YORK OVERHEAD ACTIVE CHILLED BEAM

Total comfort control

YORK ACTIVE CHILLED BEAM WITH


PERFORATED RETURN DIFFUSER

YORK OVERHEAD ACTIVE CHILLED BEAM

Table of contents
Concept & Technology

Air Distribution & Facade Orientation

Product Features

34

Dimensions

56

Performance Data

714

Selection Example

1516

Selection Summary

16

Guide Specifications

17

YORK OVERHEAD ACTIVE CHILLED BEAM

York Overhead Active Chilled Beam systems are designed to maintain a comfortable indoor climate, and
engineered for low energy consumption and compatibility in a low-height ceiling void. These systems
provide full cooling, heating, ventilation and humidity control all with near-silent operation and minimal
maintenance requirements.

Concept
The principle of the active chilled beam system is to
use terminal chilled water heat exchangers in the ceiling
to offset the room sensible cooling loads or to provide
sensible heating. The ventilation and humidity control
requirements are taken care of using a separate primary
conditioned air supplied by a central air handling unit.

Chiller
Tempered
Water
Circuit

- +
Air Handling Unit
Active
Chilled
Beams

Overhead Active Chilled Beam System

Due to the relatively high supply chilled water


temperatures approximately 57F (14C) the
heat exchangers operate dry avoiding many of the
maintenance and health concerns that are associated
with other systems that use terminal heat exchangers
such as fan coil units.
The system provides large energy savings primarily
because the amount of air circulated throughout the
building can be reduced very close to the ventilation and
humidity control requirements. This will result in large
reductions in air handling unit fan power and energy
consumption.

Further energy savings result from the use of high chilled


water temperatures serving the heat exchangers. This
can allow the water chiller to operate at higher water
temperatures improving chiller operating efficiency and
energy consumption.

Technology
York Overhead Active Chilled Beams integrate the
primary air distribution function with the secondary air
heat exchange using a proprietary air nozzle technology
to induce secondary room air into the unit and through
the heat exchanger before mixing with the primary
air. The resulting mixture of primary air and induced
secondary room air is then supplied to the room through
the contoured diffusers which are designed to keep the
air close to the ceiling using the Coanda effect.
York Overhead Active Chilled Beams series units are
designed with a nominal width of 24 (600mm) to
integrate with the ceiling grids of the most common
ceiling configurations. Standard nominal unit lengths
are 48120 (1200mm3000mm) in 12 (300mm)
increments; special lengths are also available to satisfy
specific ceiling requirements.
Nozzles
Conditioned
Ventilation Air

Mixing Section
Heat Exchange

Room Air

Perforated Screen
or Linear Bar Grille

Operating Principle of the Active Chilled Beam

YORK OVERHEAD ACTIVE CHILLED BEAM

Air Distribution
The shape of the supply slot diffusers are specifically
designed to create two opposing discharge air flows
from the active chilled beam, which travel along the
suspended ceiling. The velocity of the supply air along
the suspended ceiling creates a Coanda effect, whereby
velocity differences in cool air flow press the air stream
against the suspended ceiling, extending air throw and
preventing cool air from dropping into the comfort zone
prematurely. It is necessary for the suspended ceiling to
be flat and free of any obstacles, such as light fixtures
situated close to the supply slots, as any obstructions
can interfere with the Coanda effect.

Comfort Zone

1.8m

3.3

1.6

1.0m

0.5m

Overhead Active Chilled Beam System

Facade Orientation
Orientation of the active chilled beam in relation
to the facade has no influence on operation. The
choice between the two most common installation
arrangements, perpendicular and parallel, is generally
determined by:
Aesthetics (fitting into the pattern of the suspended
ceiling)
Level of flexibility to create offices within the floor plan

Available distance for air throw the air must have the
opportunity to mix with room air before intersecting
a wall or an opposing air stream from another chilled
beam
Obstructions in the suspended ceiling that might
interfere with air flow, such as lighting fixtures
Obstructions in the facade or floor that might interfere
with air flow, such as radiators or floor convectors

Facade

Facade

Number of active chilled beams required to condition


the space

Perpendicular to Facade

Parallel to Facade

YORK OVERHEAD ACTIVE CHILLED BEAM

Product Features
High Capacity Nozzle Configurations
YORK Overhead Active Chilled Beams series active
chilled beams are available with eight (8) optional
nozzle configurations. Each is designed to provide high
induction rates for secondary room air, resulting in high
cooling and heating capacities. This makes them suitable
for applications in building perimeter zones with higher
loads, as well as internal zones. Nozzles are factory
installed and can be blanked if single-side discharge
is required.

