Jubail Export Refinery

Material Specifications

JERMS-D-3205
Manufacture of
Atmospheric Tanks

Revision
2

Responsibility
JER Engineering Division

4 November
2008

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Revision Tracking
Revision

Revision Date

4 November 2008

Revised to update paragraphs: 3.1, 13.1.1, 8.3.2, 14.1.


Adding references: JERES-H-001, JERES-H-002 & JERES-H-005

2 October 2008

Revised to update par. 3.1, 8.6.8.2; Par. 10.1.2 and 13.1.1 and 14.3

29 April 2008

Issued for bid package.

03

14 April 2008

For adjusting formatting

02

31 March 2008

Issued for bid package. Only for Review

01

03 August 2007

The first official JERMS-D-3205 is issued

00

08 February
2007

First draft issued is based on Saudi Aramco 32-SAMSS-005


Manufacture of Atmospheric Tanks issue date 31 December, 2003.
Document was modified to incorporate amendments and modifications.

1A

Scope of Revision

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 2 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Table of Contents
Section

Contents

Page

Scope

Conflicts, Deviations and Clarifications

References

Definitions

Introduction Note

(1) Scope

Materials

Design

10

Fabrication

17

10

Erection

17

11

Methods of Inspecting Joints

22

12

Welding Procedure and Welder Qualifications

23

13

Marking

23

14

Coatings and Painting

24

15

Documentation

24

16

Disinfection

24

Appendixes

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 3 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Recommendations for Design and Construction of Foundation


for Aboveground oil Storage Tanks

26

External Floating Roofs

27

Structurally Supported Aluminum Dome Roofs

31

Internal Floating Roofs

33

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 4 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Scope
This standard covers the minimum mandatory requirements that shall be used as the
basis for developing detailed design and construction of foundations for storage
tanks.

Conflicts, Deviations and Clarifications

2.1

Any conflicts between this standard and other applicable Company Engineering
Standards (JERES), Material Specifications (JERMS), Standard Drawings (JERSD),
Engineering Procedures (JEREP), Company Forms or Industry standards,
specifications, Codes and forms shall be brought to the attention of Company
Representative by the Contractor for resolution.
Until the resolution is officially made by the Company Representative, the most
stringent requirement shall govern.

2.2

Where a licensor specification is more stringent than those of this standard, the
Licensors specific requirement shall apply.

2.3

Where applicable Codes or Standards are not called by this standard or its
requirements are not clear, it shall be brought to attention of Company
Representative by Contractor for resolution.

2.4

Direct all requests for deviations or clarifications in writing to the Company or its
Representative who shall follow internal Company procedure and provide final
resolution.

References
The selection of material and equipment, and the design, construction, maintenance,
and repair of equipment and facilities covered by this standard shall comply with the
latest edition of the references listed below as of the CUT-OFF DATE as specified
in the Contract unless otherwise noted.

3.1

Company References
Company Engineering Standards
JERES-A-007

Hydrostatic Testing Fluids and Lay-Up Procedures

JERES-A-112

Meteorological and Seismic Design Data

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 5 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

JERES-A-206

Positive Material Identification

JERES-B-017

Fire Water System Design

JERES-B-018

Air Foam Systems for Storage Tanks

4 November 2008

JERES-H-001

Coating Selection & Application Requirements for Industrial


Plants & Equipment.

JERES-H-002

External Coatings for Buried Steel Piping and Pipelines

JERES-H-005

Internal Coating for Vessels, Tanks and Equipment

JERES-J-300

Level

JERES-J-600

Pressure Relief Devices

JERES-W-017

Welding Requirements for API Tanks

Company Materials Specifications


JERMS-G-3217

Side-Entry Mixers

JERMS-H-9107

Qualification Requirements and Application of Composite


Fluropolymer/Ceramic Coatings to Fasteners

JERMS-J-4319

Radar Tank Gauging Equipment

Company Standard Drawings


JERSD-D-0001

Manholes and Vents for Tanks

JERSD-D-0002

Roof Center Vent for Cone-Roof Tanks

JERSD-D-0003

Radar, Temperature and Manual Gauging Assembly for


Floating Roof Tanks

JERSD-X-0013

Half Shell Bracelet Type Anode for Pipe Sizes 4-60 Inch

JERSD-P-0003

Tank Grounding

JERSD-D-0004

General Assembly of Gauge well for External Floating Roof


Tanks

Company Inspection Requirements


JERITP-D-324900

Tanks: Atmospheric, Steel within the Scope of JERMS-D-3205

Company Forms and Data Sheets


Form NMR-7918-1

Nonmaterial Requirements for Tanks

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 6 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

Form NMR-7918-2
3.2

4 November 2008

Nonmaterial Requirements for Floating and Internal Floating


Roofs

Industry Codes and Standards


American Petroleum Institute
API STD 650

Welded Steel Tanks for Oil Storage

API STD 2000

Venting Atmospheric and Low-Pressure Storage Tanks

API RP 2003

Protection Against Ignitions Arising Out of Static, lightning,


and Stray Currents

American Society of Mechanical Engineers (Boiler and Pressure Vessel Code)


ASME B16.11

Forged Fittings, Socket-Welding and Threaded

ASME SEC V

Nondestructive Examination

National Fire Protection Association


NFPA 68

Guide for Venting of Deflagration

NFPA 255

Standard Method of Test of Surface Burning Characteristics of


Building Materials

American Water Works Association


AWWA C652

Disinfection of Water Storage Facilities

Definitions

4.1

Definitions presented in this Standard and other JER documents have precedence
over other definitions. Conflicts between various definitions shall be brought to the
attention of Company Representative by the Contractor for resolution.
Company: Jubail Export Refinery.
Company Representative: A designated person from the Company or an assigned
third party representative.
Company Inspector: A designated person or an agency responsible for conducting
inspection activities on behalf of the Company.

4.2

List of Definitions

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 7 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Design Engineer: The Engineering Company responsible for specifying the design
requirements on the Storage Tank Data Sheet.
Design Metal Temperature: The lowest of the following temperature values:
1)

The lowest one-day mean atmospheric temperature (LODMAT) per JERES-A112, or

2)

The minimum operating temperature, or

3)

The hydrostatic test temperature

Tank Manufacturer: The Company responsible for the design and fabrication of
tanks.

Introduction Note
The API STD 650, Third Edition, September 2003, is part of this specification. The
text in each paragraph below is an addition, deletion or exception to API STD 650 as
noted in parenthesis. Paragraph numbers not appearing in API STD 650 are newly
added paragraphs inserted in numerical order. For these new paragraphs there is no
addition, deletion or exception wordings in parenthesis.
The API STD paragraph numbers are indicated in parenthesis.
Only the paragraphs of the API STD 650 that have been modified (by addition,
deletion or exception) by this standard are mentioned. The other API STD 650
paragraphs that are not mentioned in this standard remain applicable.

