard.
16 Amp., 125V.
10 Amp., 250V.
To order a comparable factory sealed cover for EDS, EDSC, EDSCM21 and the bottom
gang of EDSCM33 and EDSCM63 bodies, add suffix S697. Factory sealed for Class I,
Division 2, Group B.
Cannot be factory sealed.
Can only be used with EFD Series 11/ 2 gang back boxes. Pushbuttons include contact
blocks. Standard pushbutton color is black. For optional colors - red, green - write in
color. Example: DS511 GREEN BLACK RED-SA. First color is for uppermost button. For
optional legend markings write in marking after device operator color. Example: DS513-J3
JOG-J1 STOP GREEN-SA.
4C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Diagram
Cat. #
DSD948
DSD951
DSD925
DSD947-J1-J1
Ordering Information
Side Operated Pushbutton Station
600 VAC Heavy Duty, Factory Sealed
Normal Position
Diagram
Cat. #
1 Circuit Universal
DSD949
2 Circuits Universal
DSD950
2 Circuits
1 Open - A
1 Closed - B
Start-Stop unless
otherwise specified
DSD951
DS512 SA
DS513 SA
Description
DSD958
DSD961
DSD961
DS514 SA
DSD973
DSD974
DSD975
DSD976
DSD977
Cat. #
DSD957
Add color symbol for each pilot light from table below.
Color
Symbol
Color
Symbol
Color
Symbol
Blank Cover
Two
Position
DSD948
Blank Cover
Selector Switches
Style
DSD947
Two
Circuit
DSD923
Four
Circuit
DSD924
Red
Green
J1
J3
Amber
Clear
J6
J10
Blue
J11
DSD925
Two
Circuit
DSD926
Three
Position
Four
Circuit
DSD927
* For pushbuttons, pilot lights, & selector switches, use EFS back box with required external
conduit seal for 1 inch hub size, within 5 feet for Class I, Division 1, Group B applications.
LED pilot lights can be furnished in place of standard incandescent pilot lamps. Add suffix
LED to Cat. No. after last color symbol.
Can only be used with EFD Series 11/ 2 gang back boxes. Pushbuttons include contact
blocks. Standard pushbutton color is black. For optional colors - red, green - write in
color. Example: DS511 GREEN BLACK RED-SA. First color is for uppermost button. For
optional legend markings write in marking after device operator color. Example: DS513-J3
JOG-J1 STOP GREEN-SA.
www.crouse-hinds.com
US: 1-866-764-5454
Primary Voltage
Range
Suffix
220 / 110
440 / 110
550 / 110
220240
440480
550600
T2
T4
T5
OFF
RUN
JOG
OPEN
CLOSE
UP
RESET
TRIP
TEST
DOWN
IN
OUT
LIGHT ON
HAND
AUTOMATIC
RAISE
LOWER
RUN, JOG
HAND, AUTOMATIC
FORWARD, REVERSE
Three-Position
JOG, OFF, RUN
AUTOMATIC, OFF, HAND
FORWARD, OFF, REVERSE
FAST, OFF, SLOW
CAN: 1-800-265-0502
IN, OUT
RAISE, LOWER
START, STOP
1, OFF, 2
OPEN, OFF, CLOSE
UP, OFF, DOWN
523
4C
DSD958
DSD957
DSD961-J1
For use with EDSCM modular control device bodies see page 519 &
EFS/EDS back boxes.
4C
Ordering Information
Switch Function
Cat. #
Number of Poles
Number of Positions
ON/OFF
DSD
DSD
DSD
DSD
DSD
DSD
SR30120
SR30220
SR30320
SR30420
SR30520
SR30620
1
2
3
4
5
6
2
2
2
2
2
2
DSD SR30121
DSD SR30221
DSD SR30321
1
2
3
2
2
2
DOUBLE-THROW
without OFF
Connecting Diagram
1-6 Pole
4C
1-3 Pole
DOUBLE-THROW
without OFF
with electrically
isolated contacts
DOUBLE-THROW
with OFF
DSD SR30123
DSD SR30223
DSD SR30323
1
2
3
2
2
2
1-3 Pole
DSD SR30132
DSD SR30232
DSD SR30332
1
2
3
3
3
3
1-3 Pole
DOUBLE-THROW
with OFF
and electrically
isolated contacts
DSD SR30134
DSD SR30234
DSD SR30334
1
2
3
3
3
3
1-3 Pole
Electrical Specification
Horsepower Rating
3PH
1PH
Voltage
120
3
240
7.5
480
10
600
10
Maximum Current: 30 A
1.5
3
5
5
Options:
Description
Lockout for 2 position switch, handle in either position
Suffix
SX178
S349
DSD-SR cover assembly shown
mounted to an EDS back box
524
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Applications:
NEC/CEC:
Class I, Division 1 & 2, Groups B*, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA/EEMAC: 3, 7B*CD, 9EFG
UL Standard: 1203
CSA Standard: C22.2 No. 30
Standard Materials:
Bodies Feraloy iron alloy; copper-free aluminum
Front operated pushbutton and pilot light covers Feraloy iron
alloy
Side operated type pushbutton covers copper-free aluminum
Shafts stainless steel
Shaft bushings stainless steel
Rocker handle and pushbutton guards type 6 / 6 nylon
Sealing enclosures copper-free aluminum
4C
Features:
4C
Standard Finishes:
Options:
The following special options are available from the factory by
adding suffix to Cat. #:
Description
Suffix
Emergency "Stop" button (momentary) front operated red
mushroom button.................................................................... S111
Lockout provision on front operated pushbutton cover
(standard on buttons marked "OFF" and "STOP")................. S153
For 24 VDC operation on pilot lights ...................................... S300
Three-position selector switches with modified operation:
Momentary contact clockwise operation, spring return to
center, maintained contact counter-clockwise operation
S634
Momentary contact counter-clockwise operation, spring
return to center, maintained contact clockwise operation.... S635
Bodies and covers (single and two gang units) copperfree aluminum..........................................................................
SA
Where indicated in the catalog listings, EDS units suitable
for Class I, Division 1, Group B usage can be supplied, add
suffix -GB, EFS units are suitable for Class I, Division 1,
Group B as standard...............................................................
GB
Maintained contact mushroom head with lockout and
guard. May not be combined with a pilot light if a
transformer is required. (Push to stop only) ........................... S769
Spring return to center from right and left .............................. S842
EDS bodies and factory sealed cover and device sub-assemblies are
available for field assembly (see page 521).
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
525
4C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Factory sealed EDS and EFS pilot light, pushbutton and selector
switch control stations do not need external sealing. Device contacts
are factory sealed in explosionproof ESWP contact blocks. Small,
compact enclosures have accurately ground wide flanges on both
the body and cover for a flame-tight joint.
4C
EFS/EDS Series
Dimensions (Inches)
Covers
Bodies
Hub
Size
1
/2
3
/4
1
Dim. Dim.
"h"
"i"
/4
/8
1
3
7
/16
/16
/16
13
13
15
Side View
Selector switch
526
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
4C
1 Circuit
Universal
Marking
Specify
2 Circuits
Universal
2 Circuits
STARTSTOP
unless
otherwise
specified
Specify
2 Circuits
Universal
2 Circuits
Specify
Specify
Diagram
EDS2184 S769
Maintained
Mushroom Head
EDS215
Hub Size
Cat. #
Cat. #
Cat. #
Cat. #
Cat. #
/2
/4
1
Dead End
EDS1184
EDS2184
EDS3184
EDS2190
EDS3190
EDS115
EDS215
EDS315
EDS2192
EDS3192
EDS1155
EDS2155
EDS3155
/2
3
/4
1
Through Feed
EDSC1184
EDSC2184
EDSC3184
EDSC1190
EDSC2190
EDSC3190
EDSC115 EDSC1192
EDSC215 EDSC2192
EDSC315 EDSC3192
1
3
EDSC1155
EDSC2155
EDSC3155
EDSC225
Dimensions
Normal
Pos.
1 Circuit
Universal
2 Circuits
Universal
2 Circuits
Marking
Specify
Specify
START-STOP
unless
otherwise
specified
ED11
ED12
ED12
Diagram
Replacement
Pushbuttons
Cat. #
Cat. #
Cat. #
/4
1
Dead End
EDS2284
EDS3284
EDS2290
EDS3290
EDS225
EDS325
/2
3
/4
1
Through Feed
EDSC1284
EDSC2284
EDSC3284
EDSC1290
EDSC2290
EDSC3290
EDSC125
EDSC225
EDSC325
If desired, markings on indicating plates may be added to catalog number. Select from the list of standard markings below:
START
STOP
ON
OFF
RUN
JOG
RESET
TRIP
TEST
LIGHT ON
HAND
AUTOMATIC
EMERGENCY
FORWARD
REVERSE
OPEN
CLOSE
UP
DOWN
IN
OUT
RAISE
LOWER
* Class I, Group B: Consider using EFS series pushbuttons, see page 528. All enclosures listed above can be modified for Class I, Group B, Div. 1 usage. Add suffix GB to the Cat. No. Seals
must be installed within 11/ 2" of each conduit opening in Division 1. These products are suitable for Group B, Div. 2 as listed, without external seals. In Canada, for Group B applications
consult factory.
Two universal contact blocks, must be wired as two circuits, with one normally open and one normally closed.
Single external button operates both inner buttons simultaneously.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
527
4C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Ordering Information
Normal Pos.
1 Circuit
Universal
2 Circuits
Universal
Marking
2 Circuits
Specify
Specify
STARTSTOP
unless
otherwise
specified
ED11
ED12
ED12
2 Circuits
Universal
2 Circuits
Specify
Specify
ED12
ED12
Diagram
4C
Replacement
Pushbuttons
Cat. #
Cat. #
Cat. #
Cat. #
Cat. #
/2
/4
1
Dead End
EFS1184
EFS2184
EFS3184
EFS2190
EFS3190
EFS115
EFS215
EFS315
EFS2192
EFS3192
EFS1155
EFS2155
EFS3155
/2
3
/4
1
Through Feed
EFSC1184 EFSC1190 EFSC115 EFSC1192 EFSC1155
EFSC2184 EFSC2190 EFSC215 EFSC2192 EFSC2155
EFSC3184 EFSC3190 EFSC315 EFSC3192 EFSC3155
1
3
EFS2184 START
Standard black
pushbutton
EFS215
Dimensions
see page 526
If desired, markings on indicating plates may be added to catalog number. Select from the list of standard markings below:
START
STOP
ON
OFF
RUN
JOG
RESET
TRIP
TEST
LIGHT ON
HAND
AUTOMATIC
EMERGENCY
FORWARD
REVERSE
OPEN
CLOSE
UP
DOWN
IN
OUT
*Class I, Group B: All enclosures listed above are suitable for Class I, Group B, Div. 1 usage. Seals only have to be installed on 1 inch conduit within 5 ft. in Division 1.
For replacement contact blocks, see page 571.
Two universal contact blocks, must be wired as two circuits, with one normally open and one normally closed.
Single external button operates both inner buttons simultaneously.
528
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
RAISE
LOWER
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
4C
Dimensions
see page 526
EDS2696
EDSC2162
Two Gang
2 Circuits
Universal
2 Circuits
Normal Pos.
1 Circuit
Universal
2 Circuits
Universal
2 Circuits
Marking
Specify
Specify
START-STOP
unless
otherwise
specified
Marking
Specify
Specify
START-STOP
unless
otherwise
specified
ED11
ED12
ED12
Diagram
Diagram
Replacement
ED11
Pushbuttons
ED12
Replacement
Pushbuttons
ED12
/2
/4
1
Cat. #
Dead End
EDS1596
EDS2596
EDS3596
/2
/4
1
Through Feed
EDSC1596 EDSC1194
EDSC2596 EDSC2194
EDSC3596 EDSC3194
1
3
1
3
4C
Normal Pos.
1 Circuit
Universal
Cat. #
Cat. #
Hub Size
EDS2194
EDS3194
EDS1162
EDS2162
EDS3162
3
/4
1
Cat. #
Dead End
EDS2696
EDS3696
/2
/4
1
Through Feed
EDSC1696 EDSC1294 EDSC1262
EDSC2696 EDSC2294 EDSC2262
EDSC3696 EDSC3294 EDSC3262
EDSC1162
EDSC2162
EDSC3162
Cat. #
Cat. #
EDS2294
EDS3294
EDS2262
EDS3262
If desired, markings on indicating plates may be added to catalog number. Select from the list of standard markings below:
START
STOP
ON
OFF
RUN
JOG
RESET
TRIP
TEST
LIGHT ON
HAND
AUTOMATIC
EMERGENCY
FORWARD
REVERSE
OPEN
CLOSE
UP
DOWN
IN
OUT
RAISE
LOWER
*Class I, Group B: All enclosures listed above can be modified for Class I, Group B, Div. 1 usage. Add suffix GB to the Cat. No. Seals must be installed within 11/ 2" of each conduit opening in
Division 1. These products are suitable for Group B, Div. 2 as listed, without external seals.
For replacement contact blocks, see page 571.
Two universal contact blocks, must be wired as two circuits, with one normally open and one normally closed.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
529
4C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Applications:
EFS pilot lights are used:
In areas which are hazardous due to the presence of flammable
vapors, gases or highly combustible dusts
For installation at petroleum refineries, chemical and
petrochemical plants and other process industry facilities where
similar hazards exist
To visually indicate at a remote location that the desired function
is being performed
4C
Features:
Small, compact enclosures with accurately ground flange on both
body and cover for flame-tight joint
Pilot lights are factory sealed. Conventional external seals
are not required
Dead end (EFS) or through feed (EFSC) hubs 1/2" to 1" sizes
Options:
The following special options are available from factory by adding
suffix to Cat. #:
Description
Suffix
Pilot lights for circuit voltages up to 600 volts maximum
(standard voltage range 110125) See Listings
LED pilot lights in place of standard incandescent pilot lamps
Bodies and covers copper-free aluminum
24 VDC operation on pilot lights
Standard Materials:
Bodies Feraloy iron alloy (U.S.) and copper-free aluminum
(Canada)
Pilot light covers Feraloy iron alloy
Operating shafts stainless steel
Standard Finishes:
Feraloy iron alloy electrogalvanized with aluminum acrylic paint
Copper-free aluminum natural
Stainless steel natural
530
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
LED
SA
S300
Pilot lights listed below are factory sealed and do not require external
seals*. Lamps are 6 watt, miniature bayonets, incandescent lamps
for use on 110125 volt circuits.
LED pilot lights can be provided in place of standard incandescent
lamps by adding suffix LED after the color symbols. For Options
see pages 530531.
Enclosures with single pilot covers only can be equipped with a
transformer for each lamp for high voltages as shown.
4C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Primary
Voltage
Range
Cat. #
Suffix
220240
440480
550600
T2
T4
T5
Ordering Information
Enclosure with Single Pilot Light
Hub Size
Dead End Cat. #
EFS11561
EFS21561
EFS31561
/2
3
/4
1
1
EFSC11524
EFSC21524
EFSC31524
4C
/2
EFS11524
3
/4
EFS21524
1
EFS31524
Enclosure with Double Pilot Lights
Hub Size
Dead End Cat. #
1
Add color symbol for each pilot light from table below. Example: EFS11561 with red and green lights is EFS11561-J1-J3
Color
Symbol
Color
Symbol
Color
Symbol
Red
Green
J1
J3
Amber
Clear
J6
J10
Blue
J11
Dimensions
In Inches:
Front view
Cover
Hub Size
1
/2
3
/4
1
Dim. "h"
Dim. "i"
/4
7
/8
1
13
/16
/16
15
/16
13
* External conduit seal required for 1 inch hub size in Division 1, Group B within 5 feet
(1.5 meters) of enclosure.
LED pilot lights can be furnished in place of standard incandescent pilot lamps.
Add suffix LED to catalog number after color symbol.
