Beruflich Dokumente
Kultur Dokumente
GUIDELINES
FOR THE EXPLOSION PROTECTION OF
ELECTRICAL EQUIPMENT
EDITION 2001
ii
BOARD OF COMMISSIONERS
Chairman
Commissioner
Secretary
SURVEY DIVISION
Reporting & Certification Sect.
Monitoring & Register Sect.
Acquisition Sect.
: Ir. Haryanto
: Ir. Hadi Soetrisno
: Ir. Purnomohadi
: Soesetyo Adie , AMK-B, MM
: Ir. L. Manupassa
: Ir. Agus Wijaya
: Ir. Jeffrey B. Massie
iii
iv
STATUTORY DIVISION
Load Line & Cargo Gear Sect.
SOLAS, MARPOL & ISM Sect.
PLANNING DEPARTMENT
Budget & Reporting Sect.
Information System Sect.
: Ir. Ajatiman
: Taufik Hidayat, SE, MM
: Ir. Azril Bayma
FINANCE DIVISION
: Drs. Sukiyo
: Ora. Yayuk Mahanani, MM
: R. Sudaryo, SE
CIGADING
: JI. Raya Pelabuhan, Kompleks
Pelabuhan, Ambon 97216
: (0911) 355036
: (0911)352745
: Ir. Pieter Petrus Paulus
Address
Telephone
Telefax
Head
BALIKPAPAN
CIREBON
Address
Address
Telephone
Telefax
Head
Deputies
Telephone
Telefax
Head
DUMAI
Address
BANJARMASIN
Address
Telephone
Telefax
Head
Telephone
Telefax
Head
BELAWAN
Telephone
Telefax
Head
BITUNG
Address
Telephone
Telefax
Head
BATAM
Address
Telephone
Telefax
Head
Address
Telephone
Telefax
Head
Deputy
KENDARI
Address
: Jl. Bunga Matahari No. 64
Kemaraya - Kendari 93121
Telephone : (0401) 321622
Telefax
: (0401) 321622
:
Ir. Rachmadi S
Head
MAKASSAR
Address
Telephone
Telefax
Head
vi
PADANG
Address
: J1. St. Syahrir No. 208
Padang 25216
Telephone : (0751) 61553
Telefax
: (0751) 61553
Head
: Ir. Bambang Noeljanto
PALEMBANG
Address
: J1. Perintis Kemerdekaan 5 Ilir,
Palembang 30115
Telephone : (0711) 713171,713172,713680
Telefax
: (0711) 713173
Head
: Radjin Sitorus
PONTIANAK
Address
: J1. Gusti Harnzah No. 211
Pontianak 78116
Telephone : (0561)39579
Telefax
: (0561) 39579
Head
: Ir. Umar Faisal
SEMARANG
Address
: JI. M.Pardi No.5, Pelabuhan
Tanjung Emas Semarang 50229
Telephone : (024) 543917 , 545805
Telefax
: (024) 543917
Head
: Ir. Yansen Miri
SURABAYA
Address
J1. Kalianget No. 14
Surabaya 60165
Telephone: (031)3295448,3295449,3295450,
3295451
(031) 3294520
Telefax
Head
Ir. M. Nasrun Djafar
Deputies
Ir. Mohamad Cholil
Ir. Agung Prihanto
SORONG
Address
SINGAPORE
Address
111 North Bridge Road # 08-07
Peninsula Plaza Singapore 179098
Telephone: (65) 8830634 - 43 - 51
Telefax
(65) 3393631
Head
Ir. Onot Subagyo
vii
1.
Head Office
3.
Head Office
Telephone
Telefax
Telex
Cable
: VERITASVEIEN 1, N-1322
HOVIK, NORWAY
: 300,1322 HOVIK, NORWAY
: (47) 67579900
: (47) 67579911
: 76 192 VERIT N
: VERIT AS OSLO
: VORSETZEN 32.
D-20459 HAMBURG
Telephone
: (49) (0) 40-36149 - 0
Telefax: (49) (0) 40-36149 - 200
Telex
: 2 12828 GLHH D
E - m a i l : headoffice@germanlloyd.org
Web site
: www.germanlloyd.org
Head Office
Telephone
Telefax
Telex
Cable
E-mail
7.
Head Office
: 23-7 JANG-DONG,
YUSUNG-KU, T AEJON
REP. OF KOREA 305-600
: 29 T AEJON REP.OF KOREA
P.O. Box
Telephone
: (82) (42) 869-9114
Telefax: (82) (42) 862-6011 - 6
Web site
: http://www.krs.co.kr
viii
Head Office
Telephone
Telefax
Telex
E-mail
Web site
9.
11.
Head Office
Telephone
Telefax
E-mail
: 4-7. KIOI-CHO,
CHIYODA-KU, TOKYO
102-8567, JAPAN
Telephone
: (81) (3) 3230-1201
Telefax: (81) (3) 5226-2012
E - m a i l : cld@classnkorjp
Web site
: www.class nk or jp
Head Office
10.
Telephone
: 1 FLOOR WISMA
MARITIM
PERSIARAN SUKAN,
SECTION 13
40100 SHAH ALAM
SELONGOR DARUL
EHSAN, MALAYSIA
: 03 - 50318160
: 03 - 50318189
: scmhq@pd.jaring.my
Head Office
(RNR)
Head Office
Telephone
Telefax
Telex
Telefax
E-mail
Web site
: vr@hn.vnn.vn
: WWW.Vf.vnn.vn
ix
KIND OF
NO
STATE
CLASSIFICATION SOCIETIES
COOPER ATION
USA
Dual Class
France
Dual Class
China
Mutual Representation
Norway
Dual Class
Germany
Mutual Representation
Greece
Mutual Representation
South Korea
Mutual Representation
UK
Dual Class
Japan
Mutual Representation
10
Romania
Mutual Representation
11
Malaysia
Mutual Representation
12
Vietnam
Mutual Representation
Table of Contents
Table of Contents
A.
B.
C.
D.
E.
F.
Page
Reference to Codes and Requirements
1.
Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
2.
Constructional Rules of Biro Klasifikasi Indonesia. . .. . . . . . . . . . . . . . . . . . . . . . ..
1
Fundamental Concepts and Definitions
1.
Explosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.
Characteristic values of materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.
Explosion groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.
Temperature classes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.
Types of ignition protection .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.
Field of applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
2
5
6
6
8
9
11
12
15
20
29
31
33
34
41
42
43
43
37
37
39
40
APPENDIXES
Appendix 1 : Oil products. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
46
Appendix 2: Gases.........................................................
46
47
50
53
The manufacture, installation and testing of electrical facilities for use in explosion hazard areas
are subject to strict requirements. Since these Guidelines deal with applications on ships and
mobile offshore drilling units, only the principal international codes and requirements applicable
to these will be mentioned. Respective national requirements as may be applicable are to be
observed.
1.
Requirements
a.
b.
c.
d.
e.
IMO - Code for the Construction and Equipment of Mobile Offshore Drilling Units
(MODU Code)
f.
g.
SOLAS 1974, Chapter 11-2, Construction - Fire protection, fire detection and fire
extinction
2.
h.
i.
Rules for the Classification and Construction of Seagoing Steel Ships, Volume IV,
Rules for Electrical Installations
b.
Classification and
Construction
of Inland
Waterway Vessels,
Rules for Mobile Offshore Drilling Units and Special Purposes Units, Section 13,
Electrical Installations, Section 14, Machinery Installations, Electrical Installations,
and So on in Hazardous Areas
d.
Rules for the Classification and Construction of High Speed Craft, Section 12,
Electrical Installations
B.
1.
Explosion
by
high
temperatures
and
sharp
increase
in
pressure,
and
a.
b.
2.
2.1
Flash point
The flash point of a combustible liquid is the lowest te i -:1perature (referred to a pressure
of 760 mmHg) at which a vapour/air mixture inflammable by external ignition can form the
test liquid under specified conditions.
It follows that a combustible liquid with a flash point higher than the prevailing ambient
temperature does not constitute an explosion hazard unless the liquid is heated above its
flash point. The flash point thus gives an indication of the degree of fire and explosion
hazard of the relevant liquid.
2.2
Ignition temperature
The lowest temperature at which a potentially explosive atmosphere is ignited is called the
ignition temperature. The ignition temperature of a potentially explosive atmosphere is not
a constant but strongly depends on external conditions.
necessary to specify the experimental conditions when stating the ignition temperature of a
potentially explosive atmosphere.
2.3
The explosion limits indicate the concentration range within which the atmosphere is
potentially explosive. There is an upper explosion limit (UEL) and a lower explosion limit
(LEL). If the mixture is too lean or too rich, an explosion cannot take place, because there
is either too little combustible material or too little oxygen.
explosion limits, the less hazardous the material concerned, due to the lower explosion
point and the flash point are close together.
16
'4
,~
/%
lower explosion
(LEL)7
O--~~~~~~~~~~~~LL~~~~~~~
so
temperature tIC)
4
2.4
The minimum ignition energy is the smallest quantum of energy with which a potentially
explosive atmosphere can be ignited. The following are possible sources of ignition:
Hot surfaces
Flames and hot gases
Mechanically generated sparks
Electrically generated sparks, arcs, etc.