(1) Scope

6.1

(1.1)

6.1.2

(1.1.6) Appendix B and all other pertinent requirements of this specification shall be
used as the basis for developing detailed design and construction of foundations for
storage tanks.

6.1.3

(1.1.7)
Additional requirements for external floating roofs are contained in
Appendix C of this specification.

6.1.4

(1.1.11)
Additional requirements for optional self-supporting aluminum dome
roofs are contained in Appendix G of this specification.

General

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 8 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

6.1.5

(1.1.12)
Additional requirements for internal floating roofs are contained in
Appendix H of this specification.

6.1.6

(1.1.23)
This specification shall be attached to and form an integral part of a
purchase order.

6.2

(1.3 )Compliance

6.2.1

(1.3.1)
Any conflicts between this standard and other applicable Company
Engineering Standards (JERESs), Materials Specifications (JERMSs), Standard
Drawings (JERSDs), or industry standards, codes, and forms shall be resolved in
writing by the Company Engineering Manager.
Until the resolution is officially made by the Company Engineering Manager, the
most stringent requirement shall govern.
Direct all requests to deviate from this standard in writing to the Company
Representative, who shall follow internal Company procedure.

6.2.2

(1.3.2)
Direct all requests to deviate from this specification in writing to the
Company Representative.

6.2.3

(1.4)Referenced Publications
Materials or equipment supplied to this specification shall comply with the latest
edition of the references listed below and those referenced in API 650, unless
otherwise noted.

(2) Materials

7.1

(2.1)

7.1.1

(2.1.1)
The Tank Manufacturer shall submit a complete material specification
with the proposal.

General

The Tank Manufacturer may propose the use of alternative materials to those that are
listed in API STD 650. The alternative materials shall comply with all the other
requirements of API STD 650 and this specification. The chemical compositions
and mechanical properties of non-ASTM materials shall be submitted to the
Company Representative for approval.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 9 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Materials proposed by the Tank Manufacturer that are equivalent to those specified
in API STD 650 shall be approved by the Company Representative.
7.1.2

(2.1.2)

Exception

All materials shall be clearly identified and provided with mill test certificates.
Materials shall be alloy-verified by the Tank Manufacturer in accordance with
JERES-A-206.
7.1.3

(2.2)

Plates

7.1.4

(2.2.1)

General

7.1.5

(2.2.1.5) Annular plate material shall be of the same material group per API STD
650 as the lowest shell course.

7.1.6

(2.2.1.6)
plates.

Rimmed and capped steels shall not be used for shell, bottom and roof

7.1.7

(2.2.9.3)

Exception

The design metal temperature as defined in paragraph 1.5 of this specification shall
be used as the basis for impact test exemption of Figure 3.1 of API STD 650.
7.2

(2.7)

Bolting

Flange bolting material shall conform to A193 Grade B7 bolts with A194 Grade 2H
nuts. All bolting shall be coated with a fluoropolymer/ceramic coating in accordance
with JERMS-H-9107.
7.3

(2.9)

Gaskets

Gasket materials shall be non-asbestos.

(3) Design

8.1

(3.1)

Joints

8.1.1

(3.1.3)

Restrictions on Joints

8.1.2

(3.1.3.5) Lap-welded joints shall be lapped at least five times the nominal
thickness of the thinner plate joined; however, with double-welded lap joints, the lap

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 10 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

need not exceed 50 mm (2 in.), and with single-welded lap joints, the lap shall not be
less than 25 mm (1 in.).
8.1.3

(3.1.5)

Typical Joints

8.1.4

(3.1.5.3a) Exception
Top angles shall be attached to the shell by butt welds with complete penetration and
complete fusion.

8.2

(3.2) Design Considerations

8.2.1

(3.2.6)
Information provided by the Design Engineer on the API STD 650
Storage Tank Data Sheet and a completed Company Form 2696-ENG shall be used
for the tank design in accordance with API STD 650 and this specification.

8.2.2

(3.2.7)

Nozzle Loads

8.2.3

(3.2.7.1)

Associated piping systems loads shall be specified on the tank data sheet.

8.2.4

(3.2.7.2) Tank Manufacturer shall ensure that stresses at nozzle-to-tank


connections, due to piping loads specified on the tank data sheet, are within the
allowable limits.

8.3

(3.3)

Special Considerations

8.3.1

(3.3.4)

Weld Hardness

Weld hardness testing requirements and acceptance criteria shall be in accordance


with JERES-W-017.
8.3.2

(3.3.5)
A foundation drip ring shall be provided in order to prevent the ingress
of rainwater or condensation between the tank bottom and foundation. The ring shall
meet the following requirements.
1)

Material shall be carbon steel, 3.2 mm (1/8 inch) thick.

2)

Continuously seal welded to the edge of the tank bottom or annular plate. All
radial joints between the drip ring sections shall also be seal welded.

3)

Extend at least 75 mm (3 inch) beyond the outer periphery of the concrete ring
wall.

4)

Turn down at its outer diameter at a 45-degree angle.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 11 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

5)

Manufacture of Atmospheric Tanks

4 November 2008

The top of the drip ring and a 75 mm (3 inch) height of the tank shell shall be
painted with a 250-300 microns (10-12 mils) thick epoxy coating in accordance
with JERES-H-001.

8.3.3

(3.3.6)

Under-tank leak detection and sub-grade protection

8.3.4

(3.3.6.1) Tanks in services other than water shall be provided with under tank leak
detection and sub-grade protection according to API STD 650, Appendix I.
Acceptable construction details are Figures I-1, I-2, I-3, I-6, I-7, I-8, I-9 and I-10.

8.3.5

(3.3.6.2) Flexible membrane leak-barrier (liner) of minimum 1000 microns (40


mils) thickness compatible with the stored product shall be specified under the tank
bottom. The liner shall be placed in accordance with JERSD-X-0013, extending to
the internal top edge of the ring foundation.

8.3.6

(3.3.6.3) Joints in the liner shall satisfy the leak tightness, permeability and
chemical resistance requirements for the liner material.

8.3.7

(3.3.6.4) Alternative under-tank leak detection and sub-grade protection systems


shall not be permitted without the prior approval of the Company Representative.

8.3.8

(3.3.7)
Reinforcing pads and all other external attachment pads shall have
rounded corners of minimum 50 mm (2 inch) radius. Pads that cover shell seams
shall be provided with a 6 mm telltale hole.

8.4

(3.4)

8.4.1

(3.4.4)
Tank bottom shall be sloped in accordance with the specification
provided on the Storage Tank Data Sheet.

8.4.2

(3.4.5)
Bearing plates shall be provided under all fixed roof support columns.
The bearing plates shall be twice the diameter of the column section with a minimum
356 mm diameter (14 inch), 12.7 mm (1/2 inch) thick, and shall be attached to the
bottom by 4.8 mm (3/16 inch) continuous fillet welds.

8.5

(3.6)

8.5.1

(3.6.5)
Design methods other than the one-foot method and the variable-designpoint method provided in API STD 650 shall be approved by the Company
Representative.

