Technical Data
Specifications apply to an SC200 installed with a single IOBGP System IO Board. Refer to the IOBGP data sheet for detailed system
input and output specifications. Some features require SC200 version 2.57 software.
126
PowerManagerII
Any SNMP Network Management Software
Third party interface management software interface
specifications available.
DCTools
Web browser (IE6, Mozilla or other compatible browser)
Mechanical
Dimensions H, W, D:
Weight:
140g [5 oz]
Mounting options:
Panel mount
Rectifier slot mount
Orientation:
Vertical or horizontal
Environmental Requirements
Ambient Temperature
Nominal:
Rated Operating Range:
Extended Operating Range:
25 5C [77 9F]
-10 to +50C (14 to 122F)
-25 to +70C (-13 to 158F)
May affect product lifetime, meter accuracy and display
contrast.
Altitude:
Humidity:
<95%RH (Non-condensing)
Location:
DC Input
Rated Voltage:
Operational Range:
18V to 60V
Earthing:
Class II
Technical Data
Issue H March 2009
Viewable area:
30.5mm x 36mm
Display settings:
Contrast
Orientation
Keypad:
Adjustable
Vertical, Horizontal Left or Horizontal Right
Set/cleared:
Language (standard):
English
Language options:
Indicators
Status LEDs
Power On:
Critical / Major Alarm:
Minor Alarm:
Audible Alarm Indicator:
Green
Red
Yellow
Enabled/Disabled (default: Enabled)
Data logging
Event Log:
10,000 records
Data Log
Records:
Continuous Log Interval:
Off-normal Log Offset:
Off-normal Log Interval:
10,000 records
10s to 1 day (default: 1800s - 30 minutes)
1.0 to 8.0V (default: 4.0V)
1s to 1 day (default: 180s 3 minutes)
Technical Data
Communications
Ethernet
Settings:
10baseT
RJ-45
TCP/IP, SNMP, S3P over IP, http (Web), https (secure Web),
CSP2 (customer specific protocol EOC)
IP Address, Subnet mask, Gateway address
Version
Speed
Function
1.1
Full Speed (12Mbits/s)
Local viewing of values and configuration using DCTools
Interface:
Connector:
Protocols:
USB
RS-232 Serial
Interface:
Connectors:
Protocols:
RS-232 (DTE)
DB9M
S3P, MII (China only), CSP2
System Communications
Interface:
Connector:
Protocols:
RS-485
RJ-45 (Rear panel)
RXP
PSTN or GSM
Dial in/Dial out on alarm
Can operate as a backup for Ethernet communications.
SMS Messaging
Alarm Message:
PowerManagerII.
Any SNMP management software (MIBs provided on request).
Documentation is also available for interfacing to third-party
software using S3P.
SNMP Interface
Functions:
SNMP Version:
MIBs supported:
Trap format options:
Get/Set/Trap
1, 2c, 3
DC Power MIB (Eaton proprietary), MIB II
Eaton (multiple trap numbers) or X.733 (single trap number)
Web Interface
Functions:
Security:
Software upgrades:
Cleared:
From DCTools.
From keypad.
Technical Data
Issue H March 2009
Alarms
Alarm severity settings:
Critical
Major
Minor
Warning
Standard alarms
Low Float, Low Load, High Float, High Load, Rectifier Fail,
Multiple Rectifier Fail, Rectifier Comms Lost, Multiple Rectifier
Comms Lost, Partial AC Fail, AC Fail, System Overload*, Load
Fuse Fail, Battery Fuse Fail, MOV Fail, ACD Fan Fail, LVD1
Disconnected, LVD1 Fail, LVD1 Manual, LVD1 Characterization
Error, LVD2 Disconnected, LVD2 Fail, LVD2 Manual, LVD2
Characterization Error, Batt Temp High, Batt Temp Low, Sensor
Fail, Battery Test Fail, Equalize, Fast Charge, Battery Test, In
Discharge, Configuration Error, Monitor OK, Battery Current
Limit, Rectifier No Load, Rectifier Current Limit, Rectifier Over
Temperature, Generator Enable, Generator Fail, Cabinet Fan
Fail, New Hardware, Unknown Hardware, Missing Hardware,
String Fail, Slave Mode
* System overload alarm can be configured in System overload
or N+1 Redundancy modes.
