Beruflich Dokumente
Kultur Dokumente
Page 1 of 2
1.
The average energy used for heating a 1980s single family home is roughly 84 x 106 kJ, 80 x 106 BTU in
a climate similar to Boston or Madison, Wisconsin. Heating is mainly needed for the six coldest months.
Use the enclosed table of daily solar radiation, taken from ASHRAE Handbook of Fundamentals 1997, to
estimate, to within 15 to 20 percent accuracy, the size of a solar collector needed, in ft,or m2, to supply
75% of the heating energy for the house for the six winter months. Assume the energy collected on the
collector is 50% of the total solar radiation incident on the collector.
2.
Assume the house is a typical US home with 2000 square feet total floor area overall. Sketch a
preliminary design of the appropriate sized collector integrated into the roof. The design and
orientation is your choice. What if the long axis of the house is N-S?
3.
A solar collector costs roughly $25/ft2 of collector area for the entire system. A gallon of fuel oil
can supply roughly 140,000 BTU, 158 x 106 J, and costs 2.5 dollars. Compare the economics of a
one square foot collector versus heating with oil. Consider how to compare building cost versus
operating cost. What other alternatives should be considered?
.How big must the solar collector be to supply all of the heating energy if no back up system is included?
6.
On same consistent basis, e.g. J, Kw-hr, or BTU compare the costs of energy supplied by
electricity, and by burning natural gas and heating oil. Use average consumer prices for one area,
such as Boston. Obtain prices directly from utilities or from reference sources. Is there a disparity in
energy prices? If so, is this a consumer rip off or is there some justification? This problem is
fundamental to many energy considerations.
You have been recently hired by MIT to perform a partial energy audit of one of the new luxury
dorm rooms just built on campus. Each room comes with quite a bit of pre-installed equipment for
the students. Your task is to estimate the electricity usage of one of these rooms. Among other
items in the room are: a room air conditioner, full-size refrigerator, microwave oven, coffee maker,
toaster, iron, hair dryer, TV and VCR, PC, monitor and laser printer. Assume the electrical lighting
is the same as in your own room. Use the kill a watt meters we will supply to make your
measurements. Dont forget the energy sued by power supplies and other items in standby mode.
Now assume that the student has everything running at full blast at one time. How much electrical
power does this room need to be supplied with (in Watts)? Make some assumptions about how long
each appliance is used on a certain day. How many kilowatt-hours of electricity are used by this
room in one day? Based on your response to Problem 5, how much does electricity cost for one
day?
Submit a table with the following information for each appliance:
Appliance 1
7.
350W
2 hours/day
700 kWh/day
Name of Source
For your living group at MIT, list two or three strategies to make it more energy efficient.
Your sources may include: info on the backs of appliances, the internet, and your own
measurements.
Page 2 of 2
Table from ASHRAE Handbook of Fundamentals
Daily Solar Heat Gain Through a Single Sheet of Clear Glass at 40 N Latitude
With a Clear sky
Month
Horizontal
Vertical South Vertical East
Daily (W h/m2)
Facing
Facing
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
2234
3458
4818
6036
6828
7100
6790
5964
4658
3408
2230
1782
5130
5180
4380
3076
2256
1990
2220
2990
4238
4986
5030
4890
1621
2311
2983
3085
3781
3866
3752
3424
2859
2233
1601
1347
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
Page 1 of 2
Fall10
1.044J, 2.66J, 4.42J
Homework Set #2
1.
Fall08
1.044J, 2.66J, 4.42J
Homework Set #2
Page 2 of 2
4.
An investigator suggests use of a heat pump to provide winter heating to a
building. Instead of using the outside air as the low temperature heat source, she proposes
to use the domestic water system which enters the house at a higher temperature than the
outside air. This raises the heat pump average coefficient of performance QH/W from 2.5
to 3.0. As the heat pump operates, Qw is transferred from the water, lowing TI, the inlet
water temperature to the house. To simplify the consideration assume the initial water
temperatures is TH same as the interior temperature. The house temperature is constant at
TH. Evaluate the net energy electrical savings under two conditions:
(a)
(b)
(c)
The water quickly flows through the house and there is no heat transfer
between the water and the interior of the house. TD the water drain
temperature equals TI with or without the heat pump.
The water remains in the house for a long time. Heat transfer to the water
in the house raises it temperature to the interior temperature TH, so that TD
is equal to TH no matter how much TI changes.
Comment on the feasibility of such a system.
QH
Heat
Pump
TH
QW
Water
Inlet
T = TH
TI
I
m
D
m
TD
Drain
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
Fall 10
1.044J, 2.66J, 4.42J
Homework Set #3
______________________________________________________________________________________
1) Simmons Hall, the newest MIT student dorm on campus should be operated to minimize
energy use. One proposed strategy to reduce air conditioning energy in the summer is night
cooling. At 8 p.m. the windows are opened and cool night air is circulated through the room.
By 8 a.m. the room air and the concrete floor slab have a temperature close to that of the
outside air, 18 degrees Centigrade. The slab is four inches thick. At 8 a.m. the windows are
closed and heat transfer to the cooled floor slab helps to maintain a comfortable interior
temperature. Neglect any heat transfer through the closed windows. Assume that the average
rate of electrical and solar energy into the room totals 500 watts over the 12 hours.
a)Sketch the room temperature vs. time for the 12 hour period between 8 a.m. and 8
p.m. What is the maximum room temperature? Assume as a limiting case that the slab
and the air temperature are always equal. In reality, do you expect the slab to be at a
lower or higher temperature than the air?
b) Can you suggest an improved strategy for window opening and closing during the
day?
2) To supplement the night cooling strategy described above, it is proposed to spray liquid
water droplets into the air. If the room air at 8 a.m. is completely dry what is the maximum
amount of liquid water that can be evaporated into the room air at 18 degrees Centigrade?
Assume that the room is closed up and there is no air circulation from the outside into the
room.
3) Using both night cooling and the maximum amount of liquid water evaporation in the room,
estimate the room temperature at 8 p.m. From 8 a.m. to 8 p.m. the windows are closed and the
average electrical and solar energy into the room totals 500 watts. To solve, write an energy
balance for a system including the floor slab, the water and the air. Take state 1 as liquid
water, floor slab and air at 18 degrees Centigrade, the conditions at 8 a.m. Take state 2 as the
slab and saturated air at 8 p.m.
4) What do you think about the feasibility of the proposed solutions?
5) You are interested in investigating the thermal stratification in your dorm room, which
directly impacts our assumption that the slab and air temperatures are equal. Chose 4
locations in your room, 2 of which are in the immediate vicinity of your highest power
consuming appliances identified in the first problem set. At each location, use the Vernier
LabQuest and temperature probe to measure the floor temperature and air temperature at the
following heights (1 in, 2 ft, 4 ft, 6 ft, 8 ft above floor). Allow enough time at each height for the
temperature reading to reach steady state (ie to settle on a value and not change).
How justified is our assumption about the slab and air temperatures? Is the thermal
stratification different at each location? If so, please justify any differences.
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
Fall2010
1.044J, 2.45J, 4.42J
Homework Set #4
1.
State 2
75 oF
Exhaust
amb
M
Tamb
State 3
Room
State 1
60 oF
chiller
Q
total
M
A room at steady state has a supply air stream of cool air entering at 60oF. The lights, office
appliances and people transfer heat to the air so that it leaves at 75oF. Consider only sensible heat
transfer for this problem, with all temperatures given as dry bulb temperatures. After the air leaves
the room some is exhausted from the building. The remainder mixes with ambient air. The mixture
amb must be at least 20
is cooled by the chiller down to 60oF. For ventilation requirements M
percent of the total flow rate. The total air flow rate to the room and the entering temperature, state
1, are held constant. The amount of ambient air can be varied from 20 percent up to 100 % of
total (with corresponding increases in the exhaust flow to keep the total flow constant). The
M
temperature changes are small so Cp can be considered constant.
chiller
a) For an arbitrary ambient temperature develop an expression for Q
amb and M
total.
in terms of M
amb and M
total
b) As the ambient temperature varies between 50oF and 85oF what should M
chiller ?
be to minimize Q
amb and M
total versus TAMB. At different ambient
Show a diagram of the optimum M
temperature levels, e.g., 60, 75 oF, the strategy to minimize the chiller cooling requirement
may change. This is known as an economizer cycle.
Page 1 of 5
Fall2010
1.044J, 2.45J, 4.42J
Homework Set #4
2.
An office space is to be kept at 73oF. If cool air is constantly supplied to the space at 60oF
and the space can be assumed to be at a uniform temperature, what is the required air mass
flow in lb/hr and volume flow in CFM? The same flow of air continually leaves the space.
The heat transfer into the space from the outside through an exterior wall is 16,000 BTU/hr.
Internal "heat gains" in the office space can be taken as 2.5 W/ft2 for office equipment and
computers and 250 BTU/hr per person. Assume the space ft2 is occupied by 40 people.
The heat given due to people assume is only sensible heating, i.e., it neglects any
evaporation or changes in the moisture level in the air. Assume steady state conditions
prevail. The floor area of the office is 1500 ft2.
2b.
If all the heat gains are doubled what options are available for the cool air supply to keep
the office space at 73oF? What other factors must be considered in choosing an option?
3.
A water to air heat exchanger is used to heat the air of a home interior. The air flow rate is
2000 lbm/hr; the air enters in steady flow at 70o F and leaves the heat exchanger at 100 oF.
Heating water enters at 130oF and leaves at 110oF.
4.
a)
If the heat exchanger is operating in steady state and there is negligible heat loss
from the outside casing of the exchanger to its surroundings what is the required
water flow rate?
b)
Do you think it's possible to design a heat exchanger with a water temperature drop
from 130oF to 110oF while the air outlet temperature is raised to 125oF (for suitable
air and water flow rates)?
c)
Is it possible to have an air outlet temperature of 135oF with these same water
temperatures?