8.5.2

(3.7)

Bottom Plates

Shell Design

Shell Openings

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 12 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

8.5.3

(3.7.1)

General

8.5.3

(3.7.1.10) Number, size, type, and orientation of nozzles and manways shall be in
accordance with JERSD-D-0001 and as specified on the Storage Tank Data Sheet.

8.5.4

(3.7.6)

Shell Nozzles and Flanges

8.5.4

(3.7.6.4)

All shell nozzles shall be the API Low Type, unless otherwise specified.

8.6

(3.8)

Shell Attachments and Tank Appurtenances

8.6.1

(3.8.2)

Bottom Connections

When specified, bottom connections shall be designed in accordance with API STD
650, Appendix O.
Connections shall be fabricated from elbows; miter joints are prohibited.
Vortex breakers shall be provided for bottom connections.
8.6.2

(3.8.5)

Roof Nozzles

8.6.3

(3.8.5.3)
service.

All open vents shall be protected by bird screens, except those in asphalt

8.6.7

(3.8.9)

Threaded Connections

Threaded and socket welded connections shall be in accordance with ASME B16.11.
8.6.8

(3.8.10)

Platforms, Walkways, and Stairways

8.6.8.1

(3.8.10.1) Type and location of stairway shall be as specified on the Storage Tank
Data Sheet and Company Form 2696-ENG.

8.6.8.2

(3.8.10.2) Gauger's platform in accordance with JERSD-D-0006 shall be provided


for external floating roof tanks.

8.6.8.3

(3.8.10.3) Stairs and platforms shall be fabricated of open grating. Checker-plate


grating is not permitted.

8.6.8.4

(3.8.10.4) Walkways shall be fabricated of diamond-pattern (checker-plate) grating


with anti-skid paint.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 13 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

8.6.8.5

(3.8.10.5) Stairways on insulated tanks shall be provided with stringers on both


sides.

8.6.9

(3.8.11)

8.6.9.1

(3.8.11.1) Floating suction lines shall be provided, when specified on the Storage
Tank Data Sheet.

8.6.9.2

(3.8.11.2) Floating suction lines using rigid pipe shall be designed to prevent them
from being raised past the vertical axis.

8.6.9.3

(3.8.11.3) Floating suction lines using articulated pipe shall be designed so that the
tip of the suction line is always on the axial centerline of the tank throughout its total
travel.

8.6.10

(3.8.12)

Floating Suction Lines

Inlet Diffusers

8.6.10.1 (3.8.12.1) An inlet diffuser shall be provided for tanks with internal floating roofs.
The inlet diffuser shall be sized based on the maximum pumping in rate and the
maximum permissible exit velocity through the slots in the diffuser.
8.6.10.2 (3.8.12.2) The diffuser shall be slotted. The slots shall be located at 60 degrees (2
o'clock and 10 o'clock positions) from the vertical centerline of the diffuser.
8.6.10.3 (3.8.12.3) Number and dimensions of slots shall be calculated so that the exit
velocity does not exceed 1 m/sec (3.28 ft/sec) at the maximum inlet flow until there
is a minimum of 1m of liquid cover over the inlet.
8.6.11

(3.8.13)

Mixers

8.6.11.1 (3.8.13.1) Number and type of mixers shall be as specified on the Storage Tank
Data Sheet.
8.6.11.2 (3.8.13.2) Side-entry propeller mixers shall be designed, inspected, and tested in
accordance with JERMS-G-3217.
8.6.11.3 (3.8.13.3) Nozzles for side-entry mixers shall be designed in accordance with API
STD 650 for manways. Supports for the mixer may be needed to maintain stresses at
the nozzle-to-shell junction within the allowable limits.
8.6.11.4 (3.8.13.4) Jet-nozzle mixers shall not be used in tanks with internal floating roofs
on floats.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 14 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

8.6.12

(3.8.14)

Manufacture of Atmospheric Tanks

4 November 2008

Foam and Water Systems

Fire or cooling water and foam systems shall be provided in accordance with JERESB-017 and JERES-B-018, respectively, when specified on the Storage Tank Data
Sheet.
8.6.13

(3.8.15)

Gauging

8.6.13.1 (3.8.15.1) External-floating roofs shall be provided with a radar gage assembly in
accordance with JERSD-D-0003 and JERES-J-300.
8.6.13.2 (3.8.15.2) External floating roof tanks shall be provided with a radar liquid level
gauge in accordance with JERMS-J-4319, located adjacent to the gauger's platform.
The top of the gauge piping shall be located from 150 mm (6 inch) to 300 mm (12
inch) above the platform handrail and approximately 150 mm (6 inch) horizontally
from the gauger's platform for easy maintenance access.
8.6.13.3 (3.8.15.3) Fixed-roof tanks shall be provided with a radar gauge assembly.
8.6.14

(3.8.16)

Grounding

8.6.14.1 (3.8.16.1) Tanks in hydrocarbon services shall be provided with grounding lugs in
accordance with JERSD-P-0003 at a minimum of four points spaced equidistantly
around the base of the tank.
8.6.14.2 (3.8.16.2) The design of bonding shunts between the tank shell and the roof shall
be in accordance with JERSD-P-0003 and API RP 2003 requirements.
8.7

(3.9)

Top and Intermediate Wind Girders

8.7.1

(3.9.4)

Stiffening Rings as Walkways

Top wind girders, when specified as walkways, shall be located 1067 mm (42 inch)
from the top of the tank.
8.7.2

(3.9.7)

Intermediate Wind Girders

8.7.2.1

(3.9.7.1) The minimum required thickness for the design condition, excluding
corrosion allowance, shall be used to calculate the maximum height of unstiffened
shell.

8.8

(3.10)

Roofs

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 15 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

8.8.1

(3.10.2)

General

8.8.1.1

(3.10.2.1) Type of roof shall be as specified on the Storage Tank Data Sheet.

8.8.1.2

(3.10.2.9) When an internal coating is specified for a fixed roof, a self-supported


roof shall be used, and the roof lap joints shall be continuously welded on both sides.
For internal tank walls, surface preparation, painting, and coating specifications shall
be selected in accordance with JERES-H-005.

8.8.2

(3.10.4)

Supported Cone Roofs

8.8.2.1

(3.10.4.6) Exception
Only welded joints are permitted for all structural attachments in the roof supporting
system other than the following joints:

8.8.3

a)

Rafter clips for the outer row to the tank shell.

b)

Column-base clip guides to the tank bottom.