Static electricity
Lightning
Electromagnetic waves at radio frequencies and in the visible spectrum
Ionizing radiation
Ultrasound
Adiabatic compression
Chemical reactions.
2.5
The ignition propagation ability is the capability of hot gases to propagate ignition through
a gap of specified length and width.
specified gap width, as the energy of the flame has already been consumed.
The
The principle parameters of materials which are conveyed on seagoing tankers are set
out in the table given in the appendix to these Guidelines.
vapour
concentration
density
(% Volume)
( g/m 3 )
CIl
CIl
u
0
U
0
0
..c
CIl
ro
lower
upper
lower
upper
L...
::J
::J
ro
c
a
.iii
c E
0..
-I--
I--
L...
:z:;o...
L...
0.
a
x
Acetylene
1,5
82,0
16,0
880
305
T2
IIC
Ammonia
15,0
28,0
105,0
200
630
T1
IIA
Low-boiling nephta
<-20
1,1
7,5
280
T3
IIA
Benzene
-11
1,2
8,0
39,0
270
555
T1
IIA
n-butane
1,5
8,4
38,0
207
365
T2
IIA
Petroleum
-60
>21
0,7
5,0
~220
T3
IIA
Fuel-oil
>60
0,6
6,5
250
T3
IIA
5,0
15,0
33,0
100
595
T2
IIA
11
5,5
26,5
73,0
410
455
T1
IIA
Kerosene
>40
0,6
8,0
~220
T3
IIA
Propane
2,1
9,5
39,0
180
470
T1
IIA
Propylene
2,0
11,7
35,0
210
455
T1
IIA
Carbon disulphide
<-20
1,0
60,0
30,0
1900
102
T5
IIC
Hydrogen sulphide
4,3
45,0
60,0
650
270
T3
IIA
4,0
75,6
3,3
64
560
T1
IIC
Methane
Methyl alcohol
Hydrogen
3.
W
L...
::J
OlW
u:::
0.
e
(9
ro
0.
ro
l5
Explosion groups
Combustible gases and vapours are classified in the following explosion groups in
accordance with their ignition propagation ability through gaps under specified conditions,
the basis of the following examples being a gap length of 25 mm:
6
4.
Combustible gases and vapours are classified in temperature classes in accordance with
their ignition temperatures, as shown below:
Ignition temperature
of combustible substances
>450
>300
>200
>135
>100
>85
The above values apply not only to electrical engineering but also to mechanical
assemblies such as heat exchangers, pipework, etc. Such assemblies with high surface
temperatures,
does not exceed 80 % of the ignition temperature of the relevant substance, due
allowance being made for accumulations of heat. Other sources of ignition are to be
avoided.
5.
5.1
Flameproof enclosure Ex d
Parts of electrical facilities constituting sources of ignition are surrounded by pressuretight (but not completely gas-tight) casings, whose unavoidable sealing surfaces, cable
entries, penetrations of moving parts, etc., are rendered proof against ignition
propagation by limitation of gap lengths and widths (e.g., motors and switches). Although
explosive mixtures penetrating into the casing may be ignited, ignition of the mixtures
outside the casing is prevented.
5.2
Pressurized enclosure Ex p
In this case,
control panels or machines) are bathed in fresh air or inert gas or kept under excess
pressure, in such a way that the explosive mixtures from the surrounding atmosphere
cannot penetrate to the parts which constitute sources of ignition.
5.3
Increased safety Ex e
Electrical facilities which do not constitute sources of ignition in normal service (e.g., light
fittings, three-phase squirrel cage motors generators without sliprings and commutators
are protected against impermissible overheating in the event of faults, to avoid the risk of
ignition should a fault occur, by additional apparatus to limit current or
(e.g.,
protective
cutouts with
appropriate characteristics,
temperature
voltages
monitors).
Measures are also adopted to ensure that short-circuits are precluded with a high degree
of probability.
5.4
Parts electrical facilities constituting sources of ignition are, for example, sealed in a
totally gas-tight enclosure, thus preventing access by explosive mixtures to the source of
ignition (e.g., switches in closed, gas-tight glass vessels).
5.5
Intrinsic safety Ex i
5.6
Oil immersed Ex
This involves placing equipment in oil-filled tanks to prevent gas from reaching any arcs
that may be produced.
5.7
Sand filled Ex q
Same idea as the oil immersed except that quartz "sand" is used rather than oil. An HRC
(High Rupture Capacity) fuse-link is sand filled.
6.
Fields of application
According to IEC 79-0, electrical facilities for explosion hazard areas are to be divided to
the following groups:
Group I
Group II
C.
Explosion hazard areas are ones in which a potentially explosive atmospheres may occur in
a dangerous quantity. Identification of explosion hazard areas is often difficult, as these depend
substantially on the construction of the relevant parts of the ship, working conditions and the
characteristics and quantity of the explosive gas-air mixture to be expected. In assessment of
the concentration of the mixture, it should be remembered that most vapour/air mixtures are
heavier than air and therefore accumulate in the lower parts of rooms.
Hydrogen, methane,
ammonia, acetylene, carbon monoxide and ethylene, on the other hand, are lighter than air and
therefore become distributed through out the room, with a stronger concentration at higher
levels.
The constructional measures used on ships and mobile offshore drilling units should in all cases
be directed towards minimizing the accumulation of hazardous gas-air mixtures. Such measures
on tankers include, for example, gas displacement lines and high-speed valves, as well as
appropriate design of the tank deck, superstructures and entrances.
hazard areas can be limited by such measures.
explosion protection.
Other measures in the field of primary explosion protection are a high rate of air change in, or the
inertization of, hazard areas, disconnection of electrical facilities, e.g., on cargo ships, during
transport of hazardous sea cargoes, and the installation of gas detection equipment.
Only when all design and constructional measures have been fully exploited should secondary
explosion protection measures be adopted - i.e., the electrical equipment for installation in the
still remaining hazard areas is to be of explosion-protected construction.
1.
For
For proper selection of electrical equipment in hazardous areas of ships carrying coal cargoes in bulk and ships
where oil or other liquids of similar hazard having flash point temperature not exceeding 60 0 C (close cup test)
are handled, stored or processed reference are to be made to the lACS Reccmmendation, No. 22, 1988
(see appendix 5)
10
This zone classification is being used increasingly in the literature and in test certificates for
electrical facilities, and will therefore now be discussed in greater detail.
Zone 0
Zone 1
Zone 2
Electrical facilities are to be selected in such a way that excessive temperatures cannot
arise and that the following conditions are met in the zones specified:
Zone 0
Ignition sources are avoided even in the case of faults occur rarely, e.g. ignition
protection Ex ia.
Zone 1
Ignition sources outside the facility are precluded even in the case of faults
liable to occur relatively frequently, e.g. , types of ignition protection Ex d, p. e. s
and ib.
Zone 2
Ignition sources are not liable to occur in the course of normal working (e.g.,
three-phase squirrel cage motors), or, in the case of facilities where ignition
sources are liable to occur in normal operation, a casing is present for protection
against the penetration short-term gas clouds (minimum protection class IP 55).
2.
11
2.1
2.2
2.3
2.4
Rooms for the storage of fuels with a flash point of.::: 60C.
2.5
2.6
2.7
Holds for the transport of motor vehicles driven on and off the ship under their own power,
as follows:
2.7.1 Cargo holds on cargo ships and enclosed motor vehicle decks on passenger ships above
the main deck up to a height of 45 cm above deck.
2.7.2 Cargo holds in passenger ships below the main deck (entire height) .
2.8
Note: Methane (CH 4 ) and hydrogen sulphide (H 2S) may be given off by dredging spoil.
Adjoining the direct explosion hazard area - for example, adjoining holds for motor vehicle
transport (2.7.1) - there may be extended hazard areas, in which a potentially explosive
atmosphere is liable to occur seldom, and then only on a short-term basis (comparable
with Zone 2).
Such areas are for example, ones above a level of 45 cm right up to the
12
3.
Tankers
The specification of the explosion hazard areas set out below applies only to tankers
(including chemicals and gas tankers) with cargoes having a flash point of ~ 60C
(comparable with Zones 0 and 1) .
3.1
3.2
3.3
3.4
Closed or semi-enclosed rooms immediately above cargo tanks or with bulkheads above
or in line with cargo tank bulkheads.
3.5
Closed or semi-enclosed rooms directly above cargo pump rooms or above cofferdams
adjoining cargo tanks, unless these are separated from each other by a gas-tight deck
and adequately ventilated.
3.6
3.7
Other rooms serving as cofferdams, adjoining cargo tanks and extending to a level below
the upper edge of cargo tanks (e.g., trunks, service gangways and cargo holds).
3.8
rooms
within
a spherical radius
of 3 meters around tank outlets or outlets of pump rooms or cofferdams (e.g., cargo tank
hatches, flanges, inspection ports, ventilation openings of pump rooms or cofferdams,
entrances to cargo pump rooms).