Surface covers have same length and width dimensions as bodies.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
531
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Two gang units with single pilot light covers can be furnished with transformers.
Specify markings for each button. See table below listings.
Dimensions
4C
Dead End
Through Feed
Dead End
Through Feed
No. Pushbuttons
No. Pilot
Lights
Through Feed
1
1
Diagram
Diagram
Hub Size
/2
3
/4
1
1
Hub Size
Cat. #
Cat. #
EDS11473 EDSC11473 1/2
EDS21473 EDSC21473 3/4
EDS31473 EDSC31473 1
Cat. #
Cat. #
EDS12471 EDSC12471
EDS22471 EDSC22471
EDS32471 EDSC32471
Cat. #
Cat. #
EDS22868 EDSC22868
EDS32868 EDSC32868
Add color symbol for each pilot light from table below. Example: EDS21473 with a red light is EDS21473-J1
Color
Symbol
Color
Symbol
Color
Symbol
Red
Green
J1
J3
Amber
Clear
J6
J10
Blue
J11
If desired, markings on indicating plates may be added to catalog number. Select from the list of stardard markings below:
START
STOP
RESET
LIGHT ON
EMERGENCY
OPEN
DOWN
RAISE
STOP
RUN
TRIP
HAND
FORWARD
CLOSE IN
LOWER
ON
JOG
TEST
AUTOMATIC
REVERSE
UP
OUT
* All enclosures listed above can be modified for Class I, Group B, Division 1 usage. Add suffix GB to the Cat. No. Example: EDS11473-J1-GB. Conduit seal(s) must be installed
within 11/2" of each conduit opening. These products are suitable for Group B, Div. 2 as listed, without external conduit seals.
LED pilot lights can be furnished in place of standard incandescent pilot lamps. Add suffix LED to catalog number after color symbol. For 24 VDC operation on pilot lights add suffix S300.
532
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
4C
Furnished with pushbuttons, cam actuated by a maintained contact selector mechanism to operate in the sequences shown in the diagrams
below. Specify indicating plate markings. See table
below listings.
Dimensions
see page 526
4C
EDS11273
Position 1
Position 2
Position 3
Replacement
Contact
Blocks
Hub
Size
Dead End
Cat. #
Through Feed
Cat. #
Two-Position,
Two-Circuit
ED11
/2
/4
1
EDS11271
EDS21271
EDS31271
EDSC11271
EDSC21271
EDSC31271
Two-Position,
Four-Circuit
ED12
/2
/4
1
EDS11272
EDS21272
EDS31272
EDSC11272
EDSC21272
EDSC31272
Three-Position,
Two-Circuit
ED11
/2
/4
1
EDS11273
EDS21273
EDS31273
EDSC11273
EDSC21273
EDSC31273
ED12
/2
/4
1
EDS11274
EDS21274
EDS31274
EDSC11274
EDSC21274
EDSC31274
ED12
/2
/4
1
EDS11275
EDS21275
EDS31275
EDSC11275
EDSC21275
EDSC31275
Three-Position,
Four-Circuit
1
3
Three-Position
FAST, SLOW
OPEN, CLOSE
UP, DOWN
ON, OFF
IN, OUT
RAISE, LOWER
START, STOP
1, OFF, 2
OPEN, OFF, CLOSE
UP, OFF, DOWN
*For Class I, Group B: Consider using EFS series selector switches, see page 534. All enclosures listed above can be modified for Class I, Group B, Div. 1 usage. Add suffix GB
to the Cat. No. Seals must be installed within 11/ 2" of each conduit opening in Division 1. These products are suitable for Group B, Div. 2 as listed, without external seals. In Canada, for
Group B applications consult factory.
For replacement contact blocks, see page 571.
Suffixes S634 or S635 may be used on these catalog numbers. See page 525 for explanation of options.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
533
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Furnished with pushbuttons, cam actuated by a maintained contact selector mechanism to operate in the sequences shown in the
diagrams below. Specify indicating plate markings. See table below listings.
Dimensions
4C
EFS11273
Position 1
Position 2
Position 3
Replacement
Contact
Blocks
Hub
Size
Dead End
Cat. #
Through Feed
Cat. #
/2
/4
1
EFS11271
EFS21271
EFS31271
EFSC11271
EFSC21271
EFSC31271
/2
/4
1
EFS11272
EFS21272
EFS31272
EFSC11272
EFSC21272
EFSC31272
/2
/4
1
EFS11273
EFS21273
EFS31273
EFSC11273
EFSC21273
EFSC31273
/2
/4
1
EFS11274
EFS21274
EFS31274
EFSC11274
EFSC21274
EFSC31274
/2
/4
1
EFS11275
EFS21275
EFS31275
EFSC11275
EFSC21275
EFSC31275
Two-Position,
Two-Circuit
ED11
Two-Position,
Four-Circuit
ED12
Three-Position,
Two-Circuit
ED11
ED12
Three-Position,
Four-Circuit
ED12
Three-Position
RUN, OFF, JOG
1, OFF, 2
HAND, OFF, AUTOMATIC OPEN, OFF, CLOSE
FORWARD, OFF, REVERSE UP, OFF, DOWN
FAST, OFF, SLOW
*Class I, Group B: All enclosures listed above are suitable for Class I, Group B, Div. 1 usage. Seals only have to be installed on 1 inch conduit within 5 ft. in Division 1.
For replacement contact blocks, see page 571.
Suffixes S634 or S635 may be used on these catalog numbers. See page 525 for explanation of options.
534
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
4C
Dimensions
see page 526
EDSC2129
EDS2229
Single Gang
Two Gang
Amperes
Style
120VAC
277VAC
Dead End
Cat. #
Through
Feed Cat. #
Dead End
Cat. #
Through
Feed Cat. #
Factory Sealed
Replacement
Switch
1-pole
2-pole
20
20
20
20
EDS2129
EDS218
EDSC2129
EDSC218
EDS2229
/4
EDSC2229
EDSC228
SW5
SW6
/4
3-way
20
20
EDS2130
EDSC2130
EDS2230
/4
1
4-way
20
20
EDS2140
EDSC2140
1-pole
20
20
EDS3129
EDSC3129
EDS3229
2-pole
20
20
EDS318
EDSC318
3-way
20
20
EDS3130
EDSC3130
4-way
20
20
EDS3140
EDSC3140
Hub
Size
/4
EDSC2230
SW7
EDSC2240
SW8
EDSC3229
SW5
EDS328
EDSC328
SW6
EDS3230
EDSC3230
SW7
EDS3240
EDSC3240
SW8
*Standard as Class I, Division 2, Group B. No seals required. For Class I, Division 1, Group B: All units on this page can be modified for Class I, Division 1, Group B
usage. Add suffix GB to the Cat. No. Seals must be installed within 11/ 2" of each conduit opening in Division 1.
ON-OFF standard marking for 1-pole and 2-pole units.
Combinations of switches can be furnished.
AC rated switches are tested for resistive, inductive and tungsten filament loads up to the full current rating and for motor loads up to 80% of the ampere rating.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
535
4C
EDSC2199
EDS2229
Ordering Information
115230
Volts AC
1
2
1 hp
1 hp
Poles
Hub
Size
in.
Single Gang
3
/4
1
1
/4
1
Two Gang
3
/4
1
1
/4
1
115230
Volts DC
Allen-Bradley Switch
Cat. #
/4 hp
Dead
End
Cat. #
Through
Feed
Cat. #
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Factory Sealed
Replacement
Switch
Max.
Motor
Full-Load
Amps
Eaton's
CrouseHinds
Symbol
Number
Max.
Motor
Full-Load
Amps
Eaton's
CrouseHinds
Symbol
Number
0.17
P1
2.40
P20
0.21
P2
2.58
P21
0.25
P3
2.92
P22
0.32
P4
3.09
P23
0.39
P5
3.32
P24
0.46
P6
3.77
P25
EDS2199
EDS3199
EDSC2199
EDSC3199
SW9
SW9
0.57
P7
4.16
P26
EDS21100
EDS31100
EDSC21100
EDSC31100
0.71
P8
4.51
P27
SW10
SW10
0.79
P9
4.93
P28
0.87
P10
5.43
P29
0.98
P11
6.03
P30
1.08
P12
6.83
P31
1.19
P13
7.72
P32
1.30
P14
8.24
P33
1.43
P15
8.90
P34
1.58
P16
9.60
P35
1.75
P17
10.80
P36
1.88
P18
12.00
P37
2.13
P19
13.50
P38
15.20
P39
EDS2299
EDS3299
EDSC2299
EDSC3299
SW9
SW9
EDS22100
EDS32100
EDSC22100
EDSC32100
SW10
SW10
These heaters are for motors rated 40C continuously. For motors
rated 50C or 55C, multiply full load motor current by 0.9 and use
this value to select heaters. Symbol 0 (zero) must be used to indicate
heater omitted. Includes one interchangeable heater. Select heater
from the table below individual listings and use symbol number as
second section of the Cat. No. Example: EDS21101-W5. Insert
symbol 0 (zero) to omit heater.
* Class I, Group B: All units on this page can be modified for Class I, Group B usage. Add suffix GB to the Cat. No. Seals must be installed within 11/2" of each conduit opening in Division 1.
In Canada, for Group B applications consult factory.
Includes one interchangeable heater. Select from the heater table and use symbol number as second section of the Cat. No. Example: EDS2199-P5. Insert symbol 0 (zero) to omit heater.
536
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Ordering Information
Ordering Information
Maximum HP Ratings
4C
Maximum HP Ratings
Poles
115230
Volts AC
115
Volts DC
230
Volts DC
G.E. Switch
Cat. #
120240
Poles Volts AC
32
120
240
Cutler-Hammer
Volts DC Volts DC Volts DC Switch Cat. #
1
2
1 hp
1 hp
1 hp
1 hp
/4 hp
1 hp
CR101 Y
CR101 H
1
2
/4 hp
/4 hp
1 hp
1 hp
/4 hp
1 hp
MST01
MST02
1 hp
Factory Sealed
Replacement
Switch
Hub Dead
Size End
Poles in.
Cat. #
EDS21093 EDSC21093
EDS31093 EDSC31093
SW11
SW11
Single Gang
3
/4
EDS21101 EDSC21101 SW13
1
1
EDS31101 EDSC31101 SW13
/4
1
EDS21094 EDSC21094
EDS31094 EDSC31094
SW12
SW12
Two Gang
3
/4
1
1
EDS22093 EDSC22093
EDS32093 EDSC32093
SW11
SW11
/4
1
EDS22094 EDSC22094
EDS32094 EDSC32094
SW12
SW12
Poles
Hub Dead
Size End
in.
Cat. #
Heater
/4
1
Two Gang
3
/4
1
1
/4
1
Heater
Max.
Motor
Full-Load
Amps
Eaton's
CrouseHinds
Symbol
Number
Max.
Motor
Full-Load
Amps
Eaton's
CrouseHinds
Symbol
Number
.48
.53
.58
.65
.71
.78
.86
.95
1.04
1.14
1.25
1.37
1.49
1.63
1.78
1.95
2.13
2.32
2.53
2.76
G2
G3
G4
G5
G6
G7
G8
G9
G10
G11
G12
G13
G14
G15
G16
G17
G18
G19
G20
G21
3.01
3.27
3.56
3.88
4.22
4.60
5.00
5.43
5.90
6.41
6.98
7.60
8.25
8.95
9.75
10.60
11.40
12.50
13.60
14.80
16.00
G22
G23
G24
G25
G26
G27
G28
G29
G30
G31
G32
G33
G34
G35
G36
G37
G38
G39
G40
G41
G42
Through
Feed
Cat. #
Factory Sealed
Replacement
Switch
4C
Single Gang
3
/4
1
1
Through
Feed
Cat. #
Table (Cutler-Hammer)
Max.
Motor
Full-Load
Amps
Eaton's
CrouseHinds
Symbol
Number
.43
.48
.53
.58
.64
.71
.78
.87
.95
1.03
1.15
1.27
1.35
1.51
1.67
1.83
1.99
2.23
2.47
2.71
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
W11
W12
W13
W14
W15
W16
W17
W18
W19
W20
Max.
Motor
Full-Load
Amps
Eaton's
CrouseHinds
Symbol
Number
2.95
3.27
3.59
3.99
4.39
4.79
5.26
5.83
6.39
7.03
7.74
8.46
9.35
10.30
11.35
12.47
13.67
15.12
16.00
W21
W22
W23
W24
W25
W26
W27
W28
W29
W30
W31
W32
W33
W34
W35
W36
W37
W38
W39
Dimensions
see page 526
These heaters are for motors rated 40C continuously. For motors rated 50C or 55C, multiply full load motor current by 0.9 and use this
value to select heaters. Symbol 0 (zero) must be used to indicate heater omitted. Includes one interchangeable heater. Select heater from the
table below individual listings and use symbol number as second section of the Cat. No. Example: EDS21101-W5. Insert symbol 0 (zero) to
omit heater.
*Class I, Group B: All units on this page can be modified for Class I, Group B usage. Add suffix GB to the Cat. No. Seals must be installed within 11/2" of each conduit opening in Division 1.
In Canada, for Group B applications consult factory.
Includes one interchangeable heater. Select from the heater table and use symbol number as second section of the Cat. No. Example: EDS2199-P5. Insert symbol 0 (zero) to omit heater.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
537
4C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Applications:
EFS Fire Alarm Stations are used:
In areas which are hazardous due to the presence of
flammable vapors, gases or highly combustible dusts
For installation at petroleum refineries, chemical and
petrochemical plants and other process industry facilities
where similar hazards exist
To indicate at a remote location that a fire exists in the area
4C
Features:
Small, compact enclosures with accurately ground flange on both
body and cover for flame-tight joint
Available in red for fire alarm applications
Ordering Information
Hub Size
Dead End
Cat. #
Through
Feed Cat. #
/4
EFS21095
EFSC21095
NEC
Class I, Groups B*, C, D
Class II, Groups E, F, G
Class III
NEMA 3, 7B*CD, 9EFG
UL Standard: 1203
As indicated under catalog listings, certain units can be
supplied for Class I, Division 1, Group B (NEMA 7B).
Seals must be installed within 11/2" of each conduit opening.
EFS21095
Dimensions
In Inches:
Standard Materials:
Bodies Feraloy iron alloy (U.S.) and copper-free aluminum
(Canada)
Standard Finishes:
Feraloy iron alloy electrogalvanized with aluminum acrylic
paint
Copper-free aluminum natural
Stainless steel natural
Options:
The following special option is available from factory by adding
suffix to Cat. #:
Description
Suffix
Where indicated in the catalog listings, units suitable for
Class I, Division 1, Group B usage can be supplied.................