(3.10.5)

Self-Supporting Cone Roofs

Only welded joints are permitted for all structural attachments in the roof supporting
system.
8.8.4

(3.10.6)

Self-Supporting Dome and Umbrella Roofs

Only welded joints are permitted for all structural attachments roofs' supporting
systems in self-supporting roofs, except for self-supporting aluminum dome roofs.
8.8.5

(3.10.8)

Tank Venting

8.8.5.1

(3.10.8.1) Exception
Fixed roof tanks with internal floating roofs shall be treated as fixed roof tanks when
determining their venting requirements.
Commentary Note:
When circulation vents are not installed in fixed roof tanks with an internal floating roof,
individual designated venting devices/arrangement shall be provided for the fixed roof and
the internal floating roof according to venting requirements of API STD 2000 and this
specification.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 16 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

8.8.5.2

Manufacture of Atmospheric Tanks

4 November 2008

(3.10.8.3) Exception
Emergency venting capacity per API STD 2000 and explosion hatch per NFPA 68
shall be provided for API STD 650 fixed roof tanks. A frangible shell-to-roof joint
may be considered as an alternative to additional venting devices that are normally
provided to relieve excess pressure during emergency conditions for tanks of
diameters equal to or larger than 50 feet. Frangible shell-to-roof joint shall conform
to the requirements of API STD 650.

8.8.5.3

(3.10.8.4) Venting requirements shall be specified in accordance with API STD


2000, JERES-J-600, JERSD-D-0001 and JERSD-D-0002 and the requirements of
this specification.

(4) Fabrication

9.1

(4.1)

General

9.1.1

(4.1.1)

Workmanship

9.1.1.1

(4.1.1.3)

All flange bolt holes shall straddle the axial centerline of the tank.

9.1.2

(4.1.4)

Marking

9.1.2.1

(4.1.4.1) Marking shall be done with water soluble materials containing no


substances that would attack or harmfully affect the tank at both ambient and
operating temperature.

9.1.2.2

(4.1.4.2) Marking materials shall be free of lead, sulfur, zinc, cadmium, mercury,
chlorine or any other halogens.

9.1.3

(4.1.5)

Shipping

All flange faces and other machined surfaces shall be greased and properly protected
for shipping.
9.2

(4.2 )Shop Inspection

9.2.1

(4.2.3)
Company Inspector shall have the right to inspect the fabrication at any
state and to reject material or workmanship, which does not conform to the specified
requirements.

10

(5) Erection

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 17 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

10.1

(5.1)

General

10.1.1

(5.1.1)
The Tank Manufacturer shall check to ensure that the dimensional
tolerances of the tank foundation are satisfactory prior to start of erection.

10.1.2

(5.1.6)
The bottom side of the bottom plates shall be cleaned of all foreign
matter and grit-blast cleaned prior to being coated and placed in position for welding.
The topside surface of bottom plates, regardless whether coating is required or not,
shall also be grit-blast cleaned prior to welding. Surface preparation shall be
according Mfrs datasheet recommendation.

10.2

(5.2 )Details of Welding

10.2.1

(5.2.1)

General

10.2.1.1 (5.2.1.11) Documentation that details the welding sequences for the tank shall be
provided to Company prior to the start of field erection.
10.2.1.2 (5.2.1.12) All structural attachment welds to the tank shell, bottom, roof, and
appurtenances shall be continuously seal welded.
10.2.1.3 (5.2.1.13) All welds shall be free from coarse ripples, undercuts, grooves, overlaps,
abrupt ridges and valleys to avoid stress concentration points and interference with
interpretation of NDT results.
10.2.2

(5.2.2)

Bottoms

10.2.2.1 (5.2.2.4) Weld crowns of the bottom annular plate joints shall be ground flush at
the contact areas with the first shell course.
10.2.3

(5.2.4)

Shell-to-Bottom Welds

Exceptions
a)

Perform oil-penetrate leak test on the entire length of the first weld pass by applying
high flash point penetrant oil such as light diesel oil for a minimum 4 hours
(preferably overnight).

b)

Perform oil-penetrate leak test on the entire length of the first completed weld, before
welding the second fillet weld, by applying high flash point penetrant oil such as light
diesel oil for a minimum 4 hours (preferably overnight). Alternatively, apply a vacuum
test at 35 kPa gauge (5 psig), using a vacuum box fit to the shell-to-bottom junction.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 18 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2
c)

10.2.4

Manufacture of Atmospheric Tanks

4 November 2008

The inside fillet welds of the shell-to-bottom joint in a cylindrical flat-bottom tank
shall be examined by either the dye-penetrant or wet-fluorescent magnetic particle
method before hydrotest.

(5.2.5)

Roofs

10.2.4.1 (5.2.5.1) Internal floating roofs shall be installed in accordance with the
instructions provided by the internal floating roof manufacturer.
10.2.4.2 (5.2.5.2) Prior to the installation of fixed roof plates, roof 's column supports shall
be inspected for plumbness. Roof support columns with out-of-plumbness exceeding
1/200 of the total tank shell height shall be realigned.
10.2.4.3 (5.2.5.3) All internal clips, lugs, brackets etc. that are used temporarily for
construction purposes shall be removed from the roof supporting columns and shell
plates and ground flush and smooth prior to roof installation.
10.3

(5.3 )Inspection, Testing, and Repairs

10.3.1

(5.3.1)

General

10.3.1.1 (5.3.1.1) Inspection shall be in accordance with Company Inspection Requirement


JERITP-324900, JERES-W-017 and the following additional requirements.
10.3.1.2 (5.3.1.5) All required Nondestructive Examination shall be performed in
accordance with inspection procedures that are in complete compliance with ASME
SEC V and this specification. This written procedure shall address each inspection
method and technique used including acceptance criteria. When required by the
purchase order the procedure(s) shall be submitted to Company Inspection
Department for approval.
10.3.1.3 (5.3.1.6) All Nondestructive Examination, including Magnetic Particle and Liquid
Penetrant examinations, shall be performed by personnel certified or equivalent
National Certification Programs that has been approved by the Company Inspector.
Personnel responsible for interpretation of Nondestructive Examination results shall
be certified to a minimum of Level II.
10.3.1.4 (5.3.1.7) Prior to final inspection and pressure testing, the inside and outside of
the tank shall be thoroughly cleaned of all slag, scale, dirt, grit, weld spatter, paint,
oil, etc.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 19 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

10.3.1.5 (5.3.1.8) Company Inspector may reject the use of any materials, equipment, or
tools that do not conform to the specification requirements, jeopardize the safety of
personnel, or impose hazard or damage to Company property.
10.3.1.6 (5.3.1.9) Testing shall be in accordance with Company Inspection Requirements
Form 175-324900 and the following additional requirements.
10.3.2

(5.3.3)

Inspection of Tank Bottom Welds

Exception
Only vacuum box test method is permitted.

10.3.3

(5.3.5)

Testing of the Shell

10.3.3.1 (5.3.5.1) Tanks shall be hydrostatically tested by filling it with water of quality in
accordance with JERES-A-007 as follows:
1)

to the maximum design liquid level, H specified in API STD 650,

2)

for a fixed roof tank , to 50 mm (2 in.) above the weld connecting the roof plate
or compression bar to the top angle or shell; or

3)

to a level lower than that specified in items (a) or (b) when restricted by
overflow, an internal floating roof, or other freeboard.