An air conditioning system uses R-12 (Freon-12) as a working fluid. The flow rate of
refrigerant is 1,000 lbm/hr and it is steady. The refrigerant is condensed in the condenser to
saturated liquid at 120oF. From the condenser, it passes through an expansion valve where
the pressure is lowered and the outlet temperature is 20oF. The expansion valve is insulated
and there is no shaft work. After the expansion valve the Freon enters the evaporator where
it receives heat at constant pressure corresponding to the saturation pressure of 20oF. The
heat transferred to the Freon in the evaporation provides the cooling to the air passing over
the evaporator.
a)
Find the cooling capacity of the unit in BTU/hr if the outlet of the evaporator is
saturated vapor. Find the cooling capacity in tons. Hint: Define a control volume
around the evaporator and write the steady flow energy equation.
b)
Repeat part (a) if the outlet of the evaporator is super heated by 15oF; that is, the
vapor is heated at constant pressure to 15oF above the saturation temperature.
Assume the Freon-12 vapor is a perfect gas with Cp equal to 0.15 BTU/lbm oF.
Page 2 of 5
Fall2010
1.044J, 2.45J, 4.42J
Homework Set #4
5. An open plan office is to be cooled by natural ventilation. The long axis of the building
is aligned in the East-West direction. The depth in the North-South direction is 30 m
with operable windows on both the North and South sides. With open windows and
negligible air flow resistance in the interior, when the wind is from the South, the air
velocity at the Southern window open area can be approximately related to the wind
velocity as, Vopen area = 0.35 Vwind. Assume the North side windows have the same open
area as the South windows and there is an equal air flow out of the North side windows.
The interior height is 3 m and there is a combined heat input due to lights, people and
office equipment of 40 W/m2 of floor area.
a)
What is the air change rate per hour, ACH, of the building interior as a function of
the percent of the South faade used for open window area? The wind velocity is 1.5
m/s.
b)
Plot the temperature rise of the interior air as a function of the percent of the South
faade used for open windows. The wind velocity is still 1.5 m/s.
c)
How can the building be kept cool when the wind velocity is reduced?
d)
Compare the performance of natural ventilation between the upper and lower floors
of a high rise building.
Page 3 of 5
Fall2010
1.044J, 2.45J, 4.42J
Homework Set #4
6.
An air conditioning system uses HFC 134a as a working fluid, the refrigerant. The
flow rate of refrigerant is 500 kg/hr and it is steady. The refrigerant is condensed in
the condenser to saturated liquid at 45 C. From the condenser, it passes through
an expansion valve, flow resistance, where the pressure is lowered and the outlet
temperature is 10 C. The expansion valve is insulated and there is no shaft work.
After the expansion valve the refrigerant enters the evaporator where it receives
heat at constant pressure corresponding to the saturation pressure of 10 C. The
heat transferred to the refrigerant in the evaporation provides the cooling to the air
passing over the evaporator.
What is the enthalpy change of the refrigerant as it flows through the expansion
valve?
Find the cooling capacity of the unit in W and BTU/hr if the outlet of the evaporator
is saturated vapor. Hint: Define a control volume around the evaporator and write
the steady flow energy equation.
T= 45 C Saturated
Liquid
500 kg/s flow rate
Condensor
Compressor
Flow
Resistance
Evaporator
T=10C
T=10 C,
saturated vapor
Page 4 of 5
Fall2010
1.044J, 2.45J, 4.42J
Homework Set #4
7. MIT has a large number of fume hoods used for wet chemistry experiments. When the
hood sashes are open the air velocity, sometimes called the face velocity, must be
maintained at a safe level to prevent any dangerous fumes from escaping. The air drawn
into the hoods comes from the air supplied to the room. This air must be heated to
acceptable temperature levels for the lab occupants. For safety reasons, all of the air flow
in such a building must be exhausted and none can be recycled, a once-through system.
Use the instruments from class to measure the air flow rate in a new and an older hood as
the window is closed.
a)
Estimate for one full sized hood at MIT the energy required to heat the air use
during one winter day if the hood is left fully open for 24 hours.
b)
Use the instruments from class to measure the air flow rate in a new and older
hood as the sash is closed.
b)
Estimate the amount of energy required to heat the air for the entire heating
season if the hood is always open.
c)
Compare this to the energy required to heat an average single family house in
Boston for the heating season.
d)
What steps would you recommend to save energy with the fume hoods at MIT?
8.
A single story shopping mall has a floor plan 50m X 100 m. All energy is supplied by electricity.
It has been designed with some advanced efficiency features so that the yearly energy use is 100 kWh/m2
of floor area. The architect proposes to use a wind turbine on the top of the building to supply all of the
electricity. The wind turbine has a horizontal axis and has an average efficiency of 35 percent.
a)
Use the average wind speed in Boston (Logan Airport) to estimate what the diameter of a
single
turbine to meet the buildings energy?
Page 5 of 5
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
4.42 F10
Assignment #5
FOR ALL OF THE FOLLOWING PROBLEMS USE THE
PSYCHOMETRIC CHARTS WHEN YOU CAN TO OBTAIN THE NEEDED DATA.
1. The air leaving an office space is at 78oF dry bulb and 85% relative humidity. The
leaving air is cooled to 65oF dry bulb and 70% relative humidity and returned to the
office space. This is accomplished by first sensible cooling of the air to saturation,
then cooling and dehumidification along the saturation line and finally reheating
without vapor addition. Show the process on the psychometric curve. Find the
energy requirement for each of the three processes per pound of dry air.
2. The overall change of state described in problem 1 is to be accomplished solely by
mixing the leaving air with cool air at 55oF. What must the relative humidity of the
cool air be so that the mixture can reach the 65oF dry bulb and 70% relative
humidity state? How many pounds of cool air are needed per pound of leaving air?
3. A building in the Southwest is to be cooled by use of an evaporative cooler. Cool
liquid water is sprayed into outside air as it is brought into the building. The
outside air is at 90oF dry bulb temperature and 10% relative humidity. Show the
cooling process on a psychometric chart assuming the enthalpy of the liquid water
is negligible in the energy balance. How much water must be evaporated for each
10oF dry bulb temperature decrease of the air?
3b. Steam, hot water vapor, is mixed with the outside air. Show the process on the
psychometric chart when the enthalpy of the steam, enthalpy per mass of steam, is
equal to the enthalpy of the water vapor in the outside air at 90 F, 10% RH. What
happens when the steam enthalpy is greater than the enthalpy of the water vapor in
the outside air?
4. Within the building considered in problem 3 the sensible heat gain is twice the
latent heat gain. If the air-conditions within the office space (well mixed
conditions) is 80oF and 40% relative humidity, construct the condition line for the
building. The condition line is the line on the psychometric chart representing all
of the possible states of the supply air which yields the desired well mixed
conditions within the building. The indoor conditions are maintained by mixing the
ambient air, cooled by evaporation as given in problem 3, with the exhaust from
the building. What is the only state of the cooled ambient air which permits the
interior conditions to be maintained, i.e. for the specified state of the interior air
and the given ratio of sensible to latent heat gain?
Page 1 of 2
4.42 F10
Assignment #5
5. A small portable dehumidifier is a single self-contained unit that is placed
inside a room. It has one air inlet and one air outlet for the entire unit (the
dehumidifier does not have any direct contact with the air outside the house).
Air enters at 24 C dry bulb temperature and 80 percent relative humidity. The
volume flow rate of air is 245 CFM, 6.9 m3/min. The unit removes 40 pints of
liquid water per day, approximately 19 kg/day, from the air when operated
constantly at steady state. It consumes 400 W of electricity. Assume that there is
negligible heat transfer from the cabinet of the unit to the surrounding air. Take
the air density as 1.16 kg/m3
a) What is the specific humidity in g/kg of the air leaving the unit?
b) What is the dry bulb temperature of the air leaving the unit? Show the state of
the inlet and leaving air on the psychometric chart.
Air In
6.9 m3/min
24 C, 80% RH
Portable
Dehumidifier
Air Out
Specific humidity = ?
T dry bulb = ?
400 W
Liquid water
19 kg/day
Page 2 of 2
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
Fall10
1.044J, 2.45J, 4.42J
Homework Set #6
1. A low density fiberglass insulation has an R value of 11 (BTU/hr ft2 oF)-1 when used in
a standard 2x4 wall cavity. To achieve a higher insulation, a contractor compresses the
fiberglass so that there are two layers of the insulation in the 2 x 4 wall cavity. He states
that the wall has an R value of 22. Do you agree? Explain.
2. A flat roof insulation system uses aluminum screws to hold down flat insulation
panels. The screws are 1/4 inch diameter, 2 inches long and spaced 4 inches on center in
a square array. The top of the insulation uses a thin aluminum sheet as a weather barrier
and a reflective layer. Underneath the insulation is a corrugated steel roof. The
insulation is two inches thick and has a conductivity of 0.015 BTU/hr ft oF. The screws
pass through the insulation and are anchored in the corrugated roof. The effective U
value of the insulation system plus screws is defined as U=q(total)/A(total)T where
q(total) is the sum of the heat transfer through the aluminum screws and the insulation.
Assume that the convective heat transfer coefficient on the inside of the corrugated
surface and on the outside over the top of the thin aluminum sheet is 2BTU/hr ft2 oF.
Calculate the U value for two limiting cases: 1) There is large lateral heat transfer and the
corrugated sheet and the thin aluminum are each at a uniform temperature and ; 2) there
is no lateral heat transfer through the corrugated sheet and the aluminum panel, heat
transfer through the screws and the insulation occur in parallel with no interaction
between the heat flows in the respective cross-sections.
3. A window has two vertical panes of glass separated by an one inch air gap. The glass
panes can be considered black bodies at uniform temperatures of 40oF and 60oF,
respectively. Estimate the total heat transfer, convection plus radiation, through the
window space. Note: convection through a vertical space is a very weak function of the
layer height, as a first approximation this effect can be neglected.
4. How much does the result of problem 3 change if one glass pane has a low emissivity
coating which reduces its emissivity to 0.2. Instead of the low emissivity coating, a third
layer of opaque glass is placed midway between the two; how much is the convective
heat transfer changed, is the radiation also changed?
