Beruflich Dokumente
Kultur Dokumente
October 2005
GE Energy
These instructions do not purport to cover all details or variations in equipment nor to provide for every
possible contingency to be met in connection with installation, operation or maintenance. Should further
information be desired or should particular problems arise which are not covered sufficiently for the purchaser's
purposes the matter should be referred to the GE Company.
2005 General Electric Company
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
TABLE OF CONTENTS
I.
INTRODUCTION ......................................................................................................................................... 3
A. Background................................................................................................................................................ 3
II. DESCRIPTION OF SYSTEM.................................................................................................................... 4
A. Saturation Efficiency (Effectiveness) ........................................................................................................ 5
B. Evaporation Rate........................................................................................................................................ 6
C. Blowdown (Bleed-off) Rate....................................................................................................................... 7
D. Makeup Water Rate ................................................................................................................................... 7
E. Water Carryover......................................................................................................................................... 7
F. Water Bypass.............................................................................................................................................. 8
III. EVAPORATIVE COOLER COMPONENTS ........................................................................................ 8
A. Evaporative Cooler Media......................................................................................................................... 9
B. Recirculation Pumps and Motors............................................................................................................. 10
C. Water Distribution System....................................................................................................................... 11
D. Water Draining System............................................................................................................................ 12
E. Flashing and Media Support .................................................................................................................... 13
F. Customer / Purchaser Connections........................................................................................................... 14
G. Access and Inspection Provisions............................................................................................................ 15
H. Control, Protection and Convenience Devices ........................................................................................ 15
IV. EVAPORATIVE COOLER INSTALLATION, OPERATION, AND MAINTENANCE
PROCEDURES .................................................................................................................................................. 19
A. Evaporative Cooler Installation ............................................................................................................... 19
B. Evaporative Cooler Commissioning ........................................................................................................ 24
C. Evaporative Cooler Operation and Maintenance ..................................................................................... 24
V. EVAPORATIVE COOLER WATER QUALITY AND TREATMENT.............................................. 27
A. Makeup and Recirculating Water Constituent Limits ............................................................................. 28
B. Water Scaling........................................................................................................................................... 28
C. Biological Fouling and Other Chemical Treatment................................................................................. 29
D. Water Sampling and Testing ................................................................................................................... 30
VI. REFERENCES ......................................................................................................................................... 31
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
I. INTRODUCTION
Evaporative coolers supplied with General Electric Gas Turbines should provide reliable and trouble free
operation for the life of the gas turbine. This document is intended to provide the gas turbine operator
with general guidelines and suggestions to ensure proper operation and maintenance of the evaporative
cooler. This document is not intended to replace the information provided as part of the Operation and
Maintenance (O&M) manual provided by the Evaporative Cooler manufacturer. The scope of this GEK is
limited to media type evaporative coolers and the hardware related to such equipment.
Gas turbine operators must recognize that if suitable operational and maintenance guidelines are not
established and followed, the evaporative cooler and its media may need more frequent maintenance. In
the extreme case, the misoperation of the evaporative cooler can result in severe contamination of the gas
turbine and have extremely serious consequences in terms of forced outage time needed for maintenance,
repair and replacement of gas path components.
A. Background
Evaporation of water is one of the simplest and oldest methods of cooling air. Even with the
sophisticated technology available today, including mechanical chillers, absorption chillers and
thermal energy storage systems, evaporative cooling remains a most cost-efficient method for
temperature control of the gas turbine inlet air supply.
Evaporative cooling can be achieved by several methods. In General Electric gas turbine applications,
two forms are typically used: Media type evaporative cooling and Spray type evaporative cooling
(commonly known as fogging or SPRITS). Traditional media type evaporative coolers consist of
recirculated water sprayed over an extended surface media mounted downstream from the inlet air
filters. As inlet air passes through the water soaked evaporative cooler media, evaporation occurs
performing a dual function:
1. Energy in the form of heat is removed from the air by using that energy to evaporate water in the
media; and
2. Water vapor content of the air increases due to evaporated water approaching saturation along
constant wet bulb lines.
These two processes increase the density of the air, which in turn increases the mass flow and output
of the gas turbine.
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
Customer/Purchaser Connections
Flashing & Media Support system
Control and Protection Systems
Access and Inspection provisions
Lighting and Convenience provision
We will discuss these components in detail in Section III of this GEK document.
The function of the evaporative cooler is to increase turbine output by lowering the inlet dry bulb
temperature and increasing the air density through the evaporation of water into the inlet airflow.
