Check List
Date : 01/01/2011
Page 1 of 12
Content:1) Pre-Inspection
2) Material Required/ Installation
3) CT Operated LV Metering
4) CT VT Operated HV Metering
5) Quick reference
6) RSB Metering requirements and regulations
7) Illustrations
ADDC
Date : 01/01/2011
Page 2 of 12
1. Pre-Inspection
1.1
1.2
1.3
2.2 -
2.3 -
2.4 -
2.5 -
2.6 -
2.7 -
2.8 -
2.9 -
2.10
Metering cables both ends must be with glands. i.e. panel and
meter cabinet.
2.11
All spare breakers and future load in MDB and SMDB must be
pad locked
2.12
2.13
Date : 01/01/2011
Page 3 of 12
2.14
2.15
More than two direct meters are not allowed inside one meter
cabinet if the termination cable size is 25mm or above
2.16
2.17
All the PVC (standard) boxes mounted beside the meter for
AMR system in each floor of the building ( as mentioned
above 2.16)to be looped with PVC Conduit from floor to
floor and finally at Main Electric room. Control wire with a
size 0.75sqmm 4core also should be provided through
these PVC pipes in between floor to floor. Any other type of
such cast iron pipes, flexible GI Pipes, normal flexible pipe
etc. Would not be allowed to use expect PVC Conduit.
2.18
3.2
3.3
3.4
3.5
3.6
3.7
3.8
Date : 01/01/2011
Page 4 of 12
3.9
3.10
3.11
3.12
3.13
Metering cables both ends must be gland. i.e. panel and meter
cabinet.
3.14
3.15
3.16
3.17
4.2
4.3
4.4
4.5
Separate MCBs rated 6 Amps required for each main and check
meters VT connection
ADDC
Date : 01/01/2011
Page 5 of 12
4.6
4.7
4.8
Meter cabinet and all other requirements. see no. 2.1 to 2.9
4.9
4.10
Quick reference
Max
Length
Type of Meter
Size of
Cable to
meter
Burden
of Cable
C.T Ratio
VA
Accuracy
Load in KW
100 / 5 A - CT meter
4 mm2
13
100 / 5 A
0.5
Maximum 55 KW
200 / 5 A - CT meter
4 mm2
28
200 / 5 A
10
0.5
Maximum 110 KW
300 / 5 A - CT meter
4 mm2
28
300 / 5 A
10
0.5
Maximum 160 KW
600 / 5 A - CT meter
4 mm2
28
600 / 5 A
10
0.5
Maximum 350 KW
1000 / 5 A - CT meter
4 mm2
42
1000 / 5 A
15
0.5
Maximum 550 KW
1600 / 5 A - CT meter
4 mm2
42
1600 / 5 A
15
0.5
Maximum 800 KW
2000 / 5 A - CT meter
4 mm2
42
2000 / 5 A
15
0.2
Above 800 KW
2500 / 5 A - CT meter
4 mm2
42
2500 / 5 A
15
0.2
Special cases
3000 / 5 A - CT meter
4 mm2
42
3000 / 5 A
15
0.2
Special cases
4000 / 5 A - CT meter
4 mm2
42
4000 / 5A
15
0.2
Special cases
Maximum 9 KW
Maximum 52 KW
2000 / 5 A
2500 / 5 A
3000 / 5 A
ACB up to 3000 A
4000 / 5 A
If ACB 4000 A
4000 / 5A
ADDC
Date : 01/01/2011
Page 6 of 12
(RSB requirements)
ADDC
Date : 01/01/2011
Page 7 of 12
ADDC
Date : 01/01/2011
Page 8 of 12
AMR - Bridge box located on the wall in the main electrical room.
ADDC
Date : 01/01/2011
Page 9 of 12
ADDC
Date : 01/01/2011
Page 10 of 12
ADDC
Date : 01/01/2011
Page 11 of 12
ADDC
Date : 01/01/2011
Page 12 of 12
ADDC