5. Estimate the total heat loss from a wood frame house in the Boston area for the heating
season of one year. Boston averages 5634 degree days for a typical heating year. The
walls are 2 x 4 filled with fiberglass and covered with one inch of polyurethane foam
insulation sheathing. The windows are double glazed with a low e coating. The attic has
10 inches of low density fiberglass insulation. Neglect heat loss from the foundation.
The house is a single story with 2000 ft2 of floor area. The perimeter is 220 ft. and the
outside walls are 12 feet high. Fifteen percent of the outside walls are windows. There
are 0.3 air changes per hour in the house. Neglect additional losses through doorways,
etc. Use values from other homework problems or reference tables to determine U
values.
1
Fall10
1.044J, 2.45J, 4.42J
Homework Set #6
6. A person is seated in a room which has still air. The room surfaces are all black and at
the same temperature as the air, 70oF. The person is now seated in front of a large
window which is cold, 50oF. The window and the person can both be considered as a
black body. The rest of the room walls are still at 70oF. Estimate how much the room air
temperature must be increased for the person to have the same net heat loss from their
entire body surface as in the original case without the window? In both cases the surface
temperature of the person is unchanged. You will need to estimate some values of the
convective and radiative heat.
9. Try to determine the thermal resistance of a typical MIT window facing Killian Court.
On a cold night use the IR camera to measure the exterior surface temperature of the
various window components. Then using your estimate of the radiation and convection
heat transfer from the exterior surface make an estimate of the U value of the specific
component, e.g, glass, frame, etc.
Repeat this for the exterior surface of the masonry wall.
What is your recommendation to increase the energy efficiency of the entire exterior
envelope?
10. The courtyard in the center of the Gardner Museum in Boston is enclosed with a
glass roof. The glass is supported by a steel frame. The steel, 2 cm thick, extends in a
solid piece from the inside to the outside as shown in the figure. The outside surface of
the steel is painted black and has a convective heat transfer coefficient of 5 W/m2oK. The
inside air temperature is 0 oC. Assume the inside surface of the steel is painted with a
silver paint that has an emissivity of 0.1. The inside convective heat transfer coefficient
is 3 W/m2oK. The inside air temperature is 20 oC and the relative humidity is 45 percent.
Assume the steel surface on the inside radiates to a black body at 20 oC and the steel
surface on the outside radiates to a black body at 0 oC.
a) Draw the electric analogy for the heat transfer through the steel frame by using
the linear form for radiation heat transfer (ht).
2
Fall10
1.044J, 2.45J, 4.42J
Homework Set #6
b) What is the inside temperature of the steel frame?
c) Will water condense on the inside surface of the steel frame?
d) If the inside surface of the steel is painted black, will this cause worse
condensation problems?
Outside air Tout = 0 C
Black surface, h(convection) = 5 W/m2K
Steel frame
2cm
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
FALL 10
1.044J, 2.45J, 4.42J
Homework #7
-------------------------------------------------------------------------------------------------------------------------------
Not required
To be discussed
Example 18.4
2)
18.8
3)
18.9
4)
18.12
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
4.42J
Design Project 1
Due: November 3, 2010
In Class at 11:00 AM
MIT has undertaken a program to improve the energy efficiency of all existing buildings.
Through a cooperative agreement with the electrical utility NSTAR, MIT will be rewarded for
each efficiency improvement that can be documented. You are asked to pick one building or
wing of an existing building on campus and focus on one or two particular inefficient energy
features such as exits doors. You are asked to access the current energy use, develop redesigns
of components or operations that substantially improve energy efficiency and predict the
energy savings and economics of these new designs. The new concepts should an outstanding
sustainable design that is also financially sound.
In Design Projects 1 and 2 you are asked to select a building and propose and assess
innovative building designs, technologies and operating schemes that will yield an outstanding
sustainable building. For Design Project 1 you should first collect basic information about the
proposed building features you want to address. Some of this information might be available
from the MIT Facilities Department. In addition, you should develop general conceptual
designs and technologies for the building and site and qualitatively describe their importance.
In phase 2 you will quantitatively assess the behavior of the proposed schemes and refine your
designs.
Students should work on this project in teams of two and produce a written report. The report
should indicate the contribution of each student. Address your report to readers who have
some technical background. This report for Design Project 1 should be the preliminary
assessment of the proposed scheme and additional concepts that you propose. The report
should include an introduction, discussion of the above items and diagrams, and conclusions
and recommendations.
The grade for this project is equivalent to one half of an hour quiz.
You are required to discuss your preliminary finding with the instructor and TA (unpaid but
highly knowledgeable consultants) at least once before the due date.
Your design will be graded in terms of:
Clarity and thoroughness of the report
Originality
Practicality
Punctuality (Late reports will lose substantial credit)
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
1,2,3,4 and 10
Subject Outline
Fundamentals of
Thermodynamics
Heat Transfer
Fluid Flow
DESIGN PROJECT 2
LIGHTING IN ARCHITECTURE STUDIO 7
skylights
300mm sunpipes
Plastic Surgery
Current Situation
Before
After
477 - 479
Commonwealth
Dining Room
Windows
Storm Windows
Leaky due to wood frames
Outside trim
Estimated Savings
of Caulking and
Weather stripping
Sash pulley
and cord
Top sash
Blind stop
Parting sash
Bottom sash
$2164/year
Stool
Sill
Experiment Setting:
Dining Room
RESULTS
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
MIT Architecture
L. Glicksman
Fall 2008
4.42 FINAL
Open Book
1) (25) A company that makes heat pump components had decided to use their
knowledge and some of their existing equipment to make small electric power generators
for buildings in the developing world.. They want to use their existing refrigerant, HFC
134a as the working fluid in the power cycle. They plan to burn natural gas as the heat
source. Their initial test was disappointing as they only achieved an efficiency of 4
percent. In this test the natural gas was burned with lots of air so the combustion gas only
achieved a temperature of 50C. Heat was rejected to the environment; the environment
was at 20C
a) If we improve the heat exchangers, the boiler and condenser, by significantly
increasing their area while keeping the natural gas and environmental temperatures at
50C and 20C, respectively, what is the limit to the efficiency gain that could be achieved
with the power generator?
b) One suggestion is to significantly increase the temperature of the combustion gas
while the environment remains at 20 C. They still want to use HFC134a as the working
fluid within the power cycle. Reviewing the saturation properties of HC134a are there
some practical limits to achieving an efficiency of 20 percent or greater?
c) What is your recommendation for major charges in the overall project concept to
achieve a practical power generation device with an efficiency above 30 percent?
Work
pump
Turbine
Condensor
2) (25) The indoor conditions in a room are 21C and 50 %RH. There is still air in the
room. When the outside temperature is 0C, the inside glass surface has a temperature of
16C, measured at the center of the glass surface at night. The glass is a double glazed unit
with unknown properties. The inside surface of the glass does not have a low e coating on
it.
a) With these temperature measurements can you estimate the U value neglecting framing
elements?
b) For another window, the same inside glass temperature, 16C is measured when the sun
is shining on the window and the room air conditions and the outside temperature are the
same as part (a). Is the U value for this window the same as that in part (a)? If not, is the
U value of this window larger or smaller than the window in part a? Remember, the U
value always refers to the heat transfer through the window without the presence of solar
radiation.
c) For the same conditions as part (a), condensation just begins to form on the inside of
the framing elements. Can you estimate the U value of a framing element based on its
surface area?
d) Without replacing this window in parts a and c, suggest ways to improve its thermal
performance.
3. (25) We would like to cool a building so that the interior is maintained at 24 C and
50% RH. The outside conditions are 35 C and 50% RH. We know that 60% of the heat
in the room is sensible and 40% is latent. We will supply 1200 kg/hr of air to the space.
To achieve the supply air conditions, we will use the following processes:
1. Cool the outdoor air by mixing it with some of the return interior air.
2. Sensible cooling to saturation temperature.
3. Dehumidification.
4. Sensible heating until we reach the desired supply conditions.
a. We will supply air at 18 C. What is the relative humidity of the supply air?
b. During step 1, we will mix 60% return air with 40% outdoor air. What are the
resulting temperature and humidity of the mixed air?
c. How much water (in kg/hr) will be removed from the air during step 3?
d. During step 4, what is the rate of sensible heat (in kJ/hr) that we will need to put into
the air?
4. (25) A cooling tower can be used to remove heat from water. The cooling tower in the
diagram below cools water from 40 C to 25 C. Air enters the bottom of the tower at 20
C and 50% relative humidity. Air exits the top of the tower at 32 C and 95% relative
humidity. The mass flow rate of the water which enters the tower is 10,000 kg per
minute.
Air at 32 C,
95% RH
Water at 40 C
Air at 20 C,
50% RH
Water at 25 C
Water
a. Assuming steady state, write expressions for the energy and mass balance of this
system.
b. What is the mass flow rate of air entering the cooling tower?
c. What is the mass flow rate of water which leaves the cooling tower?
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
4.42 Quiz 1
An inventor proposes a refrigerator that makes ice which is then melted and
used to cool a cold storage room. The refrigerator is put into a closed insulated
room without any air flow into or out of the room. It is turned on when the water is
liquid at 0C, the initial room temperature. It makes 10kg of ice which is then
melted to liquid at 0C without any evaporation of the water.
a) Will the room temperature increase or decrease for the entire process
(from the time the refrigerator is turned on to the time the ice has melted)?
b) If the refrigerator has a COP of 3 and it is only used to make the ice, how
much electrical energy does the refrigerator require? Take the internal
energy change from ice to liquid water at 0C as 334 kJ/kg. The COP is the
rate of useful cooling to the rate of electrical energy consumed.
c) If 0.25 kg of water evaporates after all of the ice has melted, does the
room temperature increase or decrease over the entire process?
An MIT fraternity holds a party in their largest common room, which is 10m long x 10m
wide x 3m high. The party lasts 4 hours and 300 students attend. Because everyone is
dancing, each person gives off 300 Btu/hr of sensible heat. The home theatre system
uses 1000W. Two 100W lights are also on.