10.3.3.2 (5.3.5.2) Hydrostatic testing duration shall be minimum 24 hours. The waterfilling rate shall not exceed the rate shown in the following table:
Water Filling Rate Table
Bottom Course Thickness
Less than 22 mm

22 mm and more

Tank Portion

Filling Rate

Top course

300 mm/hour

Below top course

450 mm/hour

Top third of tank

225 mm/hour

Middle third of tank

300 mm/hour

Bottom third of tank

450 mm/hour

10.3.3.3 (5.3.5.3) Testing of the shell by a method other than hydrotesting such as painting
with highly penetrating oil, applying vacuum or a combination of both methods is
not permitted.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 20 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

10.3.3.4 (5.3.5.4) Floating roof seals, either primary or secondary, shall be completely
contained within the shell when the test water level reaches the test liquid level.
10.3.3.5 (5.3.5.5) The Tank Manufacturer shall furnish all test materials and facilities,
including blinds, bolting, and gaskets.
10.3.3.6 (5.3.5.6) The tank shall be completely drained and thoroughly dried immediately
after completion of the hydrostatic test. If sea water or raw water is used for
hydrostatic testing of tanks in other than these services, the tank shall be thoroughly
washed with fresh water immediately after draining.
10.3.3.7 (5.3.5.7) The Tank Manufacturer's plan for disposal of hydrotest water shall be
evaluated by the engineering contractor.
10.3.4

(5.3.6)

10.3.4.1 (5.3.6.1)

Testing of the Roof


Exception

All roof weld joints of a tank designed to be gas tight, such as a tank with peripheral
circulation vents or a tank with free or open vents, shall be vacuum box tested.
Applying internal pressure for the detection of leaks is not permitted. External
floating roof testing shall be in accordance with Appendix C of this specification.
Internal floating roof testing shall be in accordance with Appendix H of this
specification.
10.3.5

(5.3.8)

Magnetic Particle or Liquid Penetrant Examination

The dye penetrant or magnetic particle method before the hydrostatic test.
10.4

(5.4 )Repairs to Welds

10.4.1

(5.4.5)

10.5

(5.6 )Tank Settlement Measurements

10.5.1

(5.6.1)
The base elevation shall be established and recorded at equidistant
locations around the tank circumference in multiples of four, but not to exceed 10 m
(32.8 foot) between each reference point and no less than eight (8) locations. The
measurement points shall be at well marked locations on the bottom projection
outside the tank or on clips welded to the shell. Elevation readings shall be taken as
follows:
1)

Repairs to welds shall be in accordance with JERES-W-017.

Before hydrostatic testing has started.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 21 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

2)

At the filled point.

3)

At the filled point.

4)

After 24 hours from filling the tank at the maximum water fill height.

5)

After the tank has been emptied of test water.

10.5.2

(5.6.2)
Any differential settlement greater than 1.5 mm (60 mils) per meter of
circumference, or a uniform settlement in excess of 50 mm (2 inch), shall be
reviewed by the Company Representative. Filling shall be stopped until clearance to
continue has been received from the Company Representative.

10.5.3

(5.6.3)
For tanks 15.24 m (50 foot) diameter and larger, internal bottom
elevation measurements shall be made before and after the hydrostatic test. These
measurements shall be made at 3 m intervals along diametric lines across the bottom.
The diametric lines shall be spaced approximately 10 m (32.8 foot) apart at the tank
shell.

11

(6) Methods of Inspecting Joints

11.1

(6.1)

Radiographic Method

11.1.1

(6.1.1)

Application

Exception
Radiographic inspection is required for the weld joining the top angle to the shell.

11.1.2

(6.1.2)

11.1.2.1 (6.1.2.4)

Number and Location of Radiographs


Exception

This requirement is permitted only if a group of tanks are erected by the same tank
manufacturer.
11.1.3

(6.1.5)

Radiographic Standards

Tungsten inclusions in gas tungsten arc welds shall be evaluated as individual


rounded indications. Clustered or aligned tungsten inclusions shall be removed and
repaired.
11.1.4

(6.1.6)

Determination of Limits of Defective Welding

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 22 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

The additional spots to be radiographed shall be specified by the Company Inspector


in accordance with JERES-W-017.
11.2

(6.2 )Magnetic Particle Examination

11.2.1

(6.2.5)

Magnetic Particle Examination shall be according to JERES-W-017.

11.3

(6.5)

Visual Inspection

Welds shall be visually inspected for any defects prior to performing nondestructive
examination (radiography, magnetic particle, liquid penetrant, ultrasonic). Visual
inspection shall not replace any required nondestructive examination.
11.4

(6.6)

Vacuum Testing

11.4.1

(6.6.3)

Exception

A partial vacuum of 70 kPa gauge (10 psig) shall be used for the test.
11.4.2

(6.6.11)

Delete this paragraph.

12

(7) Welding Procedure and Welder Qualifications

12.1

(7.2)

Qualification of Welding Procedures

12.1.1

(7.2.1)

General Requirements

12.1.1.1 (7.2.1.1) All welding procedures and procedure qualifications shall be in


accordance with JERES-W-017 and be submitted for review by Company

13

(8) Marking

13.1

(8.1)

13.1.1

(8.1.5)
All tanks with internal coatings shall have the Approved Protective
Coating Systems specification number marked on the nameplate. For internal tank
walls, surface preparation, painting, and coating specifications shall be selected in
accordance with JERES-H-005.

Nameplates

For buried external section of tank walls, surface preparation, painting, and coating
specifications shall be selected in accordance with JERES-H-002.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 23 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

13.2

(8.4)
Tank number and content shall be painted in both Arabic and English at
90 degree intervals around the tank.

13.3

(8.5)
Marking shall be done with water soluble materials containing no
substances that would attack or harmfully affect the tank at both ambient and
operating temperature.

13.4

(8.6)
Marking materials shall be free of lead, sulfur, zinc, cadmium, mercury,
chlorine, or any other halogens

14

(9) Coatings and Painting

14.1

(9.1)
Type of coating and painting systems to be applied shall be as specified
on the Storage Tank data Sheet.
For external tank walls, surface preparation, painting, and coating specifications shall
be selected in accordance with JERES-H-001.
For internal tank walls, surface preparation, painting, and coating specifications shall
be selected in accordance with JERES-H-005.
For buried external section of tank walls, surface preparation, painting, and coating
specifications shall be selected in accordance with JERES-H-002.

14.2

(9.2)
Surfaces to be coated shall be cleaned and prepared prior to its coating in
accordance with the applicable coating and painting systems.

14.3

(9.3)
Tank placed directly on soil sub-grade shall be coated with Coal tar
Epoxy paint, 600 thick or Epoxy coating for Atmospheric service, 450 thick, as
applicable, on its soil side leaving minimum 2.5 cm (1 inch) wide strip of uncoated
steel along the underside of the floor plate, centered on, and directly below the weld
seam. This will typically require masking a strip along the underside of each end
(edge) of each bottom plate approximately 5 cm (2 inch) wide. Coal tar Epoxy paint
shall be specified for tank with maximum operation temperature of 70C (158F),
while Epoxy coating for Atmospheric service shall be specified for higher operation
temperatures up to 150C.