Low Height
The YORK Overhead Active Chilled Beams series is
available up to a maximum height of 8-1/4 (210mm),
providing compatibility with reduced height ceiling voids
to maximize ceiling heights. Alternatively the building
slab-to-slab height can be reduced, allowing more floors
in a given building height.
Flexible Sizes
Units are available in lengths between 48120
(1200mm3000mm), providing compatibility with
most common ceiling configurations. Unit lengths
can also be custom tailored to match specific
installation requirements.

Perforated Return Diffuser

High Efficiency Air Nozzles

Diffuser Options
The YORK Overhead Active Chilled Beams series is
available with either perforated return air diffusers or
linear blade diffusers. Performance is identical for both
configurations; options are offered to best match the
aesthetic requirements of the building. Exposed metal
surfaces are powder coated with a standard finish color
RAL 9010 (20% gloss); other RAL colors are available to
match project requirements. Units can also be supplied
with either perforated or linear blade center diffusers.

Linear Blade Return Diffuser

YORK OVERHEAD ACTIVE CHILLED BEAM

Simple Mounting
Units can be easily suspended from the overhead
concrete slab, using threaded rod or hanging wire
support systems to match with metal panel, fiber board
or plaster ceilings. Units can also be installed without
false ceilings.
Minimal Noise
Efficiently shaped nozzles create maximum induction
at a minimum sound level.
Low Maintenance
YORK Overhead Active Chilled Beams series active
chilled beams include no filter, fan, drain pan or any
other moving parts. As a result, maintenance is limited
to cleaning exposed metal surfaces and using a standard
vacuum hose to remove dust from the heat exchanger
every 25 years, depending on the cleanliness of the

supply air. The heat exchanger can be easily accessed


by releasing the center diffuser, which is equipped with
safety hanging wires.

Controls
The YORK Overhead Active Chilled Beams can be
supplied with constant air volume controllers for
primary air, water control valves with room control
sensors, as well as balancing and isolation valves and
condensation sensors.
Air Distribution Control (Optional)
YORK Overhead Active Chilled Beams series units can
be supplied with optional air discharge deflectors, which
create a variable air discharge pattern. These deflectors
can be independently adjusted to provide an array of
distribution patterns.

15

Air Discharge Deflectors for Distribution Control

15

15

15

15

15

YORK OVERHEAD ACTIVE CHILLED BEAM

Dimensions
Side Duct Connection
A

E
E/2

E/4

E/4
D

F
K

2 Duct Connections
(Models AFX-OHACB-8/10)

Top Duct Connection

D1

E
F
C1 K1

YORK OVERHEAD ACTIVE CHILLED BEAM

Water Connections (Nominal Diameter)


UNIT SIZE

4'6'
(1.2m1.8m)

7'10'
(2.4m3.0m)

CHILLED WATER

1/2"
(12mm)

5/8"
(15mm)

HOT WATER

1/2"
(12mm)

1/2"
(12mm)

Dimensional Data (Nominal)

UNIT SIZE

48"
(1200mm)

60"
(1500mm)

72"
(1800mm)

96"
(2400mm)

120"
(3000mm)

47-3/4"
(1195mm)

59-3/4"
(1495mm)

71-3/4"
(1795mm)

95-3/4"
(2395mm)

119-3/4"
(2995mm)

23-3/4"
(595mm)

23-3/4"
(595mm)

23-3/4"
(595mm)

23-3/4"
(595mm)

23-3/4"
(595mm)

3-3/4"
(96mm)

3-3/4"
(96mm)