The room has a 0.1m concrete slab floor. The air in the space and the slab are initially
at 68 F. Assume that the specific humidity remains constant for both problems.
a. If the room is perfectly insulated and there is no ventilation system, what is the
temperature of the air in the space at the end of the party? Assume that the air and floor
slab end up at the same temperature and that all electrical equipment is on the whole
time. Is this a comfortable temperature?
b. For their second party, the frat brothers decide to naturally ventilate the space using
two windows, each 1.5m x 2m. The temperature of the air outside is 60 F and the wind
velocity is 2 m/s. Let vin be the velocity of air entering the open windows. Assume that
vin = 0.35 vwind and that all the rate of air leaving the space is the same as air entering the
same. If all other conditions stay the same, what is the temperature of the air in the
space at the end of the second party? Again assume that the air and floor slab end up
at the same temperature and that all air is well-mixed. Is this a comfortable
temperature?
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
4.42 QUIZ 1
Open Book
October 27, 2006
Fall 2006
1) (50)
In the winter an automobile is driven into a well insulated garage with
internal dimensions 4m x 5m x3m. The air in the garage is initially at 100C.
The car is mostly steel with a mass of 1500 kg and a specific heat of 500
J/kg K. The car is initially at 00C except for the engine. The engine
temperature is 1000C and consists of 150 kg steel and 20 kg liquid water.
Neglect heat transfer to the envelope and floor of the garage.
(a) What is the final temperature of the garage when the car, engine
and air in the garage reach a single uniform temperature?
(b) If the engine has 10 kg liquid water and 10 kg saturated water
vapor at 1000C what is the final temperature if all of the water
vapor has condensed to liquid?
2) (50)
A building uses cross flow natural ventilation to provide cooling. The
building has two zones or rooms and the air flows at steady state through
zone 1 and then flows through zone 2 in series. Each zone has the air well
mixed so that each individual zone is at a uniform temperature. The outside
air flow rate entering zone 1 is m& 1 and this equals the air flow rate leaving
zone 2 that is exhausted to the outside. Each zone has a total rate of heat
.
(b)
(c)
(d)
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
Solution:
a) For a system composed of the room plus the refrigerator and water/ ice, the net
change of the internal energy of the water to ice and back to water is zero. The
refrigerator operates in a cycle so there isnt any energy change. There is only a
flow of electricity into the room, an energy gain, so the room temperature will
increase.
b) COP = Qcool/Welec
Welec = Qcool / COP = 10x 334 /3 = 1113 kJ which is the net energy flow into
the room
c) In this case the final state of the water has a higher internal energy of 0.25x2375 =
594 kJ. This is less than the electrical energy so the room temperature still rises.
An MIT fraternity holds a party in their largest common room, which is 10m long x 10m
wide x 3m high. The party lasts 4 hours and 300 students attend. Because everyone is
dancing, each person gives off 300 Btu/hr of sensible heat. The home theatre system
uses 1000W. Two 100W lights are also on.
The room has a 0.1m concrete slab floor. The air in the space and the slab are initially
at 68 F. Assume that the specific humidity remains constant for both problems.
a. If the room is perfectly insulated and there is no ventilation system, what is the
temperature of the air in the space at the end of the party? Assume that the air and floor
slab end up at the same temperature and that all electrical equipment is on the whole
time. Is this a comfortable temperature?
b. For their second party, the frat brothers decide to naturally ventilate the space using
two windows, each 1.5m x 2m. The temperature of the air outside is 60 F and the wind
velocity is 2 m/s. Let vin be the velocity of air entering the open windows. Assume that
vin = 0.35 vwind and that all the rate of air leaving the space is the same as air entering the
same. If all other conditions stay the same, what is the temperature of the air in the
space at the end of the second party? Again assume that the air and floor slab end up
at the same temperature and that all air is well-mixed. Is this a comfortable
temperature?
Solution:
a. First find the total amount of heat gain in the room:
Qpeople = 300 people * 300 Btu/hr * 1055 J/Btu * 4 hrs = 3.8 x 108 J
T = 21.5 C
b. We know that the total amount of heat gain in the room will be the same as in part a.
For this problem, it is easier to use the rate of heat gain in W:
dQtotal/dt = 3.97 x 108 J / (4hrs * 3600 s/hr) = 27575 W
We can also find the rate of internal energy change in the slab:
dUslab/dt = (880 J/kg-K*2100 kg/m3*10 m3*T) / (4hrs*3600 s/hr) = 1283*T W
Now find the mass flow rate of the air:
= v = 0.35* * vwind*Awindow = 0.35*(1.22 kg/m3 )*(2 m/s)*(6m 2 ) = 5.12 kg/s
m
Consider the energy conservation equation with the addition of moving air into the space:
+U
slab + m
inhin - m
inhout = 0
E = Q
Since we know that the rate of air entering the space is equal to that leaving, we can
simplify to:
+U
+m
slab + m(h
in - hout) = Q
slab * cslab * Tslab + m
air * cair * Tair = 0
E = Q
=m
slab * cslab *(Tfinal - Tinitial) + m
air * cair * (Tfinal - Tinitial)
Q
Plugging everything in, we solve:
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
a.) Calculate the heat transfer in W/m2 for the wall section shown in the figure below.
The wood studs occupy 20% of the surface area of the wall and the insulation occupies
80%. The temperature of the air outside is 0C and the temperature of the air inside is
20C. Assume that there is no lateral heat transfer. Include convection and radiation heat
transfer in your calculation. The outdoors and indoors can be considered black bodies at
0C and 20C respectively.
kplywood = 0.15 W/m-K
kinsulation = 0.035 W/m-K
kgypsum = 0.2 W/m-K
kwood = 0.15 W/m-K
Toutside = 0 C
Plywood
Insulation
1 in.
3.5 in
Stud
Gypsum
0.5 in
Tinside = 20 C
b.) A contractor you know suggests using steel studs instead of wood. He believes that
because you need less steel than wood for structural stability, the increased insulation will
decrease the total heat transfer across your wall section. Is he correct? Calculate the heat
transfer in W/m2 for a wall section with steel studs. Assume again that there is no lateral
heat transfer. For this case, the insulation occupies 90% of the wall surface area and the
steel occupies 10%. (ksteel = 43 W/m-K)
c.) Is the interior wall temperature the same over the insulated and stud sections? For
case b, approximate the temperature of the interior wall over an insulated section.
Compare this to the temperature of the interior wall over a steel stud.
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
4.42J/2.66J/1.044J
Quiz 2
Open Book
1) (50) Estimate the energy performance of MITs traditional single pane windows per
square meter of surface area. Consider both convection and mid-long range infrared
radiation from both the inside and outside surfaces of the window. Neglect air leakage,
the window frame, and do not include solar radiation for parts a and b.
a) If the inside air temperature is 23 C and the outside is 0 C, estimate the rate of heat
transfer through the window from inside to outside, Use typical numerical values for the
heat transfer components. Assume the glass is a black body for the infrared radiation in
the mid-long range wavelengths.
b) What is the total heat lost through one square meter of window over a typical heating
season in Boston? Use the same assumptions used in part a.
c) Will the result in part b increase or decrease substantially when including each of the
following: the window frame, air leakage, or solar radiation? Treat each of these
individually. You do not need to do detailed calculations for part c.
2) (50) Consider what it takes to keep an indoor pool area at a comfortable temperature
and humidity during the winter. Assume that there is one pool that is 50 m long and 20
m wide in a room that is 70 m long, 30 m wide and 10 m high. Assume that the pool
room is to be kept at 28 degrees Celsius and 50 percent relative humidity and that the
outdoor conditions are 0 degrees Celsius and 20 percent relative humidity.
a) (10) Calculate the latent heat load associated with evaporation of water from
the pool. Because the pool water is heated and air blows over the surface, some of
the water near the surface of the pool evaporates into the air, removing heat from
the pool water. Assume that 10 kg of water vapor per every 100 square meters of
pool evaporates every hour. What is the latent heat load associated with
evaporation from the pool?
b) (10) Determine the sensible heat fraction. The latent heat and sensible heat
loads are both important for determining how to condition air to keep the room at 28
degrees Celsius and 50 percent relative humidity. Assume that the latent heat load
you found in part a) is the only latent load on the room. Assume that you find that
there are sensible heat losses from the room that are one third the magnitude of the
latent heat gains. What is the sensible heat fraction, SHF = (Sensible heat load) /
(Total heat load), for the room?
c) (10) Draw the condition line on the psychrometric chart. The condition line is
the line on the psychrometric chart which defines the state of air supplied to the
room to maintain desired indoor conditions. In general, the supply air state can be
anywhere on this line. The slope of this line can be found using the SHF and the
gauge in the upper left hand corner of the psychrometric chart.
d) (20) Determine the temperature and relative humidity of the supply air
delivered to the room. Draw two lines on the chart representing the process to
produce this supply air. Assume that 20% of the air supplied to the room must be
fresh, outdoor air. Mix the indoor air with outdoor air and sensibly heat it to achieve
suitable supply air conditions in the most energy efficient way (a graphical solution is
sufficient, you need not write equations). Draw the process lines on the
psychrometric chart. What is the temperature and relative humidity of the supply
air?
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
a.) Calculate the heat transfer in W/m2 for the wall section shown in the figure below.
The wood studs occupy 20% of the surface area of the wall and the insulation occupies
80%. The temperature of the air outside is 0C and the temperature of the air inside is
20C. Assume that there is no lateral heat transfer. Include convection and radiation heat
transfer in your calculation. The outdoors and indoors can be considered black bodies at
0C and 20C respectively.
kplywood = 0.15 W/m-K
kinsulation = 0.035 W/m-K
kgypsum = 0.2 W/m-K
kwood = 0.15 W/m-K
Toutside = 0 C
Plywood
Insulation
1 in.
3.5 in
Stud
Gypsum
0.5 in
Tinside = 20 C
b.) A contractor you know suggests using steel studs instead of wood. He believes that
because you need less steel than wood for structural stability, the increased insulation will
decrease the total heat transfer across your wall section. Is he correct? Calculate the heat
transfer in W/m2 for a wall section with steel studs. Assume again that there is no lateral
heat transfer. For this case, the insulation occupies 90% of the wall surface area and the
steel occupies 10%. (ksteel = 43 W/m-K)
c.) Is the interior wall temperature the same over the insulated and stud sections? For
case b, approximate the temperature of the interior wall over an insulated section.
