Beruflich Dokumente
Kultur Dokumente
2, MARCWAPRIL 1994
485
I. INTRODUCTION
ITH THE ever-increasing use of electronic office
equipment, such as personal computers, laser printers,
and photocopiers, that utilize non-sinusoidal power supplies, the typical Delta-Wye connected power distribution
transformer is being subjected to excessive internal heating.
The distorted current waveform, rich in harmonics, produces
additional heating in the transformer core and coils. This nonlinear load heat factor, along with the normal temperature rise
that accompanies transformers under load, causes pre-mature
insulation breakdown and subsequent loss of transformer
longevity.
The transformer manufacturer response to these heating
problems has been to redesign the power distribution transformer. This new generation of transformers designed for
operation in a non-sinusoidal load environment minimizes the
eddy-current losses. Design changes to minimize losses include enlarging the primary winding to withstand the inherent
triplen harmonic circulating currents, doubling the secondary
neutral conductor to carry the triplen harmonic currents, designing the magnetic core with a lower normal flux density
by using higher grades of iron, and using smaller, insulated
secondary conductors wired in parallel and transposed to
reduce the heating from the skin effect and associated AC
resistance [ 5 ] .
Several methods of estimating the additional heat created
by non-sinusoidal loads are available to electrical designers,
but only one method portrays the effects of individual harmonic currents. This paper examines these available methods
and asserts that only one is acceptable for compliance with
Paper ICPSD 93-33, approved by the Rural Electric Power Committee
of the IEEE Industry Applications Society and presented at the 1993 Rural
Electric Power Committee Technical Conference. Manuscript approved for
publication August 11, 1993.
The author is with the United States General Services Administration,
Public Buildings Service, Design and Construction Division, Kansas City,
MO 64131-3088 USA.
IEEE Log Number 9216406.
Presently, three methods of estimating harmonic load content are practiced. The Crest-Factor and Harmonic Factor, or
Percent Total Harmonic Distortion, (%THD), are the two most
common methods of harmonic estimation. The third method,
the K-Factor, is the most complex, but the most meaningful.
The following is a brief introduction into these three methods
and an explanation of the accuracy and usefulness of each.
A. Crest Factor
B. %THD
The %THD is a ratio of the root-mean-square (RMS) value
of the harmonics to the RMS value of the fundamental. In
equation form, the definition of %THD is
%THD is a measure of the additional harmonic current contribution to the total RMS current. It is derived from a similar
486
Transformer winding eddy-current losses increase in proportion to the square of the load current and the square of
the frequency [ 11. It is this exponential characteristic that
results in tremendous heat in transformers supplying nonsinusoidal currents and causes abnormal winding temperature
rise. In order to accurately model the additional heating that
harmonic loads generate within transformers, the frequency of
the harmonics must be considered.
The crest factor is the ratio of the current peak magnitude
divided by the true RMS current magnitude. It is a measure of
waveform distortion, or waveform variance from the expected
value of 1.414. The %THD is, by definition, a measure of
current waveform distortion. Both the crest factor and the
%THD are useful when initially establishing whether harmonic
current distortion is present. But because harmonic frequency
is not taken into consideration, these two estimation techniques
are not adequate when specifying equipment for operation in
a harmonic load environment.
In order to model the exponential heating effects of harmonic load currents, frequency must be considered [6]. The
K-Factor is the only harmonic content estimation technique
available that takes harmonic frequency into account [6].
D. K-Factor
487
a""
p
Y
3
5
2
I 50 0
OI
50
"""I
300
200
100
0
1
13
17
Fig. 1.
0
2
Fig. 3.
:._:::4
3
11
13
15
17
19
21
23
K FACTOR
IEH
=
25
29
33
37
41
45
200
100 1
21
K FACTOR
K FACTOR
{
E
) (4)
( K - h2)
where IEH
is expressed as Harmonic Amperes, HA, K is the
K-Factor as calculated by Equation (3), and h2 is the square
of the harmonic number. The derivation of this equation is
shown in [ 6 ] .Examining the graphs of Equation (4) will help
to determine which harmonic index can be confidently applied
in determining total harmonic load current of differing loads.
Fig. 1 represents the relationship Equation (4) demonstrates
when h = 3. The 3 r d harmonic index reaches an infinite value
at K = 9 and is undefined for values of K > 9. Since standard
transformer K-ratings are available as high as K-50, the 3rd
harmonic is useless as a harmonic index for several K-Factors
between K = 9 and K = 50.
