Beruflich Dokumente
Kultur Dokumente
TROUBLESHOOTING GUIDE
Tesco Corporation ("TESCO") has made every effort to ensure that this document contains all of the
information necessary to troubleshoot an HMI top drive, however, the document is intended to be
used in conjunction with a complete training program and on-site supervision and TESCO does
not warrant or guarantee that the information contained herein is either complete or accurate in every
respect and the reader hereby protects, indemnifies and holds harmless Tesco Corporation together
with its directors, officers, employees and agents from and against all liability for personal injury,
death or property damage to any person arising directly or indirectly from the use by the reader of the
information contained in the document.
This equipment was filled at the factory with TESCO ULTREX brand fluids and greases. To ensure
maximum performance and to avoid cross-contamination, we strongly recommend the continued
usage of TESCO ULTREX lubricants, unless otherwise specified.
TESCO ULTREX is a trademark and TESCO is a registered trademark of Tesco Corporation.
Tesco Corporation 2009
Contact Information
Corporate Head Office
3993 W. Sam Houston Parkway No., Suite 100
Houston, Texas, 77043
USA
www.tescocorp.com
www.tescoparts.com
Telephone: (713) 359-7000
Fax: (713) 359-7001
After Market Sales and Service Contact
Toll Free North America: 1-877-TESCO-77
International: 713-359-7295
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
REVISION INFORMATION
TROUBLESHOOTING GUIDE
Revision Information
Version
Date
Description of Changes
Rev A
2003
First release
Rev 1
2007
Rev 2
May 2009
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
TABLE OF CONTENTS
CHAPTER 1: ABOUT THIS DOCUMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
CHAPTER 2: CLOSED LOOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Preparing to Troubleshoot the Closed Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mechanical Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Charge Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Saver Pumps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Low Pump Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Interpreting Pump Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Circulating Pump Case Drain Flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Interpreting Case Drain Flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Top Drive Shifting Manifold (Speed, Cold Climate and Torque) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Shifting Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Shifting Hi/Low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Torque Max/Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Loop Free Flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Top Drive Closed Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Quill Will Not Rotate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unable to Achieve Full System Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Motor Case Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Increasing Motor Case Drain Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Sundstrand Pilot Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Checking Pump Controller Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Checking Pump Controller Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
Link Tilt-Back. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Link Tilt-Float . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Extend-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Extend-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Elevator-Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Elevator-Close. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Elevator Close at Brake Handle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Grabber-Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Grabber-Close. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Grabber-Close Holding Contact Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Grabber/Pipe Handler Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Grabber/Drawworks Interlock Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Mud Saver Valve-Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Mud Saver Open Timer Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Direction Holding Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Mud Saver Valve-Close. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Mud Saver-Close Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Optional Current Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Engineering Sign-Off 77
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
Refer to
system components
INTL: 713-359-7295
CONTACT: 1-877-TESCO-77
TESCO Representative
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
TROUBLESHOOTING GUIDE
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
TESCO has incorporated pressure and temperature gauges that monitor all critical loop
components. These include flow meters for the following:
forward loop flow
hot oil shuttle flow
motor case drain
Test gauge ports are also provided on the filter manifold and top drive switching manifold.
!
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
CLOSED LOOP
TROUBLESHOOTING GUIDE
MECHANICAL INSPECTION
This is a list of general checks that can be performed as part of preliminary troubleshooting for
the closed loop system:
1. Before troubleshooting the hydraulic system, visually inspect equipment. Look
for the following:
mechanical damage to shafts or couplings (prime mover and pump drive)
kinked or ruptured hoses in the service loop
proper valve position
adequate oil reservoir level (site glass valve open)
2. If possible, listen for peculiar noises from the motors, pumps, and transmission.
3. Ensure that the flow rate is adequate to produce the desired pressure.
4. If the system is not functioning properly, check to see if the same problem occurs
in both forward and reverse.
5. Pressure test the motors in various quill positions as follows:
close the grabber
pressure test the first position
rotate the quill 20
repeat the pressure test
continue moving and testing the quill in 20 increments until each position has
been tested
6. Pressure test the pumps against closed valves at the power unit using the control
lever on the face of the Sundstrand valve.
CHARGE PRESSURE
IMPORTANT: This equipment was filled at the factory with TESCO
ULTREX brand fluids and greases. To ensure maximum performance
and to avoid cross-contamination, we strongly recommend the continued
usage of TESCO ULTREX lubricants, unless otherwise specified.
The charge pump is a fixed displacement gear pump. On four pump prime mover
configurations, each saver pump has a small gear pump attached to the back side of the main
pump. On six pump prime mover configurations, a gang of gear pumps is located opposite the
input shaft, at the center of the pump drive.
Charge pump flow rate varies with the rpm of the prime mover but remains proportionally
constant with the maximum available loop flow. The ratio of charge flow to maximum
available loop flow is .25:1.
The charge pumps maintain a pressurized closed loop, provide control pressure, cool and
lubricate the piston pumps, allow loop oil exchange through the hot oil shuttle and make up for
loop leakage.
If fluid losses in the closed loop exceed the charge pump output, the charge pressure will drop.
Pressure drop below normal operating range (minimum 333 psi) will cause damage to the
main closed loop pumps. Pressure loss points are indicated in the illustration below.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CLOSED LOOP
Hydraulic
Motor
Filter
Manifold
Closed Loop
Pump
Pump Case
Drain to Tank
Cooler
Charge
Filter
Tank
Charge
Pump
Note: A drop in charge pressure does not always signify a problem with the
charge pump. Other factors must be considered.
Perform the following checks:
1. Ensure that the charge pump has adequate oil supply.
2. Check the pressure differential across the charge pump filter.
Note: If the differential is higher than 100 psi, change or service the charge pump
filter.
3. Check the case drain from the top drive.
Note: With the auxiliary pump turned off, the case drain flow should be between
2-6 gpm at low operating pressure. If the case drain flow is higher than this, there
may be excessive system fluid losses in one or both motors.
4. Check the saver pumps.
Note: Check the output of all saver pumps using the main flow meters If pumps
are operating normally, output from all pumps should be nearly equal (+/- 5%).
Check the case drain temperature from all pumps. Elevated case drain temperature
indicates possible fluid loss over the pump relief.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
CLOSED LOOP
TROUBLESHOOTING GUIDE
6. If all other checks have been performed, and no significant problem is uncovered,
you can increase charge pressure by reducing the hot oil shuttle setting.
7. If the checks above do not reveal the source of the problem, investigate charge
pump or pumps for possible causes.
SAVER PUMPS
Saver pumps operate very reliably. If a problem arises it will usually be indicated by one or
more of the following:
reduced pump flow (according to main flowmeters)
elevated case drain temperature
unable to achieve full system pressure
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CLOSED LOOP
Case drain temperature for each pump is monitored using gauges provided. All pumps receive
the same work command and are subjected to identical load. Therefore, case drain temperature
should not vary from pump to pump.