GB*
Typical body
side view
Hub Size
1
/2
3
/4
1
Front view
Cover
Dim."h"
Dim."i"
/4
7
/8
1
13
/16
/16
/16
13
13
538
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
Sub-assembly
Cover & Device
PUSHBUTTONS
EDS2184
EDSC2184
EDS215
EDSC215
EDS2190
EDSC2190
EDS2184-S769-EM-SP
EDSC2184-S769-EM-SP
EDS2284
EDSC2284
EDS225
EDSC225
EDS2290
EDSC2290
DSD918
DSD918
DSD922
DSD922
DSD921
DSD921
DSD918-S769-EM-SP
DSD918-S769-EM-SP
(2) DSD918
(2) DSD918
(2) DSD922
(2) DSD922
(2) DSD921
(2) DSD921
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
EDS272
EDSC272
EDS272
EDSC272
EDS272
EDSC272
PILOT LIGHTS
EFS21524-J*
EFSC21524-J*
EFS21561-J*-J*
EFSC21561-J*-J*
DSD948-J*
DSD948-J*
DSD947-J*-J*
DSD947-J*-J*
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
EDS272
EDSC272
EDS272
EDSC272
*
*
*
*
*
*
SELECTOR SWITCHES
EDS21271
EDSC21271
EDS21272
EDSC21272
EDS21273
EDSC21273
EDS21274
EDSC21274
EDS21275
EDSC21275
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
www.crouse-hinds.com
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
US: 1-866-764-5454
4C
DSD923
DSD923
DSD924
DSD924
DSD925
DSD925
DSD926
DSD926
DSD927
DSD927
Insert
Insert
Insert
Insert
Insert
Insert
pilot
pilot
pilot
pilot
pilot
pilot
light
light
light
light
light
light
color
color
color
color
color
color
CAN: 1-800-265-0502
539
4C
Sub-assembly
Reference Guide
4C
Sub-assembly
Complete Control Station
DSD916
DS415A &
DSD916
DS415A &
DSD917
DS415A &
DSD917
DS415A &
EDS271
EDS271
EDSC271
EDSC271
EDS271
EDS271
EDSC271
EDSC271
SNAP SWITCHES
EDS2129
Alternative
EDSC2129
Alternative
EDS218
Alternative
EDSC218
Alternative
EDS2130
Alternative
EDSC2130
Alternative
EDS2140
Alternative
EDSC2140
Alternative
EDS2229
Alternative
EDSC2229
Alternative
EDSC228
Alternative
EDS2230
Alternative
EDSC2230
Alternative
EDSC2240
Alternative
ROCKER SWITCHES
EDS2596
EDSC2596
EDS2162
EDSC2162
EDS2194
EDSC2194
EDS2696
EDSC2696
EDS2262
EDSC2262
EDS2294
EDSC2294
DSD949
DSD949
DSD951
DSD951
DSD950
DSD950
(2) DSD949
(2) DSD949
(2) DSD951
(2) DSD951
(2) DSD950
(2) DSD950
SQ D 2510 KO-1
SQ D 2510 KO-1
GE 2368S
GE 2368S
SW5
SW5
SW6
SW7
SW7
SW8
EDS271
EDS271
EDSC271
EDSC271
EDS271
EDS271
EDSC271
EDSC271
EDS271
EDS271
EDSC271
EDSC271
EDS271
EDS271
EDSC271
EDSC271
EDS272
EDS272
EDSC272
EDSC272
EDSC272
EDSC272
EDS272
EDS272
EDSC272
EDSC272
EDSC272
EDSC272
EDS271
EDSC271
EDS271
EDSC271
EDS271
EDSC271
EDS272
EDSC272
EDS272
EDSC272
EDS272
EDSC272
Additional notes:
See Eaton's Crouse-Hinds' installation instructions for any possible additional sealing requirements.
Part numbers listed with 3/ 4" hub in back box (Ex. EDS2184). For 1/ 2" hub, change the "2" to "1" (EDS1184). For 1" hub, change the "2" to "3" (EDS3184).
Control Stations with "Stop" legend have lockout provided as standard.
Pilot Light Colors J*-- J1= Red, J3= Green, J6= Amber, J10= Clear, J11= Blue. LED pilot lights are available with LED suffix.
Pilot Light Transformers for voltages over 125V. Suffix T2= 240/220 - 110V, T4= 480/440 - 110V, T5= 600/500 - 110V (not available on double pilot cover).
Standard legend plate markings are available by adding nomenclature after the part number (EDS2184-Run).
Selector switch nameplate kits available. 2-Pos = "SS2KIT", 3-Pos = "SS3KIT". See Replacement Parts book for additional information.
Copper-free aluminum bodies and covers available with SA suffix.
Additional control station options may be found in Section 4C.
Group B ratings may be achieved by adding the GB suffix or using the EFS back box. See part number instructions for the item required.
Group B ratings may already be achieved when used in Class I, Division 2 applications. See Certifications and Compliances for item required.
Additional control station configurations available through the FlexStation Component Series.
540
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
NEMA 3, 4
Watertight
Features:
Dimensions
4C
Applications:
In Inches*:
Certifications and
Compliances:
NEMA/EEMAC 3, 4
UL Standard: 508
CSA Encl. 3, 4, 5
Standard Materials:
Bodies Feraloy iron alloy
Cover with side rocker handle copperfree aluminum
Front pushbutton, selector switch and
pilot light covers Feraloy iron alloy
Rocker handle and pushbutton guards
type 6 / 6 nylon
Selector switch handle copper-free
aluminum
Operating shafts stainless steel
Hub size
1
/2
3
/4
Type of Cover
/8
3
/4
11/2
23/8
23/8
11/16
Standard Finishes:
Feraloy iron alloy electrogalvanized and
aluminum acrylic paint
Copper-free aluminum natural
Type 6 / 6 nylon black
Stainless steel natural
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
541
4C
Watertight
Weather Resistant
NEMA 3, 4
MC dead end
side rocker handle
Replacement
Contact
Diagram Blocks
Marking
ED11
Specify
ED12
MC1810U1 MCC1810U1
MC2810U1 MCC2810U1
/2
/4
MC1810U
MC2810U
MCC1810U
MCC2810U
/2
/4
MC1810
MC2810
MCC1810
MCC2810
3
1
3
ED12*
Through Feed
Cat. #
/2
/4
Specify
START-STOP
unless
2 Circuits
1 Open - A otherwise
1 Closed - B specified
4C
Replacement
Contact
Diagram Blocks
Marking
MC1910U1 MCC1910U1
MC2910U1 MCC2910U1
/2
/4
MC1910U
MC2910U
MCC1910U
MCC2910U
/2
/4
MC1910
MC2910
MCC1910
MCC2910
Specify
ED11
Specify
ED12
3
1
START-STOP
unless
2 Circuits
1 Open - A otherwise
1 Closed - B specified
ED12*
START
OFF
RESET
LIGHT ON
STOP
RUN
TRIP
HAND
ON
JOG
TEST
AUTOMATIC
EMERGENCY
OPEN
DOWN
RAISE
LOWER
FORWARD
CLOSE
IN
REVERSE
UP
OUT
*Two universal contact blocks, must be wired as two circuits, with one normally open and one normally closed.
For Watertight NEMA 4 rating, use suffix S323 (Neoprene button covers). See Options section.
For replacement pushbuttons see page 571.
542
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Through Feed
Cat. #
4C
Watertight
NEMA 3, 4
MC dead end
selector switch
Position
1
Position
3
TwoPosition,
TwoCircuit
Replacement
Contact Blocks*
Hub
Size
Dead End
Cat. #
Through Feed
Cat. #
/2
/4
MC11271
MC21271
MCC11271
MCC21271
/2
/4
MC11272
MC21272
MCC11272
MCC21272
/2
/4
MC11273
MC21273
MCC11273
MCC21273
/2
/4
MC11274
MC21274
MCC11274
MCC21274
/2
/4
MC11275
MC21275
MCC11275
MCC21275
ED11
TwoPosition,
FourCircuit
ED12
4C
ThreePosition,
TwoCircuit
ED11
ED12
ThreePosition,
FourCircuit
ED12
OFF
RESET
LIGHT ON
STOP
RUN
TRIP
HAND
ON
JOG
TEST
AUTOMATIC
EMERGENCY
OPEN
DOWN
RAISE
FORWARD
CLOSE
IN
LOWER
REVERSE
UP
OUT
MC dead end
pilot light
Primary
Voltage
Range
Lamp
Base
Lamp
Watts
Hub
Size
Dead End
Cat. #
Through Feed
Cat. #
110125
110125
Candelabra
Candelabra
6
6
/2
/4
MC180 J1
MC-280-J1
MCC180 J1
MCC280 J1
220250
220250
Intermediate
Intermediate
10
10
/2
/4
MC184 J1
MC-284-J1
MCC184 J1
MCC284 J1
440480
440480
Candelabra
Candelabra
6
6
/2
/4
MC182 J1
MC282 J1
MCC182 J1
MCC282 J1
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
543
4C
4C
Applications:
N2S and N2SC pushbutton stations,
selector switches and pilot lights are
suitable for use:
In Class I, Groups B, C, D; Division 2
hazardous areas where flammable
vapors or gases may be present due to
accidental or abnormal operation
In damp, wet, or corrosive locations
Indoors or outdoors in Division 2 areas
of petroleum refineries, chemical plants
and other process industry facilities
where similar hazards exist
N2S and N2SC pushbutton stations and
selector switches are used:
In conjunction with magnetic starters or
contactors for remote control of motors
N2S and N2SC pilot lights are used:
To visually indicate at a remote location
that the desired function is being
performed
Optional maintained stop pushbutton(s) are
used: As emergency or normal stop
button(s) in motor control circuits for
positive shutdown.
Features:
Options:
The following special options are available from factory by adding suffix to Cat. #:
Description
Padlock attachments for all pushbuttons. For "START-STOP" stations, only "STOP"
button provided with lockout (lockout standard with STOP)............................................
Three position selector switches with modified operation:
Momentary contact clockwise operation, spring return to center, maintained contact
counterclockwise operation ..............................................................................................
Momentary contact counterclockwise operation, spring return to center, maintained
contact clockwise operation .............................................................................................
Control station with maintained stop pushbutton (requires NCD type enclosure):
One maintained stop pushbutton .....................................................................................
Two maintained stop pushbuttons ...................................................................................
Suffix
S708
S634
S635
MSR1
MSR2
Maintained stop pushbuttons are installed at bottom position(s) of control station unless otherwise specified.
LED
Dimensions
In Inches:
Certifications and
Compliances:
NEC:
Class I, Division 2, Groups B, C & D
NEMA: 3, 4X, 7BCD (Division 2) and 12
UL Standard: 1203
CSA Standard: C22.2 Nos. 14 & 30
Outside
Dims.
I
w
Mounting
(NCS)* (NCD)* Dims.
d
e
ml
mw
1
/2" & 3/4"
Hubs
a
b
1"
Hubs
a
b
71/4
313/16
43/8
53/8
63/8
215/16
11/8
11/16
11/4
15/16
113/4
313/16
43/8
53/8
107/8
215/16
11/8
11/16
11/4
15/16
*NCS box is supplied with units using 1/2" and 3/4" hubs. NCD box is supplied with units using 1" hubs or MSR option.
NCD 4 device box used with 1" hubs or MSR option.
544
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
Diagram
120
240
480
600
120
240
480
600
120
240
480
600
120
240
480
600
N2S1131
N2S1132
N2S1134
N2S1135
N2S1231
N2S1232
N2S1234
N2S1235
N2S1331
N2S1332
N2S1334
N2S1335
N2S1431
N2S1432
N2S1434
N2S1435
N2SC1131
N2SC1132
N2SC1134
N2SC1135
N2SC1231
N2SC1232
N2SC1234
N2SC1235
N2SC1331
N2SC1332
N2SC1334
N2SC1335
N2SC1431
N2SC1432
N2SC1434
N2SC1435
3
/4" Hubs
Dead End
Cat. #
N2S2131
N2S2132
N2S2134
N2S2135
N2S2231
N2S2232
N2S2234
N2S2235
N2S2331
N2S2332
N2S2334
N2S2335
N2S2431
N2S2432
N2S2434
N2S2435
Through
Feed Cat. #
N2SC2131
N2SC2132
N2SC2134
N2SC2135
N2SC2231
N2SC2232
N2SC2234
N2SC2235
N2SC2331
N2SC2332
N2SC2334
N2SC2335
N2SC2431
N2SC2432
N2SC2434
N2SC2435
1" Hubs
Dead End
Cat. #
N2S3131
N2S3132
N2S3134
N2S3135
N2S3231
N2S3232
N2S3234
N2S3235
N2S3331
N2S3332
N2S3334
N2S3335
N2S3431
N2S3432
N2S3434
N2S3435
Through
Feed Cat. #
N2SC3131
N2SC3132
N2SC3134
N2SC3135
N2SC3231
N2SC3232
N2SC3234
N2SC3235
N2SC3331
N2SC3332
N2SC3334
N2SC3335
N2SC3431
N2SC3432
N2SC3434
N2SC3435
Hub
Size
Dead End
Cat. #
Through Feed
Cat. #
Two-Position,
Two-Circuit
START-STOP
(or Specify)
/2
/4
1
N2S1121
N2S2121
N2S3121
N2SC1121
N2SC2121
N2SC3121
Two-Position,
Four-Circuit
START-STOP
(or Specify)
/2
/4
1
N2S1122
N2S2122
N2S3122
N2SC1122
N2SC2122
N2SC3122
Three-Position,
Two-Circuit
Specify
/2
3
/4
1
N2S1123
N2S2123
N2S3123
N2SC1123
N2SC2123
N2SC3123
Three-Position,
Four-Circuit
Specify
/2
/4
1
N2S1124
N2S2124
N2S3124
N2SC1124
N2SC2124
N2SC3124
/2
/4
1
N2S1125
N2S2125
N2S3125
N2SC1125
N2SC2125
N2SC3125
Switch Position
Style
Three-Position,
Four-Circuit
Specify
Specify lens color for each pilot light. As an example, N2S1231 with one red and one green would be ordered as N2S1231-J1-J3.
Color
Symbol
Color
Symbol
Red
Green
Amber
J1
J3
J6
Clear
Blue
J10
J11
If desired, markings on indicating plates may be added to catalog number. Select from the list of standard markings below:
Marking
Pushbuttons:
REVERSE
Selector Switches Two-Position:
Selector Switches Three-Position:
OPEN
START
CLOSE
RUN-JOG
RUN-OFF-JOG
STOP
UP
HAND-AUTO
HAND-OFF-AUTO
ON
DOWN
FOR-REV
FOR-OFF-REV
OFF
IN
FAST-SLOW
FAST-OFF-SLOW
RUN
OUT
OPEN-CLOSE
1-OFF-2
JOG
RAISE
UP-DOWN
OPEN-OFF-CLOSE
TRIP
LOWER
ON-OFF
UP-OFF-DOWN
RESET
IN-OUT
TEST
RAISE-LOWER
LIGHT ON
START-STOP
HAND
AUTOMATIC
EMERGENCY
FORWARD
Pilot lights are transformer type except those rated 120 volts. Lamp type is 120MB, 120 volts, 3 watts.
* LED pilot lights are available. Add suffix LED after last color symbol. See Options Sections for more information.
