Beruflich Dokumente
Kultur Dokumente
Section
10
Motor Feeders and Starters
10.1.0 Introduction
10.1.1 Sizing Motor-Circuit Feeders and Their Overcurrent Protection
10.1.2 NEC Table 430.7(B), Locked-Rotor-Indicating Code Letters
10.1.3 Motor-Circuit Data Sheets
10.1.4 480-V System (460-V Motors) Three-Phase Motor-Circuit Feeders
10.1.5 208-V System (200-V Motors) Three-Phase Motor-Circuit Feeders
10.1.6 115-V Single-Phase Motor-Circuit Feeders
10.1.7 200-V Single-Phase Motor-Circuit Feeders
10.1.8 230-V Single-Phase Motor-Circuit Feeders
10.1.9 Motor Starter Characteristics (for Squirrel-Cage Motors)
10.1.10 Reduced-Voltage Starter Characteristics
10.1.11 Reduced-Voltage Starter Selection Table
10.1.0 Introduction
Motors comprise a significant portion of a building’s electrical system loads. They
are needed to power fans and pumps for basic mechanical building infrastructure
such as heating, ventilation, air conditioning, plumbing, fire protection, elevators,
and escalators. They are also needed to power equipment endemic to the occupancy,
such as commercial kitchen equipment in an institutional facility, CT and MRI
scanners in a hospital, and process equipment such as conveyors and machinery in
an industrial plant or stone quarry. Consequently, designing motor-circuit feeders is
very much in the mainstream of the electrical design professional’s daily work. To
save time in this process, the following information is provided.
10.1
CH10_Hickey 11/15/01 10:46 AM Page 10.2
For Hermetic Motors (Special Case). Hermetic motors are actually a combination
consisting of a compressor and motor, both of which are enclosed in the same hous-
ing, with no external shaft or shaft seals, the motor operating in the refrigerant;
thus their characteristics are different from those of standard induction motors.
Calculating their feeder size and overcurrent protection is based on their nameplate
branch-circuit selection current (BCSC) or their rated-load current (RLC),
whichever is greater. The BCSC is always equal to or greater than the RLC. Hence,
the following:
1. Feeder wire size 125 percent of BCSC/RLC maximum.
2. Feeder breaker (thermal-magnetic fixed-trip type) 175 to 225 percent of
BCSC/RLC maximum.
3. Feeder breaker (instantaneous magnetic-only type) 800 percent of BCSC/RLC
maximum.
4. Feeder fuse (dual-element time-delay type) 175 to 225 percent of BCSC/RLC maxi-
mum.
5. Feeder fuse (NEC non-time-delay type) not recommended—Do not use.
DC (Constant-Voltage) Motors
For Multiple Motors on One Feeder. First, size feeder and overcurrent protection for
largest motor and add the full-load current of the remaining motors to size the
overall feeder and overcurrent protection.
Application Tips
1. Refer to NEC Articles 430 and 440 for further details on sizing motor feeders
and overcurrent protection.
CH10_Hickey 11/15/01 10:46 AM Page 10.3
2. For elevator motors, always try to get the full-load current because the nameplate
horsepower on many machines is about 10 to 25 percent below the actual rating.
3. For packaged-type evaporative condensers with many small fans nominally
rated 1 hp (for example), be sure to get the full-load current because these are
really equivalent to about 2 hp (for example) each, and feeders sized on nominal
horsepower ratings will be inadequate. Remember to size the feeder and over-
current protection as a multiple motor load. Also refer to NEC Article 440.
4. Note that maximum and minimum have precise meanings and that feeder
sizes shall not be less than the calculated minimum within 3 or 4 percent (e.g.,
30-A-rated no. 10 wire is OK for a 31-A load) and breaker sizes shall not be
more than the maximum indicated. In general, for larger motor sizes, the over-
current protection needed decreases considerably from the maximum limit.
5. In sizing nonfused disconnects for motors, use the horsepower rating table in the
manufacturer’s catalog or realize that, in general, a nonfused disconnect switch
should be rated the same as a switch fused with a dual-element time-delay fuse.
6. When sizing feeders for tape drives in mainframe data centers, it is usually
necessary to oversize both the overcurrent protection and the feeder to accom-
modate the long acceleration time characteristic of this equipment.
7. Today’s highly energy-efficient motors are characterized by low losses and high
inrush currents, thus requiring overcurrent protection sized at or near the
maximum limit prescribed by the NEC when these motors are used.
8. For NEC locked-rotor-indicating code letters, refer to Table 10.1.2 [NEC Table
430.7(B)].
TABLE 10.1.2
(© 2001, NFPA)
TABLE 10.1.4
CH10_Hickey 11/15/01 10:46 AM Page 10.5
TABLE 10.1.5
CH10_Hickey 11/15/01 10:46 AM Page 10.6
TABLE 10.1.6
TABLE 10.1.7
CH10_Hickey 11/15/01 10:46 AM Page 10.7
TABLE 10.1.8
TABLE 10.1.10
TABLE 10.1.11