If the closed loop system is operating correctly, the sum of the motor case drain, pump case
drain, and the hot oil shuttle flow should equal the theoretical charge flow. Therefore, pump
case drain can be calculated using this formula:
theoretical charge flow (hot oil shuttle + motor case drain flow) = pump case drain flow
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
CLOSED LOOP
TROUBLESHOOTING GUIDE
Shifting Hi/Low
The shifting manifold shuttle valve directs loop high pressure to the 3F valve. The 3F valve
directs control pressure to the appropriate high-flow poppit as selected at the driller's Panel
range Hi/Low switch. Range Hi/Low determines one or two motor operation.
Torque Max/Set
Control interface and valve design allows the two high flow poppits to function
simultaneously as pressure reliefs and directional control valves.
The Bosch pilot reliefs Max and Set are configured in a way that allows the user two torque
limits to be applied to the drill string. When energized, the 1A directional valve isolates Set
torque, and Max torque becomes the active torque relief.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CLOSED LOOP
If you are unable to achieve full pressure at the isolated power unit then consider
the following:
a. One of the combination high-pressure relief/ charge make-up valves may be
damaged, sticking or leaking.
Note: If pressure will not build up in one direction, inspect these valves. Heat
may be present at the faulty valve. If a faulty valve is found, change out the
valve.
b. If pressure will not build up in both forward and reverse a faulty valve is not
the likely cause (unless, by coincidence, both a forward and reverse valve are
faulty).
c. If pressure will not build in both forward and reverse, and flow is lagging or
absent at one flow meter, the problem is likely a faulty pump spline or pump
coupling. Replace pump or repair pump drive, as required.
d. If there is no pressure build up when operating in reverse only, the reverse
torque relief may be faulty.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
CLOSED LOOP
TROUBLESHOOTING GUIDE
e. If full system pressure can be developed when the pumps are deadheaded at
the power unit valves, but cannot be developed with the grabber closed to
stall the quill, one of the following may apply:
f.
If the fault occurs in specific quill positions in forward and reverse, the
problem may be a stuck vane. The faulty motor can be determined by testing
in both high and low range.
g. If the fault occurs regardless of quill position or fluid direction, the problem is
likely the top drive shift (3F directional valve speed control). Troubleshoot for
electrical causes, or change out the 3F valve. Ensure that the pipe handler is
in the locked position and check the cold climate button and shuttle valve.
h. If the fault exists only in forward, check the pilot relief valve and forward
torque relief system (motor manifold).
Note: The pilot to open check valve in the 11-station manifold blocks loop
pressure when drilling ahead. If this valve fails to check:
You will observe high flow at the motor case drain flow meter
You may observe lack of torque at the quill
These observations may lead you to assume high motor case drain and a fauly motor. Always
check the CP-458-2-B valve when high case drain is observed.
During normal operations, motor case drain flow ranges from 0.5 to 1.5 gpm.
This figure may vary depending on the operation being performed and the condition of the
motors. Operations that are more demanding result in higher case drain flow. Worn motors
also tend to have higher case drain flow.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CLOSED LOOP
If there is a sudden significant rise in motor case drain volume, damage to internal motor
components, or debris in the motor vanes is the likely cause.
Any immediate surge in motor case drain flow should be investigated immediately, as high
case drain increases the flow demand on the charge pumps.
Note: Excess case drain results in loss of rpm and mechanical efficiency. It may
be a symptom of a cracked timing plate.
If excess case drain combined with hot oil shuttle flow exceeds the theoretical charge flow, the
loop pumps may cavitate and pump failure may occur.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
CLOSED LOOP
TROUBLESHOOTING GUIDE
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
auxiliary pump
master relief valve
hoses and couplers
auxiliary manifold
unloader valve
If any one of these primary system components is faulty, repair or replace as required. If these
components are functioning correctly, troubleshoot specific functions as defined in the
following sections.
4. If pressure does not build to 2,100 psi (+/- 50), ensure that:
the motor is running at full rpm
the auxiliary pump suction is not restricted or drawing air
the suction lines are properly connected to the pump
the valve on the suction line is open
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
HYDRAULIC FUNCTIONS
TROUBLESHOOTING GUIDE
5. If the checks above do not reveal a problem, check the relief valve for heat buildup.
Note: Heat build up indicates that there is flow over the relief valve. If full auxiliary pressure cannot be developed and flow is evident at the master relief valve,
the master relief valve may be faulty. Repair or replace as required.
6. If auxiliary pump pressure is adequate and the master relief is functioning properly, go to testing the Auxiliary Hydraulic Manifold and Integrated Reliefs.
Note: Low circulating pressure (<325 psi) can indicate pump fatigue. Normal
circulating pressure when oil temperature is 20C, is 375 psi. Circulating pressure
will vary with oil temperature.
Caution: The auxiliary tank contains a suction strainer. If oil supply
to the pump is being restricted, a flow check may be required to
determine the condition of the strainer. This check should only be
performed after other flow related problems have been ruled out.g
procedure, beginning at the auxiliary pump.
GENERAL TESTING
If one or more hydraulic functions are not operating correctly, perform these checks to
determine if the problem is mechanical or electrical.
If these general checks do not resolve the problem, refer to the troubleshooting topic for the
specific function(s) that are not working.
1. Is the hydraulic oil level adequate?
If not adequate, fill oil and check hydraulic function.
2. Are the auxiliary pump and master relief operating properly?
If no, inspect and repair the auxiliary pump or master relief as required, then
check hydraulic function.
If yes, go to the next step.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
HYDRAULIC FUNCTIONS
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
HYDRAULIC FUNCTIONS
TROUBLESHOOTING GUIDE
4. If internal hose rupture is suspected (hose lining is found in the oil filter, or oil is
weeping from a hose jacket), remove the 3/4" x 225' auxiliary pressure hose from
the top drive at the JIC fitting, before the coupler.
Note: This coupler tends to screen debris from the hydraulic oil.
5. Start the auxiliary pump.
6. Displace the hydraulic oil between the hose saddle and JIC (approximately two
gallons)
Note: This will flush accumulated debris from the hydraulic line.
7. If circulating pressure is still high, remove the unloader directional valve.
8. Inspect the pressure passage through the unloader valve and auxiliary manifold
for partial blockage or debris.
Caution: When servicing the auxiliary manifold, remove auxiliary
pressure and return hoses at the top drive. This will block hydrostatic pressure exerted from the height of the hose saddle.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
HYDRAULIC FUNCTIONS
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
HYDRAULIC FUNCTIONS
TROUBLESHOOTING GUIDE
4. Observe the open rotary seal port for hydraulic oil leaks.
Note: Leakage from the open port indicates that the rotary seal is damaged.
Caution: If the rotary seal is damaged, it should be changed as
soon as operations allow. As a temporary measure you may do the
following:
Cap the rotary seal port when the damage was noted.
Use a jumper hose to bypass the damaged seal.
GRABBER LIFT UP
Before using this troubleshooting procedure:
Refer to General Testing for a more general list of checks to perform.
Using the Grabber Lift switch, select Down. This will confirm that the leg is not at the
top if its stroke.
Ensure the Grabber is open.
1. Is the grabber lift needle valve closed?
Note: This valve is located above the kidney manifold on the off-driller side.
If no, close the valve and check the function again.
If yes, remove the hydraulic line from the rotary seal area.
Install a 3,000 psi pressure gauge at the end of the line.
Function grabber up and monitor the gauge.
2. Is the pressure adequate (2,050 psi main relief)?
If yes, go to the next step.