Optional Note:
Size:
60 text characters per alarm
Viewing: from DCTools, Web, in SNMP trap, on LCD display
User Alarms
4 (Load Fuse Fail, Battery Fuse Fail, MOV Fail, ACD Fan Fail)
6
6 (one also used as Monitor OK alarm)
Analog Inputs
Bus Voltage:
Temperature:
Current:
Standard:
Maximum:
4 (single IOBGP-00)
8 (requires second IOBGP-00)
Digital Outputs:
Analog Inputs:
48
108
32
Technical Data
Low float:
Low load:
High float:
High load:
Active Voltage Control
Default status:
Enabled
0 to 26 (default: 24)
1 to 100,000Ah (default: 300Ah)
Batteries
Disabled
0 to 100% of Battery Ah (default: 10%)
Disabled
0 to 100% of Battery Ah (default: 1%)
Closing contacts on a selected digital input changes the current
limit setting from Battery Current Limit to Engine Run Limit.
Battery Test
Default status:
Lockout period:
Start date/time:
Duration:
Termination voltage:
Interval:
Disabled
48 hours after an AC fail (set Interval to zero to override
lockout)
User selectable
1 to 1000 minutes (default: 30 minutes)
18 to 60V (default: 47.5V)
0 to 366 days (default: 183 days)
Disabled
Activation:
Current Share
Default status:
Balance:
On
2% of rated rectifier current
Default status:
Equalize voltage:
Duration:
Start date/time:
Periodic Equalize interval:
Disabled
0 to 60.0V (default: 56V)
1 to 10,000 min (default: 600 minutes)
User selectable
0 to 365 days (default: 0 days no periodic equalize)
Equalize
Disabled
Closing contacts on a selected digital input starts a Manual
Equalize cycle.
Fast Charge
Default status:
Charge voltage:
Maximum duration:
Ampere hour threshold:
Voltage threshold:
Recharge percentage:
Disabled
0 to 60.0V (default: 56.0V)
0 to 10,000min (default: 1440 minutes)
1 to 100% (default: 25%)
0 to 60.0 V (default: 48.0V)
1 to 200% (default: 110%)
Generator Control
Default status:
Disabled
Technical Data
Issue H March 2009
Disabled
System Voltages
Float voltage:
Maximum voltage:
Minimum voltage:
Temperature Compensation
Default status:
Slope:
Low cut-off:
High cut-off:
Reference Temperature:
Enabled
-10.00 to -0.01mV/C/cell (default: -4.00mV/C/cell)
-40C to +20C (default 0C)
+21C to +60C (default: +50C)
0.0C to 50.0C (default 20C)
Disabled
0 to 60.0V (default: 43.2V)
0 to 60.0V (default: 48.0V)
10 to 600s (default: 10s)
10 to 600s (default: 10s)
Disabled
0 to 6000 minutes after AC fail (default: 240 minutes)
Disabled
0 to 60.0V (default: 43.2V)
0 to 60.0V (default: 48.0V)
10 to 600s (default: 10s)
10 to 600s (default: 10s)
Disabled
0 to 6000 minutes after AC fail (default: 240 minutes)
Disabled
LVD2 operates at the same time as LVD1.
LVD1 Connect/Disconnect
LVD2 Connect/Disconnect
Technical Data
Compliances
Safety:
EN 61000-6-3
EN 61000-6-2
Environmental
Certifications
China:
MII
Europe:
CE mark
North America:
Australia/New Zealand:
C tick