Recirculated water introduced over the top of the evaporative cooler media drains through and wets the
media. Filtered ambient air comes into contact with the wetted media where the air is cooled by the heat
of evaporation of water. Gas turbine mass flow rate increases due to the lower air temperature and
increased water content. Higher mass flow results in increased power output from the gas turbine. When
discussing media type evaporative coolers, a couple of key parameters are essential to the proper
operation and maintenance of evaporative coolers. These evaporative cooler parameters are: Saturation
Efficiency, Evaporation Rate, Blowdown Rate, Makeup Water Rate, Water Carryover, and Water
Bypass.
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
where:
=
Efficiency in percent.
T DBE = Entering Dry Bulb Temp
TWBE = Entering Wet Bulb Temp
T DBL = Leaving Dry Bulb Temp
WBD = Wet Bulb Depression, or
= T DBE - T WBE
1.
2.
3.
Humidity
Humidity, which is expressed by the water vapor pressure in air, is controlled by the ambient
temperature. Relative Humidity is the ratio of the vapor pressure of water in air compared the
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
saturated water vapor pressure at the same temperature. Dew Point Temperature of the air is the
temperature at which condensation of liquid water may occur.
4.
Ambient Pressure
The temperature and barometric pressure of atmospheric air vary considerably with altitude as
well as with local geographic and weather conditions. The standard atmosphere gives a standard
of reference for estimating properties of air at various altitudes. At sea level, the standard
barometric pressure is 14.696 psia [29.921 in. Hg] and the standard temperature is 59F [15C].
The temperature is assumed to decrease linearly with increasing altitude while the specific volume
increases. The lower atmosphere is assumed to consist of dry air that behaves as a perfect gas.
B. Evaporation Rate
The evaporation rate is the amount of water that is added to the gas turbine airflow as a result of the
energy transfer between airflow and water, and the subsequent evaporation of water into the air. The
amount of water evaporated into the air or evaporation rate will depend on the entering ambient air
conditions. Factors such as dry bulb temperature, relative humidity, and air ambient pressure
determine the maximum amount of water that may be evaporated before air becomes saturated with
water.
The amount of water evaporated in gallons per minute as the air passes through the cooler can be
calculated using the psychrometric chart using the following formula:
Evaporation =
Vair (WL WE )
water air
where:
VAir = Actual volumetric flow rate of air (cubic feet of air per minute or CFM)
water = density of water (lb water / gal ) at TWBE
air = density of air (lb air / ft3 ) at entering airflow conditions
WE = Moisture content of entering air (lbs. water/lb. dry air)
WL = Moisture content of leaving air (lbs. of water/lb. dry air)
mair = Mass airflow rate (lb. dry air / min) at entering conditions
air = Specific volume of air (ft3/lb. dry air) at entering conditions
Similarly, since the evaporation rate is a function of the temperature of the ambient air and airflow,
the amount of water evaporated may be obtained from the energy balance equation between air
entering and leaving the evaporative cooler media:
Evaporation =
where CpAir =
HEwater =
For practical purposes, the following version of the energy balance equation is used:
Evaporation =
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
(Evaporation Rate)
(No. of Cycles 1)
The chemistry of the sump is established by determining the maximum cycles of concentration that
the makeup water can go through. By definition, the number of cycles of concentration is equal to the
number of times that incoming (makeup) water may be recirculated before it is removed (bled) from
the system. Two methods are commonly used for controlling blowdown and maintaining the desired
chemistry in the sump of the evaporative cooler: Constant flow and Conductivity Control blowdown.
D. Makeup Water Rate
Makeup water is the water added to the sump of the evaporative cooler to replace the water lost by
evaporation into the airflow and the water removed from the sump through blowdown or bleed-off as
required.
Makeup Rate (gpm) = Evaporation Rate (gpm) + Blowdown Rate (gpm)
When conductivity control is used to control blow down, the makeup water required while blowdown
is on will be higher than the average identified by the Makeup rate formula. When the blow down is
off (Blowdown rate = 0 gpm), the required make up rate will be equal to the current evaporation rate.
A high makeup water rate is typically required during startup of the evaporative cooler system in
order to ensure enough water is available out of the sump (recirculation) tank during initial wetting of
media.
E. Water Carryover
Water Carryover is the term used to describe water droplets that become entrained in the airflow
stream and travel through the Evaporative Cooler Media (Cellulose) and plastic (PVC) Drift
Eliminators. Water carryover can be classified into two different categories: Visible and Non-Visible
Carryover. Visible Carryover consists of water droplets several microns in diameter that are visible to
the naked eye. Visible carryover is often the result of high velocities through the Evaporative Cooler
media or incorrect media installation. Non-visible water carryover refers to water droplets that are too
small to be perceived by the naked eye. Non-visible water carryover is harder to quantify due to its
smaller droplet size. Industry literature suggests that the total drift rate or percentage of drift passing
through the drift eliminator as compared to the source water flow is around 0.0030% depending on
source water flow magnitude, drift eliminator angle, and mean air velocity.