If no, manually cycle the solenoid.
3. Is pressure observed?
If no, check the auxiliary system pump relief and reset as required.
If yes, reconnect the hydraulic line with gauge teed in.
Install a 3,000 psi gauge into the Grabber down line.
Function the grabber up.
If the pressure rises on the return line, there may be leak from the pressure side
to the tank side.
4. Did the grabber lift?
If no, check for mechanical binding.
5. Is there a mechanical obstruction?
If yes, repair as required.
If no, check pressure on the Grabber Down circuit.
If pressure is less than 400 psi, remove the Grabber lift cylinder and inspect for
integrity.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
HYDRAULIC FUNCTIONS
ELEVATOR OPEN
Before using this troubleshooting procedure, refer to General Testing on page 14 for a more
general list of checks to perform.
The following procedures should be performed when it is determined that auxiliary line
pressure is building up, but the elevators will not open.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
HYDRAULIC FUNCTIONS
TROUBLESHOOTING GUIDE
4. Do the elevators open slightly when the fitting is cracked? Is the close side over
pressured?
If yes, this indicates that there is a blockage on the Close side.
If no, proceed to the next step.
5. Crack the fittings on the Open side of the main body cylinder, and the elevator
latch cylinder.
Caution: Exercise caution. The hydraulic oil pressure is 1,800 psi.
ELEVATOR CLOSE
Before using this troubleshooting procedure, refer to General Testing on page 14 for a more
general list of checks to perform.
The following procedures should be performed when it is determined that line pressure is
building up, but the elevators will not close.
!
!
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
HYDRAULIC FUNCTIONS
EXTEND FORWARD
Before using this troubleshooting procedure, refer to General Testing on page 14 for a more
general list of checks to perform.
The following procedures should be performed when it is determined that line pressure is
building up, but the extend forward function will not operate.
1. Are the extend quick couplers properly connected?
If no, reconnect and try the function again.
If yes, go to the next step.
2. Is the speed control valve located in-line properly set?
If no, reset and try the function again.
If yes, install a pressure gauge in the forward side line, as close as possible to the
cylinder. Try the function again, and monitor the pressure.
3. Does the pressure build to 1,800 psi?
If no, there is likely a line blockage on the forward side.
If yes, the problem may be a mechanical bind in the extend mechanism, or a
blockage on the Retract side.
4. Crack the fitting on the retract side.
5. Is there a build up of pressure on the retract side?
If yes, there is likely a blockage on the retract side. Investigate and repair as
required.
If no, there is likely a mechanical bind in the extend mechanism. Investigate and
repair as required.
EXTEND RETRACT
Before using this troubleshooting procedure, refer to General Testing on page 14 for a more
general list of checks to perform.
The following procedures should be performed when it is determined that line pressure is
building up, but the extend retract function will not operate.
1. Are the extend quick couplers properly connected?
If no, reconnect and try the function again.
If yes, go to the next step.
2. Is the flow control valve located in-line properly set?
If no, reset and try the function again.
If yes, install a pressure gauge in the retract side line, as close as possible to the
cylinder. Try the function again, and monitor the pressure.
3. Does the pressure build to 1,800 psi?
If no, there is likely a line blockage on the retract side.
If yes, the problem may be a mechanical bind in the extend mechanism, or a
blockage on the forward side.
4. Crack the fitting on the forward side.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
HYDRAULIC FUNCTIONS
TROUBLESHOOTING GUIDE
GRABBER OPEN
Before using this troubleshooting procedure, refer to General Testing on page 14 for a more
general list of checks to perform.
The following procedures should be performed when it is determined that auxiliary line
pressure is building up, but the grabber open function will not operate.
1. Install the following pressure gauges at the grabber cylinder port extensions:
one 5,000 psi pressure gauge on the close side
one 3,000 psi gauge on the open side
2. Function the grabber open and observe the gauges.
3. Does the pressure gauge on the open side reach 2,000 psi?
If no, check the internal needle valve on the kidney manifold and ensure it is
closed.
Note: If this valve is open, the grabber will attempt to lift whenever open is
selected.
If yes, proceed to the next step.
4. Are any of the following conditions true?
There is pressure at the grabber open solenoid and at the auxiliary manifold, but
not at the grabber cylinder. This indicates there is likely a line blockage between
these two points. Inspect and repair as required.
There is pressure at the open piston, but not on the close side. This indicates
there is likely a mechanical bind in the grabber mechanism. Inspect and repair as
required.
The pressure gauge on the close side rises when the open function is requested.
One of two conditions may exist: there may be a blockage in the grabber close
line or there may be a faulty pilot operated check valve (on pipe handler
manifold). Inspect and repair as required.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
HYDRAULIC FUNCTIONS
GRABBER CLOSE
Before using this troubleshooting procedure. If no solution is found, refer to General Testing
on page 14 for a more general list of checks to perform.
The HCI grabber is operated using auxiliary system hydraulic power. An intensifier powered
by the closed loop system provides additional clamping pressure when making and breaking
connections. Full auxiliary system pressure is critical to intensifier function and must be
achieved before loop pressure is applied.
The following procedures should be performed when it is determined that line pressure is
building up, but the grabber close function will not operate.
1. Locate the following gauges:
Pipe handler manifold gauge (port M)
Loop pressure gauge next to the Bosch relief valves (top drive main frame)
2. Install the following pressure gauges at the grabber cylinder port extensions:
one 5,000 psi pressure gauge on the close side
one 3,000 psi gauge on the open side
3. Function the grabber closed and observe the gauges.
4. Does the gauge on the close side rise to auxiliary closing pressure (2,000 psi)?
If there is 2,000 psi on both the Close side and the Open side, there may be a line
blockage or there may be a problem with the "pilot to open" check valve in the
11 station manifold (CP-45B-2-B).
If there is 2,000 psi at the Close side piston, and the Open side has return
auxiliary line pressure, there may be a mechanical bind in the grabber box or
piston. Inspect and repair as required.
If there is no pressure at the cylinder, check the pressure gauge at the pipe
handler manifold (port M).
Remove the hose from port 2 of the rotary seal.
Install a 2,000 psi pressure gauge.
Function Grabber-Close and monitor the pressure. If there is no pressure,
there may be a problem between the rotary seal and the auxiliary manifold.
The problem may be a line blockage, or a faulty solenoid.
If the Close side shows partial pressure, ensure that all checks described in
General Testing have been performed then:
Test the rotary seal ports 3 and 4 for communication from port 2.
Test the "pilot to close" check valve for possible leakage to the loop.
Ensure no other functions are energized (e.g. Elevaor-Close)
Test the pipe handler lock cylinder for leakage.
Note: The lock is energized when the grabber is closed and may effect the
Grabber-Close function.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
HYDRAULIC FUNCTIONS
TROUBLESHOOTING GUIDE
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
HYDRAULIC FUNCTIONS
Caution: The piston racks have a vent between the open and close
piston seals. A ruptured seal will vent to atmosphere.
1. Install a 2,000 psi pressure gauge on the open and close side lines.
2. Function open and monitor the pressure gauges.
3. Is there pressure in the open line?
If no, check the pressure relief on the mud saver for proper setting (1,500 psi).