3-3/4"
(96mm)

3-3/4"
(96mm)

3-3/4"
(96mm)

C1

8-5/8"
(221mm)

8-5/8"
(221mm)

8-5/8"
(221mm)

8-5/8"
(221mm)

8-5/8"
(221mm)

(1x) 5"
(123mm)

(1x) 5"
(123mm)

(1x) 5"
(123mm)

(2x) 5"
(123mm)

(2x) 5"
(123mm)

D1

(1x) 5"
(123mm)

(1x) 5"
(123mm)

(1x) 5"
(123mm)

(1x) 6"
(158mm)

(1x) 8"
(198mm)

41-7/8"
(1064mm)

53-11/16"
(1364mm)

65-1/2"
(1664mm)

89-1/8"
(2264mm)

112-3/4"
(2864mm)

18-1/16"
(460mm)

18-1/16"
(460mm)

18-1/16"
(460mm)

18-1/16"
(460mm)

18-1/16"
(460mm)

8-1/4"
(210mm)

8-1/4"
(210mm)

8-1/4"
(210mm)

8-1/4"
(210mm)

8-1/4"
(210mm)

K1

11-1/4"
(285mm)

11-1/4"
(285mm)

11-1/4"
(285mm)

11-1/4"
(285mm)

11-1/4"
(285mm)

UNIT WEIGHT

55lb
(25 kg)

66lb
(30kg)

75lb
(34kg)

97lb
(44kg)

119lb
(54kg)

25
32
38
44
51

38
47
55
64
72

51
59
68
76
85

59
70
81
91
102

68
81
93
106
119

93
110
127
144
161

B1

C1

E1

F1

G1

H1

0.19
0.26
0.35
0.45
0.57

0.21
0.29
0.39
0.51
0.63

0.20
0.28
0.37
0.48
0.59

0.23
0.32
0.41
0.52
0.64

0.23
0.34
0.48
0.63
0.81

0.19
0.29
0.42
0.57
0.75

0.17
0.26
0.38
0.52
0.68

369
456
543
651
738

543
694
825
955
1107

825
1020
1194
1389
1562

15
15
15
15
18

15
15
18
22
26

15
20
25
28
31

31
37
41
43
46

25
30
34
38
41

22
27
30
34
37

2018
2387
2756
3125
3494

1476
1758
2018
2300
2582

1280
1519
1758
1975
2213

1107
1280
1476
1649
1845

282
369
456
543
651

15
15
15
15
17

20
24
28
31
33

(Btu/hr)

AIR COOLING
CAPACITY
T=20F

(NC)

NOISE CRITERIA

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

(gpm)

WATER
FLOW

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

(ft. w.c.)

WATER
P

2184
2286
2388
2491
2559

1945
2116
2286
2423
2559

1911
2081
2252
2388
2491

1911
2081
2218
2354
2491

1740
1979
2150
2320
2457

1501
1774
2013
2218
2388

1399
1672
1945
2150
2320

1297
1604
1843
2013
2184

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 1

39
39
40
40
40

38
39
39
40
40

38
39
39
40
40

38
38
39
39
40

38
38
39
39
40

37
38
38
39
40

36
37
38
39
39

36
37
38
38
39

(F)

T
WATER

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

(gpm)

WATER
FLOW

2.64
2.64
2.64
2.64
2.64

2.64
2.64
2.64
2.64
2.64

2.64
2.64
2.64
2.64
2.64

2.64
2.64
2.64
2.64
2.64

2.64
2.64
2.64
2.64
2.64

2.64
2.64
2.64
2.64
2.64

2.64
2.64
2.64
2.64
2.64

2.64
2.64
2.64
2.64
2.64

(ft. w.c.)