Suffixes S634 or S635 may be used on these catalog numbers. See explanation in Options section.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
545
4C
Volts
4C
Marking Unless
Otherwise
Specified
Contact Symbol
START
(or Specify)
/2
/4
1
N2S1110
N2S2110
N2S3110
N2SC1110
N2SC2110
N2SC3110
START-STOP
(or Specify)
/2
/4
1
N2S1210
N2S2210
N2S3210
N2SC1210
N2SC2210
N2SC3210
Specify
/2
/4
1
N2S1310
N2S2310
N2S3310
N2SC1310
N2SC2310
N2SC3310
Specify
/2
/4
1
N2S1410
N2S2410
N2S3410
N2SC1410
N2SC2410
N2SC3410
4C
Through Feed
Cat. #
Diagram
Markings
Hub
Size
Volts
N2S12411 N2SC12411
N2S22411 N2SC22411
N2S32411 N2SC32411
480
N2S12414 N2SC12414
N2S22414 N2SC22414
N2S32414 N2SC32414
/2
/4
1
240
N2S12412 N2SC12412
N2S22412 N2SC22412
N2S32412 N2SC32412
600
N2S12415 N2SC12415
N2S22415 N2SC22415
N2S32415 N2SC32415
/2
/4
1
120
N2S13421 N2SC13421
N2S23421 N2SC23421
N2S33421 N2SC33421
480
N2S13424 N2SC13424
N2S23424 N2SC23424
N2S33424 N2SC33424
/2
/4
1
240
N2S13422 N2SC13422
N2S23422 N2SC23422
N2S33422 N2SC33422
600
N2S13425 N2SC13425
N2S23425 N2SC23425
N2S33425 N2SC33425
/2
/4
1
120
N2S13411 N2SC13411
N2S23411 N2SC23411
N2S33411 N2SC33411
480
N2S13414 N2SC13414
N2S23414 N2SC23414
N2S33414 N2SC33414
/2
/4
1
240
N2S13412 N2SC13412
N2S23412 N2SC23412
N2S33412 N2SC33412
600
N2S13415 N2SC13415
N2S23415 N2SC23415
N2S33415 N2SC33415
/2
/4
1
120
N2S14421 N2SC14421
N2S24421 N2SC24421
N2S34421 N2SC34421
480
N2S14424 N2SC14424
N2S24424 N2SC24424
N2S34424 N2SC34424
/2
/4
1
240
N2S14422 N2SC14422
N2S24422 N2SC24422
N2S34422 N2SC34422
600
N2S14425 N2SC14425
N2S24425 N2SC24425
N2S34425 N2SC34425
Specify
Specify
1
3
Specify
1
3
Specify
1
3
546
www.crouse-hinds.com
US: 1-866-764-5454
Through Feed
Cat. #
120
Dead End
Volts Cat. #
/2
/4
1
Through Feed
Cat. #
Dead End
Cat. #
CAN: 1-800-265-0502
4C
2-Pos, 2-Cct
N2S145211 N2SC145211
N2S245211 N2SC245211 480
N2S345211 N2SC345211
N2S145214 N2SC145214
N2S245214 N2SC245214
N2S345214 N2SC345214
/2
/4
1
240
N2S145212 N2SC145212
N2S245212 N2SC245212 600
N2S345212 N2SC345212
N2S145215 N2SC145215
N2S245215 N2SC245215
N2S345215 N2SC345215
/2
/4
1
120
N2S145231 N2SC145231
N2S245231 N2SC245231 480
N2S345231 N2SC345231
N2S145234 N2SC145234
N2S245234 N2SC245234
N2S345234 N2SC345234
/2
/4
1
240
N2S145232 N2SC145232
N2S245232 N2SC245232 600
N2S345232 N2SC345232
N2S145235 N2SC145235
N2S245235 N2SC245235
N2S345235 N2SC345235
Specify
1
3
Specify lens color for each pilot light. As an example, N2S1231 with one red and one green would be ordered as N2S1231-J1-J3.
Color
Symbol
Color
Symbol
Red
Green
Amber
J1
J3
J6
Clear
Blue
J10
J11
If desired, markings on indicating plates may be added to catalog number. Select from the list of standard markings below:
Marking
Pushbuttons:
START
STOP
ON
OFF
RUN
JOG
TRIP
RESET
TEST
LIGHT ON
HAND
AUTOMATIC
EMERGENCY
FORWARD
REVERSE
OPEN
CLOSE
UP
DOWN
IN
OUT
RAISE
LOWER
RUN-JOG
HAND-AUTO
FOR-REV
FAST-SLOW
OPEN-CLOSE
UP-DOWN
ON-OFF
IN-OUT
RAISE-LOWER
START-STOP
RUN-OFF-JOG
HAND-OFF-AUTO
FOR-OFF-REV
FAST-OFF-SLOW
1-OFF-2
OPEN-OFF-CLOSE
UP-OFF-DOWN
Pilot lights are transformer type except those rated 120 volts. Lamp type is 120MB, 120 volts, 3 watts.
* LED pilot lights are available. Add suffix LED after last color symbol. See Options Sections for more information.
Suffixes S634 or S635 may be used on these catalog numbers. See explanation in Options section.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
547
4C
120
3-Pos, 2-Cct
Through
Feed Cat. #
/2
/4
1
1
Dead End
Volts Cat. #
Specify
Through
Feed Cat. #
4C
To order your custom-built factory assembled control station, select the enclosure required and add the desired devices from listings below.
Custom-built factory assembled control stations may thus be ordered as follows:
Requirements:
3-device control station on Krydon material enclosure with 3/4" through feed hubs, with 1 pilot light with green jewel, rated at 120V; 1 three
position, two circuit selector switch marked HAND-OFF-AUTO; and 1 green single circuit pushbutton marked START.
ORDER:
4C
NCDC23FA
N2P310-J3
N2SW11311-HAND-OFF-AUTO
N2PS1111G-START
Pilot light jewel symbol, pushbutton and selector switch plate markings are selected from footnote tables. Suffix FA indicates factory
assembled.
Note that order of assembly of control stations should be listed in desired mounting order, reading from top to bottom of enclosure.
With One
Hub 1/2"
Cat. #
With Two
Hub 1/2"
Cat. #
With One
Hub 3/4"
Cat. #
With Two
Hub 3/4"
Cat. #
With One
Hub 1"
Cat. #
With Two
Hub 1"
Cat. #
NCD01
NCD02
NCD11
NCD12
NCDC11
NCDC12
NCD21
NCD22
NCDC21
NCDC22
NCD31
NCD32
NCDC31
NCDC32
NCD03
NCD13
NCDC13
NCD23
NCDC23
NCD33
NCDC33
NCD04
NCD14
NCDC14
NCD24
NCDC24
NCD34
NCDC34
No. of
Devices
Without
Hubs
Cat. #
With One
Hub (3/4")
Cat. #
With Two
Hub (3/4")
Cat. #
With One
Hub (1/2")
Cat. #
With Two
Hub (1/2")
Cat. #
NCS01
NCS02
NCS21
NCS22
NCSC21
NCSC22
NCS11
NCS12
NCSC11
NCSC12
NCS03
NCS23
NCSC23
NCS13
NCSC13
NCS04
NCS24
NCSC24
NCS14
NCSC14
No. of
Devices
1
Pilot Lights*
Transformer Type
Volts
Cat. #
Red
N2PLU10 J1 LED
120
240
480
600
N2PL10
N2PL20
N2PL40
N2PL50
Green
N2PLU10 J3 LED
Blue
Pilot lights are transformer type except those rated 120 volts. Lamp type is 120MB, 120 volts, 3 watts.
* LED pilot lights are available. Add suffix LED after last color symbol. See Options Sections for more information.
548
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
J1
J3
J6
Clear
Blue
J10
J11
1 Circuit
Contact Universal
Symbol Cat. #
Closure Plug
2 Circuit
Contact Universal
Symbol Cat. #
Natural
N2PS1111
N2PS1211
Red
N2PS1111R
N2PS1211R
Green
N2PS1111G
Red Mushroom
Head
N2PM1111 S111
4C
Description
Cat. #
Closure Plug
NP2
N2PS1211G
4C
Selector Switches
Style
Two Position
Two Circuit
N2SW11211
Two Position
Four Circuit
N2SW12221
Three Position
Two Circuit
N2SW11311
Three Position
Four Circuit
N2SW12321
Three Position
Four Circuit
N2SW12322
If desired, markings on indicating plates may be added to catalog number. Select from the list of standard markings below:
Marking
Pushbuttons:
REVERSE
Selector Switches
Selector Switches
START
OPEN
Two-Positions:
Three-Position:
STOP
CLOSE
RUN-JOG
RUN-OFF-JOG
ON
UP
HAND-AUTO
HAND-OFF-AUTO
OFF
DOWN
FOR-REV
FOR-OFF-REV
RUN
IN
FAST-SLOW
FAST-OFF-SLOW
JOG
OUT
OPEN-CLOSE
1-OFF-2
TRIP
RAISE
UP-DOWN
OPEN-OFF-CLOSE
RESET
LOWER
ON-OFF
UP-OFF-DOWN
TEST
IN-OUT
LIGHT ON
RAISE-LOWER
HAND
START-STOP
AUTOMATIC
EMERGENCY
FORWARD
Suffixes S634 or S635 may be used on these catalog numbers. See explanation in Options section.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
549
4C
Dimensions
4C
In Inches:
N2S
For 1/ 2" and 3/ 4" hub sizes (for 1" hub and/or MSR option, see page 544).
550
Outside Dimensions
w
d
71/4
71/4
91/2
113/4
www.crouse-hinds.com
313/16
313/16
313/16
313/16
43/8
43/8
43/8
43/8
US: 1-866-764-5454
Mounting
Dimensions
ml
mw
63/8
63/8
85/8
107/8
215/16
215/16
215/16
215/16
CAN: 1-800-265-0502
N2SU/N2SCU
Control Stations
Factory Sealed, Corrosion-Resistant
600VAC Heavy Duty
Applications:
Size Ranges:
Options:
Note:
Suffix
S708
S634
S635
MSR1
In addition to hub arrangements shown, the following can be obtained by inserting these codes for the 4th and 5th
character in the catalog number:
D = Double 1/ 2" hubs at bottom
CD = Single hub at top, double 1/ 2" hubs at bottom
DD = Double 1/ 2" hubs at each end
Dimensions
In Inches:
Features:
Compact, strong, durable enclosures are
made of Vestamid a black molded
high impact strength, polyester material
having excellent corrosion resistance and
stability to heat.
Exterior parts of pushbuttons, pilot lights,
and selector switches are made of
Krydon material. See pages 552553 for
device part numbers
Pushbutton design uses a unique internal
neoprene boot which completely
encloses all internal parts. A wiping
gasket around the pushbutton cleans the
wall of the pushbutton guard of any
foreign material accumulation as the
button is operated.
Formed-in-place gasket, and stainless
steel screws for added corrosion
resistance.
Pushbutton and pilot light guards are
fluted for no-slip installation.
Factory installed dead end (N2SU) or
through feed (N2SCU) hubs
1
/2" and 3/4" sizes.
Legend plates are available with 40
standard markings.
Lockout is standard on selector switch
devices.
LED lamps are standard to provide
longer life.
Certifications and
Compliances:
NEMA: 3, 4X, 7BCD and 12
UL Standard: 508
CSA C22.2 No. 14 & 30
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
551
4C
Description
Padlock attachments for all pushbuttons. For "START-STOP" stations, only "STOP"
button provided with lockout (lockout standard with STOP)...........................................
Three-position selector switches with modified operation:
Momentary contact clockwise operation, spring return to center, maintained contact
counterclockwise operation.............................................................................................
Momentary contact counterclockwise operation, spring return to center, maintained
contact clockwise operation............................................................................................
One maintained stop pushbutton.....................................................................................
N2SU/N2SCU
Control Stations
4C
No.
Units Contact Symbol
Dead End
Cat. #
Through Feed
Cat. #
/2
/4
N2S1110U
N2S2110U
N2SC1110U
N2SC2110U
/2
/4
N2S1210U
N2S2210U
N2SC1210U
N2SC2210U
/2
/4
N2S1310U
N2S2310U
N2SC1310U
N2SC2310U
/2
/4
N2S1410U
N2S2410U
N2SC1410U
N2SC2410U
START
(or Specify)
START-STOP
(or Specify)
2
3
Specify
Specify
3
1
3
1
4C
Marking
Unless
Otherwise
Specified
Two-Position,
Two-Circuit
START-STOP
(or Specify)
Two-Position,
Four-Circuit
START-STOP
(or Specify)
Three-Position,
Two-Circuit
Specify
Dead End
Cat. #
Through Feed
Cat. #
/2
/4
N2S1121U
N2S2121U
N2SC1121U
N2SC2121U
/2
/4
N2S1122U
N2S2122U
N2SC1122U
N2SC2122U
/2
/4
N2S1123U
N2S2123U
N2SC1123U
N2SC2123U
/2
/4
N2S1124U
N2S2124U
N2SC1124U
N2SC2124U
/2
/4
N2S1125U
N2S2125U
N2SC1125U
N2SC2125U
1
3
1
3
1
3
1
Three-Position,
Four-Circuit
Specify
Three-Position,
Four-Circuit
Specify
If desired, markings on indicating plates may be added to catalog number. Select from the list of standard markings below:
Marking
Push Buttons:
REVERSE
Selector Switches
Selector Switches
START
OPEN
Two-Position:
Three-Position
STOP
CLOSE
RUN-JOG
RUN-OFF-JOG
ON
UP
HAND-AUTO
HAND-OFF-AUTO
OFF
DOWN
FOR-REV
FOR-OFF-REV
RUN
IN
FAST-SLOW
FAST-OFF-SLOW
JOG
OUT
OPEN-CLOSE
1-OFF-2
TRIP
RAISE
UP-DOWN
OPEN-OFF-CLOSE
RESET
LOWER
ON-OFF
UP-OFF-DOWN
TEST
IN-OUT
LIGHT ON
RAISE-LOWER
HAND
START-STOP
AUTOMATIC
EMERGENCY
FORWARD
552
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
N2SU/N2SCU
Control Stations
/4" Hubs
No.
Units
Through Feed
Cat. #
Dead End
Cat. #
Through Feed
Cat. #
120
240
N2S1131U
N2S1132U
N2SC1131U
N2SC1132U
N2S2131U
N2S2132U
N2SC2131U
N2SC2132U
120
240
N2S1231U
N2S1232U
N2SC1231U
N2SC1232U
N2S2231U
N2S2232U
N2SC2231U
N2SC2232U
120
240
N2S1331U
N2S1332U
N2SC1331U
N2SC1332U
N2S2331U
N2S2332U
N2SC2331U
N2SC2332U
120
240
N2S1431U
N2S1432U
N2SC1431U
N2SC1432U
N2S2431U
N2S2432U
N2SC2431U
N2SC2432U
Diagram
4C
Volts
Dead End
Cat. #
J1
J3
J6
Clear
Blue
J10
J11
Pilot lights are transformer type except those rated 120 volts.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
553
4C
N2SU/N2SCU
Control Stations
Specify
STARTSTOP
(or Specify)
Volts
Through Feed
Cat. #
120
240
N2S12411U
N2S12412U
N2SC12411U
N2SC12412U
N2S22411U
N2S22412U
N2SC22411U
N2SC22412U
120
240
N2S13421U
N2S13422U
N2SC13421U
N2SC13422U
N2S23421U
N2S23422U
N2SC23421U
N2SC23422U
120
240
N2S13411U
N2S13412U
N2SC13411U
N2SC13412U
N2S23411U
N2S23412U
N2SC23411U
N2SC23412U
120
240
N2S14421U
N2S14422U
N2SC14421U
N2SC14422U
N2S24421U
N2S24422U
N2SC24421U
N2SC24422U
4C
Diagram
Marking
Unless
Otherwise
Specified
Specify
STARTSTOP
(or Specify)
Selector Switches
Position No.
Pilot
Lights*
Pushbuttons
Two-Position, Two-Circuit
Markings
120
N2S145211U
N2S245211U
N2SC145211U
N2SC245211U
/2
/4
240
N2S145212U
N2S245212U
N2SC145212U
N2SC245212U
/2
/4
120
N2S145231U
N2S245231U
N2SC145231U
N2SC245231U
/2
/4
240
N2S145232U
N2S245232U
N2SC145232U
N2SC245232U
1
3
Specify
1
3
Three-Position, Two-Circuit
1
3
Specify
1
3
Red
Green
Amber
Push Buttons:
J1
J3
J6
Clear
Blue
J10
J11
START
STOP
ON
OFF
RUN
JOG
TRIP
RESET
TEST
LIGHT ON
HAND
AUTOMATIC
EMERGENCY
554
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
Applications:
4C
Features:
Factory sealed. External seals are not
required.
Enclosures are made of Krydon
fiberglass-reinforced polyester material
having excellent corrosion resistance
and stability to heat and sunlight.
Highly visible molded-in red color for
quick identification.
Break-glass rod is attached to station
with a chain for ready access during an
emergency.
Factory installed dead end (N2FA) or
through feed (N2FAC) hubs 1/2", 3/4" and
1" sizes.