If yes, there may be a ruptured seal in the mud saver valve. Check the seals as
follows:
Remove the close hose from the valve actuator.
Leave the test gauge on the close port.
Function the mud saver open.
If both gauges read 1,500 psi, then the seals are bypassing.
Service seals as required. If the seals are good, put close hose on, function
open and monitor pressure gauges, then go to next step.
4. Is there pressure in close line?
If yes, there may be a problem with the shuttle valve. Inspect and repair as
required.
If no, there may be a mechanical bind in the actuator or mud saver valve. Inspect
and repair as required.
Note: The actuator drive keys can be removed to determine whether the actuator
is working. Actuator function can be confirmed without operating the mud saver
valve.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
HYDRAULIC FUNCTIONS
TROUBLESHOOTING GUIDE
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
HYDRAULIC FUNCTIONS
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
Caution: Using the float function allows the bails to move in any
direction that will relieve force on the cylinders. If the bails are subject to external stresses when the float function is used, the bails
may move in an unanticipated direction. See the illustration below
for an example.
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
HYDRAULIC FUNCTIONS
TROUBLESHOOTING GUIDE
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
HYDRAULIC FUNCTIONS
Caution: Using the float function allows the bails to move in any
direction that will relieve force on the cylinders. If the bails are subject to external stresses when the float function is used, the bails
may move in an unanticipated direction.
GEARBOX LUBRICATION
The HCI gearbox incorporates flood design lubrication. Oil level is maintained above the top
bearing. Gear train movement causes the oil to circulate throughout the gearbox.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
HYDRAULIC FUNCTIONS
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
TROUBLESHOOTING GUIDE
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
COOLING SYSTEM
TROUBLESHOOTING GUIDE
During normal operations, the hot oil shuttle should be set between 35-70 gpm. Shuttle flow
into the top side of the Modine cooler can be monitored using a gauge mounted opposite the
power unit's main electrical panel.
If loop temperature is rising beyond acceptable levels, you may need to increase the hot oil
shuttle volume.
Caution: Increasing the hot oil shuttle results in a closed loop flow
loss. The charge pump must compensate for this flow loss. If the
demands on the charge pump become too great, the system may
actually start to increase temperature rather than decrease.
1. At the drillers panel, use the Pump Direction switch, select Forward.
2. Using the Increase/Decrease switch, increase pump speed.
Note: 1000 psi is required to activate the shuttle.
3. Unlock the shuttle control knob (aft side of the filter manifold).
Figure 4-2: Adjusting Hot Oil Shuttle
Caution: If sequence is set too low, shuttle will occur in reverse and
reverse pressure will relieve over the shuttle.
4. Observe the flow meter on the right side of the Modine cooler (opposite the main
electrical panel).
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
COOLING SYSTEM
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
COOLING SYSTEM
TROUBLESHOOTING GUIDE
RE-CIRCULATION PUMP
The re-circulation pump moves oil from the storage tank through the Modine cooler and back
to tank. The re-circulation pump provides supplemental cooling of tank oil during demanding
operations.
Figure 4-3: Re-circulation pump
If the re-circulation pump will not start, see Motor Starter Problems on page 68.
Always ensure that the pump's suction valve is open before starting the re-circulation pump.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
COOLING SYSTEM
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
COOLING SYSTEM
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
TROUBLESHOOTING GUIDE
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
WIRING NOTES
The 37 conductor cable that runs from the top drive to the drillers panel and from the driller's
panel to the power module contains 37 colour coded wires.
Each colour-coded wire corresponds to a single terminal number. For example, conductor wire
5 (solid yellow wire) will be connected to terminal number 5 at the top drive, drillers panel
and power module.
For additional information, refer to the HCI System Schematics.
TESTING SOLENOIDS
You can confirm whether solenoids are receiving power using a simple magnetism test.
Hold any ferrous tool close to the solenoid. If magnetism is detected, the solenoid is receiving
power.
When testing for power, always test both sides of the solenoid. If both sides are receiving
power, the associated function may not work properly. This is because power supplied to both
sides simultaneously will tend to hold the function in the neutral position.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
6. Install the DMM leads across pin 1B pig tail to terminal 2B terminal strip.
Note: The DMM should read OL-, which indicates "open line" or no continuity.
7. Check pin 1 across B terminals 3 37.
Note: Ensure that the DMM read OL- on all terminals. Continuity would indicate that a short is present.
8. Repeat the continuity check for all pins.
9. Follow the procedure described above to check the 37C cable and Pyle national
connectors for soundness.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
7. If no power is present to the breaker, check the power unit supply from the rig and
the main 80 amp fuses in the top left of the main panel, fuse 1,2 and 3.
8. If you have performed all of these tests and have not located the trouble source,
contact TESCO.
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
GRABBER LIFT-UP
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Grabber Lift-Up.
3. Determine whether an electrical signal is arriving at the unloader and Grabber Lift
Up solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
4. If there is no power to the Grabber Lift-Up solenoid only, remove the cover for the
Grabber solenoids.
5. Remove wire nuts for the Grabber Lift-Up wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Grabber Lift-Up, the other side contains
wires for Grabber Lift-Down. A common wire from each coil leads back to the
24V return wire.
8. Select Grabber Lift-Up and observe the DMM.
9. Ensure that when Grabber Lift-Up is functioned (with power on), there is 24V
power at the Grabber Lift-Up coil.
10. If the Grabber Lift-Up coil is not receiving power, install the DMM on wire 221
(terminal 20 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Grabber Lift-Up .
12. Check the DMM to confirm that terminal 20 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 20 should have wire 221 connected to it.
16. Select Grabber Lift-Up.
17. If there is no power, move the DMM positive to port 221 on the back side of the
Grabber Lift-Up switch (back side of the drillers panel).
18. Select Grabber Lift-Up.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
19. If there is no power, check switch incoming wire #1, which is +24 VDC.
Note: This switch should have power all the time whether Grabber Lift-Up is
selected or not.
20. If there is no power to wire #1, check B strip red terminal blocks for +24VDC and
24 V return power.
21. If there is no power at the terminal blocks, proceed main electrical panel at the
power unit.
22. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
GRABBER LIFT-DOWN
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Grabber Lift-Down.
3. Determine whether an electrical signal is arriving at the unloader and Grabber Lift
Down solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid, the problem likely originates at the
drillers panel.
4. If there is no power to the Grabber Lift-Down solenoid only, remove the cover for
the Grabber solenoids.
5. Remove wire nuts for the Grabber Lift-Down wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Grabber Lift-Down, the other side contains
wires for Grabber Lift-Up. A common wire from each coil leads back to the 24V
return wire.
8. Select Grabber Lift-Down and observe the DMM.
9. Ensure that when Grabber Lift-Down is functioned (with power on), there is 24V
power at the Grabber Lift-Down coil.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
10. If the Grabber Lift-Down coil is not receiving power, install the DMM on wire
223 (terminal 22 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Grabber Lift-Down .
12. Check the DMM to confirm that terminal 22 is receiving power.
13. If no power is received, check the Pyle National connectors.
14. If the connectors are properly in place, proceed to the drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 22 should have wire 223 connected to it.