3.9
The open deck above cargo tanks, plus 3 meters fore and aft and across the full width of
the ship (even if there are lateral ballast tanks), up to a height of 2,4 meters above deck.
3.10
3.11
Closed or partially enclosed rooms containing pipework through which cargo is conveyed.
3.12
the 3 meters
(2,4 meters) areas mentioned above are to be extended to at least 4,5 meters.
3.13
13
Closed or partially enclosed rooms not in themselves presenting a hazard but having
openings to the hazardous area on the open deck are to be regarded as at risk, unless
they satisfy the following conditions (e.g., on gas tankers) :
a)
Access is by way of gas locks. There is to be an audible and visual alarm system
which gives a warning signal on both sides of the gas lock if the locking devices on
more than one door are not completely closed.
b)
c)
The excess pressure or air flow is to be monitored and, if the ventilation fails, an
audible and visual alarm is to be given and the power supply to all equipment not of
explosion-protected construction is to be disconnected automatically, if necessary
after a time lag. Equipment which presents a serious hazard if disconnected is not
to be disconnected.
d)
e)
Interlocking facilities
equipment
are
required
to ensure
that non-explosion-protected-
3.14
Areas on the entire open deck and above and aft of superstructures.
3.15
Areas in front of cargo tanks at the same level as, or below, the tank deck and having a
direct opening to the main deck.
3.16
Ventilated rooms above cofferdams adjoining cargo tanks and with oil-tight and gas-tight
separation from the latter.
3.17.
Rooms for the installation of electric drive motors for cargo pumps or residuals pump
above pump rooms.
C (example)
""~.'.'"~,,Y"""""~:-~~"'~""""
~'''''''''~'','\..~,,~~'''~'<
:......'\~''''''~''~'~''~~, ~
:......,,,~~''''~~~\~~~~'.
~~~~ ~'''''''' ~~,~,~~:
~~~~~~~~~~~~-'
,-""
'~~'~":
~'
t::
/'l: Fi
: / ' /_
'/
/....
;-...","'\~
. . . , " ' ,..
OJ
....
~
D)
CJ)
Engine room
:::;;
~
D)
:::J
0-
:::J
CD
CJ)
Q5-
"'"''''
~~~~~~~
4.
15
The explosion hazard areas set out below correspond to those of the IMO-MODUCode for mobile offshore drilling units. Other units, such as process platforms, may be
treated" in the same way where this does not conflict with national requirements. The
explosion hazard areas are classified in zones as described in C.1.
4.1
4.2
4.2.1
Enclosed areas which contain open parts of the well washing system and are located
between the well bore and the outlet of the degassing system.
4.2.2
Closed or semi-enclosed areas below the rotary table and liable to constitute a hazard,
e.g., the washing outlet of the well bore.
4.2.3
Enclosed areas on the drilling deck, where not separated from hazard areas by gas-tight
bulkheads.
4.2.4
Areas on the open deck and in semi-enclosed rooms at a distance of 1,5 m from
openings of systems with gas-containing well washing and around all ventilation openings
and accesses to Zone 1 rooms. Exceptions: areas in accordance with item 4.2.2.
4.2.5
Recesses, channels and similar locations situated in the area of Zone 2, in which
ignitable gas mixtures may accumulate.
16
4.3
4.3.1
Closed installation rooms with open components of the well washing system between the
degassing system outlet and the intake connections of the washing pumps in the well
washing tanks.
4.3.2
Areas in the open inside the drilling derrick up to a level of 3 meters above the rotary
table.
4.3.3
a)
Semi-enclosed areas below and adjoining the rotary table and inside the area of the
drilling derrick or in limited areas in which gas may accumulate.
b)
Areas in the open below the rotary table and within a distance of 3 meters around
components from which ignitable mixtures may issue, e.g., the washing outlet an
the drill pipe.
4.3.4
Areas 1,5 meters from areas adjoining Zone 1 (item 4.2.4) and adjoining semi-enclosed
areas of Zone 1 (item 4.2.2).
Areas in the open within 1,5 meters of venting outlets and openings to rooms of Zone 2.
4.3.5
Lined drilling derricks above the rotary tables as far as the top of lining, but not less than
up to a height of 3 meters.
17
Outlet
'"
r,= 1,5 m
1,5 m
o
~:
'm
..
Pit Ventilation
Outlet
18
D.
Ex d
FI meproof enclosure
Ex p
Pr ~ssurized enclosure
Exe
In reased safety
Ex s
S~ !ecial protection
Exi
such
as oil-immersed Ex
or sand-filled Ex q,
Type of ignitior
protection
Flameproof
enclosure
Symbol
Diagram
Explosive
mixture
, *>
sJ
s = Gap
Pressurized
enclosure
Applications
(examples)
l\ . . .Jj
0-
.......
........
sLw
F
Heavy current
applications motor,
including commutator
motors, transformers,
switchgear, light fittings
and other sparkproducing equipment
19
Type of ignition
protection
Increased safety
Special protection
Symbol
Diagram
l------I
----- -_.- ----- ------ -- -
------~-=-
Intrinsic safety
Applications
(examples)
-:: =-
--- --
--
Low-voltage applications:
measuring and control
equipment (facilities and
circuits)
20
1.
a.
Flamep
of enclosure Ex d
This is an
explosive at osphere which may have penetrated into the interior of the enclosure,
without bein
Examples of pplication:
001,
It is essenti I for the dimensions of the gaps to be maintained even in the event of an
explosion, a a constriction may lead to a dangerous increase in the explosion pressure,
while a wide ing might allow the explosion to propagate to the exterior.
Screws acc
sible from outside, the slackening of which might endanger safety, may be
Machines
Machines a
switches or quivalent means. Unless special conditions are laid down in the motor test
certificates,
the tempera ure on the out-side of the casing from exceeding the maximum permissible
values even n the event of a fault - e.g., stalled rotor.
21
SWitchgear
When contacts in electrical circuits are made or broken, sparks or arcs normally having
sufficient energy to ignite a potentially explosive atmosphere are formed. For this reason,
switchgear is normally housed in casings having the Ex d type of protection.
For ordinary industrial switchgear having no specified type of ignition protection, only
casings tested and certified as Ex d when empty may be used.
Where air gap contactors are installed, it is important to ensure that the specified minimum
distances between the arc chambers and metal walls are observed.
disconnection.
This represents an
economic solution to the problem of producing explosion protected switchgear, and control
systems.
Light Fittings
Light fittings with ignition protection of type Ex d are required to have an interlock which
allows the casing to be opened only if the equipment is not connected to the supply. After
disconnection, input terminals which are still live are required to be covered. It may only
be possible to connect the supply after the non-ignition-propagating seal of the light fitting
casing has seen restored.
22
Interlock may be dispended with if the casing carries the words "Do not open when Live".
Light fittings may only be fitted with lamps whose power ratings and types conform to the
specifications featuring on the fitting. Note that the specified lamp rating applies only to
voltages for which the fitting has been certified. However, sodium vapour lamps are not
permissible.
Only plugs and sockets with mechanical interlocks are permissible (e.g., for navigation
lights).
b.
Pressurized enclosure Ex p
It is essential to ensure that any potentially explosive atmosphere which may have
penetrated into a casing with the equipment shut down is purged before starting, and that
mixtures cannot penetrate to the inside during operation.
Examples of applications:
ignition
Pressurized enclosure casings may either be constantly bathed in inert anti-ignition gas or
a static excess pressure may be maintained in them by the inert anti-ignition gas with
compensation for leakage losses.
Safety measures - e.g., time lag relays or flow monitors - are required, to ensure that
facilities with pressurized enclosures can only be connected after the free casing space,
including inlet and outlet lines, has first been purged at least five times. Complete and
thorough purging of all parts of the casing is required.
23
An automatic safety device is required, operating if the excess pressure in the discharge
line or at the outlet opening falls below a minimum value of D,S mbar. Audible and visual
warnings are to be given.
The required operating pressure is about 2,5 mbar. These conditions are also applicable
mutatis mutandis to rooms having excess pressure ventilation as a protective measure
against the penetration of explosive gas-air mixtures (see also C.3.13).
c.
Increased safety Ex e
Examples of application:
Machines
Where the Ex e type of Ignition protection is used in three-phase squirrel cage motors,
additional measures, also relating to interaction with the associated protection switch, are
required. The temperature limitation requirements for machines with Ex e ignition
protection are substantially stricter than for machines with Ex d protection, as not only the
surface temperature of the casing but also the temperature in the winding space has to be
limited. Only machines with at least protection class IP 44 may be used.
The correct motor protection switches or overcurrent relays are chosen in accordance
with the criterion of prompt disconnection of the motor from the mains before it can
assume dangerous temperatures.
24
it
200;-~~~~~~-L~~~~~~~~~~~~
175 -r----------.....",...-J~:::::.;::.:..::.:.:::r..::==:..:
105
Ambient temperature
__
-._ Time (8)
Stalled rotor
With the rotor stalled, there is a risk of the stator and rotor windings quickly attaining
temperatures exceeding the ignition temperature of the relevant gas-air mixtures. For this
reason the concept of heating time tE has been introduced; this indicates the time after
which the permissible limit temperature is exceeded with the rotor stalled. This time tE
may in no case be less than 5 seconds. The ratio IA : IN may not exceed 10 (see also
lEe 79-2).