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
F. Water Bypass
Water bypass is the term used to describe water droplets that become entrained in the airflow and
travel around the drift eliminators and media flashing. It is often the result of manufacturing and/or
installation defects such as poor caulking, welding, or gaps in between adjacent pieces of drift
eliminators. It is generally characterized by location (sidewalls, module interfaces, structural member,
etc.) and relatively large droplet size.
III. EVAPORATIVE COOLER COMPONENTS
Clean water supplied by the customer enters the lower part of the evaporative cooler section through the
Makeup water supply (PC-IE5) connection. Makeup water empties into an evaporative cooler main
collection (sump) tank. The level of water in the sump is maintained and controlled by water level
switches or transmitters. The water level transmitters control the level in the sump by opening and closing
(as required) the makeup water solenoid valve(s).
Water in the sump is pumped to a distribution manifold located directly above the evaporative cooler
media. The pumps continually recirculate water to the media during operation. Water quantity to the
media is regulated via orifices and trim lines for small adjustments to the water flow (based on site
specific needs).
The distribution manifold evenly wets the media by jetting water through small holes, spaced along its
length, into a deflector shield or splash cover. This water enters the distribution pads installed above the
media blocks, providing an even distribution of water to the entire top surface of the media blocks. The
media blocks are made of corrugated layers of fibrous material with internal channels formed between
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
layers. The water flows down by gravity through water channels and diffuses throughout the media by
wicking action. Any excess water flows down to the module drain pans before it returns to the
evaporative cooler sump where it is recirculated back into the media.
An off-season drain valve and piping is provided on the access side of the cooler module for maintenance
of the evaporative cooler system. This is required for off-season draining of the evaporative cooler sump
as to enable winterization of the system during possible freezing events / seasons. This line can also be
used to quickly drain the sump or to enable a manual sump blowdown for troubleshooting of the system.
A. Evaporative Cooler Media
Two types of Evaporative Cooler Media are normally provided with GE Evaporative Cooler Systems:
Cellulose Paper Media and Plastic Drift Eliminators.
1.
2.
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
of the eliminator without becoming entrained into the flow. Water separated out of the air stream
by the mist eliminator blocks drains forward by gravity into the bottom of the cooler into the
sump.
Moisture separators should be installed so that there are no air leakage gaps between moisture
separator panels, at supports, or at the moisture separator perimeter, and oriented so as to drain
any captured water droplet runoff to the drain tank / sump (away from turbine airflow). The panels
are normally installed into the support structure (flashing) at a 5 to 10-degree slant in order to
allow for the water to drip out.
B. Recirculation Pumps and Motors
Pumps are used to recirculate the water from the sump tank to the evaporative cooler media. Two
designs are typically available with GE Evaporative Cooler systems: Single Pump and Dual Pump
systems. Dual Pump arrangement requires two (2) separate distribution manifolds per evaporative
cooler level. Water is fed by two separate pumps operating at the same time into each manifold from
the end near the cooler sidewall to the center of the module. Single Pump arrangement requires each
distribution manifold to span the full width of the evaporative cooler module. Water is fed from a
single pump located on the main access side of the unit. Pumps draw water from the sump and supply
water to the distribution manifolds located directly above the distribution pads and media.
Redundant Pumps / Motors are available as an option for Evaporative Cooler Systems provided by
GE Energy. Redundant pumps/motors are operated in a lead-lag relationship by the GE Turbine
Motor Control Center (MCC). In a lead/lag system, there are two sets of pump(s) and flow
switch(es) designated A and B. Either the A or B system may be in operation at any time. When in
automatic mode, the same number of pump starts is maintained on each of the A and B systems.
When in manual mode, the operator can select operation of either the A or B system. If pump A, does
10
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
not respond as requested, the system will automatically initiate pump B to run the evaporative cooler
system. Below is a top-level summary diagram of a dual pump evaporative cooler.
C.
Water
Flow to
Water
Flow to
Distribution Headers
The water distribution header is a length of pipe with a number of holes drilled along the top that
ejects water upward into the splash cover and wets the media. The header lays either on top of the
media and distribution pads or is suspended directly above it. The Evaporation Cooler distribution
header may be run as a center fed pipe (with a T connection in the middle) or it can be fed from
one side and run the entire length of the module. The header is located toward the front side of the
media (air entering side) to reduce chances of water carryover from the downstream side and to
deliver water up front where most of the evaporation occurs. Flush valves, plugs or caps are
provided at the end of each manifold for cleaning / maintenance needs.