Compare this to the temperature of the interior wall over a steel stud.
Solution:
a.) Approximate hout ~ 20 W/m2-K, hin ~ 5 W/m2-K
b.) The heat transfer through the insulation section is the same.
Calculate total resistance for steel stud section:
The contractor was wrong. The steel stud wall allows more heat transfer than the wood
stud wall, even though there is more insulation in the steel stud section.
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
Heat Transfer
Leon R. Glicksman
1991, 1997, 2004, 2005, 2010
1)Introduction
Heat transfer deals with the rate of heat transfer between
different bodies. While thermodynamics deals with the magnitude of
heat exchanged in a process, heat transfer is necessary to determine
the time required for a process or alternatively the size of a surface
necessary to achieve a certain total rate of heat transfer.
Heat transfer analysis permits a calculation of the heat loss
from a building surface to the surroundings for a given building size,
window area and wall design, e.g. the level of insulation in the wall
cavity. The comfort conditions for occupants in a room is determined
by a balance of heat transfer from the person to the air surrounding
him or her as well as the heat transfer to the walls of the interior.
The size and cost of a heat exchanger is also determined by
considering the heat transfer between the fluid streams in the
exchanger.
In other fields, heat transfer plays a key role as well. The
design of integrated microprocessors which contain very closely spaced
elements, each with a finite amount of heat generation, is limited by
the requirement for adequate cooling so that the operating temperature
of the electronic components is not exceeded. Reentry of the space
shuttle in the earth's atmosphere must be carefully programmed so that
temperature extremes due to air friction are confined to the
insulating tiles on the shuttle's surface.
Modes of Heat Transfer
Following thermodynamics, heat transfer is that energy transfer
which takes place between two bodies by virtue of a temperature
difference between the bodies. From the second law considerations it
can be demonstrated that there is always a net positive energy
transfer from the body at a high temperature to a second body at a
lower temperature. Following the definition of heat, there are only
two physical mechanisms for heat transfer: (1) electromagnetic waves
produced by virtue of the temperature of a body, referred to as
thermal radiation heat transfer and (2) atomic or molecular motion in
a medium between the bodies exchanging energy, referred to as
conduction heat transfer.
q ~ A gradT
(2.1)
kA
dT
dx
(2.2)
kA
T1 T2
L
(2.3)
For this case the temperature varies linearly across the width
of the slab. One can consider an analogy between the solution
for steady conduction and for steady D.C. electric current flow,
Ohm's Law,
V2 V1
R
(2.4)
Table 2.1
Thermal Conductivity of
Common Materials
k(BTU/hr ft
F)
(W/mK)
Solids
Copper
Aluminum
Steel
Brick,common
Concrete
Glass
Glass fiber insulation
Ice
Plastic
Wood
219
119
25
0.2 - 0.1
0.5 - 0.8
0.5
.03
1.3
0.1
0.1 - 0.2
378
206
43
0.17 - 0.34
0.87 - 1.38
0.87
0.05
2.2
0.17
0.17 - 0.34
0.3
0.04
0.08
0.34
5
0.5
0.07
0.14
0.59
8.7
Liquids
Ammonia
Refrigerant-12
Light Oil
Water
Mercury
Gases
Air,dry
Carbon Dioxide
Helium
Hydrogen
Water Vapor (Steam)
0.015
0.026
0.009
0.016
0.09
0.16
0.11
0.19
0.015(at 212 F)0.026 (at 100
Refrigerant-11
0.005
C)
0.009
kWB A
T1 T2
LWB
(2.5)
T1 T2
For the insulation
LWB
kWB A
(2.6)
T2 T3
LI
kI A
(2.7)
T1 T5
LWB
kWB A
LI
kI A
LP
kP A
LS
kS A
(2.8)
or
T1 T5
L
kA
(2.9)
T
R
(2.10)
q5
T1 T5 A
LWB
kWB
LI
kI
LP
kP
(2.11)
LS
kS
L
kP
1/12
0.1
0.8
hr ft 2 F
BTU
(2.12)
L
kI
3.5 /12
0.028
11
hr ft 2 F
BTU
2.13)
For the composite wall in figure 2.3, the R-value of the insulation
dominates all of the terms in equation 2.11
8
Convection Heat Transfer, Introduction
temperature on the inside wall
surface, T1, and the outside
siding surface T5 are not
generally known. Rather the
interior room air temperature,
Ti, and the exterior air
temperature, Te, are the known
quantities. Consider a
wintertime condition, when the
building is at a higher
temperature then the exterior
air. The temperature through the
built-up wall continuously decreases from the inside wall at
Fig. 2.5 Temperature Distribution with Convection
T1 to the outside surface at T5.
at the Surfaces
This is shown in figure 5. The
outside surface temperature T5 is higher than the exterior air
temperature Te. In the air layer close to the building surface
the air is in motion parallel to the surface. There is heat
transfer by conduction from the building surface through this
air layer. Because there is also energy transfer by the motion
of the fluid the temperature through the air layer does not vary
linearly. Rather, there is a large temperature gradient near
the surface which decreases further from the surface until the
temperature reaches the constant air temperature Te. The layer
over which the temperature change occurs is thin, typically one
quarter of an inch or less.
energy transfer by fluid motion is called convection heat
transfer. The rate of heat transfer is proportional to the
surface area and the temperature difference between the surface
and the uniform air temperature outside of the thin surface or
boundary layer,
q ~ A(T5
Te )
(2.14)
9
q
hA Tsurface
(2.15)
Table 2.2
Convection Heat Transfer Coefficients
BTU/hr ft2
Gases, Natural Convection
Gases, Forced Convection
Liquids, forced Convection
Boiling Liquids
Phase Change
0.5-50
2-50
30-1000
200-50,000
500-5,000
10
Example
For a single glazed window
what is the increase in
thermal efficiency if the
glass is made of plastic with
k = 0.1 BTU/hr ft F instead
of glass with a k = 0.5
BTU/hr ft F? Assume that
the radiation heat transfer
remains the same.
SOLUTION
In this case convection heat
transfer from the inside air at
Ti to the glass surface acts in
series with conduction through
Figure2.7Electrical Analogy
the glass and convection to the
outside air.
The equivalent electrical circuit is shown on
figure 7 and the steady state heat transfer, neglecting
radiation, becomes
L / kA
1/ hA
1/ h
L/k
1/ h
(2.16)
e
11
1
hi
1
BTU
1
1
hr ft 2 F
1
he
1
3
BTU
0.33
hr ft 2 F
(2.17)
L
kg
1/ 8 1/12
0.5
1
BTU
50 hr ft 2 F
(2.18)
q UA(Ti Te )
(2.19)
Although U has the same units as h, U can involve a combination
of conduction and convection heat transfer and is not physically
meaningful although it may be helpful for estimate purposes. A
number of handbooks like the ASHRAE Handbook of Fundamentals
list values of U for typical built up wall and roof
construction.
These values of U include convection heat
transfer on the inside and outside for an assumed wind velocity
and interior air circulation conditions.
Two-dimensional Heat Transfer
12
Fig. 2.8
Most walls are not uniform across their entire surface
area. Wood framing using 2 by 4's has studs spaced at regular
intervals in the wall cavity, fig 2.8.
Clearly the heat
transfer through the studs is higher than the heat transfer
through
an
equivalent
cross-sectional
area
containing
insulation.
The heat transfer through the wall cavity is due to two
parallel conduction paths, one through the studs and the other
through the insulation.
If the lateral resistance is very
large, i.e., the lateral conductivity of the wallboard and the
plywood approaches zero, then the overall heat transfer can be
modeled as two separate parallel heat flow paths from Ti to Te,
shown in fig. 2.9.
The heat transfer through the studs is
qstud
Ti Te Astud
1/ hi
( L / k )WB ( L / k ) S
( L / k ) P 1/ he
(2.20)
13
qinsulation
Ti Te Ainsulation
1/ hi
( L / k )WB ( L / k )insulation ( L / k ) P 1/ he
(2.21)
The total heat transfer rate is the sum of equations 2.20 and
2.21. The true value of the two-dimensional heat transfer lies
between these two limiting cases of very small lateral
conductivity and very large lateral conductivity.
The electrical analogy of this, in one limit, is shown in figure
2.9 with the insulation and the studs in parallel.
It is important to note that this approximation for the twodimensional case represents one limiting case, the temperature
on the inside of the wall board where it contacts the stud will
be different from the temperature of the wall board in contact
Fig 2.9 Limiting Case of Small Lateral Conductivity in Wall Board and Plywood
with the insulation. Similarly the temperature of the plywood
will differ in the lateral direction between the stud and the
insulation. These temperature differences across the wall board
will cause heat to flow laterally into the stud, fig. 2.10.
Similarly
heat
will
flow
laterally out from the stud
through the plywood. These
lateral effects will enhance
the
total
heat
transfer
through the stud. This will
increase the overall heat
transfer
over
the
values
calculated from the sum of
equations 2.20 and 2.21.
Fig. 2.10
lateral heat Flow in the vicinity of the stud
The
exact
analysis
of
these
two-dimensional
effects
is
difficult. We can look at the other extreme case. If the wall
board and plywood were replaced by metal sheets, something
sometimes seen in metal walled buildings, then the resistance to
lateral conduction through them would be reduced. In the
limiting case w e could assume that the wall board and plywood
would have a very high conductivity and the temperature would be
uniform in the lateral direction across these elements. The
electrical analogy for this case is shown on fig. 2.11.
The
solution shown in figure 10 is only valid when the lateral
resistance is small, i.e., the y direction conductivity of the
wall board and the plywood approaches infinity.