The starting current, rated current and heating time tE are to be stated on the specification
plates of squirrel cage motors.
25
IA : IN
IA
IN
tE
tA
For the above example, the diagram below shows that the relevant safety device would
trip after 7 seconds with an IA : IN ratio of 6,5. Hence the tripping time tA is greater than
the minimum value of the heating time tE (5 seconds) but less than the motor-specific
heating time tE (10 seconds).
-<Il
.......
30
20
"'-
t
10
~,
-4
.........
""'"
3
2
1
3
7
6,5
26
Since the explosion protection of machines with Ex e ignition protection largely depends
on the correct choice and setting of the protective device (usually, a bimetal cutout), it is
recommended that this prescribed protective device be supplemented by temperaturedependent
It is recommended that PTC resistors are to be used, as their resistance increases with
increasing temperature, so that an "overtemperature" signal is given even in the event of
an open circuit. A PTC temperature monitor monitors itself. Another advantage is the
step-type characteristic which gives an unambiguous indication.
In a critical-stator machine, the stator winding reaches the maximum permissible winding
temperature first in the event of stalling of the rotor, while the maximum permissible
winding temperature is first attained in the rotor in the case of a critical-rotor machine.
In this
In the case of motors rated at over 20 kW, protective devices are required which ensure
motor protection even in the event of failure of one external conductor - e.g., phasefailure-sensitive thermal overcurrent relays or cutouts.
Light fittings
The efficacy of the explosion protection in this case substantially depends on the lamps
used.
Owing to the trend towards a reduction in the size of lamp bulbs for a given power, or for
the power to be increased while the glass bulb remains the same size, there is a risk of
the permissible temperatures being exceed.
27
ii.
Incandescent lamps
iii.
Mixed-light lamps
iv.
Other lamps in which there is no possibility of parts of the light source assuming a
higher temperature than the limit temperature after bulb fracture; however, lamps
containing free metallic sodium are not permissible.
Light
fittings may only be fitted with lamps whose power and type conform to the
specifications featuring on the fitting. Note that the specified lamp rating applies only to
the voltage for which the fitting is certified. General-service lamps for light fittings with
Ex e ignition protection are to conform to IEC 79-7. This requirement is deemed to be
satisfied if the lamps bear the identification mark "Ex".
with a voltage of > 42V are to be of impact-resistant construction to IEC 79-0. Impactresistant incandescent lamps are marked "Ex".
d.
Type Ex s ignition protection refers to measures differing from the conditions of the other
ignition protection types and which ensure equipment safety by other means. This method
of protection is often used in conjunction with other types of ignition protection. It is most
usually achieved by encapsulation with epoxy resin.
28
e.
Intrinsic safety Ex i
A circuit is intrinsically safe if sparks or thermal agencies arising in normal operation (e.g.,
when the circuit is made or broken) or in the event of faults (e.g., short-circuits and earth
faults) cannot ignite a potentially explosive atmosphere.
A definite and universally valid limit for the minimum ignition energy cannot be specified,
as many factors are involved, including the resistance, inductances and capacitances in
the circuit, the material of the contact electrodes and the form of the electrodes.
The
intrinsic safety of a circuit may be cancelled out by external agencies, such as cable
capacitance or stray electrical and magnetic fields.
permissible inductances and capacitances within intrinsically safe circuits are specified in
the test certificates. However, a power of about 1 watt can be specified as a rough guide.
"Safety barriers" are also sometimes used, the effective voltage in the intrinsically safe
circuit here being limited by zener diodes, which afford protection without electrical
separation.
Only intrinsically safe circuits with separation from the ship's or unit's mains are
permissible on board tankers and mobile offshore drilling units. Where safety barriers are
used, additional electrical separation may also be necessary.
In equipment with intrinsically safe circuits for Zone 0, only the "ia" type of
ignition
protection to lEe 79-2, may be used, unless the test certificate expressly allows use in
Zone O. Facilities, such as hermetically sealed contacts, for use in Zone 0 require special
approval, even if they are included in an intrinsically safe circuit Ex ia.
29
The type of ignition protection for equipment with intrinsically safe circuits for Zone 1 is to
be at least" ib " to IEC 79-2. Ordinary electrical facilities without a specified type of ignition
protection may be used within intrinsically safe circuits for use in Zone 1 provided that the
intrinsic safety of the circuit is not endangered by, for example, additional capacitances
and inductances.
In measuring and control cabinets and similar equipment, the connection terminals are to
be located separately from those of non-intrinsically-safe circuits.
This condition is
deemed to be met if there is an insulating partition or if the distance between the strips is
at least 50 mm. This also applies to the separation from each other of intrinsically safe
circuits of Zone 0 and Zone 1. Conductors of intrinsically safe circuits and other
conductors may not be run together in cables, lines, conduits and cable ducts. Only metalsheathed or metal-shielded cables and lines may be used for permanent wiring. The
distance between cables of intrinsically safe circuits and other cables is to be at
least 50 mm.
Intrinsically safe circuit may not earthed and may not be connected together, unless this
expressly permitted in or required by the certificate, e.g, at safety barriers.
Cables, lines and intrinsically sate facilities which are not immediately recognizable as
belonging to the intrinsically safe system are to be coded; they may, for example, be
colour-coded light blue.
2.
Only portable electrical facilities having their own power source may be used in the
explosion hazard area (Zones 0 and 1).
Exceptions are permissible only if the facility is supplied via an intrinsically safe
circuit Ex i.
30
A test requirement for portable electrical facilities is that they are to be dropped, in
working condition, four times from a height of at least 1 meter on to a flat, horizontal
concrete surface.
This test may not cause any damage which impairs the ignition
protection of the electrical facility. Where it is possible for the facility to fall further, e.g.,
when being carried over a cargo tank, measures are to be taken to protect the facility
from falling.
Portable lights for use on the tank deck and in cargo tanks should preferably be of the
type with Ex p ignition protection, having a built-in generator driven by compressed air.
These lights have the advantage of requiring no electricity supply line, and they are also
available for use in Zone 0.
Where portable electrical facilities are used, it is essential to ensure that the type of
ignition protection is sufficient for the relevant application. To give as wide a range of
application as possible, the minimum requirement to be observed should be:
Temperature class T3
and, for facilities with Ex d ignition protection, additionally;
Explosion group II C.
In the case of facilities to be used in Zone 0, suitability for this use must be demonstrated.
Use of the above ignition group and explosion class takes account of the most frequently
occurring gas-air mixtures on board ships and mobile offshore drilling units, thus as far as
possible precluding incorrect utilization.
It is recommended that all portable electrical facilities used on board tankers - e.g.,
portable radio telephones, torches, etc. - be of explosion-protected construction whether
or not they are intended for use in the explosion hazard area.
3.
31
Types of installation
The following main types of installation are used for explosion-protected electrical
facilities with type Ex d ignition protection:
1. Cable system (indirect entry)
2. Direct cable entry
3. Conduit system (direct entry)
'//
Flameproof
equipment
chamber
Equipment
chamber
(explosion-proof)
Flameproot
chaniber
77
Indirect entry
Direct entry
(Cable system)
(Cable system)
Ignilion
bamer
t~-l.
conduit
for connect mg line
Direct entry
(Conduit system)
32
3.1
In the cable system, high-grade cables and lines (e.g., H07RN-F) are used and fed
indirectly into the flameproof casings of the electrical facilities. This type of installation is
based primarily on the lEG requirements.
With this system of installation, cables and lines are fed through cable entries into a
terminal box with type Ex e ignition protection and connected to the relevant terminals,
which are of type Ex e ignition protection.
through cable entries into the flameproof enclosure containing the electrical facilities.
Where cables are liable to be mechanically damaged, they are to be run in conduits. To
avoid damage due to condensation, these conduits may not constitute a totally enclosed
system but are to have drain openings at low points.
3.2
With this system, it is possible to feed cables and lines directly into flameproof casings,
the necessary cables and lines and their entries forming part of the Ex d protective
measures. There are two main forms of this type of installation: the French system, with
non-armoured cables, and the British system, whereby the cables are fed into the
flameproof enclosures by special screwed cable connections.
It is essential to ensure
that the correct connections are used for the type of cable and its construction and for the
relevant site.
3.3
Conduit system
Only metal conduits with drawn-through or mineral-insulated cables are permitted in the
lEG Zones 0 and 1. In practice, metal conduits are usually used, while mineral-insulated
cables are employed primarily as heating lines and fire-resistant 2) signal and control
lines.
In the design of the conduit system, it is essential to ensure that each casing containing
electrical switchgear is separated from the connected conduits by ignition barriers.
In
addition, in the case of long lengths and large diameters, supplementary ignition and gas
barriers are to be incorporated at specified intervals, to limit the explosion pressure in the
event of the ignition of any explosive mixture which may be present in the conduit.
2)
33
Fields of application for this system are offshore drilling platforms and American-type
process platforms.