3.
Splash Covers
The splash cover consists of semi-circular deflector shield that runs the entire length of the
distribution header pipe at every horizontal module section. It is used to disperse water from the
distribution header jets into the distribution pad and deter water from impinging into the roof of
the housing.
11
GEK 111331
4.
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
Distribution Pads
Distribution pads are made of corrugated cellulose based material containing 45x45 Cross-fluted
channels with reinforced edges to evenly disperse the water across the top cross-section of the
evaporative cooling media. They are usually installed directly on top of the evaporative cooler
media bank for maximum water transfer efficiency.
2.
Drain Lines
The drain lines from upper level drain pans to the sump are designed to be fully redundant. Drain
lines are normally configured to be outside of the evaporative cooler module or in line with
structural support in order to minimize interference with airflow and maximize effective media
area.
12
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
3.
GEK 111331
Media
(Top)
Media
(Bottom)
Similarly, flashing at the base of any bank of media flares out to assure that all water running down
the upstream or down stream face of the media is redirected back into the media and never contacts
the outboard side of the flashing.
Flashing at the sidewalls is designed to prevent water from flowing downstream along the interface of
the evaporative cooler sidewall and the outside edge of the evaporative cooler media. Flashing and
baffles are designed to completely seal off any potential airflow paths in order to reduce risk for
water bypass.
Evaporative Cooler media will vary in weight depending on media dimensions, amount of water
retained during operation, and general condition of the media (new, old, heavy deposits, etc.). The
evaporative cooler media supporting system has been designed to provide full support to all
evaporative cooler media (dry, wet, new and clean, old and scaled, etc.) and any applicable hardware
(distribution headers and splash cover) that might be resting on top of it.
13
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
14
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
Two windows are provided on the access hatch to allow for water carryover / bypass inspection
during Evaporative Cooler commissioning and routine checks. The windows are installed so that one
person can hold a light in one window and look through the other window simultaneously while
inspecting the downstream side of the drift eliminators and the clean air plenum for any presence of
water. Some evaporative cooler designs are available with an internal walkway (accessible through
an access hatch or door) in between the Cellulose Evaporative Cooler media and the Drift Eliminators
for enhanced inspection ability and performance. Other designs may have an access manway (hobbit
door) that transverses the media and drift eliminator banks.
H. Control, Protection and Convenience Device
Devices used in the evaporative cooler system are typically wired to the Evaporative Cooler Junction
Box (JB78A). The following control, protection and convenience features are currently provided with
the Media Type Evaporative Coolers: Blowdown Control, Water Level Control, Temperature
Control, Motor Control & Protection, and Water Carryover Control.
1. Blowdown Control System
Due to the isolated locations of some of the installations and the limited water sources often
available, the use of the evaporative cooler to condition inlet air for the gas turbine results in some
of very challenging water control requirements. The use of high mineral content waters can result
in scale formation in the media, which decreases the efficiency of the cooler and increases the
static pressure drop. Conversely, the use of very high purity water can result in corrosion
problems and may have a destabilizing effect on the evaporative cooler media. Blowdown is
required for all recirculated water evaporative cooling applications.
15
GEK 111331
a.
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
b.
Sump water conductivity is measured using two Conductivity Sensors (Device Codes 96AC-22,
-23) that each sends a signal to the Turbine Control System (TCS). Two sensors are provided for
redundancy to ensure proper and accurate function. The turbine control system uses these signals
to control the blowdown system solenoid valve. The number of desired concentration cycles
determines the high conductivity setting of the sensors. The number of cycles of concentration is
the ratio between supply makeup (evaporation + blowdown) and drain (blowdown) water flow
16
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
rates. Maximum allowed constituent limits for makeup and recirculation water are set forth by
the Evaporative Cooler Water Quality document GEK 107158.
S
Recirculating
back to tank
Blowdown
JB78A
/ TCS
Blowdown
discharge from
The Blowdown Solenoid Valve(s) (Device Code 20AC-X) is a two-position three-way valve (as
shown above) that either directs the blowdown into the drain system for blow down or
recirculates the water back into the sump. This is required to provide a constant flow through the
blow down line and eliminate fluctuations in the flow from the evaporative cooler recirculation
pumps. The three-way blowdown valve is normally provided on a pressurized distribution line
from the recirculation pump(s). A flow meter is provided upstream of the solenoid valve to
calculate the amount of blowdown water.
2.
17
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
AT-ID-X) are also available upstream of the evaporative cooler module for monitoring of
ambient air temperature.