In this case, the heat transfer through the studs and insulation
acts in parallel between T2 and T3, the sheet rock and plywood
temperatures, respectively. The heat transfer through the two
elements is summed,
T2 T3
( L / kA)insulation
T2 T3
( L / kA) stud
(2.22)
T2 T3
( L / kA)insulation ( L / kA) stud
T2 T3
Requivalent
(2.23)
of
the
Fig. 2.13
dE
dT
hA(T T )
(2.24)
Mc
dT
dt
hA(T T )
(2.25)
d (T T )
(T T )
hAdt
Mc
(2.26)
T T
(T0 T ) exp
hAt
Mc
(T0 T ) exp
(2.27)
where
is the thermal time constant of the slab with convective
heat transfer coefficient h and
Mc
hA
(2.28)
Example
A two inch thick steel structural beam has natural convection
heat transfer over one surface; the opposite side is insulated.
Find its time constant.
Solution
First it must be determined if the steel can be assumed
uniform in temperature across its width.
Since only one side
has convective heat transfer, referring to figure 2.13, L in
this case should be the full width of the steel beam. The Biot
number is
hL
k
2(2 /12)
20
1
60
(2.29)
Mc
hA
LAc
hA
Lc
h
400(0.1)(2 /12)
2
3.5hrs
1.2
q
A Ts Ta
(3.1)
distance at which the thermal effects are felt, at any location x, will be specified as , the thermal
boundary layer thickness.
At any position x the variation of air temperature normal to the plate surface, the y axis is shown
on figure 3.3. The rate of heat transfer from the plate surface is determined by the conduction
into the air at y=0. This can be calculated from,
T
y
ka
(3.2)
y 0
Cka
Ts Ta
(3.3)
where the constant C should be of order of magnitude unity. Now substituting this into the
definition of the convective heat transfer coefficient,
q
(Ts Ta )
ka (Ts Ta )
(Ts Ta )
ka
(3.4)
A smaller temperature increase will reduce the thermal boundary layer thickness. Therefore, an
increase in the density will increase the heat transfer coefficient, one reason that liquid water has
a higher convective heat transfer rate than air. An increase in the specific heat of the fluid flowing
over the plate has the same behavior as an increase in density.
As the plate length is increased the air will flow over the plate for a longer time. Heat transfer will
penetrate a further distance from the plate surface. The thermal boundary layer thickness will
grow larger. When averaged over the entire plate length , the average thermal boundary layer
thickness will become larger and the average heat transfer coefficient will be smaller. Note, the
total heat transfer will be higher for the longer plate but the heat transfer per unit area will be
smaller. To augment the heat transfer when possible, designers will break a long surface up into a
series of smaller surfaces. This can be done by physically separating sections of the plate or by
placing an array of ribs at right angles to the flow to break up the boundary layer and restart it.
Table 3.1 Key Parameters Influence on Convective Heat Transfer
Parameter
Velocity increase
decreases
h increases
Density increase
decreases
h increases
decreases
h increases
Thermal conductivity ka
increase
increase
h increases
decreases
h increases
When the thermal conductivity of the fluid passing over the plate is increased, y using a higher
conductivity gas or liquid there are two elements in play. The thermal boundary layer thickness
will increase because of augmented means of heat transfer through the fluid. Remember that h is
proportional to the ratio of conductivity to boundary layer thickness. In this case k increases faster
than and the heat transfer coefficient increases. It should be expected that when we increase
the mechanism for heat transfer, in this case the molecular conductivity, that the rate of
convection will increase.
Turbulent Flow
At low velocity, the fluid flows in very smooth paths about parallel to the plate surface. As
the velocity is increased a point is reached where the fluid motion is much more chaotic
characterized by eddies in the flow near the plate surface. This is termed turbulent flow.
Turbulent flow over a flat plate is found to occur when the Reynolds number Vx/ exceeds
300,000. x is used to indicate the distance from the leading edge; the front of the flat plate can
have laminar flow while the rear experiences turbulent flow. The distinction between laminar and
turbulent flow is important because the eddies in the turbulent flow tend to bring fluid at the
ambient temperature Ta much closer to the heated plate surface. In effect the eddies reduce the
distance for conduction heat transfer and can markedly increase the heat transfer coefficient,
sometimes by an order of magnitude or more.
At can be seen that the convective heat transfer is a function of the fluid properties such as
density and conductivity, the flow conditions and the surface geometry. Given below are a few
dimensional expressions that can be used for specific cases. The constants in the equations
already include the fluid properties.
Laminar flow expressions for h
Using air properties at room temperature h for laminar flow over flat plates can be found as
V
h 0.71
L
0.5
(3.5)
V
h 12.7
L
0.5
(3.6)
In this form h is in BTU/hrft2F, V is in ft/sec and L is in ft. Note, water gives a much higher heat
transfer coefficient than air because it has a much higher thermal conductivity as well as a higher
density and specific heat.
Turbulent Flow
At low velocity, the fluid flows in very smooth paths about parallel to the plate surface. As
the velocity is increased a point is reached where the fluid motion is much more chaotic
characterized by eddies in the flow near the plate surface. This is termed turbulent flow.
Turbulent flow over a flat plate is found to occur at higher velocities and longer plate lengths. Also
flowing liquids will reach turbulent flow at lower velocities than gases.
For air near room temperature turbulent flow is reached when the product of plate length and air
velocity exceeds,
VL 50
ft
ft
s
(3.7)
0.55
V 0.8
L0.2
(3.8)
For water
ft
ft
s
V 0.8
21.2 0.2
L
VL 3.9
h
(3.9)
q
D x TS TM
(3.10)
0.34
V 0.8
D 0.2
(3.11)
V 0.8
h 13 0.2
D
where V is given in ft/sec and D is in feet.
(3.12)
Just as forced flow, laminar flow exists at low velocities. The exact expression for natural
convection of air over a vertical plate at room temperature is
TL3 1000 o F ft 3
h
0.29
T
L
1/ 4
(3.13)
TL3 1000
h
0.21
1/ 3
(3.14)
wall. The overall heat transfer can be represented by a heat transfer coefficient defined in terms
of the two wall temperatures,
(3.15)
Figure 3.5 shows measured results for eight foot high walls. hc is a function of the
spacing between the walls and , the temperature difference from the hot to the cold wall. At a
small spacing and/or a small temperature difference the buoyancy effects are minimal and hc is
simply the ratio of air conductivity to wall spacing. As the spacing is increased, hc reaches a
constant, typically a spacing between 1/2 and 3/4 inch is optimum. Radiation heat transfer
across the cavity must be added to the convection. If there is infiltration of outside air into the
cavity the energy transfer may be increased considerably.
10
0.9
0.8
0.7
0.6
0.5
60 F
40
30
20
10
0.4
0.3
0.2
Conduction only
0.1
0
1.50
2.00
2.50
3.00
3.50
A T4
qemitted
(4.1)
where T is the absolute temperature and is the Stefan-Boltzmann constant, which has the
value 0.17 x 10-8 BTU/hr ft2 R4 or 5.7 x 10-8 W/m2 K4. Because of the non-linear nature of the
expression, radiation becomes progressively more important at higher temperatures although
there is considerable radiative heat transfer between bodies at room temperature.
The black body radiation is emitted over a range of wavelengths. The emitted energy at
a single wavelength , qre , can be defined so that
qemitted
qre d
(4.2)
Figure 20 shows the distribution of qre as a function of wavelength for black bodies at three
temperature levels. For solar radiation, the sun has an effective black body temperature near
10,400 R, a majority of the emitted energy is in the visible wavelengths and the balance of the
energy is in the near infrared below 3 m. In contrast, the energy emitted by a black body at
room temperature falls in the infrared wavelength range from 8 m to 40 m. For any black body
at temperature T eighty percent of the total black body emissions occurs when the product of
the wavelength and the absolute temperature, T, is between 4000 ( m)( R) and 17,000
( m)( R). One half of the total radiation is emitted at wavelengths equal to or below the value of
T equal to 7400 ( m)( R).
Material Properties
In the visible wavelengths many common building materials are not good absorbers.
The fraction of the black body radiation absorbed by a body at a given wavelength is given by
the monochromatic absorptivity , the values of
lie between zero and one. In the visible
wavelengths, white paint, wood and plaster have
values between about 0.1 and 0.5 see
Table 3. In the infrared above 4 or 5 m wavelengths almost all common building materials
except shiny metals have
of 0.8 or higher. Plate glass which is transparent in the visible
wavelength becomes a very good black body in the infrared wavelengths with
0.9.
greater than
q1
A1 T14
(4.3)
All of the energy emitted by plate 1 is absorbed by plate 2. Similarly all of the energy emitted by
plate 2, A2 T24 is absorbed by plate 1. The net radiative heat transfer is
q1
A1
T14 T2 4
(4.4)
This heat transfer takes place independent of any conduction or convection heat transfer
assuming the temperature T1 and T2 can be maintained. Thus the total heat transfer is the sum
of the radiative heat transfer given by Eqn. 70 plus the convective heat transfer between the two
plates.
In many cases it is useful to linearize the relationship given by Eqn. 70. Taking the
mean temperature as (T1+T2)/2 and T as the temperature difference T1-T2 then T1=TM+ T/2 and
T2=TM - T/2 and
T14 T2 4
T1 T2 T1 T2
2TM 2
T2
4
(4.5)
T14 T2 4
4 TM 3 T1 T2
(4.6)
qr
hr A T1 T2 where hr
4 TM 3
(4.7)
Table 4.1 gives values of hr for different values of mean temperature. These values should be
compared to the values given for convection in Table 2. At room temperatures heat transfer
Table 4.1 hr for radiation at mean temperature T
___________________________________________________________________________
Mean Temperature oF
hr (BTU/hr ft2 F)
hr(W/m2K)
0
0.7
3.8
60
1.0
5.7
200
2.0
11
500
6.0
34
1500
51
290
___________________________________________________________________________
by radiation is comparable in magnitude to natural convection. For heat transfer between two
glass sheets that make up a double glazed window, infrared radiation is important. To reduce
the radiation heat transfer one of the glass layers is coated with a very thin metallic layer. For
residential buildings this layer allows visible solar radiation to pass but reflects most of the
infrared radiation. The layer is referred to as a low e coating. The net infrared radiation can be
expressed as,
q1
A1
T14 T2 4
(4.8)
where is the emissivity of the glass covered by the metallic layer. Typically can be less than
0.1, substantially reducing the net radiation transfer.