Transitions from one installation system to another are permissible in all cases. Where
equipment subject to different requirements is installed together, the measures to be
taken are to be agreed upon with SKI.
One method of working transition from the conduit system to indirect cable entry and vice
versa
facility
by means of the conduit system via a short length of conduit, usually without
ignition barriers.
adaptor via cable entries into a chamber with the "increased safety" type of ignition
protection, further connections being made by the usual techniques in this chamber.
4.
The required types of ignition protection in the different explosion hazard areas are set
out in the following table. The ignition groups, and also the explosion classes for facilities
with Ex d type of ignition protection, are given.
requirements.
SKI's Construction Rules are to be observed concerning limitation of the use of electrical
facilities in explosion hazard areas.
34
In accordance
with C.2
Abbreviated description
IIC T1
T1
T1
T1
T1
2.1
2.2
IICT2
T2
T2
T2
T2
2.3
liB T3
T3
T3
T3
T3
2A
liB T3
T3
T3
T3
T3
2.5
IIAT3
T3
T3
T3
T3
2.6
2.7
2.7.1
2.7.2
2.8
5.
According to cargo
IIA T3
T3
T3
T3
T3
IIAT3
T3
T3
T3
T3
IIA T3
T3
T3
T3
T3
Only explosion-protected electrical facilities of at least the following ignition group and
explosion class may be used in the explosion hazard areas specified in C.3 and CA for
seagoing ships and mobile offshore drilling units:
Temperature class T3
and, for facilities of type Ex d ignition protection, additionally;
Explosion group II B.
35
More stringent explosion protection requirements may be necessary in ships used for
transporting special cargoes, e.g., carbon disulphide:
Temperature class T5
and, for facilities with type Ex d protection, additionally;
Explosion group IIC.
All other types of ignition protection, including Ex i circuits not suitable for use in Zone 0
(ib), may not be used for this application. The identifying symbols for intrinsically safe
circuits for use in the interior of cargo tanks, pipework, pumps etc., are as follows; Ex ia
36
Submerged pumps for use on gas tankers are excluded from these requirements.
Submerged pumps, including their electric drive motors and supply cables, may be
installed direct in the cargo tanks without any specific type of ignition protection, but the
following conditions are then to be met:
i.
The pump motors may only be operated below the surface of the liquid. Reliable
means of preventing operation in a gas-air mixture are required.
ii
Automatic disconnection, with alarm in the cargo monitoring room, is required in the
event of:
a.
b.
c.
For safety reasons, a combination of several disconnection criteria should be used with a
safety circuit - e.g., a 1-out-of-2 or preferably a 1-out-of-3 circuit.
37
E.
1.
Requirements
The following governs the construction and testing of explosion protected electrical
facilities:
lEG 79-0,
General Requirements
lEG 79-2,
lEG 79-1,
lEG 79-7,
Tests conducted on the basis of the equivalent standards will be recognized by SKI, if
their equivalence is demonstrated.
2.
SKI does not conduct tests of electrical facilities to verify conformity with the' explosion
protection requirements.
E.4) confirming that the above requirements are satisfied, are to be submitted to SKI.
Since these test requirements are based on the environmental and operating conditions
of shore installations, an assessment by SKI
environmental and operating conditions on board ships or mobile offshore drilling units is
required in addition to submission of the test certificate. The environmental conditions,
and hence the requirements, differ as between shore and marine installations in particular
in the following points:
Environmental
conditions
Ambient temperature
Shore installations
40 0 C
Vibration
General: freq.
Specific: freq.
Atmospheric humidity
Inclinations
Up to 45
38
Additional tests for the purposes of type approval may cover the following, depending on
the type of equipment:
Vibration test
Accelerated climatic test
High-temperature test
Salt mist test
Inclined orientation test
Reference should be made to the "Regulations for the Performance of Type Tests."
In addition to these tests, SKI will examine the equipment and its individual components
on board to verify the following:
i.
ii.
iii.
Conformity of the test certificate number with the unit concerned, and compliance
with any other requirements
iv.
v.
Functional test.
3.
39
According to IEC 79-9, the following testing stations (examples) are approved in various
countries:
Austria
Belgium
Canada
France
Germany
Italy
Japan
Norway
UK
USA
lEe Publication 79
"d "
Ex d IIA T3
"p"
Ex P II T1
"e"
Ex ell T3
"i"
Ex ia IIC T5
Ex ib liB T5
40
4.
J!l
c
II>
J!J
c
..,11>
.gJ
"l!!
e,'=
tlW
cE
:;:;
~'5
ern
.sOl
Ole:
~~
Austria
l!!
;0
.,cW
.
0
.!!
'II>~
:u=s
~
'6
.5
c
0
1:
11Co
.e
.. 0
()()
:8
Il..
OVE 165
cab
Ex
d:#8#286
e:#8#717
1:#8#683
Reg. gen
cab+
con
Ex
ADF
CSAStd.
C22.2 No.3D
CSASld.
C.22.1
con
Exp
(Endosures)
(Ind.)
C.22.2
No.145
(MoIolS)
C.22.5
0.0
!!"iG
0
()
aVi
().!!
OVE 171
.!!!
11.f:
:z;-g
l!!
;:J
1:
OJ
Co
;:J
D>
II>
1:
im
uc
~
rn
.::!;:J
.,
OJ
OJ
.Y
rn
e:
'1:
.f:
l!!
Do
:s
13n
I,
lIa..,
2c-f
e
(SA)
(SI)
(i)
C.1.1
DA
I,
IIA-C
11Co
iii
If)
11Co
.~
l!!
"".I!I
8.
.2
OJ
Xl
2
II)
e:
D>
.s:
""~
OJ
EVTA
Wien
GlG5
Electr. Gas
Belgium
C.E.B
Canada
CON
CSA
CENELEC
Denmark
France
CLC
CC31
Harmonis
OK
Reg.
Alsinit33
p:#8#716
0,1,2
1,2
TlT6
IN lEX
end 3
CSA
(SA
(for mines)
EX
EEx
Afsinit
cab
Ex
Ex300
con
MS
(L.O)
NFC 12
3001320
C20~1
UTE
N.O,
P,Q
Gl-G5
lab
EG
TlT6
DEMKO
<300'C
!,3oo'C
ADF
GI,
GIIIV
SA
1 3n
SP
81
E,F,G
(2oo'C)
CERCHAR
AE
C23210
(SA)
Germany
VDE 0170
VDE0171
VDE 0118
VDE0165
VDElDEK
EXVo
Hungary
Interna.
Elect. Com.
Italy
cab+
cab
(con)
(Sch)
lip
Gl-G5
.
0.1,2
(Ex)
RSZ4874
NSZ
160018
cab+
con
Ex
I,
1IIVk
sz
IEC
IEC Publ.
79111
TC311
WG9
cab+
con
Ex
I,
11AIIC
i., b
CE1311
(1.1969)
CEI642
(ab7.73)
con
AD
Ex
PE
IIA-C
CI.1
FE
81
JIS
Re. Pract.
65 (eng I)
cab+
con
1-3n
(S .. )
I,
IIAB
Ex
IIA-C
Ex
1-3n
Gl-G5
avs
PTB
BKI
Budapest
TC
31H
T1T6
0,1,2
C1.2
T1T6
0,1,2
CESI
Gl-GS
0,1,2
RIIS
SRI
TlT6
CEI
Japan
Jugoslavia
YU
JUS
Gruppe N,
S,B
SL. L
18187
cab
Nelhe~ands
NL
NEN 3750
NEN
3125169
NEN10l0
cab+
con
Sunlich
VDE 0171
Sunlich
VDE0165
ART 495
cab
PN-63IE
05050
cab+
con
B
Ex
I,
11A-C
NEGO
Norway
NVE
TlTB
4Z.
KEM
Gl-G5
(0)
las
lie, b
(2)
NEMKO
Oslo
TlTB
(N)
Poland
PL
Sweden
SEN
21.08/0.69
cab
Y
(SP)
1-3
T1T5
CH
SEV 1015
cab
Ex
t
1-3
AD
Ex
FLP
Gr.I,
IIIV
IIAC
IS
Switzerland
PN721E
08110
EIRK
SEMCO
ZEV
Zurich
United
Kingdom
United
Stata of
America
UK
USA
as
d:
229
i: BS 1259
BS 4683
CP
100312
IPEI
SC63
cab+
UL Siand.
lor salety
No. 674
913
NEC500
SARP 12
API
con+
con
(200 'C)
con
Cl.l
(Gas)
Expl.
Proof
0,1,2
BASEEFA
i
TlTB
DA
IS
CI,II,III
Gr.E,
F,G
1,2
FM
UL
5.
41
IIA
liB
IIC
Methane
CH 4
Benzene
CnH2n +2
Ethylene
CH 2-CH 2
Hydrogen H2
Carbon disulphide CS 2
Acetylene
CH-CH
Austria
(Sch) d
(Ex) d1
(Ex)d2
Belgium
Ex I
Ex lIa
Ex lib
Ex IIc
CSSR
CS
Ex3M
Ex 3 P
Ex 3 S
France
ADFGI
ADFGII
ADFGIII
ADF GIV
Germany
(Sch) d
(Ex)d 1
(Ex)d 2
Hungary
Sb-n I
Rb-n II
Rb-n III
Int. Elect
Comm.