4. Motor Control and Protection System
One set of pumps is provided to power the circulation of water from the sump tank to the
evaporative cooler media. The pumps are driven by Totally Enclosed Fan Cooled (TEFC)
Motors (Device Code 88AC-X) with rated operational voltage as required per the local electrical
system rating. Each pump motor is provided with a separate Overload Relay (Device Code
49AC-x) and a local Pump Disconnect (Device Code 8AC-x). The overload relay protects the
motor from thermal overloads while the local disconnect electrically disconnects both the motor
feed and the motor heater feed when so required. Multiple pump motors share local disconnects
for safety and convenience.
Motor Heaters (Device Code 23AC-X) are provided with each motor to protect against
moisture damage. A low Flow Switch (Device Code 80AC-x) is provided for each motor/pump
set. The switch provides a signal to the turbine control system to initiate an alarm and/or pump
shutdown when the water flow drops below the normal operating setting or to verify pump
startup in redundant pump arrangements.
5. Lighting and Convenience Outlet Provisions
Lighting (Device Code AL-32) is provided on the upstream side of the evaporative cooler
module section. The Light Switch (Device Code ASW-14) is accessible from the outside the
evaporative cooler module normally next to the bottom level access door. A Convenience Outlet
(Device Code AR-20 or AR-21) is also provided at the same location for maintenance.
6.
18
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
Device Name
Description
8AC-X
20AC-X
20AC-21
20AC-32
Turbine Inlet Air Evaporative Cooler Redundant Make-Up Water Solenoid Valve
23AC-X
26AC-1
33AC-1
Turbine Inlet Air Evaporative Cooler Drain Line Valve Position Switch
49AC-X
71AC-12
71AC-13
80AC-X
88AC-X
96AC-21
96AC-22
96AC-23
96TD-X
AL-32
ASW-14
AR-21
19
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
(preferred) path of the 15-degree flutes. Media should be oriented at assembly so that when
viewed in elevation, the 45-degree flutes direct water downward toward the upstream side of the
media. The 15-degree flutes should be oriented downward toward the downstream side of the
media. A red stripe is typically added at the bottom of the evaporative cooler media blocks for
ease of installation. However, it is recommended to double check correct orientation by carefully
inserting a 12-inch straight length of round-nosed weld rod (or similar device) into alternate air
and water corrugation flutes.
Gaps in excess of 1/8 are not allowed between adjacent pieces of evaporative cooler media or
between media and module sidewalls. End pieces are typically field cut to ensure a tight fit in
between media blocks and against module sidewalls. Media shall be inspected for damage on the
upstream and downstream side (when looking in the direction of airflow) and replaced
accordingly. Damage on the upstream side is not considered as critical as damage on the
downstream side barring large indentations in the media that are several layers deep or wide.
However, damage on the downstream side can result on unrestricted wicking of water, which can
overwhelm the drift eliminators, and result in water carryover. Damage on the downstream side of
the media requires immediate replacement of the blocks to ensure proper operation.
Distribution pads provided on top of the media blocks ensure even water distribution from the
headers and splash cover across the evaporative cooler media top surface. Distribution pads are
smaller than media blocks (2-inches thick) and feature 45x45 cross-fluted channels with
reinforced edges for handling and ease of installation.
20
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
2.
GEK 111331
Drift Eliminators
Drift Eliminators must be installed as to allow for draining of water droplets through the S-shaped
channels in the direction opposite to airflow. Complete interlock (0.50-inch nominal and 0.25-inch
minimum) is required between adjacent pieces of drift eliminator panels. The last piece of drift
eliminator panel is cut to interlock with the adjacent piece and fit tightly against the module
sidewall on the cut side. A yellow line is typically provided at the upstream and bottom edge of
the drift eliminator panels for ease of installation.
Drift Eliminators shall be inspected for damage after installation, and prior to operation.
Separation between layers within a panel is common when drift eliminators are left exposed to
sunlight and UV rays for long periods of time. Since drift eliminators play a pivotal role in the
elimination of water carryover and/or bypass, it is imperative that damaged pieces be replaced
immediately.
3.
21
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
these holes while the media is still in place. Newer systems employ a removable splash cover for
added convenience.
4.
Media
(Top)
Media
(Bottom)
Similarly, flashing at the base of any bank of media flares out to assure that all water running
down the upstream or down stream face of the media is redirected back into the media and never
contacts the outboard side of the flashing. Flashing that does not confirm to these guidelines may
be carefully bent back into position to maximize efficiency (depending on amount of deflection).
Flashing at the sidewalls is designed to prevent water from flowing downstream along the
interface of the evaporative cooler sidewall and the outside edge of the evaporative cooler media.