14.4

(9.4)
In tanks where internal coating is not required, top side of the bottom and
the bottom portion of the shell, starting from the tank bottom up to minimum one
foot above water line, shall be coated according to the applicable coating
specifications.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 24 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

14.5

(9.5)

Gasket contact surfaces shall not be coated or painted.

14.6

(9.6)
The tank number and content shall be painted in both Arabic and English
at 90 degree intervals around the tank.

15

(10 )Documentation
The Tank Manufacturer and internal floating roof manufacturer shall prepare
drawings, calculations, and data in accordance with Form NMR-7918-1 and Form
NMR-7918-2, Non-Material Requirements, as applicable.
Drawings and calculations, which are approved by the Design Engineer, shall not
relieve the Manufacturer of the responsibility to comply with the Code and this
specification.

16

(11)

Disinfection

16.1

(11.1)
All potable water storage tanks shall be disinfected in accordance with
AWWA C652.

16.1.1

(11.2)
The chlorine and bacteriological tests shall be approved by the Company
Representative.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 25 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Appendix B Recommendations for Design and Construction of Foundations for


Aboveground Oil Storage Tanks
B.2

Subsurface Investigation and Construction

B.2.6

Top fill layer 10-15 cm (4-6 inch) shall be a mixture of sweet sand and 3% cement
(33:1 ratio, i.e., 3% cement). The material specifications and mixing requirements
shall be as follows:
1)

The maximum permissible soil content is 0.1%. Sand shall be dried to a freemoisture content of not more than 2.0% by weight of dry soil.

2)

The dry sand must be screened through 6.4 mm (1/4 inch) mesh (maximum).
Care must be taken in using clean mixing and handling equipment to ensure
mixture remains free from foreign matter.

3)

The sand shall then be thoroughly mixed with cement in a 33:1 ratio by weight
in a concrete mixer. After laying the mixture shall be rolled a minimum six
times by a 3-ton roller. Vibratory plate tampers may be used in lieu of rollers
for areas where a roller cannot reach and/or cover.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 26 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Appendix C - External Floating Roofs


C.2

MATERIAL
Exceptions
Galvanized parts shall not be used.

Electrical bonding shunt materials shall be Type 304 stainless steel.


C.3

DESIGN

C.3.3

Decks

C.3.3.1

Exception
Roofs shall be of the contact type designed to eliminate the presence of any air-vapor
mixture under the deck.

C.3.4

Pontoon Design

C.3.4.1

Floating roofs shall have sufficient buoyancy to remain afloat based on the lower of
the product specific gravity or 0.7, with the primary drain inoperative for the
conditions stated in API STD 650.

C.3.3.5

The deck of single deck pontoon floating roofs shall be in contact with the liquid
during normal operation.

C.3.3.6

Roofs greater than 91 m (300 foot) in diameter shall be of the double-deck type.

C.3.7

Ladders

C.3.7.1

Rolling ladders shall meet the following requirements:


1)

The minimum inside width of the ladder shall be 710 mm (28 inch).

2)

Wheels shall be provided at the lower end of the ladder and sized to prevent
binding of the ladder at any position and provided with sealed non-lubricating
bearings.

3)

Self-leveling treads shall be used for the ladder.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 27 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

C.3.8

Manufacture of Atmospheric Tanks

4 November 2008

Roof Drains
Exception
External floating roofs shall be provided with primary drains of either the flexible pipe
(Coflexip or equal), or the articulated pipe type. A swing type check valve shall be provided
at the inlet of the drain. Siphon type drains are not acceptable for primary roof drains.
Siphon type drains, however, may be provided as a secondary roof drain if specified on the
Storage Tank Data Sheet. Emergency drains for double deck floating roofs shall be of the
open-type design.

C.3.9

Vents

C.3.9.1

As a minimum, two overpressure/vacuum bleeder type vents shall be installed.


Vents shall be sized to handle a total of 125% of the maximum filling/withdrawal
rates that are specified on the Storage Tank Data Sheet.
Commentary Note:
Bleeder vents shall be designed to open and close automatically when the roof is 75mm
above its low support legs position upon emptying and filling the tank, respectively.

C.3.9.2

Vents for protection against overpressure/vacuum, while the roof is floating, shall be
provided as follows:
1)

Their overall capacity shall be determined according to API standard 2000


requirements, considering 25% of the filling/emptying rates and 100% of
thermal breathing.

2)

Vents shall be evenly distributed and close to the roof periphery enough vents
shall be provided close to the inlet diffuser in services where gas slugs are
expected.

3)

Vents shall be designed so as not to allow any carry over of stored liquid onto
the floating roof.

Commentary Notes:
1)

Normally, vents are of the open type that does not undergo testing but rather in-situ
inspection. In case relief valves are used, their number shall be such that the total
required venting capacity is always available when a number of valve(s) are removed
for testing.

2)

Anticipated operation upset conditions such as an increase in temperature of the input


stream to a tank or chemical injection that will result in vaporization beyond that

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 28 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

associated with the true vapor pressure design limit of 90 kPa (13 psia) and gas
purges shall be also considered in determining the required venting capacity.

C.3.10

Supporting Legs

C.3.10.3 Support legs shall be carbon steel pipe, Schedule 80 minimum thickness.
C.3.10.4 Support legs shall be adjustable to two positions. The lower position shall allow the
roof to descend to a position at least 75 mm (3 inch) above internal accessories or
roof seal mechanism. The higher position shall provide a 2 m (79 inch) clearance
between the lowest portion of the roof and the tank floor.
C.3.10.5 Bearing plates shall be provided under all support legs so as to distribute the weight
of the internal floating roof on the tank bottom plates and to avoid damage to internal
tank coatings. The bearing plates shall be twice the diameter of the support section,
12.7 mm (1/2 inch) thick, and shall be attached to the bottom by 4.8 mm (3/16 inch)
continuous fillet welds.
C.3.11

Roof Manholes
Roof manholes shall be provided in accordance with JERSD-D-0001.

C.3.13

Seals
Exceptions
1)

If the sealing device employs steel shoes in contact with the shell (pantograph-type),
such shoes shall be made of only Type 304 stainless steel with a minimum nominal
thickness of 1.5 mm (16 gauge).
A low-density polymer type plastic insulation cover shall be provided at the joint
between the middle arm of the pantograph hanger and the connecting rod of the steel
shoe. The insulation cover shall have a press-type locking system and completely
electrically insulate the pantograph hanger with the seal shoe.