16. Select Grabber Lift-Down.
17. If there is no power, move the DMM positive to wire 223 on the back side of the
Grabber Lift-Down switch (back side of the drillers panel).
18. Select Grabber Lift-Down.
19. If there is no power, check switch incoming wire #1 which is +24 VDC.
Note: This switch should have power all the time whether Grabber Lift-Down is
selected or not.
20. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPM 19/20 (24VDC return).
21. If there is no power at the terminal blocks, proceed to the power module analog
panel.
22. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
PIPE HANDLER-UNLOCK
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Pipe Handler-Unlock.
3. Determine whether an electrical signal is arriving at the unloader and Pipe
Handler-Unlock solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
4. If there is no power to the Pipe Handler-Unlock solenoid only, remove the cover
for the Pipe Handler solenoids.
5. Remove wire nuts for the Pipe Handler-Unlock wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Pipe Handler-Unlock, the other side
contains wires for Pipe Handler-Lock. A common wire from each coil leads back
to the 24V return wire.
8. Select Pipe Handler-Unlock and observe the DMM.
9. Ensure that when Pipe Handler-Unlock is functioned (with power on), there is
24V power at the Pipe Handler-Unlock coil.
10. If the Pipe Handler-Unlock coil is not receiving power, install the DMM on wire
112 (terminal 15 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Pipe Handler-Unlock.
12. Check the DMM to confirm that terminal 15 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 15 should have wire 112 connected to it.
16. Select Pipe Handler - Unlock.
17. If there is no power, move the DMM positive to wire 112 on the back side of the
Pipe Handler-Unlock switch (back side of the drillers panel).
18. Select Pipe Handler-Unlock.
19. If there is no power, check switch incoming wire #1 which is +24 VDC.
Note: This switch should have power all the time whether Pipe Handler-Unlock is
selected or not.
20. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPM 19/20 (24VDC return).
21. If there is no power at the terminal blocks, proceed to the power module analog
panel.
22. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
PIPE HANDLER-LOCK
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Pipe Handler-Lock.
3. Determine whether an electrical signal is arriving at the unloader and Pipe
Handler-Lock solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
4. If there is no power to the Pipe Handler-Lock solenoid only, remove the cover for
the Pipe Handler solenoids.
5. Remove wire nuts for the Pipe Handler-Lock wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Pipe Handler-Lock, the other side contains
wires for Pipe Handler-Unlock. A common wire from each coil leads back to the
24V return wire.
8. Select Pipe Handler-Lock and observe the DMM.
9. Ensure that when Pipe Handler-Lock is functioned (with power on), there is 24V
power at the Pipe Handler-Lock coil.
10. If the Pipe Handler-Lock coil is not receiving power, install the DMM on wire 110
(terminal 14 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Pipe Handler-Lock.
12. Check the DMM to confirm that terminal 14 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 14 should have wire 110 connected to it.
16. Select Pipe Handler-Lock.
17. If there is no power, move the DMM positive to wire 110 on the back side of the
Pipe Handler-Lock switch (back side of the drillers panel).
18. Select Pipe Handler-Lock.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
19. If there is no power, check switch incoming wire #1, which is +24 VDC.
Note: This switch should have power all the time whether Pipe Handler-Lock is
selected or not.
20. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPM 19/20 (24VDC return).
21. If there is no power at the terminal blocks, proceed to the power module analog
panel.
22. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
LINK TILT-FORWARD
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Link Tilt-Forward.
3. Determine whether an electrical signal is arriving at the unloader and Link TiltForward solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
4. If there is no power to the Link Tilt-Forward solenoid only, remove the cover for
the Link Tilt solenoids.
5. Remove wire nuts for the Link Tilt-Forward wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Link Tilt-Forward, the other side contains
wires for Link Tilt-Back. A common wire from each coil leads back to the 24V
return wire.
8. Select Link Tilt-Forward and observe the DMM.
9. Ensure that when Link Tilt-Forward is functioned (with power on), there is 24V
power at the Link Tilt-Forward coil.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
10. If the Link Tilt-Forward coil is not receiving power, install the DMM on wire 34
(terminal 9 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Link Tilt-Forward.
12. Check the DMM to confirm that terminal 9 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 9 should have wire 34 connected to it.
16. Select Link Tilt-Forward.
17. If there is no power, move the DMM positive to wire 34 on the back side of the
Link Tilt-Forward switch (back side of the drillers panel).
18. Select Link Tilt-Forward.
19. If there is no power, check switch incoming wire #1 which is +24 VDC.
Note: This switch should have power all the time whether Link Tilt-Forward is
selected or not.
20. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPM 19/20 (24VDC return).
21. If there is no power at the terminal blocks, proceed to the power module analog
panel.
22. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
LINK TILT-BACK
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Link Tilt-Back.
3. Determine whether an electrical signal is arriving at the unloader and Link TiltBack solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
4. If there is no power to the Link Tilt-Back solenoid only, remove the cover for the
Link Tilt solenoids.
5. Remove wire nuts for the Link Tilt-Back wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Link Tilt-Back, the other side contains
wires for Link Tilt-Forward. A common wire from each coil leads back to the 24V
return wire.
8. Select Link Tilt-Back and observe the DMM.
9. Ensure that when Link Tilt-Back is functioned (with power on), there is 24V
power at the Link Tilt-Back coil.
10. If the Link Tilt-Back coil is not receiving power, install the DMM on wire 36
(terminal 10 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Link Tilt-Back.
12. Check the DMM to confirm that terminal 10 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 10 should have wire 36 connected to it.
16. Select Link Tilt-Back.
17. If there is no power, move the DMM positive to wire 36 on the back side of the
Link Tilt-Back switch (back side of the drillers panel).
18. Select Link Tilt-Back.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
19. If there is no power, check switch incoming wire #1 which is +24 VDC.
Note: This switch should have power all the time whether Link Tilt-Back is
selected or not.
20. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPM 19/20 (24VDC return).
21. If there is no power at the terminal blocks, proceed to the power module analog
panel.
22. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
Link Tilt-Float
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
The Link Tilt Float circuit contains two relay switches (5 and 6). These are holding contacts
for the float function.
If there is a problem with relay 6, the float function will only operate as long as float button is
held down. If the float button is released, the float action is interrupted. If you are experiencing
this problem, check the relay 6 circuit before performing the following.
1. Open the auxiliary hydraulics panel.
2. Select Link Tilt-Float.
3. Determine whether an electrical signal is arriving at the Link Tilt-Float solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at this solenoid, refer to the auxiliary hydraulic troubleshooting
procedures.
If there is no power at this solenoid the problem likely originates at the drillers
panel.
4. If there is no power to the Link Tilt-Float solenoid only, remove the cover for the
Link Tilt solenoids.
5. Remove wire nuts for the Link Tilt-Float wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Link Tilt-Float, the wires on the other side
contains are unused. A common wire from each coil leads back to the 24V return
wire.
8. Select Link Tilt-Float and observe the DMM.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
9. Ensure that when Link Tilt-Float is functioned (with power on), there is 24V
power at the Link Tilt-Float coil.
10. If the Link Tilt-Float coil is not receiving power, install the DMM on wire 32
(terminal 8 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Link Tilt-Float.