Caulking (Sikaflex 221 or similar as approved by GE Engineering) may be used to seal off any
potential water bypass locations or non-conforming flashing. Caulk should be applied to a clean
and dry surface as per the manufacturers recommendations. Baffles are designed to completely
seal off any potential airflow paths in to prevent water bypass and highest efficiency.
22
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
5.
GEK 111331
Gasketting
A modular concept has been adopted in the design of the inlet filter house and evaporative cooler
system. This modular design allows for similarity and configuration options between multiple
designs. Bolted gasketed joints are provided throughout the inlet system in order to prevent dirty
air bypass and allow for air management between modules. Neoprene (closed cell) gaskets are
used at all dirty-to-clean air bolted joints (external joints) as well as module-to-module
connections.
It is essential to the integrity of the inlet system that all gaskets and bolted joints are installed
correctly as to minimize the risk of dirty air and/or water contaminating the clean air side of the
gas turbine. Prefilters and Final filters need to be installed tight against the retaining frame or
tubesheet in order to ensure a positive seal between the dirty and clean air side. Gasket use and
presence shall be verified to meet the installation drawings and instructions provided by the inlet
filter house supplier.
It is recommended to seal off external gasketed joints with a caulk profile on the outside as a
redundant sealing method for the clean air side. Missing gasketting can be corrected by use of
rope gasket or caulking depending on size. The use of correct caulking profile and application
procedures is critical. While applying caulk, one must ensure that the surface is clean and dry as to
ensure good caulk adhesion to the receiving surface. Caulking (Sikaflex 221 or similar as
approved by GE Engineering) may be used to seal off any potential air bypass locations or nonconforming bolted gasketed flanges.
6.
Cleanliness
It is important to remember that the evaporative cooler system and associated hardware inside the
filter house resides in the clean air side of the gas turbine. Thus, it is extremely important that
critical steps be taken to ensure the integrity of this location.
After installation is complete, it is important to do a walkthrough inspection throughout the entire
filter house in order to ensure that all equipment has been installed as per the manufacturers
23
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
Water Quality
Confirm suitability of makeup water per Water Supply Requirement for Gas Turbine Inlet Air
Evaporative Coolers GEK 107158. Establish frequency of sampling and testing for makeup water
and sump quality. See Section V of this document for details.
2.
3.
4.
24
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
1.
GEK 111331
Media Wetting
Uneven water distribution will cause too much water flow to one section of the pad and not
enough water to another. Wetting of cellulose media may be verified through visual inspection by
means of the internal access platforms and ladders provided on the upstream side of the cooler
media. Even and uniform wetting of evaporative cooler media is required regardless of
configuration except for some minor dry streaks at the center and/or at the ends evaporative cooler
modules.
Isolated dry streaks may be caused by accumulated debris
inside of the distribution header and can be easily corrected
by regular maintenance and use of the flushing valves located
at the end of each Distribution header. Random and excessive
streaking throughout the evaporative cooler media can be
attributed to either a high degree of blockage on the
distribution header spray holes or issues with media wetting.
Media wetting issues typically manifest themselves in the
form of water carryover or bypass downstream of the media.
Therefore, it is imperative that this media be replaced as soon
as a media wetting issue is identified by qualified personnel.
2.
General Electric evaporative cooler designs typically utilize 12-inch deep cellulose media pads.
These pads have been proven historically to provide a good balance between saturation efficiency,
and pressure drop both of which affect performance of the gas turbine. Per manufacturers wetting
guidelines, a 12-inch deep media pad requires 1.5 gallons of water per square foot of top media
25
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
area (1.5-gpm H20/ ft2). As a general rule, the following formula may be used to estimate the
water flow rate to each level of evaporative cooler media.
Distribution Flow Rate (gpm) = 1.5 x Module width (feet) / Number of Pumps
These values shall be verified via the flowmeters provided with the evaporative cooler system.
The table below highlights the required Distribution header flows based on the specific filter
house arrangement.
Gas Turbine
Arrangement
PG Model
Series
PG7121
36 feet
54 GPM
27 GPM
7EA Arrowhead
PG7121
N/A
N/A
35 GPM
PG7241
44 feet
66 GPM
33 GPM
7FA Arrowhead
PG7241
28 feet
N/A
42 GPM
PG7251
44 feet
66 GPM
33 GPM
PG9351
60 feet
90 GPM
45 GPM
It is important to point out that regardless of ambient air conditions (altitude, pressure,
temperature or relative humidity), the water flow rate to the cooler media will not change
regardless of location and / or season of evaporative cooler operation. Under extremely dry
conditions, the water flow to the media may be increased to ensure proper wetting throughout the
media bank, however this is done in very rare occasions and always under operator supervision /
surveillance as to not compromise the evaporative cooler system and gas turbine.