For radiation between walls and ceiling or between a person and surrounding surfaces which
are each black bodies at different temperatures the geometry of the configuration must be
included. For example the radiation heat tranfer between a person and a large glazed wall can
be expressed as
q1
A1 F12 T14 T2 4
(4.9)
where F12 is the configuration factor between surface 1, the person, and the glazed surface. F
represents the fraction of radiation form the entire surface of the person that is directed toward the
glazed wall. When the person is very close to a large glazed surface extending from floor to ceiling, the
value of F will be close to . On the other hand when the person moves further from the window F will
decrease. If the person sits in the center of a cubic room, F from the person to the glazed wall drops to
1/6.
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
(1)
p v V = nv RT = mv R a T
(2)
for the water vapor. In these equations, the subscript a refers to the air and v to the water
vapor, n is the number of moles, m the mass, T the absolute temperature, in deg Kelvin or
Rankine, R is the universal gas constant and Ra and Rv are the ratios of R to their respective
molecular weights. At low pressure, if their and water vapor are mixed together the interaction
between the molecules of the two gases is modest so that the mixture can be considered an
ideal gas,
pV = ( na + nv )RT
(3)
where p is the total pressure of the mixture. Adding equations 1 and 2 and comparing to
equation 3 it can be seen that the total pressure in the mixture is just the sum of the pressure of
each gas existing alone at the same temperature and in the same total volume, Daltons Law,
p = p a + pv
(4)
When the gases are mixed together pa and pv are referred to as the partial pressure of air and
water vapor, respectively.
The total enthalpy is the sum of the enthalpy of the air and water vapor,
H = H a + H v = m a h a + mv h v
(5)
Dividing the total enthalpy of the mixture by the mass of the air (note, this is not the total
mixture mass), we obtain the enthalpy of the mixture per unit mass of dry air which will be
written as h without any subscript,
ma a (
H
ma
)= ma (h)= m ha + mv hv
(6)
Although this seems an odd choice just now, it will become evident why this is a convenient
choice. Dividing equation 6 by the mass of the air in the mixture,
m
h = ha +
v
hv = ha + hv
ma
Note the new enthalpy of the mixture we just defined, h, is the sum of the specific enthalpy of
the air and the product of the specific enthalpy of the water vapor and the ratio of the mass of
water vapor to the mass of air in the mixture. The air mass is sometimes called dry air to
remind the reader that only the air without the water vapor mass is being considered. Note, be
careful when you use h since different tables can use different states for the zero values of hv
and ha which are added together to get h of the mixture.
Humidity ratio or Specific Humidity
The ratio of mass of water vapor to mass of air in a mixture is referred to as the specific
humidity or the humidity ratio with the symbol (no this is not the humidity the goofy
weathermen are reporting). The advantage in dealing with the specific humidity is that if the
amount of water vapor in the air remains unchanged, the specific humidity remains constant. The specific
humidity is expressed in grams of moisture (water vapor) per kilogram of dry air. Alternatively
it is given as lbsv /lbsa or grains of water vapor per pound of dry air where 7000 grains is one
2
(7)
pound mass.
The internal energy of the mixture can also be defined in a similar form as the enthalpy,
m
u = u a +
v
u v = u a +
u v
ma
(8)
but since we will be considering open systems in steady state, we wont spend much time on
this.
Alternate definitions of humidity
Specific humidity we defined above will be useful in writing energy balances and the like but it
does not give a good feel for the degree of moisture in the air. For that there is the relative
humidity, . For ideal gases, this is the ratio of the partial pressure of the water vapor in the
mixture, pv, to the partial pressure of water vapor in a mixture saturated with water vapor at the
same temperature, Ts
pv
ps
(9)
The specific humidity and relative humidity can be related by (see for example, McQuiston and
Parker)
pa
0.622 p s
Note, must be expressed as kg water vapor/kg of dry air or lb water vapor/lb dry air in
equ.10.
Another term frequently used is the dew point temperature, Td . Td is found by cooling the
mixture of air and water vapor, at constant total pressure, until liquid water just begins to
condense. The temperature at which condensation first occurs is the dew point temperature.
It is also shown on Figure 1. Note that in this case the cooling of the mixture takes place
without adding or subtracting any water vapor from the air, i.e., at a constant specific humidity.
When the relative humidity is high, near 100%, or the dew point temperature is close to the air
temperature, the air is close to being saturated with water vapor. When this happens in the
summer you had better look for an air-conditioned space.
Example
A mixture of water vapor and air at sea level has a specific humidity of 0.013 kg
water vapor per kg of dry air.
The temperature is 25oC. What is the relative humidity and enthalpy of the mixture?
Solution
From saturation tables of water find Ps for water corresponding to 25 oC, ps=3.17
kPa
hv=2547 kJ/kg for saturated water vapor (If the water vapor is an ideal gas, hv(T) is
equal to hv sat at the same temperature).
The total pressure of air and water vapor is approximately 101 kPa. At this point Pv
is unknown, but it is generally one to two orders of magnitude less than Pa . As a
first guess take Pa as 101 kPa.
The related humidity, from Equ. 10 is,
(10)
To be more precise we can now calculate Pv from (= Pv/Ps) and correct our
guess for Pa.
To find the mixture enthalpy, we need the water vapor enthalpy, hv, found above and
ha the enthalpy of the dry air. Taking ha as zero at 25oC,
o
ha ( 25 C)= C p (25 - 0)= 1.005(25)= 25.13
kJ
kg
h = ha + hv = 25.13+(0.013) 2547 =
h = 25.13+ 33.11= 58.24
Note that in the mixture the magnitude of the air enthalpy, referenced to air at 0oC,
and the water vapor enthalpy, referenced to liquid water at 0oC, is about the same.
Therefore, changes in air temperature of about 10oC and evaporation of water
increasing relative humidity by fifty percentage points lead to the same order of
magnitude change in the mixture enthalpy. Both effects are important in an energy
balance for the air-water vapor mixture.
Measurement of the State of Mixture
The state of the air-water vapor mixture can be defined by knowing the temperature, the ratio
of mass of water vapor to air in the mixture and the total pressure in the mixture. In our
consideration the total pressure is at or close to (the building may be slightly pressurized) the
local barometric pressure. This does make some difference between say Boston and Denver
but generally sea level pressures are used. The temperature (called the dry bulb temperature in
this instance) can be found by using a conventional thermometer, thermocouple or thermistor.
The latter two are electronic devices whose voltage output is proportional to the temperature.
The most tricky measurement is the amount of water vapor in the air. In earlier days, use was
made of a wet bulb thermometer whose bulb was kept in contact with a wet wick. Some water
would evaporate from the wick, lowering the thermometer reading below the dry bulb
temperature. The difference in reading between the wet and dry bulb thermometers can then
be used to calculate the humidity of the air. The lower the relative humidity, the more
evaporation ensues and the lower the wet bulb temperature. In recent times, the humidity is
determined from the capacitance measurement of a thin film whose electrical properties are
found to vary with water vapor content. There is also an automated instrument which has a
cooling and heating element. The temperature of a mirror is adjusted until condensate is first
detected; the measured mirror temperature at this condition is the dew point temperature.
Graphical Representation
The dry bulb temperature and amount of water vapor in a moist air mixture can be graphically
shown on a psychrometric chart. Such a chart is very useful to visualize the changes undergone
by a mixture of air and water vapor as the air is conditioned. The chart is also useful in
determining the amount of energy required for a specific conditioning of the air. It is strongly
suggested that you become familiar with the chart.
Figure 2 shows the psychrometric chart for sea level in SI units. Similar charts are available for
selected altitudes and in English units. The right hand vertical scale gives the humidity ratio or
specific humidity of the mixture. Note that in most situations encountered in buildings practice
the mass of water vapor is much less than the mass of air in the mixture. Typical values of
are 0 to 20 grams of water vapor per kilogram of air. Thus, the mass of water vapor is only at
most one to two percent of the mass of air.
The horizontal axis is the dry bulb temperature. There are parallel slanted straight lines starting
from the upper left which are lines of constant mixture enthalpy per mass of dry air defined by
equ. 7. To keep the enthalpy lines straight and parallel, it turns out that lines of constant dry
bulb temperature deviate somewhat from vertical.
The chart also shows other information. Curves of constant relative humidity, , are shown as
are lines of constant wet bulb temperature. Thus, if the dry bulb temperature and relative
humidity are known, the state of the mixture can be located on the chart and the corresponding
value of the mixture enthalpy and humidity ratio read from the chart.
The left hand border represents saturation conditions of the mixture, 100% relative humidity.
0.2
0.3
0.4
-10
PE
10
0.82
15
0.76
0.74
25
20
20
-1
0
M
5
30
Y AIR
-2
0
G DR
-5
Y
UMIDIT
TIVE H
LA
10% RE
20%
30%
%
40
%
50
0.84
-15
-10
10
15
20
ER K
-15
10
15
20
25
30
25
0.88
-20
-15
-5
60
70
80
90
10
0
35
30
30
0.20
0.90
-25
-20
-10
-5
50
-4.6
-2.3
ER P
ET
IC M
-2
0
20
30
0.0
40
2.0
- CU
-1
0
10
Dh
DW
- :
-4 8.0
.0
4.0
- 8.0
UME
SEA LEVEL
SI Units
Normal Temperature
PSYCHROMETRIC
CHART
ENTHALPY
HUMIDITY
RATIO
Qs
Qt
0.1
T
EN
LO
0.5
SENSIBLE HEAT
TOTAL HEAT
0.6
J
-K
PY
HA
L
KI
PE
R
AI
Y
0.8
RA
DR
-:
VOL
UR
A
SA
C
-
1.0
W
ET
BU
LB
40
2%
4%
6%
R
8%
%
15
45
40
EH
TIV
ELA
RE
TE
M
PE
RA
TU
ITY
MID
50
10
12
14
16
18
20
22
24
26
28
0.25
0.30
0.35
SENSIBLE HEAT RATIO = Qs / Qt
1.0
RA
TU
R
4.7
7.0
11.7
90
%
3.5
TI
TE
-1.