Ordering Information
Hub Size
/2
3
/4
1
N2FA11
N2FA21
N2FA31
N2FAC11
N2FAC21
N2FAC31
DS K14
DS K14
DS K14
Dimensions*
In Inches:
Certifications and
Compliances:
NEC:
Class I, Division 2, Groups B, C, D
NEMA 3, 7BCD (Division 2), 12
1
/2" & 3/4" Hubs
a
b
11/8
11/16
www.crouse-hinds.com
1" Hubs
a
b
11/4
US: 1-866-764-5454
15/16
CAN: 1-800-265-0502
555
4C GHG43 Series
Control Stations
Nonmetallic or 316L Stainless
Steel Corrosion Resistant
UL/cUL listed
Cl. I, Div. 2, Groups A, B, C, D
Cl. I, Zones 1 and 2,
(A) Ex de IIB + H2 T6
Cl. II, Div. 1, Groups E, F, G (cUL)
4C
Applications:
Control stations are used as a remote
means of:
Motor control
Visual indication of equipment
performance
On-off control of circuits
Circuit selection
Common applications include:
Areas which are hazardous due to the
presence of flammable vapors, gases or
highly combustible dusts
For installation at petroleum refineries,
chemical and petrochemical plants and
other process industry facilities where
similar hazards exist
Features:
Certifications and
Compliances:
UL/cUL Listed
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 1, Groups E, F, G (cUL)
Class I, Zones 1 and 2, Ex de IIB + H2, T6
AEx de IIB + H2, T6
Type 3, 4, 4X; IP66
CENELEC-PTB 00 ATEX 3117
Ex de IIC, T6, Zones 1 and 2, IP66
Options:
Description
Eaton's Crouse-Hinds GHG43
Series control stations are now
available with 316L stainless steel
enclosures, making them ideal for
corrosive and adverse locations especially offshore platform
applications
556
www.crouse-hinds.com
Suffix
S860
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
4C
Pushbutton DRT
Double
Pushbutton
Mounting Area*
Key Operated
Pushbutton
Mushroom-Head
Pushbutton
Mounting Area*
Signal Lamp
For a GHG43 control station with 316L stainless steel enclosure, add suffix "S860" to end of catalog number.
*Unoccupied spaces must be filled in with KLM for correct positioning of devices.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
557
4C
Cable Entries
NPT
Metric
No entries
No entries
2 x M25 Plastic
Cable gland M25
Blanking plug
4C
Potentiometer
Two entries
Measuring Instrument
One entry
Switch
1 x M25
Threaded Entry,
Blanking plug and
Gland plate
2 x M25
Threaded Entry,
1 blanking plug and
Gland plate
For a GHG43 control station with 316L stainless steel enclosure, add suffix "S860" to end of catalog number.
*Unoccupied spaces must be filled in with KLM for correct positioning of devices.
558
www.crouse-hinds.com
2 x M25
Threaded entries
Gland plate
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
Pushbutton
Ex de IIC T6
PTB No. Ex-87.B.1007U
PTB, UL, cUL
Up to 400V
NEC/CEC 10A IEC 16 A
2 x 2.5mm2 / 14AWG
>105 Operations
Type of Protection
Certificate of Conformity
Approvals
Rated Voltage
Rated Current
Terminal Wiring
Mechanical and Electrical Life
Pushbutton DRT
D
Code
4C
Contact System
Code B
13
14
Inscription
ALL *
0 I
II Stop
Code C
01
02 03 04 06
Lockout see page 565
Code D (leave blank if no lockout required)
15
Start
Special-Text On Order
07
99
Code
Contact System
Code B
43
Inscription
Code C, D Left/Right
44
ALL *
01
02 03 04 06
II
45
Stop
Start
Special-Text on Order
07
99
Contact System
Code B
23
Pushbutton
Key
Not Depressed
Lockable
Key Removable
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
Yes
Lockable
Key Removable
Yes
No
No
No
Yes
Yes
Yes
Yes
Auto
Yes
Yes
Yes
Depressed
Code C
24
25
* 01 - Includes the following discs - Start, stop, I, O, and red, green, yellow, white and black blank discs.
For Marking Guide for Pushbuttons see page 565.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
559
4C
Code
4C
Contact System
Code B
53
54
55
Color of Pushbutton
Code C
Red
Yellow
Black Actuator
Function
Spring Return
Maintained
Key Release
Code D
Inscription
Stop
Start
Black Actuator
Code E
06
07
11
Lockout
see page 565
Code F (leave blank if no lockout required)
Signal Lamp
Lamp
Type of Protection
Certificate of Conformity
Approvals
Lamp Life
Ex de IIC T6
PTB No. Ex-88.B.2106U
PTB, UL, cUL
>100,000 Hours (11.5 Years)
Up to 240VAC, 50 / 60 Hz
Up to 110VDC
Max. 15 mA
<1.2W
2 x 2.5mm2 / 14AWG
Red, Green, Yellow, Clear & Blue
Rated Voltages
Rated Current
Power Consumption
Terminal Wiring
Colors
I
A
Colored
Lens Cover White
Code B
1
560
www.crouse-hinds.com
US: 1-866-764-5454
L
B
Yellow
Red
1 pkg
white,
yellow, red,
green
Green
Voltage
20-250VAC/DC
10-33VAC/DC
Code C
01
31
CAN: 1-800-265-0502
Blue
6
4C
Terminal Blocks
Ex e II
PTB No. Ex-88.B.3112U
Up to 400V
23A
4mm2 / 12AWG
Type of Protection
Certificate of Conformity
Rated Voltages
Rated Current
Conductor Size
A
6 Terminals 2 x 4 mm2
61
00
Potentiometers
4C
Code B
Potentiometers
Type of Protection
Certificate of Conformity
Approvals
Rated Voltages
Power Consumption
Resistance
Angle of Rotation
Scale
Connection Terminals
Ex de IIC T6
PTB No. Ex-87.B.1007U
PTB, UL, cUL
>250V
1.0W
10010,000W
270
0100%
2 x 2.5mm2 / 14AWG
Potentiometer POT
P
Code
O
A
T
B
Power Consumption
1W
Resistance W
Code B
1,000
4
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
2,200
7
4,700
5
10,000
6
561
Ammeters
Technical Data
4C
4C
Ammeters
Type of Protection
Certificate of Conformity
Ex e II T6
PTB No. Ex-87.B.2016U
Approvals
Movement
Accuracy
Measuring Range
Operating Position
Vertical
Scale
Zero Adjustment
At instrument
Terminal Wiring
Red indicator
Ammeter Measuring
Instrument AM 72*
M
Code
Movement
Direct
n/1 A
0 - 2 mA
Code B
1
2
3
Movements 0-20 mA and 4-20 mA are only available with 0 - 100 / 120% scale
Direct Measurement
Code C
Scale
02
03
04
05
07
02
03
04
05
06
08
0
0
0
0
0
-1/1.5A
- 2.5/3.75A
-5/7.5A
- 10/15A
- 16/24A
0
0
0
0
0
0
-1/1.5A
- 2.5/3.75A
-5/7.5A
- 10/15A
-15/22.5A
- 20/30A
09
10
11
12
13
14
15
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Scale
Code C
Scale
0
0
0
0
0
0
0
16
17
18
19
20
21
22
0
0
0
0
0
0
0
- 30/45A
- 40/60A
- 50/75A
- 60/90A
-75/112.5A
- 100/150A
- 150/225A
* Requires 2 spaces.
562
4-20 mA
200/300A
250/375A
300/450A
400/600A
500/750A
600/900A
100/150A
4C
Rotary Switches
Technical Data
Type of Protection
Certificate of Conformity
Approvals
Rated Votage
Rated Current
Terminal Wiring
Mechanical Life
Electrical Life
Switching Capacity
Ex 23
Ex de IIC T6
Ex.87.B.1007U
PTB, UL, cUL
400 V
NEC 10 A
IEC 16 A
2 x 2.5mm2 / 14 AWG
>105 Operations
>105 Operations
AC II: 20V/6A
400V/4A
DC II: 24V/6A
60V/0.8A
110V/.5A
220V/.2A
Ex de IIC T6
PTB no. Ex-88.B.1047U
PTB, UL, cUL
Up to 500 V
NEC 10 A
IEC 16 A
2 x 2.5mm2 / 14 AWG
>105 Operations
>105 Operations
AC I: 500G/10A
AC II: 230V/6A
500V/6A
DC II: 24V/6A
48V/4A
60V/0.8A
110V/0.5A
220V/0.4A
4C
SCT
Code
T
A
Switch Mechanism
Code B
Code C
01
03
04
06
29
Same as SCT above except up to 4
independent contacts
Inscription
0
STOP
HAND
REMOTE
OFF
I
START
AUTO
LOCAL
ON
Code C
Inscription
07
13
14
15
99
I
LOCAL
STOP
HAND
Special text
0
II
REMOTE
AUTO
0
START
0
AUTO
to be given on order
Contact
System
Code D
Code B
01
03
04
06
07
13
14
23
24
27
29
32
99
Inscription
0
I
STOP
START
HAND
AUTO
remote
local
I
0
LOCAL
REMOTE
STOP
0
OFF
0
HAND
OFF
START
STOP
OFF
ON
ON
OFF
Special text to be given on order
AUTO
START
ON
AUTO
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
563
4C
Rotary Switches
Technical Data
Type
Code C
00
2 Position
09
3 Position
01
2 Position
10
3 Position
02
2 Position
12
3 Position
03
Single Pole
Changeover
13
2 Position
05
HOA
14
2 Position
07
3 Position Single
Level
15
3 Position Double
Pole Changeover
4C
Code C
Contact System
Contact System
Type
Switched Mechanism
Code D
Padlocking Facility
Code E
Contact Configurations
Normally Closed
Normally Open
564
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
Z
Code D
Padlocking Fire Alarm
Cover For Pushbutton
4C
X
Code ED
Padlocking Cover For
Double Pushbutton
Without Hole
Z
Code F
Padlocking Cover For
Emergency Stop Pushbutton
With Bolt & Chain
Not permitted in IEC hazardous
locations.
Standard Abbreviation
AK
AM
AU
CL
DN
Fast
Forward
Hand
High
In
Jog
FS
FW
HN
HI
IN
JG
FAST
FWD
HAND
HIGH
IN
JOG
Local
Lower
Maintain
Manual
Normal
Off
LC
LO
MT
MN
NR
OF
LOCAL
LOWER
MAINT
MANUAL
NORMAL
OFF
On
Open
Out
Raise
Remote
Reset
ON
OP
OT
RA
RM
RS
ON
OPEN
OUT
RAISE
REMOTE
RESET
Reverse
Run
Slow
Test
Trip
Up
RV
RN
SL
TT
TP
UP
REV
RUN
SLOW
TEST
TRIP
UP
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
565
4C
Dimensions
4C
Box Type
Dimension (inches)
A
4.72
4.72
4.96
4.96
3.60
3.94
3.94
3.15
2.76
0.79
2.36
2.36
6.69
4.72
6.93
4.96
3.60
5.90
3.94
5.12
2.76
0.79
4.33
2.36
8.66
4.72
8.90
4.96
3.60
7.87
3.94
7.09
2.76
0.79
6.30
2.36
10.63
4.72
10.87
4.96
3.60
9.84
3.94
9.06
2.76
0.79
8.27
2.36
566
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Features:
Water-shedding construction with female
threaded bottom opening and male
threaded cover
Threaded cover is deep dome type,
which surrounds the enclosed device
All enclosures are suitable for hazardous
area use
Pushbutton stations have a guarded
rocker type operating handle at the front
arranged for padlocking to prevent
unauthorized operation
Selector switches have a lever type
operating handle at the top
Provided with vertical through feed
conduit hubs of sizes indicated in the
listings
Units are factory sealed for Cl. I, Div. 1
and 2, Groups B, C, D
Standard lockout on selector switches.
Locks two or three-position switch
handle in any position.
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
4C
Certifications and
Compliances:
NEC/CEC
Class I, Division 1 & 2, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA/EEMAC: 3, 4, 7ABCD, 9EFG, 12
UL Standard: 1203
CSA Standard: C22.2 No. 30
4C
Options:
The following special options are available from factory by adding suffix to Cat. #:
Description
Suffix
Back boss drilled and tapped for 3/4" and 1" sizes........................................................ Specify
Three-position selector switches with modified operation:
Momentary contact clockwise operation, spring return to center,
maintained contact counter-clockwise operation..................................................
S634
Momentary contact counter-clockwise operation, spring return to center,
maintained contact clockwise operation...............................................................
S635
Dimensions
In Inches*:
Standard Materials:
OAC
Standard Finishes:
Feraloy iron alloy electrogalvanized
and aluminum acrylic paint
Copper-free aluminum natural
Stainless steel natural
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
567
4C
4C
2 Circuits
Universal
2 Circuits
Universal
Single
Replacement
ED21
Pushbuttons
Diagram
Double
Single
Operating
Both Buttons Double
ED22
ED22
Hub Size
Cat. #
Cat. #
/4
1
Oper.
Handles
2 Circuits*
3
/4
1
Cat. #
2 Circuit Universal
ED22*
OAC2291
OAC3291
Cat. #
568
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
4C
Position
1
Position
2
Position
3
TwoPosition,
TwoCircuit
TwoPosition,
FourCircuit
ThreePosition,
FourCircuit
ED21
3
/4
1
OAC2471
OAC3471
ED22
3
/4
1
OAC2472
OAC3472
ED21
3
/4
1
OAC2473
OAC3473
ED22
3
/4
1
OAC2474
OAC3474
ED22
3
/4
1
OAC2475
OAC3475
FAST, SLOW
OPEN, CLOSE
UP,DOWN
ON, OFF
Dimensions*
In Inches:
IN-OUT
RAISE-LOWER
START-STOP
Three-Position
RUN, OFF, JOG
HAND, OFF, AUTOMATIC
FORWARD, OFF,
REVERSE
FAST, OFF, SLOW
1, OFF, 2
OPEN, OFF, CLOSE
UP, OFF, DOWN
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
569
4C
ThreePosition,
TwoCircuit
Replacement
Contact Blocks*
Enclosure with
Selector Switch
Hub
Size Cat. #
4C
4C
Hinged Cover
Applications:
Hinged Covers
Cat. #
NC CH1
NC CH1
NC CH1
NC CH1
NC CH1
NC CH1
NC CH1
NC CH1
NC CH1
Cat. #
NC CH1 3L
NC CH1 N2S 3L
NC CH1 N2S 4L
Cat. #
NC CH2
NC CH2L
NC CH3L
NC CH2 FS
NC CH2 FD
NC CH1 MC3
EFS
MC
FS
FD
EGF 11
N2S
N2D
GHG
Cat. #
NC CH1
NC CH1
NC CH1
NC CH1
NC CH1
NC CH1
NC CH1
NC CH1
Cat. #
NC CH1 3L QA
NC CH1 N2S 3L QA
NC CH1 N2S 4L QA
Cat. #
NC CH2 QA
NC CH2L QA
NC CH3L QA
NC CH2 FS QA
NC CH2 FD QA
QA
EFS QA
MC QA
FS QA
FD QA
EGF QA
N2S QA
N2D QA
Custom covers can be supplied but must be accompanied by either a sample of the device to be covered or a copy of a drawing with all
actual measurements of the device to be covered. Covers can also be color-coded. Consult factory.
570
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4C
2 Circuits
1 Open - A
1 Closed - B
2 Circuits
Universal
Where Used
Cat. #
Cat. #
Cat. #
ED11
ED21
ED38
-
ED12
ED22
ED32
ED35
-
ED12
ED22
ED32
-
3 Circuits
Universal
4C
1 Circuit
Universal
ED13
FlexStation Series Pushbutton Contacts (for control stations built in 1997 or later)
Contact Block without Mounting Strap
1 Circuit
Universal
2 Circuits
Universal
2 Circuits
1 Open - A
1 Closed - B
Cat. #
Where Used
Cat. #
Cat. #
ESWP126
-
Max. Current
(Amperes)
Make
Break
600 VAC Heavy Duty (NEMA
120
60
6.0
240
30
3.0
480
15
1.5
600
12
1.2
Direct Current (NEMA P150)
125
1.1
1.1
ESWP126 (3)
Contact Ratings
Volts
3 Circuits
Universal
Continuous
Current
(Amperes)
Voltamperes
Make
Break
A600)
7200
720
7200
720
7200
720
7200
720
10
10
10
10
138
138
Where Used
CF859
CF705
Colors Available Cat. #
DOWN
IN
OUT
RAISE
LOWER
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
571
4C
4C
572
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
5C
Description
Page No.