New Design Evaporative coolers are provided with orifice plates and flow meters on distribution
line in order to guarantee adequate flow to the cellulose media. Excessive water flowrates to the
distribution headers will result in oversaturation of the evaporative cooler media pads and
potential risk of water carryover and/or bypass.
3.
26
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
PG Model
Series
Airflow rate
Evaporation
flow rate
MS7001EA
PG7121
643 lb/s
40 GPM
170 GPM
210 GPM
MS7001FA
PG7241
952 lb/s
60 GPM
200 GPM
260 GPM
MS9001FA
PG9351
1375 lb/s
90 GPM
270 GPM
360 GPM
Please note that these values are based on the approximate dimensions for the evaporative
cooler module and filter house. These dimensions may vary slightly depending on inlet filter
house (MLI A040) vendor. These values apply to single face evaporative arrangements only.
New Design Evaporative coolers are provided with orifice plates and conductivity controllers on
the blowdown line in order to guarantee adequate bleed-off to the evaporative cooler system drain.
Electronic conductivity control allows for less waste of cooling water by directing water back to
the sump tank once the conductivity in the sump tank is back to within allowable limits.
Blowdown on units not equipped with electronic conductivity control shall be adjusted
periodically during the evaporative cooler running season depending on expected water
evaporation rates and makeup water quality (maximum number of attainable cycles).
4.
27
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
In the evaporative cooler, there are three main goals for a water treatment programs:
1. Prevention of corrosion from carryover of solid contaminants into the gas turbine. Carryover into
the gas turbine can result in corrosion and fouling in both the compressor and turbine sections.
2. Prevention of fouling, scaling, corrosion and media deterioration in the cooler. Scale build-up will
foul the media, affect operating efficiency and reduce the service life of the media. Corrosion will
reduce the service life of the framing, sumps, piping, and support systems.
3. Prevent microbiological infestation that can foul the media and affect operating efficiency. It can
also produce spore formation, objectionable odors, reduce the service life of the media, and induce
corrosion in the system piping and sump.
A. Makeup and Recirculating Water Constituent Limits
Due to the isolated locations of some of the installations, and the limited water sources often
available, the use of the evaporative cooler to condition inlet air for the gas turbine results in some
very challenging water control requirements. The water available ranges from brackish, with
extremely high mineral concentrations to demineralized water. The evaluation of the water supplies
to be used in the evaporative cooler should be done as early as possible. All the critical factors as
listed below, which bear on suitability, must be considered in making a choice.
The following table contains the Makeup and Circulating water limits for media type evaporative
coolers as described in GEK 107158. The Circulating water limits are based on the maximum levels
allowed for each constituent on the clean air side of the gas turbine. They are driven by the makeup
water chemistry and number of cycles allowed.
B. Water Scaling
Scale formations occur when soluble salts are deposited from the recirculating water due to
evaporation. Three main problems are associated with scale formation in evaporative cooling units:
Uneven airflow and water distribution which can lead to water bypass and carryover, Increase in
system pressure drop due to plugging of the cellulose media, and decreased effectiveness due to
reduced evaporation surface area.
28
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
The parameter that has been found to be most effective in defining the required chemistry for the
circulating water in the cooler is its Scaling Index. Scaling Indices were developed for the
specification and control of water in cooling towers and the water-side of shell-tube heat exchangers.
There are three main scaling indices currently in use in the industry: The Puckorius or Practical
Scaling Index (PSI), The Ryznar Scaling Index (RSI), and the Langelier Scaling Index (LSI).
Scaling indices are calculated using total dissolved solids, temperature, calcium hardness, total
alkalinity and pH of the water. Each parameter is used in weighted formulae to determine whether the
water is scale forming or scale dissolving, and the extent to which it is either. For evaporative
cooling, it is desirable to maintain the water so that it has a slightly scale dissolving index. In doing
so, the recirculating water has the ability to dissolve mineral deposits. However, the water should not
be so aggressive (scale dissolving) that it softens the media and attacks the glues, binders, and
rigidifying salts, which hold the media together.
For the Puckorius (PSI) and Ryznar Scaling (RSI) indices:
If the Index is 6.0 the water is stable.
If the Index is above 6.0, the water is scale dissolving.
If the Index is below 6.0, water is scale forming.
For the Langelier Scaling Index (LSI):
If the index is positive the water is scale forming
If it is negative is scale dissolving or corrosive.
Scale formation can be prevented in evaporative coolers by:
1. Maintaining a scaling index that is slightly on the scale dissolving side of neutral (PSI > 6.5)
depending on makeup water chemistry.
2. Pre-treatment of the raw water, by demineralization (reverse osmosis, ion exchange, etc.), to
remove hardness.