2)

Any fabric or non-metallic materials used as a seal or seal component shall be


selected based on the design temperature, flammability, permeability, abrasion
resistance, aging, resistance to aromatics, and chemical resistance, and selected from
the following Table.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 29 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Seal Materials Table


Fluid Stored
Crude Oil

Refined Products

Gasoline/MTBE Blend

MTBE (100%)

Non-Metallic Seal Material


Viton GF (FKM-GF)
Aflas (TFE/P)
Viton (FKM)
PFA(Perfluoroalkoxy)
PTFE(Teflon) laminate
PTFE (Teflon) laminate
KALREZ (Perfluoroelastomer)
CHEMRAZ (Perfluoroelastomer)
KALREZ (Perfluoroelastomer)
CHEMRAZ (Perfluoroelastomer)
PTFE (Teflon) laminate

Materials properties verification shall be performed by an independent laboratory.


3)

The Tank Manufacturer may offer an alternate design and material at the time
of proposal. However, the alternate design shall comply with the following
requirements:
a)

Seals shall be located on the skirt.

b)

Materials for non-metallic components of seals shall meet requirements


in paragraph C3.13 (2) of this specification.

4)

All fabric or non-metallic materials used as a seal or seal component shall have
a flammability spread index not exceeding 25 established per NFPA 255.

5)

All fasteners used in sealing devices shall be Type 304 stainless steel.

6)

Design of secondary seals shall permit the inspection of primary seals without
removal of the secondary seals.

7)

Fabric seal in sealing devices that employ steel shoes in contact with the shell
may be installed after the hydrostatic test.

C.3.14

Gauging devices shall be provided per paragraph 3.8.15 of this specification.

C.3.15

Bonding Shunts
Bonding shunts shall be provided on floating roofs in accordance with JERSD-P0003 and API RP 2003 requirements.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 30 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Appendix G Structurally Supported Aluminum Dome Roofs


G.1

General

G.1.4

Special features

G.1.4.2

Exception
The aluminum dome roof materials shall have a mill finish.

G.2

Materials

G.2.1

General
Exception
Materials for all roof components shall be compatible with the intended service.
Alternate material for any roof component (structural frame, roof panels, node
covers, bolts, fasteners, sealant and gasket material, and skylight panels) shall not
be used without prior approval of the Company Representative, as defined in Section
3 of this specification.

G.2.3

Roof Panels
Exception
Roof panels and node covers shall be fabricated from Series 3000 (H32 or H34 temper) or
5000(H32 or H34 temper) aluminum with a minimum nominal thickness of 1.2 mm (0.05
in.).

G.2.4

Bolts and Fasteners


Exception

Bolts and fasteners shall be of 7075-T73 aluminum, 2024-T4 aluminum, or 300 Series
stainless steel (AISI 302 or AISI 304). Only 300 Series stainless steel (AISI 302 or AISI
304) bolts shall be used to attach aluminum to steel.

400 Series stainless steel or aluminized mild steel HV-Huck-Lock bolts shall be used for
joining structural members (struts) at the space truss nodes.

G.5

Roof Attachment

G.5.3

Separation of carbon Steel and Aluminum

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 31 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Exception
Aluminum shall be isolated from carbon steel by austenitic stainless steel spacers.
G.5.5

The dome surface paneling shall be designed as a watertight system under all design
load and temperature conditions. All edges of aluminum panels shall be covered,
sealed, and firmly clamped with batten in an interlocking manner to prevent slipping
or disengagement under all load and temperature conditions.

G.8

Roof Vents

G.8.4.3

Surface appurtenances and closure panel joints shall be designed watertight without
the use of sealants.

G.10

Testing

G.10.2

100% liquid penetrant examinations shall be performed on structural welds and


components joined by welding.

G.11

Fabrication and Erection

G.11.5

Erection
Exception
Structural frame members (struts) shall be joined at nodes by preset-torque level HVHUCK-Lock bolts.

G.11.6

Workmanship
Exception
Sealant shall be applied and installed in a manner suitable to that of architectural class
work. Joint surfaces shall be clean to ensure adhesion of sealants. All exposed sealant
surfaces shall be tooled slightly concave after sealant is placed in joints. Misplaced excess
sealant shall be removed.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 32 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Appendix H - Internal Floating Roofs


H.1

Scope
Exception
Types of internal floating roofs are limited to those specified in paragraph H.2.2 of this
specification. Other types stipulated or referenced in API 650, Appendix H shall not be
considered.

H.2

Types

H.2.1

Exception
The internal floating roof shall be selected by the design engineer.

H.2.2

Exception
Only type c(metallic pontoon roofs), type d(metallic double-deck roofs) or type
e(metallic roofs on floats) shall be used.

H.3

Material

H.3.1

Exception
The Design Engineer shall specify the materials required.
Internal floating roofs with non-metallic components as part of the floats are
prohibited.

H.3.2

Steel
Exception
Galvanized components shall not be used.

H.3.3

Aluminum
Exceptions
Aluminum shall not be used in services where caustic constituents are present in the stored
liquid.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 33 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Delete reference to sandwich panel type.


H.4

Requirements for All Types

H.4.1

General

H.4.1.6

(Exception)

H.4.1.6.1 A minimum of four anti-static stranded stainless steel cables of minimum 3 mm in


diameter, uniformly distributed, shall be provided from the fixed roof to the internal
floating roof. Design of the cables shall take into account strength, flexibility, joint
reliability and service life.
H.4.1.6.2 All moveable cover accessories (hatches, manways, pressure relief devices and other
openings) on the internal floating roof shall be bonded to the internal floating roof to
prevent static electricity sparking when they are opened. The cable shall be
minimum 3.2 mm (1/8) in diameter of stranded stainless steel, with a length at least
twice the normal travel of these device covers. Design of the cables shall take into
account strength, flexibility, joint reliability and service life.
H.4.1.8

Exceptions
All closed floating compartments shall be seal welded to prevent liquid or vapor
entry.
Delete reference to floating roof type H.2.2.g.

H.4.1.9

Delete this paragraph.

H.4.1.10 Exception
Drains for decks surfaces above the liquid level shall be designed to return any
spillage or condensate to the product. Such drains shall close automatically or
extended at least 100 mm (4 in.) into the product to minimize vapor loss.
H.4.2

INTERNAL FLOATING ROOF DESIGN

H.4.2.4

Delete reference to floating roof type H.2.2.g.

H.4.3

JOINT DESIGN

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 34 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

H.4.3.3

Manufacture of Atmospheric Tanks

4 November 2008

Exception
Pivot joints that allow flexure between adjacent floats shall be provided on internal
floating roof designs that employ a metallic roof on tubular floats.

H.4.3.3.1 Exception
Only austenitic type stainless steel SS 304 hardware shall be used to join aluminum
and/or stainless components to each other or to carbon steel.
H.4.4

PERIPHERAL SEALS

H.4.4.2

The peripheral seal type and material shall selected by the Design Engineer.

H4.4.5

Seal Types
Exceptions

Any fabric or non-metallic materials used as a seal or seal component shall be selected
based on the design temperature, permeability, abrasion resistance, aging, flammability,
resistance to aromatics, and chemical resistance, and selected from the table in
paragraph C3.13.2 of this specification.