12. Check the DMM to confirm that terminal 8 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 8 should have wire 32/31 connected to it.
16. Select Link Tilt-Float.
17. If there is no power, move the DMM positive to wire 32 on the back side of the
Link Tilt-Float switch (back side of the drillers panel).
18. Select Link Tilt-Float.
19. If there is no power, check the incoming wire to the float button - #47.
20. If there is no power to wire #47, check relay 5.
Note: Relay 5 interrupts power to the float button if link tilt forward or backward are energized (terminals 14 (+24 VDC) and 15 (24 VDC return)).
21. Check wire 1 (red) to terminal 9 on relay 5.
Note: This wire should have power to it at all times. If no power is present, refer
to Testing for Generalized Power Problems on page 39.
22. If power to the float function is only present while the button is depressed,
troubleshoot relay 6.
Note: Relay 6 is energized when the float button is pressed. It holds power to the
float solenoid until Link Tilt - Forward or Link Tilt - Backward is selected.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
EXTEND-IN
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Extend-In.
3. Determine whether an electrical signal is arriving at the unloader and Extend-In
solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
4. If there is no power to the Extend-In solenoid only, remove the cover for the
Extend solenoids.
5. Remove wire nuts for the Extend-In wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Extend-In, the other side contains wires for
Extend-Out. A common wire from each coil leads back to the 24V return wire.
8. Select Extend-In and observe the DMM.
9. Ensure that when Extend-In is functioned (with power on), there is 24V power at
the Extend-In coil.
10. If the Extend-In coil is not receiving power, install the DMM on wire 52 (terminal
6 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Extend-In.
12. Check the DMM to confirm that terminal 6 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 6 should have wire 52 connected to it.
16. Select Extend-In.
17. If there is no power, move the DMM positive to wire 52 on the back side of the
Extend-In switch (back side of the drillers panel).
18. Select Extend-In.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
19. If there is no power, check switch incoming wire #1 which is +24 VDC.
Note: This switch should have power all the time Extend-In is selected or not.
20. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPM 19/20 (24VDC return).
21. If there is no power at the terminal blocks, proceed to the power module analog
panel.
22. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
EXTEND-OUT
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Extend-Out.
3. Determine whether an electrical signal is arriving at the unloader and Extend-Out
solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
4. If there is no power to the Extend-Out solenoid only, remove the cover for the
Extend solenoids.
5. Remove wire nuts for the Extend-Out wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Extend-Out, the other side contains wires
for Extend-In. A common wire from each coil leads back to the 24V return wire.
8. Select Extend-Out and observe the DMM.
9. Ensure that when Extend-Out is functioned (with power on), there is 24V power
at the Extend-Out coil.
10. If the Extend-Out coil is not receiving power, install the DMM on wire 55
(terminal 7 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
ELEVATOR-OPEN
To open the elevators you must select Elevator-Open, and simultaneously push the Elevator
safety button. The elevators will not open unless the safety button is pushed.
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Elevator-Open.
3. Determine whether an electrical signal is arriving at the unloader and Elevator
Open solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
4. If there is no power to the Elevator-Open solenoid only, remove the cover for the
Elevator solenoids.
5. Remove wire nuts for the Elevator-Open wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Elevator-Open, the other side contains
wires for Elevator-Close. A common wire from each coil leads back to the 24V
return wire.
8. Select Elevator-Open and observe the DMM.
9. Ensure that when Elevator-Open is functioned (with power on), there is 24V
power at the Elevator-Open coil.
10. If the Elevator-Open coil is not receiving power, install the DMM on wire 9
(terminal 12 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Elevator-Open.
12. Check the DMM to confirm that terminal 12 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 12 should have wire 9 connected to it.
16. Select Elevator-Open.
17. If there is no power, move the DMM positive to wire 9 on the back side of the
Elevator-Open switch (back side of the drillers panel).
18. Select Elevator-Open.
19. If there is no power, check switch incoming wire #1 which is +24 VDC.
Note: This switch should have power all the time Elevator-Open is selected or
not.
20. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPB 19/20 (24VDC return).
21. If there is no power at the terminal blocks, proceed to the power module analog
panel.
22. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
ELEVATOR-CLOSE
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Elevator-Close.
3. Determine whether an electrical signal is arriving at the unloader and ElevatorClose solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
4. If there is no power to the Elevator-Close solenoid only, remove the cover for the
Elevator solenoids.
5. Remove wire nuts for the Elevator-Close wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Elevator-Close, the other side contains
wires for Elevator-Open. A common wire from each coil leads back to the 24V
return wire.
8. Select Elevator-Close and observe the DMM.
9. Ensure that when Elevator-Close is functioned (with power on), there is 24V
power at the Elevator-Close coil.
10. If the Elevator-Close coil is not receiving power, install the DMM on wire 13
(terminal 11 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Elevator-Close.
12. Check the DMM to confirm that terminal 11 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 11 should have wire 13 connected to it.
16. Select Elevator-Close.
17. If there is no power, move the DMM to the output side of diode 17.
18. Select Elevator-Close.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
19. If there is no power, move the DMM to wire 5 (the input to diode 17).
20. Select Elevator-Close.
21. If there is no power, move the DMM to wire 4 at the Elevator-Close switch at the
drillers panel.
22. Select Elevator-Close.
23. If there is no power, attach DMM positive to wire 4 on the back side of the
Elevator-Close switch (back side of the drillers panel).
24. Select Elevator-Close.
25. If there is no power, check the brake handle circuit as follows.
a. Attach the DMM to wire 14.
b. Select Elevator-Close.
c. If there is no power to wire 14, attach the DMM to wire 25.
d. Select Elevator-Close.
e. If there is no power to wire 25, move the DMM to terminal 2, relay 2.
Note: This is the incoming power to the brake handle switch.
f.
g. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPB 19/20 (24VDC return).
26. If there is no power at the terminal blocks, proceed to the power module analog
panel.
27. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem
is likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power
Problems on page 39.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
GRABBER-OPEN
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Grabber-Open.
3. Determine whether an electrical signal is arriving at the unloader and Grabber
Open solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
4. If there is no power to the Grabber-Open solenoid only, remove the cover for the
Grabber solenoids.
5. Remove wire nuts for the Grabber-Open wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Elevator-Open, the other side contains
wires for Elevator-Close. A common wire from each coil leads back to the 24V
return wire.
8. Select Grabber-Open and observe the DMM.
9. Ensure that when Grabber-Open is functioned (with power on), there is 24V
power at the Grabber-Open coil.
10. If the Grabber-Open coil is not receiving power, install the DMM on wire 89
(terminal 1 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Grabber-Open.
12. Check the DMM to confirm that terminal 1 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip, terminal 1, and negative on the
24V return.
Note: Strip A, terminal 1 should have wire 89 connected to it.
16. Select Grabber-Open.
17. If there is no power at terminal 1, move the DMM to the grabber open contact
block wire 73.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
18. If there is no power at the contact block, check incoming wire #1 which is +24
VDC.
Note: This switch should have power all the time whether Grabber-Open is
selected or not.
19. If there is no power to the contact block, check B strip red terminal blocks DPB
17/18 (+24VDC) and DPM 19/20 (24VDC return).