3. Inhibiting scale adhesion and formation by chemical treatment
In addition to meeting the makeup water and recirculation limits as set forth in Section V, A, the
evaporative cooler system shall be configured to operate with recirculated water within the following
scaling indices in order to limit scale formation on the evaporative cooler media:
Langelier Saturation Index (LSI)
Calculation and examples of these Scaling indices based on total dissolved solids (TDS), alkalinity,
hardness, pH of cooling water, and operating temperature are covered in the Water Supply
Requirements document (GEK 107158). Please refer to GEK for details.
C. Biological Fouling and Other Chemical Treatment
Uncontrolled growth of bacteria, and other organisms, can lead to plugged media, metal deterioration,
spore formation, and undesirable odors in the air supply. Traditionally, due to GE gas turbine design
29
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
methodology, evaporative cooler systems are provided downstream of the inlet filtration system, and
in the clean air path of the gas turbine. Consequently, theres a limited amount of light and food
sources available for biological growth. Nevertheless, if biological growth is identified inside the
evaporative cooler, an effective program to control algae, bacteria, fungi, molds and yeasts is an
essential part of any water treatment program.
The recommendations of the manufacturers of the evaporative cooler and its media should be
followed in establishing a proper maintenance program for the water system in the cooler. A biocide
program, appropriate for gas turbine application, should be implemented to provide effective control
of the microbiological problems. Regardless of the water treatment program used, all critical
constituents in the makeup and recirculation water shall be maintained within the limits shown in
Section V, A. Proper chemical residuals must be maintained in the system. Biological control should
not be used in place of proper maintenance.
Chemical treatment programs, which were designed for controlling scale in cooling towers, should
not be used for evaporative coolers. In evaporative coolers, the media surface has relatively much less
water flowing over it and is subjected to many wet/dry cycles. When mineral concentrations in the
water become too high, because of too many cycles of concentration and/or insufficient water flow
over the media surface, mineral salts precipitate and deposit. In such a mechanism, the use of scale
inhibitors will have little or no positive effect and in fact the scale inhibitors will become part of the
scale deposit. Thus, conventional cooling tower water treatment methods do not apply to evaporative
coolers.
D. Water Sampling and Testing
As the result of wide seasonal changes in temperature and rainfall, at many sites there may be
significant variations in the chemistry of the water at different times of the year. It is essential that the
effects of these changes on the makeup water supply to the evaporative cooler be known. Prior to the
commissioning of a new evaporative cooler, either in a new plant or as an addon to an existing
plant, the water to be used for the makeup supply must be evaluated. To allow a complete pre
operational evaluation, all the critical parameters describing the water chemistry must be determined.
Since the water will be used as a makeup source to the circulating water in the evaporative cooler,
and not as a once through supply, its chemical properties must be calculated after a number of cycles
of concentration. This is essential so that the water chemistry can be estimated at the design operating
conditions of the cooler.
30
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
GEK 111331
**It is recommended that a troubleshooting water sample analysis be taken quarterly (every three
months) in order to allow for at least two samples of the complete water quality spectrum.
A full water quality analysis report shall be submitted to GE Engineering for review as part of the
initial commissioning for the evaporative cooler system. This is required in order to assign adequate
blowdown control constants for the Turbine Control System. Site-specific control constants optimize
the system to allow for minimal water consumption while maintaining water quality within
recommended recirculation limits for gas turbine operation. These are typically submitted through a
Power Answer Center (PAC) case. Makeup water sample shall be representative of water quality as
seen at the Supply (PC-IE5) Connection as missing or inaccurate information would invalidate all
conclusions drawn per the assessment. In the absence of actual values, minimum reporting limits
shall be provided. It is the responsibility of the customer to maintain Makeup water constituents level
within the levels identified per this analysis, and to ensure full compliance with GEK 107158 makeup
water limits, recirculation water limits, and sampling plans.
VI. REFERENCES
1.
2.
3.
GEI 41040: Specification for Fuel Gases for Combustion in Heavy-Duty Gas Turbines.
4.
5.
6.
GEK 107158: Water Supply Requirements for Gas Turbine Inlet Air Evaporative Coolers
Document.
7.
GEK 107230: Specification for Alkali Metal Contamination in Fuels for the FB and H Model Gas
Turbines.
31
GEK 111331
O&M Recommendations for Media Type Gas Turbine Inlet Air Evaporative Coolers
8.
GEK 111330: Operation and Maintenance Recommendations for Gas Turbine Inlet Air
Compartments.
9.
GEK 111332: Operation and Maintenance Recommendations for Gas Turbine Inlet Air Ducting
Systems.
10.
GE Energy
General Electric Company
www.gepower.com
32