1.2
80
%
.0
70
%
-2
0.86
60
%
2.3
25
%
-0.5.4
-0
-0.3
-0.2
-0.1
0.92
55
50
-10
-5
10
15
20
25
30
13.0
12.0
11.0
0.90
0.95
1.00
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
25.0
26.0
27.0
28.0
29.0
30.0
31.0
32.0
33.0
34.0
0.85
0.80
0.75
0.70
0.65
0.60
0.55
0.50
0.45
0.40
0.94
0.80
0.78
60
70
80
90
10
0
11
0
12
0
13
0
Comfort Conditions
pe
Effective tem
The psychrometric chart can also be used to show typical comfort conditions for indoor
environments. Shown on Figure 3 are comfort conditions for individuals doing light duties such
reading while seated wearing typical summer or winter clothing. These are obtained by
subjecting volunteers to different
temperature and humidity conditions and
Standard effective temperature and ASHRAE comfort zones
tabulating their vote on their sensation of
comfort. There are factors other than dry
70%
15
bulb temperature and humidity which are
20 100% rh
60%
important to comfort: such as air velocity,
radiant energy, and temperature gradient.
50%
For our purposes at this time we will take
15
the operative temperature in Figure 3 as
10
the dry bulb temperature.
If the
Summer
Winter
occupants
are
doing
more
intensive
10
30%
activities, such as working out in a gym,
the conditions for comfort will change
5
5
and a new chart analogous to Figure 3 can
0
be produced.
rature ET
20o
-5
-10
25o
15
20
25
Operative temperature, oC
30
Conditioning Processes
The purpose of heating, cooling and ventilation systems within buildings is to provide proper
ventilation and comfort conditions for all of the occupants of a building. Ventilation is
concerned with supplying enough fresh air to keep the concentration of pollutants such as CO2
in the building within a safe level. In terms of the comfort conditions shown on Figure 3, the
aim is to maintain the temperature and humidity conditions throughout the building within the
comfort bands shown. This requires heating or cooling the air and in some instances changing
the amount of water vapor in the air. There are a number of techniques which can be used to
accomplish this. We will start with the most straightforward ones.
Heating
When the air dry bulb temperature is below the comfort zone, such as state 1 in Figure 4a, the
temperature can be raised by forcing the air over a heat exchanger surface. On the other side of
the surface, e.g. tubes, is a fluid at a higher temperature. The heat transfer from the hot fluid
increases the energy of the air. Taking a control volume around the heat exchanger as shown in
Figure. 4b, and assuming steady state operation we can write first a mass balance for the air,
m 1 = m 2
(11)
In this process, we will write the mass flow rate of dry air without the subscript a. There isnt
any water vapor added to the air so the mass balance for the water becomes,
m w = m 1 1 = m 2 2
(12)
1 = 2
(13)
Thus, the humidity ratio remains constant during the heating. We can also write an energy
balance for the control volume,
Q = m 2 ha 2 + m v 2 hv 2 - (m 1 ha 1 + m v 1 hv 2 )
(14)
Q = m 2 ( ha 2 + 2 hv 2 ) - m1 ( ha 1 + 1 hv 1 )
(15)
Using the enthalpy of the mixture per unit mass of the dry air, eqn 15 becomes,
Q = m 2 h2 - m 1 h1
Now you can see the utility of the way h was defined for the mixture.
All of the enthalpy change for both the air and the water vapor is associated with temperature
increase and each could be given as cp T. The heat transfer in this process is referred to as
sensible heat.
The heating process is represented on the psychrometric diagram as a horizontal line from 1 to
(16)
2 since remains constant. Note that the relative humidity decreases in this process as the dry
bulb temperature increases.
To reduce the dry bulb temperature of a mixture of air and water the mixture is passed over
heat exchanger tube containing cold fluid inside. The cooling process without any addition or
subtraction of water vapor is shown on Figure 5a. The equations for the mass and energy
balance are exactly the same as the heating case.
Dehumidification
If the air has too high a moisture content and must be reduced, the process gets a little
trickier. The heat exchanger tube must be at a temperature below the dew point for the air
water vapor mixture. When that occurs, some of the water vapor will condense as liquid on the
tubes. The liquid water drains off the tubes by gravity and is collected below and disposed of.
In the idealized case, the process is shown as 2-3-4 on Figure 5a. First the mixture is cooled to
state 3 on the saturation curve without loss of water vapor. As it is cooled further, it moves
down the saturation curve to state 4 which has a lower humidity ratio and a lower dry bulb
temperature.
In the real process shown on Figure 5c, the condensation begins before the saturation curve is
reached since the tube wall temperature is normally lower than the dew point temperature.
For this process conservation of air mass yields,
m 2 = m 4
(17)
while conservation of water must balance the water vapor carried into the exchanger with the
sum of the water vapor and liquid water leaving at steady state,
m v 2 = m 2 2 = m v 4 + m l 4 = m 4 4 + m l
The energy balance between states 2 and 4 must also include the stream of liquid leaving,
10
(18)
Q 2-4 = m 4 ha 4 + m v 4 hv 4 + m l hl - ( m 2 ha 2 + m v 2 hv 1 )
(19)
Since the enthalpy of the air and water leaving the exchanger is lower than that entering, Q2-4 is
negative, the mixture is cooled. The energy balance can be rearranged by use of the enthalpy of
the air-water vapor mixture again,
Q 2-4 = m 4 ( h4 )+ m l hl - m 2 h2 = m 2 ( h4 h2 )+ m l hl
(20)
Note that in this case the rate of cooling, Q , involves the change of mixture enthalpy as well as
the enthalpy of the leaving water stream. In general the magnitude of the latter term is small
and it can be neglected.
(21)
11
(22)
Example
For the cooling, dehumidification and reheat process shown on the following figure,
use the psychrometric chart to show how an additional heat exchanger can be used to
reduce both the cooling energy and reheat energy (no, this is not violating some sacred
law, its just a use of smarts to save energy albeit with the need for an additional heat
exchanger).
Q
4
Cooling
coil
Q
Heat exchanger
12
m ( h2 - h1 )= Q T
(23)
where Q T represents the total, latent plus sensible, energy transfer rate to the air. Similarly the
increase in the water vapor can be determined by,
( m v 2 - m v 1 ) h fg = m ( 2 - 1 ) h fg = Q L
(24)
where Q L represents the latent energy transfer associated with the evaporation of water added
to the air.
Taking the ratio of equation 24 to 23,
2 - 1 = Q L
h2 - h1
Q T
We can see that the airflow rate into the room falls out and
the ratio of /h is determined by the ratio of latent to total
energy input. That is, the state of the well mixed air in the
room, state 2, must be on the line, called the condition line,
with slope /h which passes through the inlet state 1 as
shown on Figure 8b.
13
(25)
Table 1
Rates of Heat Gain from Occupants in Conditioned Spaces
Sensible (W)
Seated, light work (e.g. MIT student)
Moderate dancing (BU student)
Athletics (Harvard student)
70
90
210
Latent (W)
45
160
315
Adiabatic Mixing
To conserve fan energy and duct size in some buildings, the
temperature of the cold air in the supply system of a building
can be lowered (but at the cost of a decreased COP for the
chiller). To prevent cold drafts on occupants near the diffuser
outlet we can use a mixing box which mixes warmer room air
with the cold supply air, see Figure 9. The question is: how to
determine the dry bulb temperature and humidity of the
mixture leaving the box? In most cases the box is small enough
so that heat transfer from the external surface of the box is negligible. We can write a mass
balance for the air entering and leaving the box at steady state,
14
m 3 = m 1 + m 2
(26a)
3 m 3 = m 1 1 + m 2 2
(26b)
3 =
m 1
m 2
1+ 2
m 3
m 3
(26c)
m 3 h3 = m 1 h1 + m 2 h2
(27a)
h3 =
m 1
m 2
h1 + h2
m 3
m 3
When the supply air flow m 1 is equal to the room air to the
box, m 2 , it is easy to see that the enthalpy of the mixture at
state 3 is the average of h1 and h2 , while 3 is the average of
1 and 2. State 3 shown of the figure is half way along a
straight line between 1 and 2. For any other mixture
proportions it can be shown that state 3 is always on the
straight line between 1 and 2 with its location set by the
proportion of cold air to recycled air in the mixing box.
(27b)
In some instances, the air entering a building has too small an amount of water vapor. Water or
steam sprays are used to add moisture. In earlier times, people would put out pans of liquid
water. Water vapor evaporating from the surface would mix with the air passing over.
Sometimes this technique can be used in hot dry climates to supplement or replace the
conventional air conditioning system.
We will assume that the spray mixes with the air stream in a small mixing box which is
adiabatic, with no heat transfer from the outside surface of the box. See Fig. 10a. Just as before
we can write conservation of mass for the steady state process,
m a 1 = m a 2 = m 1
(28)
m w = 2 m a 2 1 m a 1 = ( 2 - 1 ) m 1
(29)
m 1 h1 + m w h w = m 2 h2
(30)
Note this holds whether the spray is liquid water or steam. Dividing both sides of eqn. 30 by
ma1, we can find an expression for h2,
h2 = ( 2 - 1 ) h w + h1
When the spray is a cold liquid, the enthalpy of the liquid stream
is small compared to that of the air mixture and as a good first
approximation, the enthalpy of the air mixture leaving the
mixing box is equal to the enthalpy of the mixture entering. On
the psychrometric chart the process line 1 to 2 moves at
constant h from a low humidity ratio and high dry bulb
temperature to a final state at higher humidity and lower dry
bulb temperature. The energy necessary to evaporate the liquid
water comes from the air, causing a lower temperature. In a way
this could be termed free cooling, but the price is water
consumption.
When hot liquid or steam with progressively higher enthalpy is sprayed into the air, eqn. 31
indicates that the enthalpy of the air leaving the mixing box will increase. Figure 10b illustrates
this. When the enthalpy of the steam in the spray is the same as the enthalpy of the water vapor
in the mixture entering, the leaving mixture is at the same temperature as the entering mixture.
16
(31)
17
MIT OpenCourseWare
http://ocw.mit.edu
For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.