COPPER XLPE 3C
HEAVY DUTY SCREEN

APPLICATION

STANDARD

AS/NZS 1429.1:2000

Primary supply to urban networks. Suitable unenclosed where


not subject to mechanical damage, buried direct or in underground
ducts. For systems having high lt fault values.

VOLTAGE

6350/11000V

CONDUCTOR

Compacted Annealed Copper

Suitable for glanding.

INSULATION

TR-XLPE
Numbered Cores

Heavy Duty Screen A minimum screen fault rating of


13.1kA for 1 second but not exceeding the conductor rating or a
minimum coverage allowable in standard.

SCREEN

Annealed Copper Wire


Heavy Duty

SHEATH

PVC, 5V-90 or
PVC, 5V-90 / HDPE

MAX. OPERATING TEMP.

90 C

Conductor

Overall Diameter

Approximate
Mass

Bending Radius
Minimum
Minimum
Installed
During
Installation
mm
mm
PVC
HDPE
PVC
HDPE

mm2

No of
strands

Minimum
mm

Maximum
mm

kg/km

16
25

7
7

38.5
42.0

46.0
49.0

1360
1825

560
590

690
740

830
890

1150
1230

35

44.0

51.0

2250

620

770

920

1280

50

19

46.5

53.5

2815

650

810

970

1340

70

19

50.0

57.5

3720

670

870

1040

1440

95

19

54.0

61.5

4760

740

930

1110

1540

120

19

57.5

65.0

5565

780

980

1170

1630

150

19

61.0

68.0

6430

820

1020

1230

1700

185

37

64.5

72.0

7590

870

1080

1300

1800

240

37

70.0

77.5

9500

930

1170

1400

1940

300

37

76.0

83.5

11450

1010

1260

1510

2010

Lengths and packing can be supplied to customers requirements.


For glanding details, contact your local service centre.
NB: Stranding in compacted conductors may be subject to minor variations.

4.2.11.6.3.3.3

CONDUCTOR
Nominal Area

mm
16
25
35
50
70
95
120
150
185
240
300

CURRENT RATING (a))


Unenclosed Buried Direct
Buried In
In Air
Ducts (c)

A
100
125
155
195
235
285
330
375
430
500
575

A
115
140
170
215
260
300
345
385
435
495
565

A
100
130
155
185
220
265
300
340
380
440
495

ELECTRICAL CHARACTERISTICS (CONT.)


1 Sec Fault Rating(b)
Max.
Stress
3 Phase
Screen
Symmetrical
kV/mm
kA
kA
2.3
3.6
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9

3.0
3.8
5.1
7.3
10.1
13.1
13.1
13.1
13.1
13.1
13.1

2.4
2.2
2.1
2.0
1.9
1.9
1.8
1.8
1.7
1.7
1.6

Max. DC
Resistance
@ 20C

ohm/km
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601

Screen fault ratings are based on an initial temperature of 80C and a


final temperature of 250C.
Conductor fault ratings are based on an initial temperature
of 90C and a final temperature of 250C.

4.9
6.1
7.0
8.1
9.8
11.4
12.9
14.3
16.0
18.4
20.8

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

14.2
15.5
16.3
17.4
19.1
20.7
22.3
23.7
25.3
27.7
30.2

17.1
18.4
19.2
20.3
22.0
23.6
25.2
26.6
28.2
30.6
33.1

Diameter over
Insulation Screen

SCREEN
Number &
Nominal Area
Diameter
Total 3 Cores
of Wires
per Core
mm2
12
15
20
29
40
52
52
52
52
52
52

x
x
x
x
x
x
x
x
x
x
x

0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85

20.4
25.0
35.0
50.0
68.0
88.5
88.5
88.5
88.5
88.5
88.5

4.2.11.6.3.3.3

General Cable Australia Pty Ltd


Sales:
1300 363 282
Fax:
1300 363 382
www.generalcable.com.au

mV/A.m
2.56
1.62
1.18
0.88
0. 62
0.46
0.38
0.32
0.27
0.23
0.20

(c)- Based on a duct size of 150mm internal diameter.

Maximum
mm

16
25
35
50
70
95
120
150
185
240
300

F/km
0.20
0.22
0.24
0.27
0.30
0.34
0.37
0.40
0.43
0.48
0.53

(b)- For fault durations other than one second, divide the appropriate given
value by the square root of the required time (in seconds).

Minimum
mm

mm2

ohm/km
0.137
0.126
0.117
0.112
0.106
0.100
0.0969
0.0943
0.0914
0.0882
0.0858

of 0.8m, soil temperature of 25C and thermal resistivity of 1.2Cm/W.

mm

Nominal
Diameter

ohm/km
1.47
0.927
0.668
0.494
0.342
0.247
0.196
0.159
0.127
0.0986
0.0798

3 Phase
Voltage
Drop

(a)- Based on 40C ambient air temperature and where applicable, burial depth

CONDUCTOR
Min.Average
Insulation
Thickness
mm

Nominal Area

ELECTRICAL CHARACTERISTICS
Max. AC
Equivalent
Capacitance
Resistance
Star
@ 90C
Reactance

Diagrams of cables are illustrative only and are not necessarily to scale.
General Cable New Zealand Limited and General Cable Australia Pty Ltd reserves the
right to change or vary the construction of any of their products without notice. Whilst
every care has been taken in the preparation of this publication, General Cable New
Zealand Limited and General Cable Australia Pty Ltd accept no liability of any kind and
are not responsible for the results of any actions taken on the basis of this information or
resulting from errors or omissions. This technical data sheet is intended as a guide only;
any person using it must make reference to the appropriate local standards or authorities.
All rights reserved. No part of this work covered by copyright may be reproduced or
copied in any form or by any means without the written permission of General Cable
New Zealand Limited. or General Cable Australia Pty Ltd.
2001.

Das könnte Ihnen auch gefallen