35/11kV
COPPER XLPE 3C
HEAVY DUTY SCREEN
APPLICATION
STANDARD
AS/NZS 1429.1:2000
VOLTAGE
6350/11000V
CONDUCTOR
INSULATION
TR-XLPE
Numbered Cores
SCREEN
SHEATH
PVC, 5V-90 or
PVC, 5V-90 / HDPE
90 C
Conductor
Overall Diameter
Approximate
Mass
Bending Radius
Minimum
Minimum
Installed
During
Installation
mm
mm
PVC
HDPE
PVC
HDPE
mm2
No of
strands
Minimum
mm
Maximum
mm
kg/km
16
25
7
7
38.5
42.0
46.0
49.0
1360
1825
560
590
690
740
830
890
1150
1230
35
44.0
51.0
2250
620
770
920
1280
50
19
46.5
53.5
2815
650
810
970
1340
70
19
50.0
57.5
3720
670
870
1040
1440
95
19
54.0
61.5
4760
740
930
1110
1540
120
19
57.5
65.0
5565
780
980
1170
1630
150
19
61.0
68.0
6430
820
1020
1230
1700
185
37
64.5
72.0
7590
870
1080
1300
1800
240
37
70.0
77.5
9500
930
1170
1400
1940
300
37
76.0
83.5
11450
1010
1260
1510
2010
4.2.11.6.3.3.3
CONDUCTOR
Nominal Area
mm
16
25
35
50
70
95
120
150
185
240
300
A
100
125
155
195
235
285
330
375
430
500
575
A
115
140
170
215
260
300
345
385
435
495
565
A
100
130
155
185
220
265
300
340
380
440
495
3.0
3.8
5.1
7.3
10.1
13.1
13.1
13.1
13.1
13.1
13.1
2.4
2.2
2.1
2.0
1.9
1.9
1.8
1.8
1.7
1.7
1.6
Max. DC
Resistance
@ 20C
ohm/km
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
4.9
6.1
7.0
8.1
9.8
11.4
12.9
14.3
16.0
18.4
20.8
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
14.2
15.5
16.3
17.4
19.1
20.7
22.3
23.7
25.3
27.7
30.2
17.1
18.4
19.2
20.3
22.0
23.6
25.2
26.6
28.2
30.6
33.1
Diameter over
Insulation Screen
SCREEN
Number &
Nominal Area
Diameter
Total 3 Cores
of Wires
per Core
mm2
12
15
20
29
40
52
52
52
52
52
52
x
x
x
x
x
x
x
x
x
x
x
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
20.4
25.0
35.0
50.0
68.0
88.5
88.5
88.5
88.5
88.5
88.5
4.2.11.6.3.3.3
mV/A.m
2.56
1.62
1.18
0.88
0. 62
0.46
0.38
0.32
0.27
0.23
0.20
Maximum
mm
16
25
35
50
70
95
120
150
185
240
300
F/km
0.20
0.22
0.24
0.27
0.30
0.34
0.37
0.40
0.43
0.48
0.53
(b)- For fault durations other than one second, divide the appropriate given
value by the square root of the required time (in seconds).
Minimum
mm
mm2
ohm/km
0.137
0.126
0.117
0.112
0.106
0.100
0.0969
0.0943
0.0914
0.0882
0.0858
mm
Nominal
Diameter
ohm/km
1.47
0.927
0.668
0.494
0.342
0.247
0.196
0.159
0.127
0.0986
0.0798
3 Phase
Voltage
Drop
(a)- Based on 40C ambient air temperature and where applicable, burial depth
CONDUCTOR
Min.Average
Insulation
Thickness
mm
Nominal Area
ELECTRICAL CHARACTERISTICS
Max. AC
Equivalent
Capacitance
Resistance
Star
@ 90C
Reactance
Diagrams of cables are illustrative only and are not necessarily to scale.
General Cable New Zealand Limited and General Cable Australia Pty Ltd reserves the
right to change or vary the construction of any of their products without notice. Whilst
every care has been taken in the preparation of this publication, General Cable New
Zealand Limited and General Cable Australia Pty Ltd accept no liability of any kind and
are not responsible for the results of any actions taken on the basis of this information or
resulting from errors or omissions. This technical data sheet is intended as a guide only;
any person using it must make reference to the appropriate local standards or authorities.
All rights reserved. No part of this work covered by copyright may be reproduced or
copied in any form or by any means without the written permission of General Cable
New Zealand Limited. or General Cable Australia Pty Ltd.
2001.