Only resilient foam-filled liquid-mounted and vapor-mounted rim seals shall be used.

Circumferential joints in envelope fabric seals shall overlap by at least 150 mm (6 in.).

Galvanized steel components are prohibited.

All fabric or non-metallic materials used as a seal or seal component shall have a
flammability spread index not exceeding 25 established per NFPA 255.

H4.4.6

Fabric or non-metallic materials used as a seal or seal component shall be tested for
their compatibility with the intended service by an independent laboratory.

H.4.5

ROOF PENETRATIONS
Exception
All roof penetrations shall be surrounded by a well that extends at least 100 mm (4
in.) into the stored liquid.

H.4.6

Roof Supports

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 35 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

H.4.6.1

Manufacture of Atmospheric Tanks

4 November 2008

Exception
The floating roof shall be provided with fixed or adjustable supports.

H4.6.2

Exception
The height of the floating roof shall be adjustable to two positions with the tank out
of service. The design of the supports shall prevent damage to the fixed roof and
floating roof at the tank maximum design liquid level.

H.4.6.3

Exception
The high (maintenance) of adjustable roof supports position shall provide a 2 m (79
foot) clearance between the lowest portion of the roof and the tank floor.

H.4.6.4

Exception
Delete reference to floating roof types H.2.2.a, b and g.

H.4.6.5

Exception
Drainable pipe supports shall be used.

H.4.6.6

Exception
Steel bearing plates shall be provided under all support legs so as to distribute the
weight of the internal floating roof on the tank bottom plates and to avoid damage to
internal tank coatings. The bearing plates shall be twice the diameter of the support
section, 12.7 mm ( inch) thick, and shall be attached to the bottom by 4.8 mm (3/16
inch) continuous fillet welds.

H.4.6.9

Where propeller-type mixers are used, the support legs shall provide a minimum
clearance of 300 mm (12 inch) from the underside of the internal floating roof to the
top of the mixer paddle(s).

H.4.6.10 Jet-nozzle mixers are not permitted.


H.5

OPENINGS AND APPURTENANCES

H.5.2

Vents

H.5.2.1

Pressure-Vacuum (Bleeder) Vents

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 36 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

Exception
As a minimum, two overpressure/vacuum bleeder type vents shall be installed in the
internal floating roof. Vents shall be sized to handle a total of 125% of the maximum
filling/withdrawal rates that are specified on the Storage Tank Data Sheet.
Commentary Note:
Bleeder vents shall be designed to open and close automatically when the roof is 75 mm (3
inch) above its low support legs position upon emptying and filling the tank, respectively.

H.5.2.2

Tank Circulation Vents

H5.2.2.1 Exception
Peripheral circulation vents shall be located at the top of the shell with an outward
projecting cover. Air intake shall be from the cover bottom side to minimize dust
ingress.
H.5.2.2.4 Circulation venting and venting devices shall provide protection against
overpressure/vacuum for normal conditions (resulting from operational requirements
and atmospheric changes) and emergency conditions (resulting from exposure to an
external fire) according to API STD 2000.
H5.2.3

Vents for protection against overpressure/vacuum, while the roof is floating, shall be
provided as follows:
1)

Vents shall be sized according to API STD 2000 requirements, considering


25% of the filling/emptying rates and 100% of thermal breathing.

2)

Vents shall be evenly distributed and close to the roof edge with enough vents
shall be provided close to the inlet diffuser in services where gas slugs are
expected.

3)

Vents shall be designed so as not to allow any carry over of stored liquid onto
the floating roof.

Commentary Note:
Anticipated operation upset conditions such as an increase in temperature of the input
stream to a tank or chemical injection that will result in vaporization beyond that associated
with the product true vapor pressure design limit of 90 kPa absolute (13 psia) or gas purges
shall be also considered in determining the required venting capacity.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 37 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

H.5.5.3

Manufacture of Atmospheric Tanks

4 November 2008

Inspection Hatches
Exception
Inspection hatches shall be located on the fixed roof to permit visual inspection of the
seal region.

H.5.6

Inlet Diffuser
Exception
Inlet diffuser shall be specified according to paragraph 3.8.12 of this specification.

H5.7

Gauging And Sampling Devices


Exception
Internal floating roofs shall be provided with gauging and sampling devices when specified
by the Design Engineer.

H.6

Fabrication, Erection, Welding, Inspection, and Testing

H.6.4

Exception
Floatation test and initial fill inspection shall be performed by the erector and
witnessed by the purchaser.

H.6.4.1

Exception
Delete reference to floating roof types H.2.2.a, b, g and f.

H.6.4.3

Exception
Potable water having less than 500 ppm chlorides shall be used for testing when the
internal floating roof is constructed of aluminum or stainless steel.

H.6.5

Internal floating roof components that are fabricated or attached by welding, such as
clips, gusset plates, etc., shall be completely seal-welded.

H.6.6

Shop Fabrication

H.6.6.1

Straightening of material shall be done by pressing or other non-injurious methods


before the material is laid out or worked on in any way. Materials shall not be
hammered.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 38 of 39

Jubail Export Refinery


Material Specifications
JERMS-D-3205
Rev-2

Manufacture of Atmospheric Tanks

4 November 2008

H.6.6.2

When the edges of plates are cut with a torch, the resulting surface shall be uniform,
smooth, and free from scale and slag before performing any welding.

H.6.7

Shop Inspection and Testing

H.6.7.1

Internal floating roofs manufactured in accordance with this specification are subject
to verification by the Company Inspector in accordance with Company Inspection
Requirements Form 175-324900.

H.6.7.2

Inspection at the mill, shop, or fabrication yard shall not release the manufacturer of
the internal floating roof from responsibility for repairing or replacing any defective
material or workmanship that may be subsequently discovered in the field.

H.6.7.3

All support brackets that are welded to tubular pontoons shall be dye-penetrant
inspected.

H.6.7.4

Welded tubular pontoons shall be pneumatically pressure tested with air at 35 kPa (5
psig) and the welds visually inspected by using a soapy water solution or by
immersing the pontoons under water. All defective welds shall be repaired and the
pontoons re-tested prior to shipment.

H.7

Installation

H.7.1

Internal floating roofs shall be installed by contractors who have been approved by
the manufacturer of the internal floating roofs.

H.7.2

Internal floating roofs shall be installed in accordance with the procedures specified
by the internal floating roof manufacturer.

H.8

Drawings and Calculations


The internal floating roof manufacturer shall prepare drawings, calculations, and data
in accordance with Form NMR-7918-2, Nonmaterial Requirements. Drawings and
calculations that are approved by the Design Engineer shall not relieve the internal
floating roof manufacturer of the responsibility to comply with API STD 650 and
this specification.

This document is the property of Jubail Export Refinery and no parts of this document shall be reproduced by
any means without prior approval by the Company.

Page 39 of 39