20. If there is no power at the terminal blocks, proceed to the power module analog
panel.
21. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
GRABBER-CLOSE
Before using this troubleshooting tree, refer to General Electrical Testing on page 38 for a
more general list of checks to perform.
1. Open the auxiliary hydraulics panel.
2. Select Grabber-Close.
3. Determine whether an electrical signal is arriving at the unloader and GrabberClose solenoids.
Note: You can determine if power is supplied using the simple magnetism test.
See General Electrical Testing on page 38.
If there is power at both of these solenoids, refer to the auxiliary hydraulic
troubleshooting procedures.
If there is no power at either solenoid the problem likely originates at the
drillers panel.
4. If there is no power to the Grabber-Close solenoid only, remove the cover for the
Grabber solenoids.
5. Remove wire nuts for the Grabber-Close wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Grabber-Close, the other side contains
wires for Grabber-Open. A common wire from each coil leads back to the 24V
return wire.
8. Select Grabber-Close and observe the DMM.
9. Ensure that when Grabber-Close is functioned (with power on), there is 24V
power at the Grabber-Close coil.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
10. If the Grabber-Close coil is not receiving power, install the DMM on wire 75
(terminal 2 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Grabber-Close.
12. Check the DMM to confirm that terminal 2 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 2 should have wire 75 connected to it.
16. Select Grabber-Close.
17. If there is power at relay terminal 76 and 81, move the DMM positive to port 2 on
the back side of the Grabber-Close switch (back side of the drillers panel).
18. Select Grabber-Close.
19. If there is no power, check switch incoming wire #1 which is +24 VDC.
Note: This switch should have power all the time Grabber-Close is selected or
not.
20. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPB 19/20 (24VDC return).
21. If there is no power at the terminal blocks, proceed to the power module analog
panel.
22. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
4. If there is no power to the Mud Saver-Open solenoid only, remove the cover for
the Mud Saver solenoids.
5. Remove wire nuts for the Mud Saver-Open wires.
Note: Ensure that you do not short any of the wires.
6. Check for wire breaks or corrosion on the wires.
Note: If corrosion is found, clean and retest the function. If breaks are found,
reconnect the wires and retest the function.
7. Install a digital multi-meter across the wires from 24 V return and +24VDC.
Note: The solenoid contains wires for Mud Saver-Open, the other side contains
wires for Mud Saver-Close. A common wire from each coil leads back to the 24V
return wire.
8. Select Mud Saver-Open and observe the DMM.
9. Ensure that when Mud Saver-Open is functioned (with power on), there is 24V
power at the Mud Saver-Open coil.
10. If the Mud Saver-Open coil is not receiving power, install the DMM on wire 171
(terminal 3 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Mud Saver-Open.
12. Check the DMM to confirm that terminal 3 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 3 should have wire 171 connected to it.
16. Select Mud Saver-Open.
17. If there is no power, move the DMM to wire 171.
18. Select Mud Saver-Open.
19. If there is power at wire 171, move the DMM positive to wire 261.
20. Select Mud Saver-Open.
21. If there is no power at 261, move the DMM positive to wire 263 at the output of
diode 30.
Note: If there is power at wire 261, then there may be problem with diode 24.
22. Select Mud Saver-Open.
23. If there is no power at wire 264, move the DMM positive to wire 260, the input to
diode to 30.
24. Select Mud Saver-Open.
25. If there is no power at wire 260, move the DMM positive to wire 57.
26. Select Mud Saver-Open.
27. If there is no power, check switch incoming wire #1 which is +24 VDC.
Note: This switch should have power all the time Mud Saver-Close is selected or
not.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
28. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPB 19/20 (24VDC return).
29. If there is no power at the terminal blocks, proceed to the power module analog
panel.
30. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
9. Ensure that when Mud Saver-Close is functioned (with power on), there is 24V
power at the Mud Saver-Close coil.
10. If the Mud Saver-Close coil is not receiving power, install the DMM on wire 59
(terminal 4 on the auxiliary panel terminal strip).
Note: Ensure the negative lead is installed on the 24 V return.
11. Select Mud Saver-Close.
12. Check the DMM to confirm that terminal 4 is receiving power.
13. If no power is received, check the Pyle National A connectors and the 37C cable
for continuity.
14. If the A connectors are properly in place, and continuity is sound, proceed to the
drillers panel.
15. Using the DMM, place the positive on the A strip terminal, and negative on the
24V return.
Note: Strip A, terminal 4 should have wire 59 connected to it.
16. Select Mud Saver-Close.
17. If there is no power, check wire 264/59.
18. If there is power at wire 264/59, move the DMM positive to wire 59/66/264.
19. Select Mud Saver-Close.
20. If there is no power at 59/66/264, move the DMM positive to wire 59.
21. Select Mud Saver-Close.
22. If there is no power at wire 59, move the DMM positive relay 10, terminal 2.
23. Select Mud Saver-Close.
24. If there is no power at relay 10, terminal 2, move the DMM positive to relay 10,
terminal 10.
25. Select Mud Saver-Close.
26. If there is no power at relay 10, terminal 10, move the DMM to wire 256.
27. Select Mud Saver-Close.
28. If there is no power, check switch incoming wire #1 which is +24 VDC.
Note: This switch should have power all the time Mud Saver-Close is selected or
not.
29. If there is no power to wire #1, check B strip red terminal blocks DPB 17/18
(+24VDC) and DPM 19/20 (24VDC return).
30. If there is no power at the terminal blocks, proceed to the power module analog
panel.
31. Using the DMM, check for 24V power between MPB 17/18 (24 VDC) and MPB
19/20 (24 V return).
If there is power at the MPB strip but not at the drillers panel, the problem is
likely related to improper Pyle National connections.
If there is no power to functions at the MPB strip, there may be a more
generalized power problem. Refer to Testing for Generalized Power Problems
on page 39.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
prime mover
pump drive
pumps
filter manifold
storage tank
cooling system
interconnecting pipework
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
POWER UNIT
TROUBLESHOOTING GUIDE
Each of these functions is connected to its own circuit breaker and on/off control on the main
distribution panel.
All starters are 120 VAC. Each starter circuit includes a normally open switch (located in the
power module). When a switch is closed it energizes the starter and connects the 480 V power
to the specified motor.
Each starter contains heater elements that have been sized for the running current draw of each
motor. If a motor continuously draws more power than it is designed for, the heater element
temperature sensor will trip the starter, and the motor will stop.
Note: Unlike the other motors listed, the cooling fan has a two position switch.
The settings are hand and auto. When the switch is in the hand position, 120V
power is supplied directly to the fan's motor starter. If the auto is selected, 120V
power is directed through a temperature switch in the top drive cooling tank. This
switch will close only when the fluid temperature exceeds a preset value.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
POWER UNIT
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
POWER UNIT
TROUBLESHOOTING GUIDE
5. Check wire 7.
6. If there is power on wire 7, check the auxiliary motor switch.
7. If there is no power to the switch, check wire 6, incoming power to the switch.
8. If there is power to the switch, examine the switch for defects.
9. If no switch defects are found, check wire 5.
If power is present, check switch function.