Fig. 2 represents the relationship Equation (4) demonstrates
when h = 5. The 5th harmonic index reaches an infinite value
at K = 25 and is undefined for values of K > 25. Again,
since standard K-ratings are available as high as K-50, the 5th
harmonic is useless as a harmonic index for several K-Factors
between K = 25 and K = 50.
Fig. 3 represents the relationship Equation (4) demonstrates
when h = 7. The 7th harmonic index reaches an infinite value
at K = 49 and is undefined for values of K > 49. Since the
index cut-off of 49 is approximately the highest available Krating, K-50, the 7th harmonic is a reasonable choice for the
Equivalent Harmonic Current Index. The majority of standard
available K-ratings are governed by the linear portion of the
curve between K = 2 and K = 40. Thus, the 7th harmonic
current index has the most useful relationship with K-Factor
in the development of a weighted sum approach to supplying
multiple non-linear loads with a single transformer [ 6 ] .
IEH
=
{M
(K - 49) x 100
x 100 = 123.54 HA
IEH(K-~
= ~ ) (' - 13) x 100 = 57.74 HA
~
(13 - 49)
(6)
(8)
The third step is to calculate the weighted sum of the KVAEquivalent Harmonic Current factor for the various types of
loads and add them together. This is determined by multiplying
the nameplate load KVA by the Equivalent Harmonic Current
determined above for each type of load. The resulting values
488
is required.
Power Transformers, along with being tested for the addiThis weighted sum method for determining the resultant tional heating under non-sinusoidal load conditions [9]. The
system load K-rating is the most practical approach available listing for Power and General Purpose Transformers, Dry ripe
to specify transformers supplying several different non-linear (XQNX), states, in part, that, Transformers that have been
and linear loads [6]. This simple expansion of the IEEE evaluated for use where significant non-sinusoidal current is
recommendations for specifying transformers serving non- present are marked, Suitable for non-sinusoidal current load
sinusoidal loads is easy to implement and will prevent costly with K-Factor not to exceed -, where the blank is filled in
over-design.
with one of the standard K-Factor ratings of 4, 9, 13, 20, 30,
40, or 50 [9].
Iv. CODES AND STANDARDS
Since UL tests transformers for suitability in supplying nonK-Factor transformers, because of their special design to sinusoidal load current, lists, and labels these transformers as
minimize losses due to harmonics, are more expensive than K-Factor transformers, electrical engineers must calculate
traditionally designed transformers. Some electrical designers a K-Factor for the distribution system and must select Kcontend that K-rated transformers are undesirable due to this rated transformers for all non-siwsoidal operating conditions
added expense. The selection of a derated 225 or 300 KVA to fulfill the listing and labeling requirements of Underwriters
transformer that is not K-rated in lieu of the K - 20, 150 Laboratory and the safety requirements of the 1993 National
KVA transformer would be acceptable. That trade-off is not Electrical Code [6].
acceptable according to the applicable codes and standards that
govem electrical design and installation.
Frequency must be taken into consideration for an accurate
V. CONCLUSION
estimation of the additional heat non-sinusoidal loads inflict
upon transformers [ 11. Only the K-Factor considers the harNon-sinusoidal loads cause accelerated loss of insulation
monic magnitude and frequency. Because of these two facts, life in power distribution transformer windings because of the
the K-Factor is the only acceptable method for estimating har- exponential heating effects of high frequency harmonics. Of
monic content and for specifying distribution transformers for the available methods of calculating the additional heating
use under non-linear load conditions according to ANSI, IEEE, associated harmonic currents, only the K-Factor produces
the 1993 National Electrical Code, (NEC), and Underwriters results acceptable for specifying non-sinusoidal, K-Factor
transformers as required by the National Electrical Code and
Laboratory, (UL) [ 6 ] .
Although the 1993 NEC does not address the issue of Underwriters Laboratories. For practical applications, the K harmonic load currents directly, the requirement for K-Factor Factor can be expanded and adapted to account for multiple
are listed below:
REFERENCES
ANSILEEE Srd (257.1 10-1986: American National Standard Recommended Practice for Establishing Transformer Capability When Supplying Non-Sinusoidal Load Currents.
CBEMA Information Letter, CEEMA, E X - 3 Committee, November
1987.
Freund, Arthur, Double the Neutral and Derate the Transformer Or
Else!, Electrical Construction and Maintenance, March 1988.
IEEE Srd 519-1981: IEEE Guide for Harmonic Control and Reactive
Compensation of Static Power Converters.
I. Kerszenbaum, A. Mazur, M. Mistry and J. Frank Specifying DryType Distribution Transformers for Solid-State Applications, IEEE
Trans. Indusrry Applicat., Vol. 27, No. 1, Januarykbruary 1991.
489
~ Laboratory,
~
~