5C
Lighting Contactors
XLC Series
Timers
DSD-TS Series
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
573
XLC Explosionproof
Lighting Contactors
5C
Features:
Standard Materials:
Electrical Ratings*:
Voltage: 120V
Amperage: 30A
Number of Poles: 1-12 standard
Options:
Description
Suffix
Terminal block** . . . . . . . . . . . . . . . .
TB
Timer** . . . . . . . . . . . . . . . . . . . . . . . . TR
EV2IH20 photocell (120V) . . . . . . . . . PC1
EV2IH208 277 photocell
(208-277V)* . . . . . . . . . . . . . . . . . . . . PC2
Epoxy finish (external) . . . . . . . . . . . . S752
Epoxy finish (internal and external) . . S753
Lamacoid Nameplate . . . . . . . . . . . . LID
Heater . . . . . . . . . . . . . . . . . . . . . . . . R11
Ordering Information:
Amps = 30A
Poles
120V
2
3
4
5
6
7
8
9
10
11
12
XLC30A2
XLC30A3
XLC30A4
XLC30A5
XLC30A6
XLC30A7
XLC30A8
XLC30A9
XLC30A10
XLC30A11
XLC30A12
574
www.crouse-hinds.com
US: 1-866-764-5454
Certifications and
Compliances:
Applications:
5C
CAN: 1-800-265-0502
1.
2.
3.
4.
XLC Explosionproof
Lighting Contactors
5C
XLC
30
Operators
Nameplates
Options
SXAB
39X0708
S752
Series
XLC
5C
Amperage
30
60*
100*
Voltage
A - 120V
B - 208V*
C - 240V
D - 480V*
E - 600V*
Number of Poles
2
8
3
9
4
10
5
11
6
12
7
Select one operator symbol for each of the four positions.
The first operator is in position 1, second operator in position 2, etc.
NOTE: If no operator is required, use the symbol X.
A - Pilot Light - Red (EMP009-J1)
B - Pilot Light - Green (EMP009-J3)
C - Pilot Light - Amber (EMP009-J6)
G - On/Off Single Pushbutton - Black (EMP019)
Q - On/Off 2-Position Switch (EMP049)
S - HOA 3-Position Switch (EMP069)
X - No Operator
Select one device nameplate symbol for each of the four positions.
The first nameplate is in position 1, second nameplate in position 2, etc.
NOTE: If no nameplate is required, use the symbol X.
05 - Start (DSL05)
06 - Stop (DSL06)
07 - On (DSL07)
08 - Off (DSL08)
17 - Emerg. Stop (DSL17)
29 - Hand Auto (DSL29)
39 - Hand Auto Off (DSL39)
65 - Start Stop (DSL65)
X - No Operator
Options
TB
Terminal Block**
TR
Timer**
PC1
EV2IH20 Photocell (120V)
PC2
EV2IH208 277 Photocell (208-277V)*
S752 Epoxy Finish (External)
S753 Epoxy Finish (Internal and External)
R11
Heater
Additional EMP operators available, see page 581
Photocells are shipped separate for field installation.
*Additional configurations are available upon request. Please contact Customer Service for details.
**Timer and/or terminal block may require larger enclosure.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
575
5C
Applications:
Features:
The foundation of the Custom-Built Control Panel is our tried and tested copper-free aluminum EJB enclosure. This corrosion resistant,
heavy-duty enclosure features bolted construction, stainless steel hinges, and flexible tap-in mounting feet.
5C
Captive, quick-release
stainless steel triple-lead cover
bolts make it easier to get in
and out of the enclosure
EMP Series
the most complete line of
devices in the industry
pilot lights
pushbuttons
selector switches
potentiometers
NPT or metric
entries available
Copper-free
aluminum construction
available with Corro-free
epoxy powder coat for
additional protection in
corrosive atmospheres
ATEX Certifications
NEC/CEC:
Class I, Divisions 1 & 2, Groups B*, C and D
Class I, Zones 1 & 2
Class II, Division 1, Groups E, F and G
Class II, Division 2, Groups F and G
Class III
NEMA: 3, 4, 7B*CD, 9EFG
cUL to CSA Standard C22.2 No. 30C22.2 No. 25 Cl. II (E, F, G)
Ex d IIB + H2 T6
UL Standard 1203
IP66
Certified to the ATEX Directive when ordered with -ATEX suffix.
Custom Control Panel is component certified only. For assembly
certification, please consult factory.
II 2 G Ex d IIB + H2
EMP Devices
II 2 G Ex d IIB + H2
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Certificate #: ITS07ATEX15652U
Certificate #: ITS07ATEX15638U
ECD Breather/Drain
II 2 G Ex d IIB + H2
576
Certificate #: ITS08ATEX15797U
Certificate #: ITS07ATEX15639U
5C
Ordering Information
Building a Custom Solution
5C
Step 1
Specify the openings required for the cover of the enclosure.
Indicate in Section 1 of the order form the combination of devices, openings without devices, and windows required.
Total the number of device openings required based on the devices, openings and windows specied in Section 1.
Using Table 1, you can determine the smallest size enclosure required based upon the total number of devices/openings
and the number of devices a window requires. (NOTE: The actual size of your custom panel enclosure may change based
on the number and size of your entry requirements.)
TABLE
Total # of Device
Openings Available
Device Layout
EJB Enclosure
Catalog Number
EJB100806
16
EJB121204
16
EJB121206
16
EJB121208
36
EJB161606
36
EJB161608
24
EJB181206
24
EJB181208
36
EJB241208
36
EJB241210
54
54
=
=
9
9
X
X
6
6
EJB241808
EJB241810
81
EJB242408
81
EJB242410
52
13
GUB0108Symbol W
4-3/4" dia. viewing area
SIZE REQUIREMENTS
EJB Size
EJB361208
121204 to 181208
241208 to 362408
78
78
=
=
13
13
X
X
6
6
EJB361808
EJB361810
117
13
EJB362408
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
577
5C
Ordering Information
Building a Custom Solution
5C
578
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Ordering Information
Building a Custom Solution
5C
5C
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
579
5C
Ordering Information
Building a Custom Solution
5C
Eatons
580
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
5C
Order Form
5C
Quantity
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
581
5C
Order Form
5C
582
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Order Form
5C
Distributor:
Contact:
Customer:
Phone Number:
EATONS CROUSE-HINDS FACTORY USE ONLY
B#
OPTIONS
size
1
Top
(column)
6
7
10
11
5C
EJB__________________________________
12
13
A
B
C
size
Section 4
Device Markings:
Indicate by row and column position
markings/legends for each device.
Right Side
G
H
I
Engraved Plate:
Specify markings for each nameplate based upon
the following:
Maximum Number of Characters/Line
J
K
L
Marking Size
1/8"
3/16"
1/4"
1/2"
Number of
Characters
36
24
18
M
Bottom
Note: All device openings are spaced 2.62" center to center.
Specify
Row
Column
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Marking Size
583
5C
Single pushbutton
Double pushbutton,
single operator
5C
Certifications and
Compliances:
Short
Cat. #
Standard
Cat. #
EMPS019
EMP019
EMPS029
EMP029
Double pushbutton,
double operator
Diagram
Short
Assembly
Cat. #
Standard
Assembly
Cat. #
EMPS039
EMP039
Ordering Information:
Short
Assembly
Cat. #
Standard
Assembly
Cat. #
EMPS049
EMP049
EMPS059
EMP059
Diagram
Position 1
Group 1:
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
NEMA 3, 7BCD, 9EFG
Diagram
Position 1
Position 2
Position 2
Position 3
Pilot light
Short
Assembly
Cat. #
Standard
Assembly
Cat. #
EMPS069
EMP069
EMPS079
EMP079
EMPS089
EMP089
Diagram
(120V)*
EMP009
If desired, markings on indicating plates may be added to catalog number. Select from the
list of standard markings below:
OFF RESET
RUN TRIP
JOG TEST
LIGHT ON
HAND
AUTOMATIC
EMERGENCY
FORWARD
REVERSE
OPEN
CLOSE
UP
DOWN
IN
OUT
RAISE
LOWER
LED pilot lights can be furnished in place of standard incandescent pilot lamps. Add suffix LED to end of catalog number
after last color symbol.
* Other voltages available. Consult factory. For 24 VDC operation, add suffix S300.
The following suffixes may be used with these catalog numbers: S634 - Momentary contact clockwise, spring return to
center; S635 - Momentary contact counter-clockwise, spring return to center.
584
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
NEMA 3, 7BCD, 9EFG
5C
Maintained Contact
Pushbutton
Illuminated pushbutton
Up
Diagram
Down
Long
Assembly
Cat. #
EMP098
Diagram
120V pilot
light
EMP0090
120V pilot
light
EMP0098
Add color
Color
Red
Green
Amber
Clear
Blue
J10
J11
Diagram
Position 2
J1
J3
J6
If desired, markings on indicating plates may be added to catalog number. Select from the
list of standard markings below:
Two-position selector
switch, key operated
Position 1
5C
Long
Assembly
Cat. #
OFF RESET
RUN TRIP
JOG TEST
LIGHT ON
HAND
AUTOMATIC
Key
Removal
Short
Assembly
Cat. #
Standard
Assembly
Cat. #
Both positions
Left only
Right only
EMPS0491
EMPS0492
EMPS0493
EMP0491
EMP0492
EMP0493
Both positions
Left only
Right only
EMPS0591
EMPS0592
EMPS0593
EMP0591
EMP0592
EMP0593
EMERGENCY
FORWARD
REVERSE
OPEN
CLOSE
UP
DOWN
IN
OUT
RAISE
LOWER
Position 2
Position 3
Key
Removal
Short
Assembly
Cat. #
All
Center only
Left only
Right only
EMPS0691
EMPS0692
EMPS0693
EMPS0694
EMP0691
EMP0692
EMP0693
EMP0694
All
Center only
Left only
Right only
EMPS0791
EMPS0792
EMPS0793
EMPS0794
EMP0791
EMP0792
EMP0793
EMP0794
All
Center only
Left only
Right only
EMPS0891
EMPS0892
EMPS0893
EMPS0894
EMP0891
EMP0892
EMP0893
EMP0894
Standard
Assembly
Cat. #
LED pilot lights can be furnished in place of standard incandescent pilot lamps.
Add suffix LED to end of catalog number after last color symbol.
The following suffixes may be used with these catalog numbers: S634 - Momentary contact clockwise,
spring return to center; S635 - Momentary contact counter-clockwise, spring return to center.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
585
5C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
NEMA 3, 7BCD, 9EFG
Dimensions*
In Inches:
5C
EMP-EMPS029
EMP009
EMP-EMPS019
EMP-EMPS039
EMP098
EMP0090
EMP0098
586
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
UL/cUL Listed
NEMA 3, 4X, 7BCD, 9FG, 12
Explosionproof
Dust-Ignitionproof
Raintight / Wet Locations
5C
Applications:
EGL Static Grounding Indicator is the ideal product for safe
loading/unloading of ethanol, biofuel, petroleum, chemicals, plastics
and other combustible materials. The EGL is mounted adjacent to
loading/unloading areas and connected to transportation tank
vehicles, railcars, drums or other portable containers to prevent
explosions due to static discharge during product transfer by
providing:
A ground path for static build-up
Automatic pump shutdown when static grounding circuit is broken
Visual indication of safe, static grounding before, during and after
loading and unloading operations
5C
Ordering Information:
Description
Indicator with two pilot lights*
Catalog Number
EGL210 J1 J3
Options:
Description
Internal space heaters to limit condensation build-up
Transformer suitable for both 220/240VAC or 440/480VAC
applications
50 foot cord
Suffix
R11
S883
50FC
Options:
Replacement Parts:
Ground clamp
Ground clamp assembly (includes 25 ft. cord,
connector and clamp)
EGL210 universal interior replacement kit
Pilot lights (Red)
Pilot lights (Green)
Mounting feet
Transformer (220/240VAC; 440/480VAC)
Space heater
Pilot light plug kit
EGL-K1
EGL:20109-B
EGL210-R1
EMP009-J1-LED
EMP009-J3-LED
EJB-KIT5
EGL S883 KIT
EGL R11 KIT
EGL PLUG KIT
Standard Materials:
Enclosure: Copper-free aluminum with interior and exterior epoxy
powder coat
Clamp: Stainless steel
Clamp Grips: Polyvinylchloride dipped
Gasket: Neoprene
11.07
(28.12)
12.80
(32.51)
11.13
(28.27)
120-volt AC supply
Control relay interlocking contact: 15A at 277VAC; 10A at 600VAC
Dual-tapped 240 and 480 VAC Step Down Transformer available
Provides 2k ohms or less switching impedance
5.00
(12.70)
CL
8.41
6.30 (21.36)
(16.00)
3.00
(7.62)
1.75
(4.45)
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
587
5C
5C
Applications:
AFU and AFUX conveyor control switches
are used:
As emergency or normal "STOP" switch
for conveyor lines, cranes, unloaders,
bulk handling systems and similar
equipment
In steel mills, mining and ore and coal
handling operations, automotive and
other assembly lines, warehouses,
loading docks and various process
industry facilities
In the control circuit of magnetic motor
starters to shut down motor-driven
conveyors or other machinery when
switch is actuated
AFU series complies with requirements for
use in Class II areas having combustible
dusts that may or may not be electrically
conductive.
AFU series are also gasketed for use in
hosedown areas even when combustible
dusts are present.
AFUX series complies with requirements
for use in NEC Class I areas which are
hazardous due to the presence of
flammable vapors or gases. AFUX series
also complies with requirements for use in
NEC Class I areas which are hazardous
due to the presence of flammable vapors
or gases. AFUX series also complies with
NEC requirements for use in Class II
hazardous areas, or for use in NEC
hazardous areas classified simultaneously
as Class I and Class II.
Certifications and
Compliances:
Standard Finishes:
Feraloy iron alloy electrogalvanized
and aluminum acrylic paint
Steel electrogalvanized with chromate
finish (red acrylic paint on indicating
arm)
Bronze natural
AFU Series
NEC/CEC:
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
Encl. 3, 5
NEMA: 3, 4, 9EFG
IP66
UL Standard: 698
CSA Standard: 22.2 No. 30
AFUX Series
NEC:
Class I, Division 1 & 2, Groups C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA: 3, 7CD, 9EFG
IP65
UL Standard: 698
cUL
Options:
Description
Finish: Corro-free epoxy powder
coat for coating outside only.
Suffix
S752
Electrical Rating:
Control circuit switch 15 AMP, 600
VAC max.
Standard Materials:
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Features:
Furnished with one or two end units,
each containing 2-NO and 2-NC contact
arrangements.
Precision switches provide maintained
contact (switches have a snap action
mechanism).
Enclosure has three 1" conduit hubs
two for horizontal through feed and one
at the bottom. Cast mounting lugs on
11/ 2" centers permit attachment to the
web of a standard 3" angle iron.
In installation, the actuating line or cable
is connected from a fixed point to the
loop on the end unit. A pull on the line
of the required operating force and with
a total movement of 1/2" actuates the
plunger, opens the switch and trips the
red painted indicating arm forward,
which locks the plunger in the actuated
(switch open) position. Returning the
indicating arm to its normal position
resets the mechanism. A typical
installation would include single end
switch units at each end of the conveyor
with double end switch units between.
Depending on the size and length of
line, supports at properly spaced
intervals may be necessary to ensure
that the line or cable weight alone will
not actuate switch.
Ordering Information
Description
Maximum Weight of
Unsupported Line or
Cable Without
Actuating Switch
(lbs.)
Total
Operating
Force
Required
(lbs.)