IEC
Exd I
Exd II A
Exd liB
Exd IIC
Jugoslavia
StI
StllA
StllB
S t IIC.
Netherlands
NEM 3125
NL
1M
1 II
ExF IIA
1 III
Ex F liB
1 IV
ExF IIC
Poland
PL
BM
Ex-M IIA-
Ex-M III
Russia
BI
PB a
B2
B3
B4
Sweden
xt1
xt2
xt3
Switzerland
CH
(Ex)d1
(Ex)d2
(Ex) d3
United Kingdom
UK
Ex FLP Gr.1
Ex FLP Gr. II
United State of
America
USA
C1.1.Gr. D
C1.I.GrD
C1.I. Gr. C
C1.I.Gr,B,B,A
42
F.
1.
Basic concepts
In addition to the hazard of potentially explosive gas-air mixtures discussed above, there
may also be a hazard due to potentially explosive dust-air mixtures.
sources of ignition are the forms of energy mentioned in B.2.4. Inflammability from hot
surfaces is particularly important with dust-air mixtures.
The smouldering
43
Particle size
Bulk density
Smouldering
Ignition
IJm
kg/l
temperature
temperature
Dusts
( 5 mm thickness)
from
to
Soot
10
20
Iron dust
100
150
Zinc
10
Rye flour
535
>690
1,6
240
430
15
4,9
430
530
50
100
0,19
305
430 - 500
Fishmeal
80
100
0,66
carbonized, charred
485
Peat mould
300
500
0,07
295
420
0,3 - 0,4
260
350 - 450
610
595
Lignite
2.
of a hot surface 0 C
Coking coal
10
0,42
280
Charcoal
0,36
340
Explosion hazard areas are ones in which a potentially explosive atmosphere may occur
owing to a dangerous quantity of a dust-air mixture. These areas are classified in zones in
the same way as for shore installations and by similar criteria to those set out in C.1, but
the zone identification differs:
Zone 10
Zone 11
to
Construction, testing and use of electrical facilities with dust explosion protection
Where facilities are used in areas presenting a dust explosion hazard, such as cargo holds,
it should be remembered that not only dust-air mixtures but also gas-air mixtures constitute
a potential explosion hazard, as for example with cargoes of gas-releasing coal. In such
cases, only facilities protected against both hazards may be used.
44
3.1
3.2
3.2.1
The facilities are to be so constructed that neither potentially explosive dust-air mixtures
nor dangerous deposits of dust can form inside them. These requirements are met if the
facilities conform at least to protection class IP 55.
3.2.2
The surface temperature of the facilities may not be high enough for it to be possible for
raised dust or dust deposited on the facilities to be ignited. For this purpose, the following
conditions are to be met:
3.2.3
a)
The surface temperature may not exceed 2/3 of the ignition temperature in DC
of the relevant dust-air mixture.
b)
c)
d)
determined in
Facilities with the types of ignition protection specified in 0.1 may be used provided that
the requirements of 3.2.1 and 3.2.2 are met.
3.2.4
Sodium vapour lamps may not be used. Ballasts of fluorescent lamps are to be protected
by temperature-limiting devices unless the surface temperature required by 3.2.2 is not
exceeded even in the event of a short-circuit.
3.2.5
45
Power sockets are to be oriented so that the plug opening points downwards. Insertion
and removal of the plug may be possible only with the power off. When the plug is not
inserted, the plug opening of the socket is to be closed off with a captive cover in such a
way that the conditions of protection IP 55 are satisfied. Sockets are to be permanently
installed. Coupler plugs and sockets and adaptors may not be used.
APPENDIXES
Appendix 1 :
Appendix 2:
Appendix 3:
Appendix 4:
Oil products
Gases
Petrochemical product may be equated with oil
products with regard to explosion hazard
Chemicals
Appendix 5:
46
Name of substance
Flash pOint
Explosion
Temperature
Explosion
(0C)
group
class
protection
Petrol
<-20
IIA
T3
Jet fuel
<-20
IIA
T3
Diesel fuel
>60
IIA
T3
Petroleum
>21
IIA
T3
>60
IIA
T3
>65
IIA
T3
Petroleum ether
<-20
IIA
T3
Kerosene
~40
IIA
T3
Lubricating oil
>100
Appendix 2
Gases
Explosion
Temperature
Explosion
(0C)
group
class
protection
Acetylene
IIC
Ammonia
IIA
IIA
IIA
T2
IIA
liB
T2
T2
T1
Coking gas
T2
T1
T2
liB
T1
Motor methane
IIA
T1
IIA
T1
T1
T3
T1
Name of substance
Butane
Butylene
Natural gas (methane)
Liquefied gas
Propane
Propylene
Hydrogen sulphide
hydrogen
Flash pOint
IIA
IIA
IIA
IIC
X
X
X
X
X
X
X
47
Appendix 3
Petrochemical product which may be equated with oil products
with regard to explosion hazard
()
Name of
substance
c
0
a..
a..
:::l
0
.....
0>
c
0
.iii
en
en
ro
c
:p
- -
(3
:::l
ro
.....
Q)
a..
a..
c
0
:B
c
c..
u::::
I-
0>
Acetone
-19
IIA
T1
25
IIA
T2
Amyl acetate-n
37
IIA
T2
Amyl acetate-sec
32
IIA
Amyl alcohol-n
38
IIA
Amyl alcohol-piso
43
IIA
Amyl alcohol
sec-n
34
IIA
Amyl alcohol-seciso
30
IIA
Amyl alcohol-tert
30
IIA
Benzyl alcohol
100
Butyl acetate-iso
18
IIA
T2
Butyl acetate-n
22
IIA
T2
Butyl acetate-sec
19
IIA
T1
Butyl alcohol-iso
27
IIA
T2
Butyl alcohol-n
29
IIA
T2
Butyl alcohol-sec
24
IIA
T2
Butyl alcohol-tert
11
IIA
T1
><
E
Q)
Q)
0
.....
()
..c
en
ro
a..
Name of
substance
:::l
e0>
0
a..
c
0
.iii
..c
en
ro
c..
en
en
ro
c
0
1:5Q)
- -
(3
:::l
Q)
a..
E
0.....
a..
c
0
u::::
><
w
.2>
p-Cymene
47
IIA
T2
Decanol-iso
96
Decanol-n
82
T3
Decyl alcohol-n
82
T3
T2
160
T2
Di-iso-butyl
phthalate
Di-iso-butyl ketone
49
Di-iso-butylene
>-7
Diacetone alcohol
58
Dibutyl phthalate
166
Dicyclopentadiene
32
IIA
T3
Diethylbenzene
56
IIA
T2
Diethylene glycol
124
T3
Diethylene glycol
diethyl ether
82
Diethylene glycol
monobuthyl ether
107
Diethylene glycol
monobuthyl ether
acetate
116
Diethylene glycol
96
110
T2
X
X
T2
T2
IIA
T2
X
X
IIA
T1
T3
Butyl benzyl
phthalete
199
Butylene glycol
>65
GammaButyrolactone
98
Diethylene glycol
monoethyl ether
acetate
31
Diethylene glycol
monomethyl ether
93
Cumene
Cyclohexane
-18
82
Cyclohexanol
68
Diethylene glycol
monomethyl ether
acetate
monoethyl ether
T2
IIA
T3
48
Appendix 3
Petrochemical product which may be equated with oil products
with regard to explosion hazard (continued)
a.
0
0
Name of substance
a.
.c
I/)
ttl
u:::
I/)
I/)
<U
eOl
13
in
C
0
~
Q)
a.
x
E
Q)
:::J
:::J
a.
l-
c
0
a.
u
2
0....
a.
Name of substance
c
0
204
Dioctyl phthalate
218
Dipentene
45
Dipenyl ether
115
Dipropylene glycol
Dipropylene glycol
monomethyl ether
rn
0a.
'in
0
0
a.
X
c
0
'.p
+-'
2
0
....
Q)
Q)
....
:::J
....
ttl
a.
a.
u:::
I-
E
C
m
Ethylene glycol
monomethyl ether
acetate
49
IIA
T2
I/)
ttl
E!
Diisooctyl
phthalate
....