WATER
P

2491
2627
2764
2866
2934

2218
2423
2627
2764
2934

2218
2388
2559
2730
2866

2184
2388
2559
2696
2832

2013
2252
2491
2661
2832

1740
2047
2320
2525
2730

1570
1945
2218
2457
2661

1467
1808
2081
2320
2491

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 2

37
38
38
38
38

37
37
38
38
38

37
37
37
38
38

37
37
37
38
38

36
37
37
38
38

36
36
37
37
38

35
36
37
37
38

35
36
36
37
37

(F)

T
WATER

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

(gpm)

WATER
FLOW

4.68
4.68
4.68
4.68
4.68

4.68
4.68
4.68
4.68
4.68

4.68
4.68
4.68
4.68
4.68

4.68
4.68
4.68
4.68
4.68

4.68
4.68
4.68
4.68
4.68

4.68
4.68
4.68
4.68
4.68

4.68
4.68
4.68
4.68
4.68

4.68
4.68
4.68
4.68
4.68

(ft. w.c.)

WATER
P

2661
2798
2934
3037
3139

2354
2593
2798
2969
3105

2354
2559
2730
2900
3037

2320
2525
2730
2866
3037

2116
2423
2627
2832
3003

1843
2184
2457
2696
2900

1672
2047
2354
2593
2832

1570
1945
2218
2457
2661

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 3

36
36
37
37
37

36
36
36
37
37

36
36
36
37
37

36
36
36
37
37

35
36
36
37
37

35
35
36
36
37

35
35
36
36
37

35
35
35
36
36

(F)

T
WATER

YORK Overhead Active Chilled Beam 4 (4')


COOLING (TRC - TCHS = 18F)

0.32
0.32
0.32
0.32
0.32

0.32
0.32
0.32
0.32
0.32

0.32
0.32
0.32
0.32
0.32

0.32
0.32
0.32
0.32
0.32

0.32
0.32
0.32
0.32
0.32

0.32
0.32
0.32
0.32
0.32

0.32
0.32
0.32
0.32
0.32

0.32
0.32
0.32
0.32
0.32

(gpm)

WATER
FLOW

0.50
0.50
0.50
0.50
0.50

0.50
0.50
0.50
0.50
0.50

0.50
0.50
0.50
0.50
0.50

0.50
0.50
0.50
0.50
0.50

0.50
0.50
0.50
0.50
0.50

0.50
0.50
0.50
0.50
0.50

0.50
0.50
0.50
0.50
0.50

0.50
0.50
0.50
0.50
0.50

(ft. w.c.)

WATER
P

4393
4659
4886
5113
5302

4204
4507
4810
5037
5265

4090
4469
4810
5113
5378

4053
4431
4772
5075
5340

3598
4090
4507
4848
5189

3447
3977
4431
4848
5189

3144
3787
4318
4772
5151

2500
3333
4015
4545
4999

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 1

57
58
60
61
62

56
58
59
61
62

55
57
59
61
62

55
57
59
61
62

53
55
58
60
61

52
55
57
60
62

50
53
56
59
61

46
51
55
58
60

(F)

T
WATER

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

(gpm)

WATER
FLOW

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

1.17
1.17
1.17
1.17
1.17

(ft. w.c.)

WATER
P

53
54
55
56
57

52
54
55
56
57

52
53
55
56
58

51
53
55
56
58

49
52
54
55
57

49
51
53
55
57

47
50
53
55
57

44
48
51
54
56

(F)

T
WATER

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

(gpm)

WATER
FLOW

2.04
2.04
2.04
2.04
2.04

2.04
2.04
2.04
2.04
2.04

2.04
2.04
2.04
2.04
2.04

2.04
2.04
2.04
2.04
2.04

2.04
2.04
2.04
2.04
2.04

2.04
2.04
2.04
2.04
2.04

2.04
2.04
2.04
2.04
2.04

2.04
2.04
2.04
2.04
2.04

(ft. w.c.)

WATER
P

6141
6482
6824
7127
7392

5876
6293
6672
7013
7316

5724
6255
6710
7127
7468

5648
6179
6634
7051
7430

5042
5724
6293
6786
7241

4814
5573
6179
6748
7241

4360
5269
5990
6634
7203

3526
4663
5573
6331
6975

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 3

4) Performance ratings are subject to tolerances of plus/minus 5%.

3) Water heating capacities are based on 4-pipe chilled beams with THWS-TRW = 70F. For other conditions, multiply the table water heating capacity by the required (THWS-TRW) divided by 70F.