Contact Arrangements
With 2-NO, 2-NC in
Each End Unit
Cat. #
Cat. #
15
25
15
25
15
25
25
50
25
50
25
50
AFU0333
AFU0333
AFU0333
AFU0333
AFU0333
AFU0333
Dimensions
In Inches*:
588
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
50
60
05
06
55
66
AFUX0333
AFUX0333
AFUX0333
AFUX0333
AFUX0333
AFUX0333
50
60
05
06
55
66
Applications:
Features:
Furnished with precision switches that
provide normally open and normally
closed contacts (switches have a snap
action mechanism).
Housing consists of a center section
which can be mounted either vertically
or horizontally, and a switch housing
with an attached switch operating arm.
Enclosure has three 1" conduit hubs.
Cast mounting lugs on 11/2" center permit
attachment to the web of a standard 3"
angle iron.
Operating arm has 31/2" long stainless
steel protective roller. Approximately 3/4"
lateral movement of operating arm
actuates switch.
Spring loaded operating arm will
automatically return switch to normal
position when belt interference is
removed.
A severe conveyor belt run-off can rotate
the operating arm counter-clockwise up
to 85 degrees without damage to the
switch mechanism.
Installation of AFA or AFAX unit on either
side of a conveyor belt allows
approximately 1" or a predetermined
allowable belt misalignment before
switch is actuated. A typical installation
would include a pair of AFA or AFAX
units at each end of the conveyor belt
where belt returns.
5C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Certifications and
Compliances:
AFA SERIES
NEC/CEC:
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA: 3, 4, 9EFG
IP66
UL Standard: 698
CSA C22.2 No. 25
AFAX SERIES
NEC:
Class I, Division 1 & 2, Groups C, D
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA: 3, 7CD, 9EFG
IP65
UL Standard: 1203
CSA Standard: C22.2 No. 30
5C
Electrical Rating:
Control circuit switches 15 AMP, 600
VAC max.
Ordering Information
Contact
Arrangement Diagram
Standard Materials:
Enclosure Feraloy iron alloy
Bearing and operating arm stainless
steel with plastic end caps
Cat. #
2 normally
open
AFA20
Standard Finishes:
2 normally
closed
AFAX20
Options:
Description
Suffix
Finish: Corro-free epoxy powder
coat for coating outside only.
S752
Dimensions
In Inches*:
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
589
5C
NEMA 3
Raintight
Wet Locations
Applications:
AFU mine signal switches are used:
For signalling circuits or remote control
of magnetic motor starters
In non-hazardous areas of mines or
process industry facilities where a
rugged enclosure is needed for
protection from falling ore and other
material or dripping water
Mounted on walls or in shaft ways and
actuated by pulling line or cable
attached to the loop at the bottom
5C
Features:
Sturdy raintight enclosure with heavy
mounting lugs
Wires enter enclosure through clearance
holes in the underside
Switches are actuated by a springloaded plunger which returns to the
normal position when the operating
force is removed
Units are furnished with heavy duty
motor control push buttons. Several of
these may be interconnected electrically
for remote control of a magnetic motor
starter from more than one location
Certifications and
Compliances:
NEMA: 3
Ordering Information
Maximum Wt. of Line or Total Operating
Cable Without Actuating Force Required
Switch (lbs.)
(lbs.)
With Pushbutton
Heavy Duty
600 VAC Max.
Cat. #
25
15
AFU254
AFU154
50
25
Dimensions
Standard Materials:
Enclosure Feraloy iron alloy
Plunger steel
Loop bronze
In Inches*:
Standard Finishes:
Feraloy electrogalvanized and
aluminum acrylic paint
Steel electrogalvanized
Bronze natural
590
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Applications:
5C
Standard Materials:
Body and cover steel reinforced neoprene
Strain relief and reinforcement plates stainless
steel
Exterior hardware stainless steel
Standard Finishes:
5C
Features:
Safety cushioned neoprene
encapsulation protects internal switches
and connectors from impact damage
and provides extra protection for
personnel.
Stress relief for your cable is built-in.
A separate cable grip is not needed.
Uses Eaton's Crouse-Hinds ESWP factory
sealed contacts suitable for use in Class I,
Division 2, Groups B, C, and D.
Switches are rated for 10 amps 600 VAC
(NEMA A600).
Indicator plates meet OSHA
requirements for clear identification of
functions. A full set of plates is included
with each station.
Jam-resistant operator buttons are
raised flexible diaphragms an integral
part of the molded one-piece cover.
Compact design.
Safety yellow finish.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
591
5C
Ordering Information
Pendant Pushbutton Stations
Description
Cable Dia.
Cat. #
2-Button
4-Button
.31 .75
.50 .75
D2X8635 210
D2X8635410
6-Button
.59 .81
D2X8635 610
8-Button
.59 .92
D2X8635 810
Replacement Switch
5C
2-Button
Cat. #
315116
315116
315116
315116
315116
315116
1
2
3
4
5
6
Description
Cat. #
Description
Down/West
Start/North
Stop/South
Off/In
On/Out
Fwd/Right
315116 7
315116 8
Rev/Left
Up/East
Description
Cat. #
Description
Cat. #
Replacement Switch
ESWP126
4, 6 and 8-Button
Cat. #
314850 1
Bridge
314850 6
314850 2
Trolley
314850 9
314850 3
Hoist
In/Out
Up/Down
Right/Left
East/West
314850 4
314850 5
Description
Fwd/Rev
North/South
On/Off
Start/Stop
Dimensions
In Inches:
2-Button
592
www.crouse-hinds.com
4-Button
US: 1-866-764-5454
CAN: 1-800-265-0502
6-Button
8-Button
NEMA 3, 4X, 5, 6, 12
Applications:
A cable grip
is used with
pilot light
option, and
is included
with kit.
Raintight
Watertight
Dust-tight
Wet Locations
5C
5C
Features:
Safety insulated to meet OSHA
requirements for enclosing live parts. The
entire unit except the strain relief is
insulated with neoprene.
Safety cushioned neoprene
encapsulation protects internal switches
and connectors from impact damage
and provides extra protection for
personnel.
Stress relief for your cable is built-in. A
separate cable grip is not needed unless
the optional pilot light kit is used.
Positive action long life momentary
contact switches.
Maintained Off-On toggle switch is
optionally available on 4, 6, and 8 button
units.
Jam resistant operator buttons are raised
flexible diaphragms an integral part of
the molded one-piece cover.
Compact 3" x 3" enclosure easily fits
your hand.
Indicator plates meet OSHA
requirements for clear identification of
functions. A full set of plates is provided
with each station.
Certifications and
Compliances:
NEMA: 3, 4X, 5, 6, 12
UL Standard: 508
CSA Approved
Standard Materials:
Body and cover steel reinforced
neoprene
Strain relief and reinforcement plates
stainless steel
Exterior hardware stainless steel
Standard Finishes:
Neoprene safety yellow
Steel stainless steel
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
593
5C
NEMA 3, 4X, 5, 6, 12
Raintight
Watertight
Dust-tight
Wet Locations
1 Speed
2 Speed
DC
20A 460V 10A 230V
10A 125V
Switch* 2 hp. 230V 1/2 hp. 230V 1/8 hp. 125V
Cable
Diameter
Shipping
Weight
(lbs.)
Dimensions
Length Width Depth
None
X8635 20
21/2
83/4"
21/4"
3"
X8635 40B
131/2"
3"
35/8"
X8635 60B
61/ 2
17"
3"
35/8"
3316317 X8635 81
X8635 80
211/2"
3"
37/16"
2-Button
X8635 21
X8635 22
4-Button
5C
6-Button
8-Button
X8635 82
8 Button
Lamp Voltage .50 thru .62 .63 thru .74 .75 thru .87 .69 thru .97
110125V AC 3316533
3316533 1 3316533 2 3316624
210250V AC 3316534
3316534 1 3316534 2 3316625
Contact
Style
Cat. #
X8995 1
Yellow
Momentary
Switch
Pilot light kit includes: lamp assembly with lens and bulb, cable support grip, and "S" hook.
Support grip and "S" hook not required on 8-button. NEMA 3,4,5,12 only.
Voltage
240 AC
120 AC
24 AC
250 VDC
125 VDC
Amps
Make
7.5
15.0
15.0
0.27
.055
Amps
Break
0.75
1.5
2.5
0.27
0.55
4, 6 and 8-Button
Cat. #
Description
Cat. #
Description
Cat. #
Description
Cat. #
Description
315116 1
Down/West
315116 7
Rev/Left
314850 1
Bridge
314850 6
Fwd/Rev. (North/South)
315116 2
Start/North
315116 8
Up/East
314850 2
Trolley
314850 9
On/Off (Start/Stop)
315116 3
Stop/South
315116 9
Raise/Lower
314850 3
Hoist
314850 12
Raise/Lower
314850 13
315116 4
Off/In
315116 10
Up/Down
314850 4
In/Out (Up/Down)
315116 5
On/Out
315116 11
Right/Left
314850 5
315116 6
Fwd/Right
Inbd/Outbd
Off/On
Shoulder Bolts for Fastening Front to Back Cover 2-Button (P/N 1316311-2); 4- & 6-Button (P/N 1316311-1); 8 button (P/N 1316311-3).
NOTE: Refer to price list for identification of stock items.
Replacement Parts
Cat. #
Style
Front
Cover
2-Button A335578
Back
Cover
1 Speed
20A, 460V
2hp, 230V
2 speed
DC
Toggle
10A, 230V 10A, 125V Off/On
1
/2 hp. 230V /8 hp. 125V Element Barrier
314896
Parts
Separator Kit
314903
RX8635 21
3316480
314896
314903
314849 1
1316313 (4 Req'd)
3316480
314896
314903
314849 1
1316313 (6 Req'd)
8-Button 3344153
3316480
314896
314903
3344154
3316317
Toggle switch kit includes: toggle switch, guard, assembly and screws.
Parts kit includes cable grommets, legend plates and assembly screws.
594
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Pilot
Light
Kit
335616
(1 Req'd)
335571
(1 Req'd)
RX8635 41 See
Above
RX8635 61 Chart
EGF Series
Ground Fault Control Station
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
5C
Applications:
EGF Series of control stations are used:
For the additional safety of personnel,
and for equipment protection in
remote areas.
Features:
Certifications and
Compliances:
NEC:
Class I, Div. 1 & 2, Groups C, D
Class II, Div. 1, Groups E, F, G
Class II, Div. 2, Groups F, G
Class III
NEMA 3, 7CD, 9EFG, 12
5C
Ordering Information
Number of
Breakers
Number
of Poles
1
1
2
1
1
2
1
1
2
1
1
2
Add 15, 20, 25, or 30 amp breaker rating.
Milliamp
Trip
Cat. #
5
5
5
30
30
30
EGF11
EGF12
EGF21
EGF11EPD
EGF12EPD
EGF21EPD
Dimensions
In Inches:
Standard Materials:
Bodies, covers, threaded barrels, guards,
collars, and toggle operator copperfree aluminum
Pushbuttons type 6 / 6 nylon
Operating shafts stainless steel
Standard Finishes:
Copper-free aluminum natural
Sheet steel zinc electroplate with
chromate finish
Stainless steel natural
Electrical Rating:
GFI, EPD breakers 120 VAC (single
pole), 120 / 240 VAC for two pole
(10,000 AIC)
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
595
5C
For use with Eaton's Crouse-Hinds EDS/EDSC back boxes (single and two-gang) and EDSCM modular control device bodies (up to nine-gang
maximum). These bodies are to be ordered separately from the DSD-TS covers.
Applications:
Provides automatic shut-off for fans, heaters, pumps, lights, and
other energy consuming loads in Class I and Class II hazardous
areas
Features:
Spring wound, mechanical timer switch
Copper-free aluminum covers
5C
NOTE: Suitable for use in Zone 1 and Zone 2 classified areas (gas groups IIB and IIA) as per
Canadian Electrical Code, Part I, Section 18-100(a).
Electrical Ratings:
11
SA
Series:
DSD-TS
Poles:
11 - SPST
12 - SPDT
21 - DPST
Minutes or Hours:
M - Minutes
H - Hours
Time:
Minutes:
5 - 5 Minutes
15 - 15 Minutes
30 - 30 Minutes
60 - 60 Minutes
Hours:
2 - 2 Hours
4 - 4 Hours
6 - 6 Hours
12 - 12 Hours
Material:
SA - Aluminum
Note:
596
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
6C
Explosionproof
Variable Frequency Drives
Description
Page No.
6C
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
597
6C
6C
598
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
6C
Applications:
For speed control of pumps, compressors, fans, conveyors,
separators, mixers, and other process equipment
Designed to meet the high reliability and safety requirements of
process industries such as oil and gas, chemical and mining
6C
UL Classified
Class I, Divisions 1 and 2, Groups B, C, D
cUL Classified
Class I, Divisions 1 and 2, Groups B*, C, D
Standards
UL 1203
Environmental Ratings
NEMA 3, 4X, 7BCD
Raintight
Wet locations
Operating Temperature Range
-10C to 50C (14F to 122F)
Horsepower Ratings:
Available up to 60HP
Higher horsepower ratings coming soon
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
599
6C
System Design
6C
Fused disconnect.
600
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
6C
Shroud
covering top
lters
maintains
NEMA 4X
rating.
6C
Filters in top
and bottom
of enclosure
allow airow
into and out of
the enclosure,
cooling the
VFD and
eliminating risk
of overheating.
Pre-lter
screens
(not shown) eliminate clogging of the primary
lters, ensuring reliable and consistent airow.
Pre-lter screens can be easily removed and
cleaned without shutting down operations.
Heavy duty blower, shroud, lters, and pre-lter screens not included
with units containing 1.5 to 5.0 horsepower VFDs.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
601
6C
6C
Cat. #
ACE10
ACE10
ACE10
ACE10
ACE10
ACE10
1
2
3
5
7
10
1.5 (1.1)
2.0 (1.5)
3.0 (2.2)
5.0 (3.0)
7.5 (5.5)
10.0 (7.5)
ACE10
ACE10
ACE10
ACE10
15
20
25
30
15.0
20.0
25.0
30.0
ACE10 40
ACE10 50
ACE10 60
(11.0)
(15.0)
(18.5)
(22.0)
40.0 (30.0)
50.0 (37.0)
60.0 (45.0)
Max.
Disconnect Disconnect
Rating
Fuse
Enclosure
(Amps)
Type
Size
Input
Rating
(Amps)
Max.
Output
Rating
(Amps)
Power
Loss
(Watts)
Temp.
Rating
30
J
J
J
J
J
J
1
1
1
1
1
1
2.3
3.1
4.0
6.6
12.0
16.0
3.0
3.6
4.8
8.0
12.2
15.6
106
112
132
178
606
674
T6
T6
T6
T6
T4A
T4A
60
J
J
J
J
2
2
2
2
20.0
26.0
30.0
36.0
23.0
30.0
35.0
44.0
737
737
847
903
T4A
T4A
T4A
T4A
100
J
J
J
2
2
2
55.0
65.0
82.0
58.0
72.0
81.0
1217
1397
1577
T4A
T4A
T4A
De-rating may be required to account for specific environmental conditions (high ambient temperature, altitude, etc). Consult factory for de-rating information.