0
"+-'
.c
:ec
:::J
en
en
13
ttl
Q)
T3
Ethylene glycol
monophenyl ether
121
T1
Farmamide
154
138
Furfuryl alcohol
65
85
Glycerine
160
Dodecyl alcohol
>100
Heptane-n
-4
Dodecyl benzene
130
Heptanol-all
isomers
74
Dodecyl phenol
163
<0
IIA
T3
2-ethoxyethanol
40
Heptene
(mixed isomers)
2-Ethoxyethyl
acetate
49
Hexane-n
-22
IIA
T3
1-Hexene
-23
IIA
T3
Ethyl acetate
-4
IIA
T1
1-Hexanol
63
Ethyl alcohol
::25
IIA
T2
Hexylene glycol
96
Ethyl benzene
15
IIA
T2
Lactic acid
Ethyl cyclohexane
35
IIA
T3
Latex
2-ethyl hexanol
75
Ethylene carbonate
143
Ethylene glycol
111
IIA
T2
IIA
T2
T3
T2
Methyl acetate
-10
IIA
T1
Methyl alcohol
11
IIA
T1
Methylamyl ketone
49
-1
IIA
T1
IIA
T1
T3
Ethylene glycol
methyl butyl ether
61
Methyl isobutyl
ketone
31
Ethylene glycol
monobutyl ether
88
2-methyl-1pentene
<7
Ethylene glycol
monobutyl ether
acetate
Methylamyl
acetate
43
Ethylene glycol
37
Methylamyl alcohol
41
monomethyl ether
liB
T3
Molasses
49
Appendix 3
Petrochemical product which may be equated with oil products
with regard to explosion hazard (continued)
0..
()
D
Name of substance
.....
c
0
0..
..c:
::l
0
.....
Ol
en
en
co
"0
Q)
.....
::l
c
0
.iii
ro....
0..
Q)
en
co
u::::
c..
x
w
I-
Nonane
30
IIA
T3
Nonyl alcohol
E
Q)
c
0
0..
:;:::;
<.)
Q)
.....
0
....
0..
()
::l
.....
c
Ol
Name of substance
0
0..
..c:
en
co
Ol
u::::
e
c
0
iii
0
c..
x
w
en
en
co
"0
Q)
.....
::l
.....
Q)
0..
E
Q)
l-
c
0
tsQ)
.....
0
.....
0..
c
0
:;:::;
E!
Propylenetetramer
78
74
Propylene trimer
40
Nonyl phenol
140
Solvent naphtha
15
Octane
13
Sulpholane
177
Octanol-all isomers
75
Tall oil
182
Paraffin wax
199
Tetrahydronaphthalene
71
Pentane-n
<-20
Pentane-iso
IIA
IIA
T2
IIA
T1
T2
T3
Toluene
IIA
T1
<-20
T2
Trichloroethane-alpha
Pentene-n
<-20
T3
Trichloroethane-beta
Pentene-iso
<-20
T3
225
Tricresylphospate
(cont. less than 1 %
ortho-isomers)
Tridecanol
118
Triethyl benzene
111
Perchloroethylene
Petrolatum
60
IIA
Petroleum naphtha
T3
iso-Phorone
96
Triethylene glycol
166
Pinene
32
1,2,4- Trimethyl
benzene
54
Tripropylene glycol
141
Tripropylene gl~col
monomethyl et er
121
Trixylenyl phosphate
232
Turpentine
33
Polypropylene
glycols
Propionaldehyde
<-20
Propyl acetate-iso
IIA
T1
Propyl acetate-n
10
IIA
T2
Propyl alcohol-iso
12
IIA
T2
15
IIA
T2
Urea ammonium
nitrate solutions
Propyl alcohol-n
Propylene glycol
99
T2
Urea ammonium
phosphate solutions
White s~irit ~oiling
range 2 0-3 0 DC)
IIA
Propypylene glycol
monoethyl ether
Propypylene
glycol monomethyl
ether
38
Wine
Xylenes
T1
T3
=40
IIA
T3
25
IIA
T1
50
Appendix 4 : Chemicals
a.
()
0
Name of substance
'0
a.
.r:.
f/)
ro
f/)
f/)
ro
c
0
a.
e0>
c
0
'iii
ro
Q)
a.
x
E
Q)
.r:.
u:
-
::J
Q)
"-
::J
"-
a.
U
Q)
"0
"-
a.
()
0
Name of substance
C
a.
'0
f/)
::J
e0>
c
.Q
f/)
f/)
f/)
ro
Q)
"-
::J
.-
Q)
c
0
1:5
2
ea.
c
a.
l-
E'
a.
x
E
Q)
u:
l-
c
E'
Acetic Acid
40
IIA
T1
Carbon Tetrachloride
Acetic Anhydride
49
IIA
T2
Acetone
Cyanohydrin
75
Caustic Potash
Solution
Acetonitrile
Caustic Soda
Solution
Acrylic Acid
54
Chlorobenzene
28
IIA
T1
Acrylonitrile
-5
Chlorethanol-2
55
IIA
T1
Adiponitrile
93
Allyl Alcohol
21
liB
T2
Chlorohydrins,
Crude
Ally Chloride
<-20
IIA
T2
Chloroprene
-27
Aminoethylthanola
mine
129
T2
2- or 3Chloropropionic Acid
107
T1
Chlorosulfonic Acid
T1
T1
T1
Ammonia aqueous,
28 % or less
IIA
76
Benzene
-11
Benzyl Chloride
60
n-Butyl Acrylate
41
X
X
liB
T1
IIA
Aniline
T1
IIA
iso-Butyl Acrylate
ro
Chloroform
IIA
-11
IIA
T3
Creosote
76
IIA
T2
Cresols (Mixed
isomers)
>81
T1
Crotonaldehyde
13
liB
T3
Cyclohexanone
43
IIA
T2
32
IIA
T3
Cyclohexylamine
Butyl methacrylate
54
Decyl Acrylate
n-Butyraldehyde
<-5
IIA
T3
Dibutylamine
57
iso-Butyraldehyde
<-15
IIA
T3
O-Dichlorobenzene
66
66
1,1 Dichloroethane
-10
IIA
Dichloroethyl Ether
55
IIC
T5
Carbon Disulphide
<-20
25
Carbolic Oil
IIA
n-Butyl Ether
Camphor Oil
'c
T1
IIA
T2
Dichcloromethane
1,3Dichcloropropane
15
51
Name of substance
00
::J
......
OJ
'0
a.
..c
0~
en
en
ro
U
~
::J
......
ro
a.
'00
Q)
c
:;:;
Q)
......
T1
1,3 Dichcloropropene
29
IIA
Diethanolamine
138
Dietheylamine
<-20
IIA
e
a.
u::
E
Q)
r-
:;:;
ro
0..
Formaldehyde
Solutions (45 % or
less)
>50
liB
T2
Formic Acid
69
T1
Furfural
60
IIA
T2
<-20
liB
T3
Mesityl Oxide
31
IIA
T2
Methyl Acrylate
-3
liB
T2
Methyl
Methacrylate
10
IIA
T2
Methyl Styrene
58
IIA
T2
2-methyl, 5 ethyl
Pyridine
74
..c
OJ
Q)
a.
c
0
'c
..!2>
T1
T2
Diethylethanolamine
46
Diethylenetriamine
102
Diisopropanolamine
127
Diisopropylamine
-7
Dimethyl
Ethanolamine
31
Dimethylamine
(40 % Aq)
IIA
OJ
:;:;
ro
en
a.
IIA
0~
::J
......
15
1,2 Dichcloropropane
u::
......
::J
en
en
c
0
'00
a.
x
w
0..
00
c
'0
E
Q)
r-
ro
Name of substance
:e
c
en
a.
T2
Hydrochloric Acid
Isoprene
Dimethylformamide
58
IIA
T2
1A-Dioxane
12
IIA
T2
Epichlorohydrin
34
liB
-18
Ethyl Acrylate
liB
88
<-20
IIA
MonoNitrobenzene
Monoethanolamine
85
Monoisopropanolamine
71
Morpholine
38
Naphthalene, molten
80
Ethyl Ether
T4
Ethyl Methacrylate
27
2 Ethyl 3 Propyl
Acrolein
68
Ethylene
Cyanohydrin
>21
Ethylene Diamine
34
IIA
T2
Ethylene Dichloride
13
2-Ethylhexyl Acrylate
82
IIA
T2
T1
Ethylene Dibromide
Nitric Acid, 70 %
and over
1-or-2
Nitropropane
39
liB
T2
52
0..
()
Name of substance
c:
:::l
0>
c:
0..
iii
.c:
(IJ
ro
u:
0
0
Ci
><
ro
c:
- -e
Q)
(IJ
(IJ
0..
:0::;
t)
()
Q)
L.
:::l
Q)
0..
E
Q)
l-
0..
Name of substance
c:
0
0..
..c:
E
c:
L.
0>
c:
ro
U
~
:::l
iii
~
Q)
0..
c:
:0::;
t)
e0..
c:
2
c
u:
Ci
E
Q)
l-
E>
(IJ
ro
E>
:::l
><
ortho-Nitrotoluene
106
Sulfuric Acid
para-Nitrotoluene
106
Sulfuric Acid
(Spent)
Oleum
Paraldehyde
17
T3
Pentachlorothane
Phenol
79
135
Trichloroethylene
32
Tricresyl
Phosphate
(1 % ortho-)
238
Triethanolamine
179
Triethylamine
-17
Triethylenetetramine
135
Phosphorus
(yellow or white)
74
Propionic Acid
50
Propionic
Anhydride
74
-26
Propylamine
<-20
Propylene Oxide
Pyridine
T1
T1
liB
IIA
IIA
IIA
T2
<-20
liB
T2
iso-Valeraldehyde
17
IIA
T1
n-Valeraldehyde
12
liB
Vinyl Acetate
-8
IIA
-45
Vinyl Toluene
71
IIA
Vinylidene Chloride
-10
IIA
32
IIA
T1
- 165
Xylenols
T2
T2
T3
Urea Ammonium
Solution
(conatining aqua
ammonia)
Sodium
Hydrochlorite
(15 % Solution)
Sulfur Liquid
Sodium
Hydrosulphide
(45 % Solution or
less)
Styrene Monomer
IIA
-17
Toluene
Diisocyanate
B-Propiolactone
152
T1
Phosphoric Acid
Phthalic
Anhydride
Tetrachloroethane
T2
T2
<40
.:: 80
X
X
T2
T4
X
X
T2
53
Appendix 5
lACS Recommendation, No. 22, 1988
Recommendations for the classification of areas where flammable gas or
vapour risks may arise to permit the proper selection of electrical equipment
1.