10. If no power is present at wire 5, check terminal 1 or relay 22
Note: Relay 22 is the auxiliary pump off control from the driller's panel. If relay
22 is energized, check the 24 VDC circuit and switch in the driller's panel.
11. If relay 22 is not energized, check terminal 9 of relay 22.
Note: There should be 120 VAC to this terminal from L2 of the 20 kVa transformer.
12. If there is no power to relay 22, see testing for Testing for Generalized Power
Problems on page 39.
Auxiliary Pump Operates from Main Panel but not the Driller's
Panel
1. Turn the auxiliary pump off.
2. Try to start the [pump from the driller's panel.
3. Check wire 1 at the main panel.
4. If there is no power when the driller's panel control is functioned, ensure that
terminal 12 or relay 21 is being supplied 120 VAC power from L2.
Note: L2 is fused. Check the fuse before proceeding.
5. Check terminal 14 of relay 21 (+24 VDC when the pump is started from the
driller's panel) and terminal 13 of relay 21 (24V return).
6. If 24 VDC power is not present when the switch is operated, proceed to wire 144
(terminal 11 on the MPB strip).
7. If 24 VDC is not present, proceed to the drillers panel.
8. At the drillers panel, check wire 144, terminal 11 on the DPB strip.
9. If 24 VDC is not present, check wire 144 on the auxiliary pump switch.
Note: Ensure that wire 1 on the other side of the switch has 24 VDC continuously.
10. If wire 1 is not transmitting 24 VDC, refer to Testing for Generalized Power
Problems on page 39.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
POWER UNIT
When Auxiliary Pump-On is selected at the drillers panel, wire 144 energizes and switches
relay 21. This directs 120V current to the auxiliary start/run circuit and to the auxiliary pump
on light (power module).
When Auxiliary Pump-Off is selected at the driller's panel, wire 143 energizes and switches
relay 22. Energizing relay 22 interrupts power to the holding contact. The motor stops and the
power module indicator light shuts off.
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
POWER UNIT
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
TROUBLESHOOTING GUIDE
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
INDEX
Numerics
3F valve, 10
A
auxiliary hydraulic manifold
checking, 14
auxiliary pump, 69
auxiliary pumpauxpump, 71
B
bail movement
unanticipated, 29
unbalanced, 27
C
case drain
and worn motors, 10
excess, 11
flow rate for motor, 10
flowmeter, 10
increasing motor case drain, 10
interpreting flow rates, 7
motor, 10
pump, 6
surge in motor flow, 11
temperature, 7
charge pump, 4
closed loop
introductiocloop, 3
cold climate switch, 11
introduction, 35
commissioning, 1
connectors
Pyle National, 38
cooling schematics, 1
current sensor, 66
D
diode
testing, 40
direction holding circuit
mud saver valve, 64
drill ahead, 1
drillers panel functions, 1
electrical schematics, 1
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
electrical testing
diode, 40
elevator-close, 55
elevator-open, 53
extend-in, 51
extend-out, 52
feedback, 40
general, 38
grabber lift-down, 42
grabber lift-up, 41
grabber/drawworks interlock interface, 61
grabber/pipe handler interface, 60
grabber-close, 58
grabber-close holding contact, 59
grabber-open, 57
link tilt-back, 48
link tilt-float, 49
link tilt-forward, 46
mud saver open timer circuit, 63
mud saver valve-close, 64
mud saver valve-open, 61
mud saver-close light, 66
multiple functions, 40
pipe handler-lock, 45
pipe handler-unlock, 43
power, 39
elevator close
hydraulic testing, 20
elevator open
hydraulic testing, 19
elevator-close
electrical testing, 55
elevator-open
electrical testing, 53
elevators, 19, 20
extend forward
hydraulic testing, 21
extend quick couplers, 21
extend retract
hydraulic testing, 21
extend-in
electrical testing, 51
extend-out
electrical testing, 52
F
feedback
tesing for, 40
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
INDEX
TROUBLESHOOTING GUIDE
G
gearbox lubrication system
hydraulic testing, 29
general testing
hydraulic, 14
grabber
interface with pipehandler-lock, 14
grabber close
hydraulic testing, 23
grabber lift down
hydraulic testing, 19
grabber lift up
hydraulic testing, 18
grabber lift-down
electrical testing, 42
grabber lift-up
electrical testing, 41
grabber open
hydraulic testing, 22
grabber/drawworks interlock interface
electrical testing, 61
grabber/pipe handler interface
electrical testing, 60
grabber-close
electrical testing, 58
grabber-close holding contact circuit, 59
grabber-open
electrical testing, 57
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
Linde pumps, 7
charge pressure, 4
low flow, 6
troubleshooting, 6
link tilt float
hydraulic testing, 27, 29
link tilt forward
hydraulic testing, 26
link tilt reverse
hydraulic testing, 28
link tilt-back
electrical testing, 48
link tilt-float
electrical testing, 49
link tilt-forward
electrical testing, 46
make connections, 1
manifold
auxiliary, 26, 29
auxiliary hydraulic, 15
checking auxiliary hydraulic, 14
grabber accumulator, 19
kidney, 18, 22
pipe handler, 22
Modine cooling fan
introduction, 31
motor case drain
flow rate, 10
increasing, 10
surge in, 11
motor pot board, 12
motor starter, 68
motor startermotorstarter, 69
mud saver open timer circuit
electrcial testing, 63
mud saver valve, 25, 26, 63, 64, 66
direction holding circuit, 64
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
TROUBLESHOOTING GUIDE
timer circuit
mud saver valve, 63
tripping operations, 1
valve
3F, 10
unloader, 16
parts lists, 1
pipe handler lock, 24, 60
hydraulic testing, 24
pipe handler unlock
hydraulic testing, 24
pipe handler-lock
electrical testing, 45
pipe handler-unlock
electrical testing, 43
pre-operational checklists, 1
pressure losses, 4
pump controller, 11
checking, 11
electrical connections, 12
pumps
cavitation, 11
R
re-circulation pump
introduction, 34
rig out, 1
rig up, 1
rotary seal, 18, 23
checking, 17
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
INDEX
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
TROUBLESHOOTING GUIDE
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
SYSTEM DESCRIPTION
ENGINEERING SIGN-OFF
This sign-off sheet indicates that this document has been approved for release by the
Engineering Department at TESCO.
Document Complete By
Signature
Kristen Sabo
May 2009
ER ERASM
PI
ET
EN G I N
PR
O FES S I O
L
NA
Digitally signed by
Pieter Erasmus
DN: cn=Pieter
Erasmus, o=Teaco
Corporation,
ou=Engineering Sustaining,
email=pieter_erasm
us@tescocorp.com,
c=CA
Date: 2008.04.08
10:47:48 -06'00'
A LB E R T
ER S
U
Pieter
Eras
mus
2008.04
.08
10:46:4
1
-06'00'
Document Reviewed/Approved
Date Signed
N
L E G INE
N A ER ERASM
T
PI
PR
A LB E R T
ER S
U
O FES S I O
Date Signed
27 May 2009
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM
SYSTEM DESCRIPTION
CONTACT: 1-877-TESCO-77
INTL: 713-359-7295
WWW.TESCOCORP.COM
WWW.TESCOPARTS.COM