When not installed in a well ventilated environment, provisions must be made to account for heat generation to ensure proper operation of the device.
add suffix
Communication Modules
Profibus
Devicenet
CAN Open
Modbus
Ethernet
CP
CD
CC
CM
CE
Potentiometer in Cover
AB 800H
PT
Current Rating
ACE10 60
CE
PT
FJ90
Potentiometer
Fuse (81A
requirement +
5A for blower,
rounded up
to 90)
Ethernet
Communications
Cat. #
ACE
ACE
ACE
ACE
ACE
KIT
KIT
KIT
KIT
KIT
1
2
3
4
5
602
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
6C
15.08
[383.0]
21.83
[554.5]
31.98
[812.2]
9.38 [238.2]
17.25
[438.2]
9.22 [234.2]
4.40 [111.7]
15.25
[387.4]
5/8" BOLT
(4 PLACES)
5.00 [127.0]
6C
9.09 [230.9]
6.75 [171.3]
Pre-lter Screen
.50 [12.7]
3.70 [93.9]
3.50 [88.9]
8.00 [203.1]
1" NPT
1-1/2" NPT
(2 PLACES)
15.59
[395.9]
21.88
[555.6]
44.31
[1125.3]
22.02
[559.3]
17.04
[432.9]
28.25
[717.6]
11.08
[281.5]
16.30
[414.1]
5/8" BOLT
(4 PLACES)
9.48 [240.8]
4.42 [112.2]
Pre-lter Screens
8.00 [203.2]
5.85 [148.7]
.50 [12.7]
3.25 [82.6]
3.70 [93.9]
9.00 [228.5]
1" NPT
2" NPT
(2 PLACES)
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
603
6C
6C
604
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
6C
6C
UL Classified
Class I, Divisions 1 and 2, Groups B, C, D
cUL Classified
Class I, Divisions 1 and 2, Groups B*, C, D
Standards
UL1203
Environmental Ratings
NEMA 3, 4X, 7BCD
NEMA 3X rating with PB23 or RR3 options added
Raintight
Wet locations
Operating Temperature Range
0C to 50C (32F to 122F)
Horsepower Ratings:
Available up to 50HP
Higher horsepower ratings coming soon
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
605
6C
6C
Fused Disconnect
606
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
6C
Shroud*
covering top
lters
maintains
NEMA 4X
rating.
6C
Wireless Interface
Module Option
Filters*
in top and bottom of
enclosure allow airow
into and out of the
enclosure, cooling the
VFD and eliminating risk
of overheating.
Pre-lter screens*
eliminate clogging of the
primary lters, ensuring
reliable and consistent
airow. Pre-lter screens
can be easily removed
and cleaned without
shutting down operations.
* Heavy duty blower, shroud, lters, and pre-lter screens not
included with units containing 1.5 to 5.0 horsepower VFDs.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
607
6C
Temp.
Rating
T6
T6
T6
T6
9.5
12.5
19.9
24.8
31.2
36.7
11.0
14.0
22.0
27.0
34.0
40.0
594
618
726
794
841
859
T4A
T4A
T4A
T4A
T4A
T4A
47.7
59.6
52.0
65.0
1010
1117
T4A
T4A
Max.
Input
Disconnect
Disconnect Enclosure Rating
Rating (Amps) Fuse Type Size
(Amps)
1.6
2.6
30
J
1
3.9
6.9
ACE20 7
ACE20 10
7.5
10
30
ACE20
ACE20
ACE20
ACE20
15
20
25
30
15
20
25
30
60
ACE20 40
ACE20 50
40
50
100
Cat. #
ACE20
ACE20
ACE20
ACE20
6C
Max.
Output
Rating
(Amps)
2.1
3.4
5.0
8.0
Nominal
Horsepower
(KW)
1
2
3
5
1
2
3
5
VFD Manufacturer
Part #
20BD027A0AYNANC0
20BD027A0AYNANC0
20BD065A0AYNANC0
Above data is for a 480V drive. For 600V drive, please consult factory.
De-rating may be required to account for specific environmental conditions (high ambient temperature, altitude, etc.). Consult factory for de-rating information.
When not installed in a well ventilated environment, provisions must be made to account for heat generation to ensure proper operation of the device.
Add Suffix
Communication Modules
Profibus
Devicenet
CAN Open
Modbus
Ethernet
Wireless
CP
CD
CC
CM
CE
WL
Options
Potentiometer
Hand-Off-Auto Switch
Pushbutton Start-Stop
600 VAC VFD
PT
RR3
PB23
Consult Factory
FJ
Current Rating
Fuse Type J
ACE20 50
Allen-Bradley
VFD With 50
HP Rating
CE
PT
FJ90
Potentiometer
Fuse (81A
requirement +
5A for blower,
rounded up
to 90)
Ethernet
Communications
Cat. #
ACE KIT
ACE KIT
ACE KIT
ACE KIT
1
2
3
5
608
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
6C
555.6
21.88
398.4
15.69
128
5.04
812.2
31.98
248.7
9.79
6C
487.7
19.20
438.2
17.25
156.6
6.17
5/8" BOLT
(4 PLACES)
106.4
4.19
171.5
6.75
12.7
.50
101.5
4.00
106.6
4.20
215.8
8.50
1" NPT
1-1/2" NPT
(2 PLACES)
638.8
25.15
125.7
4.95
1176.3
46.31
203.2
8.00
717.6
28.25
88.8
3.50
532.1
20.95
12.7
.50
93.9
3.70
228.5
9.00
281.5
11.08
1" NPT
414.1
16.30
2" NPT
(2 PLACES)
148.7
5.85
398.4
15.69
5/8" BOLT
(4 PLACES)
Pre-lter Screens
& Filters
Enclosure Size 2 (7.5 to 50.0 Horsepower VFDs)
*5HP and below listed for Group B.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
609
6C
6C
610
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Engineered Solutions
Hazardous and Non-hazardous
7C
Description
Page No.
Specialty Products
Switch Racks
General Information
Bus Duct Assemblies
Selection Guide
7C
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
611
7C
Engineered Solutions
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Applications:
Capabilities:
7C
Integrated Solutions:
Enclosed metering and
instrumentation
Component populated
enclosures
Custom machining,
painting, and legend
Installed fittings and
seals
Portable Solutions:
Power distribution
Lighting products
Plugs
Protection equipment
Interested in a custom engineered product? Contact your local Eaton's Crouse-Hinds sales representative to see how we can design a
solution for you. Fill out the request form on the following page to receive a custom quote for your inquiry.
612
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Engineered Solutions
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Request a Quote
Customer: ______________________________________
Project: ________________________________________
Prepared By: ____________________________________
Bid
Quotation For:
Estimate/Budget
Quotation Required By (Date): ______________________
7C
Dimension Restrictions:
Width _____________
Depth _____________
C
Height _______________
Div. 2
E
3R
4X
____ VOLT
____ PH
____ W
____ HZ
____ AMP
Class III
NON-HAZARDOUS
Ordinary Locations
NEMA Rating
Description: _______________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
Please attach any supporting documentation to this form, including: sketches, single line diagrams, drawings, bill of
materials, specifications, etc.
CONTACT:
E-mail: crouse.customerctr@cooperindustries.com
Phone: (866) 764-5454
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
613
7C
Area Classification:
7C
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
7C
Applications:
Free-standing switch rack assemblies are
used:
To provide a complete motor control
center in one integrated package
Outdoors and indoors
In damp, wet or corrosive locations such
as sewage treatment plants, lumber
mills, marine installations, and food
preparation areas
In areas made hazardous due to the
presence of flammable vapors or gases,
such as petroleum refineries, chemical
and petrochemical plants, gas gathering
plants, pipeline compressor stations,
and drilling rigs, both onshore and
offshore
In areas where hazardous dusts are
present, such as coal handling facilities,
grain processing and handling plants,
and certain food process industries
Features:
Complete factory assembled and wired
switch racks
Pre-drilled bus boxes allow for quick
and easy changing or adding of
components
Complete assembly covered under one
order, eliminates engineering costs,
additional costs of placing separate
orders with several vendors for various
components, and assembly and
scheduling problems at job site
Wiring is simple. After switch rack is in
place, feeders are connected to the
main bus and connections made from
starters motors. No other field wiring is
necessary
Maintenance time and costs are
reduced by having controls grouped.
Work is performed in one location
instead of moving from one control to
another in various locations
Major components are standard EBM,
EPC, NMC, NMG, NCB, FLB, D2PB,
EXD, D2D, EPL, and D2L enclosures
featuring ready access to starters and
breakers for inspection and maintenance
Custom built racks to meet your exact
requirements are an Eaton's CrouseHinds specialty. Complete quotations
will be supplied for any job, large or
small (38' length max)
614
www.crouse-hinds.com
US: 1-866-764-5454
Certifications and
Compliances:
NEC:
Class I, Divisions 1 & 2, Groups C, D
(Group B optional)
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
NEMA: 3, 4X (optional), 7B (optional) CD,
9EFG, 12
Standard Materials:
Standard Finishes:
Rack frame hot dip galvanized steel
or natural aluminum
Components see sections A & C for
finishes
Options:
Rack frame finish corrosion resistant
primer with air dry epoxy
Options listed for individual components
can be incorporated in complete switch
racks
CAN: 1-800-265-0502
Construction:
General:
Structure:
Class I, Division 1:
Main bus material shall be copper only
and capable of withstanding up to 65K
amps fault current. Cable bus will be
wired to terminal blocks enclosed in
cast, copper-free aluminum,
explosionproof junction boxes, Eaton's
Crouse-Hinds type EJB. Such junction
boxes for incoming power and
distribution wiring shall be provided at
either the top or bottom of the rack.
Enclosures shall be connected by rigid
conduit with conduit seals installed in
accordance with the NEC. Load conduit
or cable will leave rack either below or
above. Manufacturer shall provide
conduit layouts.
Class I, Division 2:
Main bus material shall be copper only
and capable of withstanding up to 65K
amps fault current. Cable bus will be
wired to terminal blocks enclosed in
cast, copper-free aluminum
weathertight junction boxes, Eaton's
Crouse-Hinds type WJB. Such junction
boxes for incoming power and
distribution wiring shall be provided at
either the top or bottom of the rack.
Enclosures shall be connected by rigid
conduit with conduit seals installed as
required by the NEC. Load conduit or
cable will leave rack either below or
above. Manufacturer shall provide
conduit layouts.
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Canopy (Optional):
Single- or double-pitched canopy shall
have minimum 15-degree pitch with a
minimum 7'6" ground clearance, and 2foot overhang. Roofing material shall be
corrugated aluminum. Canopy roof
trusses, cross channels, roof material,
and mounting hardware shall be
shipped unassembled for quick
assembly at the job site. All holes in
structure shall be provided except for
roof mounting holes which will be drilled
in the field. Manufacturer will supply
drawings and material for complete field
assembly of canopy.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
615
7C
Grounding:
7C
7C
7C
Motor Control
Components:
Explosionproof Quick Opening
Enclosures:
All circuit breakers, motor circuit
protectors and combination or acrossthe-line motor starters shall be enclosed
in quick-opening enclosures (Eaton's
Crouse-Hinds types EBM or EPC).
Types:
Ground joint bolted cover enclosure
shall be Eaton's Crouse-Hinds type
EBM, Underwriters Laboratories Inc.
classified for use in Class I, Groups C,
D, Divisions 1 and 2, Class II, Groups E,
F, G, Divisions 1 and 2 and Class III
hazardous locations and shall also be
suitable for Type 3, 3R and/or Type 4
(NEMA 3, 3R and 4) areas.
All enclosures shall be cast of a
corrosion-resistant copper-free
aluminum alloy (less than 0.4% copper)
and shall be of a semi clamshell design
with external flange to promote ease of
apparatus installation, adjustment and
maintenance. Most importantly,
enclosure inside dimensions shall
conform to the wire bending space
requirements of the National Electrical
code NFPA70 paragraph 373-6.
Enclosures with flat covers, internal
flanges or those not conforming to
NFPA70 paragraph 373-6 are not
permitted.
Covers shall be hinged on the left side
and, when closed, shall be affixed top
the body by multiple lead thread bolts to
promote quick opening and closing of
the enclosure.
Cover bolts shall be hex head stainless
steel without screwdriver slots, to
promote the use of a socket or wrench
for proper tightening. They shall be
captive to the cover and stainless steel
spring loaded to indicate the fully
unthreaded position. Spring loading shall
give visual indication that the bolts are
free of the body when the cover is being
opened. The cover flange ground joint
shall have an integeral gasket to prevent
the entry of windblown dust, rain or
sleet.
616
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
General:
All enclosures shall be bolted to the
horizontal frame members on either the
front or back or both front and back.
Enclosures shall be connected to the
main bus via conduit seals. (To be field
poured). All hardware used to mount the
enclosures shall be stainless steel.
Lighting Panelboards:
Wiring:
Standard wire shall be copper only,
600 volt, 75C minimum rating, UL
listed.
No power wire less than 12AWG
shall be used.
Control wire shall be 14AWG
minimum, 7 strands, THW
minimum.
Wiring shall be sized in accordance
with the NEC requirements.
Drawings:
Standard drawings supplied for
customer approval shall include
complete rack wiring diagram,
component data, nominal weight of
the rack, and overall rack
dimensions.
7C
Class I, Division 1:
Panelboards shall be Eaton's CrouseHinds type, factory-sealed EXD or EPL
as specified and shall meet the following
electrical ratings:
EPL 1, 2 or 3 pole, 240 volt maximum,
100 amp maximum branch trip rating,
10,000 AIC.
EXD 1, 2 or 3 pole, 600 volt
maximum, 100 amp maximum branch
trip rating.
Class I, Division 2:
Lighting panelboard shall be Eaton's
Crouse-Hinds type D2L factory-sealed,
120 / 240 volt panelboards and be
provided with single-pole, two-pole, or
three-pole branch circuit breakers with
up to 100 amp trip rating; main breaker
ranging to 225 amp. Similarly, lighting
panelboard shall be type D2PB factorysealed, 120 / 240 volt panelboards and
be provided with single-pole or two-pole
factory sealed circuit breakers with 15,
20 or 30 amp trip ratings and maximum
10,000 AIC. Power panelboards type
D2D factory-sealed, up to 600 volt are
provided with single-pole, two-pole, or
three-pole branch circuit breakers with
up to 100 amp trip ratings; main breaker
rating to 225 amp.
7C
NEMA 4X Option:
All bus boxes, control enclosures and
lighting panelboards will be made of
KRYDON material to meet NEMA 4X
requirements.
Fittings:
All fittings shall be made and provided
by the manufacturer. Seals and unions
will be provided for each incoming and
outgoing conduit as required. All
interconnections between components
shall be done by the manufacturer with
galvanized rigid conduit, and conduit
fittings as required to meet the
hazardous classification. Interconnecting
conduits to be provided with conduit
seals as required. All incoming and
outgoing rack conduit entrances shall
include conduit seals as required by the
hazardous location specified. Such seals
will be provided by the manufacturer and
will not be filled where field wiring is to
be introduced.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
617
7C
NEMA 3R
Up to 600 Volts
Applications:
Features:
7C
618
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
UL Listed.
NEMA 3R.
Maximum voltage rating 600V.
400 Amp or 600 Amp @ 25KAIC or 50KAIC.
External flange on bus duct enclosure and lip on covers prevents
water leakage and allows covers to hang freely for ease of
installation and maintenance.
3 degree pitch at top, for water run-off, on all flush mounted
bottom entry designs.
Chorosulfonated polyethlene (Hypalon) gasket material at all bus
box section joints, covers and end plates.
Standoff (Glastic) insulators molded of (UL) recognized flameresistant fiberglass-reinforced thermoset polyester molding
compound.
Bus bar sizing and bracing complies to UL857 requirements.
All welded construction - sheet aluminum, sheet steel (galvanized),
or stainless steel.
Stainless steel hardware throughout.
Two hole compression lugs at all power phase connectors
attatched with stainless steel hardware.
One (1) drain is standard per bus duct section (typical 4 foot
sections).
Solid copper bus bars (tin, silver plated and/or insulated optional
per customer request).
Solid copper ground bar standard.
Incoming main lugs supplied size and location specified with
customer.
Space heaters optional per customer request.
Pre-drilled copper bars (when specified by customer).
Conduit entries for Myers hubs optional per customer request.
7C
7C
For pricing and lead times, contact Eaton's Crouse-Hinds Customer Service at 866-764-5454 or fax to 315-477-5179.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
619
7C
7C
Selection Guide
620
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight
7C
7C
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
621
7C
7C
Selection Guide
622
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Watertight