Scope
1.1
These recommendations provide guidance on the area classification of ships carrying coal
cargoes in bulk and ships where oil or other liquids of similar hazard having a flash point
temperature not exceeding 60C (closed cup test) are handled, stored or processed, in
order to permit the proper selection of electrical equipment in those areas.
1.2
Attention should be given to the statutory regulations of the relevant National Authority.
1.3
areas where risks may arise due to the presence of ignitable dusts or fibres except
coal dust
b)
catastrophic failure such as the rupture of a bulk storage tank, process vessel or a
pipeline or the loss of well control, i.e. blowout.
c)
d)
e)
f)
1.4
1.5
The degree of hazard and the extent of the hazardous areas are based on marine practice,
however, attention should also be paid to any regulations of the Port Authorities which may
be applicable during loading and discharging operations.
2.
Definitions
2.1
Hazardous area: An area in which explosive gas/air mixtures are or may be expected to be
present in quantities such as to require special precautions for the construction and use of
electrical equipment.
54
Appendix 5
lACS Recommendation, No. 22,1988 (continued)
2.2
Zone O-A
Zone O-B
Zone 1-A
Zone 1-B
Zone 2
2.3
Flashpoint: The lowest temperature at which sufficient vapour is given off from a flammable
material to form an explosive gas/air mixture.
3.
Hazardous areas
3.1
The hazardous areas for ships where oil or other liquids of similar hazard having a flash
point temperature not exceeding 60C (closed cup test) are handled, stored or processed
are defined in Table 1; the following general principles apply:
a)
b)
c}
Spaces adjacent to bulk storage tanks which are mechanically ventilated during
loading/discharging of bulk storage tanks are regarded as Zone 1 hazardous areas
but with restrictions on the electrical equipment permitted in such spaces.
d)
e}
f)
55
Appendix 5
lACS Recommendation, No. 22, 1988 (continued)
3.2
The hazardous areas for ships intended for the carriage of coal cargoes in bulk are defined
in Table 2.
3.3
The hazardous areas as specified may be extended, or reduced depending on the actual
arrangements in each case, by use of windshields, special ventilation arrangements,
structural arrangements etc, subject to the approval of the individual Society.
4.
4.1
Electrical equipment should normally be installed outside hazardous areas. Where this is
not practicable for operational reasons, the electrical equipment should be of a type
permitted by these recommendations and should be suitable for the gas grouping and
temperature class of the atmospheres involved. The design construction and testing of
such equipment is to be in accordance with the relevant lEG Publications or equivalent
standards acceptable to the individual Society.
4.2
Within the airlock as permitted in Table 3, lighting fittings and prescribed monitoring and
alarm equipment are to be of a type permitted in the hazardous area into which the
opening leads.
4.3
5.
Ventilation
5.1
56
Appendix 5
lACS Recommendation, No. 22,1988 (continued)
Table 1 Sheet 1 Ships where Oil or Other Liquids having a Flash Point not exceeding 60 0 C
(Closed Cup Test) are handled, Stored or Processed
Zone
Description of
Location
Zone O-A
Inner spaces of
containment systems and
associated pipework.
Typical Example
Permitted
Equipment/Cables
a. Intrinsically safe - Exia
b. Electrical equipment
specifically approved for
use in Zone 0
c.
EEl
Zone O-B
a) EquipmenUcables as
permitted in Zone O-A
"'-
./ 0000
1/
"-
0000
0000
0000
0000
i) Cofferdam
loolggo
00 00 ql
00
0 00000
fgOgOOOOO~1
0000000000
0000000000
NOTE:
Gastight enclosures
and gastight joints
are to be to the
satisfactions of the
individual Society.
57
Appendix 5
lACS Recommendation, No. 22, 1988 (continued)
Table 1 Sheet 2
Ships where Oil or Other Liquids having a Flash Point not exceeding 60 DC
(Closed Cup Test) are handled, Stored or Processed
Zone 1-A i)
Spaces separated by a
single bulkhead from
storage tanks and which
are mechanically ventilated
during loading/discharging
operations.
e.g., - Cargo pump rooms
Permitted
Equipment/Cables
Typical Example
Description of Location
Zone
a. EquipmenUcables as
permitted in Zone O-B.
b. Intrinsically safe - Exib
/"
XXXx
XX Xx
XXXX
XXXX
"""- xx x'x
--
IX x )( x x I( x x x ~I
XX)(JC)()(XXX
IL
II<XX)()(>()(XXX
i<)( )( x: X]<. i < " ~
__
x XXX'J( XXxxx
58
Appendix 5
lACS Recommendation, No. 22, 1988 (continued)
Table 1 Sheet 3 Ships where Oil or Other Liquids having a Flash Point not exceeding 60 0 C
(Closed Cup Test) are handled, Stored or Processed
Zone
Zone 1-8
Description of Location
i)
Spaces separated by a
single bulkhead from
storage tanks and which
have continuous
mechanical ventilation
except when the ship is in
a gas free condition. Loss
of ventilation alarmed at
a manned station.
e.g.- Pump rooms of
storage barges,
Typical Example
Permitted
Equipment/Cables
a. EquipmenUcables as
permitted in Zone 1-A
['
~~;o.:5!'l
./
1Q ~~ ~f.
"'-
c.
IX
d. Pressurized - Exp
e. Electrical equipment
specifically approved
for use in Zone 1 and
acceptable to individual
Society.
- Spaces separated
by single bulkhead
from tanks for
recovered oil on oil
recovery ship.
NOTE: This classification is
not applicable to
cargo pump rooms
of oil tanks.
ii) Spaces with closed
process plant and
associated pipe flanges
and valves which may by
dismantled during normal
operation and which have
continuous mechanical
ventilation. Loss of
ventilation alarmed at a
manned station.
iii) Spaces in which pipes
containing cargo are
located and which are
continuously mechanically ventilated except
when the pipes are in a
gas free condition. Loss
of ventilation alarmed at
a manned station.
b. Flameproof - Exd
OISI
1)6<
1% QSgg
88) <6<
~ ~/S('
---
XI< XI< ~
~ W~~
*'roce.s: ~
P1ar::J
.(+
-~
----------
59
Appendix 5
lACS Recommendation, No. 22, 1988 (continued)
Table 1 Sheet 4
Description of Location
Zone
Zone 1-8
(cont'd)
Ships where Oil or Other Liquids having a Flash Point not exceeding 60 0 C
(Closed Cup Test) are handled, Stored or Processed
iv)
v)
vi)
ix)
Typical Example
Permitted
Equipment/Cables
60
Appendix 5
lACS Recommendation, No. 22,1988 (continued)
Table 1 Sheet 5
Ships where Oil or Other Liquids having a Flash Point not exceeding 60 0 C
(Closed Cup Test) are handled, Stored or Processed
Zone
Description of Location
Zone 1-8
(cont'd)
Typical Example
"'c"
.m
Permitted
Equipment/Cables
Q)
0>
ii5
i)
Zone 2
a. Equipment/cables
as permitted in
Zone 1-8
b. Equipment of a
type which ensures
absence of sparks
or arcs and
absence of ignition
capable surfaces
during normal
operation.
c.
Equipment
specially designed
for Zone 2 and
acceptable to the
appropriate
authority.
61
Appendix 5
lACS Recommendation, No. 22, 1988 (continued)
Table 1 Sheet 6 Ships where Oil or Other Liquids having a Flash Point not exceeding 60 0 C
(Closed Cup Test) are handled, Stored or Processed
Description of Location
Zone
v)
Zone 2
(cont'd)
Typical Example
Permitted
Equipment/Cables
vi)
Table
Description of Location
Zone
i)
Zone 1-B
Permitted Equipment/Cables
ii)
hold spaces.
iii)
62
Appendix 5
lACS Recommendation, No. 22,1988 (continued)
Table 3
Accessed from
Typical Example
Requirements
Hazard Category
Zone O-A
Not applicable
Zone 0-8
Zone 1-A
Zone 1-8
ii)
iii)
i)
_.
--------------
63
Appendix 5
lACS Recommendation, No. 22, 1988 (continued)
Table 3
Accessed from
Typical Example
Requirements
Hazard Category
i)
Zone 2
5 mm WG in relation to the
hazardous area.
ii)