2) Water cooling capacities are based on TRC-TCHS = 18F. For other conditions multiply the table water cooling capacity by the required (TRC-TCHS) divided by 18F.

5573
5914
6217
6482
6710

5345
5724
6065
6369
6634

5194
5686
6103
6482
6786

5156
5611
6028
6407
6748

4587
5194
5724
6179
6558

4360
5042
5648
6141
6596

3943
4777
5459
6028
6520

3184
4246
5080
5762
6331

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 2

HEATING (T HWS - TRH = 70F)

1) Air cooling capacities are based on TAC = TRC-TCSA = 20F. For other conditions, multiply the table air cooling capacity by the required (TRC-TCSA) divided by 20F.
Alternatively, air cooling capacity can be calculated from the formula: Air cooling capacity QS = 1.085 x Airflow (cfm) x (TRC-TCSA).

17
21
25
30
34

A1

0.14
0.26
0.40
0.58
0.79

(in. w.c.)

(cfm)

13
17
21
25
30

PLENUM
PRESSURE

PRIMARY
AIRFLOW

A0

NOZZLE

2-Way Air Flow / 4-Pipe

Performance Data

49
50
51
52
53

49
50
51
52
53

48
50
51
52
53

48
49
51
52
53

46
48
50
51
53

46
48
50
51
53

44
47
49
51
52

42
45
48
50
52

(F)

T
WATER

YORK OVERHEAD ACTIVE CHILLED BEAM

52
73
97
126
158

47
66
88
113
142

12
15
18
21
24

18
22
26
30
34

24
28
32
36
40

28
33
38
43
48

32
38
44
50
56

44
52
60
68
76

B1

C1

E1

F1

G1

H1

218
267
315
364
412

15
20
25
28
31

534
631
728
825
922

388
461
534
607
679

340
400
461
522
582

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

(l/s)

WATER
FLOW

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

(KPa)

WATER
P

640
670
700
730
750

570
620
670
710
750

560
610
660
700
730

560
610
650
690
730

510
580
630
680
720

440
520
590
650
700

410
490
570
630
680

380
470
540
590
640

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 1

3.8
4.0
4.2
4.4
4.5

3.4
3.7
4.0
4.2
4.5

3.4
3.7
3.9
4.2
4.4

3.3
3.6
3.9
4.1
4.3

3.1
3.5
3.8
4.1
4.3

2.6
3.1
3.5
3.9
4.2

2.4
2.9
3.4
3.7
4.1

2.2
2.8
3.2
3.5
3.8

(C)

T
WATER

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

(l/s)

WATER
FLOW

7.9
7.9
7.9
7.9
7.9

7.9
7.9
7.9
7.9
7.9

7.9
7.9
7.9
7.9
7.9

7.9
7.9
7.9
7.9
7.9

7.9
7.9
7.9
7.9
7.9

7.9
7.9
7.9
7.9
7.9

7.9
7.9
7.9
7.9
7.9

7.9
7.9
7.9
7.9
7.9

(KPa)

WATER
P

730
770
810
840
860

650
710
770
810
860

650
700
750
800
840

640
700
750
790
830

590
660
730
780
830

510
600
680
740
800

460
570
650
720
780

430
530
610
680
730

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 2

2.9
3.1
3.2
3.3
3.4

2.6
2.8
3.1
3.2
3.4

2.6
2.8
3.0
3.2
3.3

2.6
2.8
3.0
3.2
3.3

2.3
2.6
2.9
3.1
3.3

2.0
2.4
2.7
3.0
3.2

1.8
2.3
2.6
2.9
3.1

1.7
2.1
2.4
2.7
2.9

(C)

T
WATER

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

(l/s)

WATER
FLOW

14
14
14
14
14

14
14
14
14
14

14
14
14
14
14

14
14
14
14
14

14
14
14
14
14

14
14
14
14
14

14
14
14
14
14

14
14
14
14
14

(KPa)

WATER
P

780
820
860
890
920

690
760
820
870
910

690
750
800
850
890

680
740
800
840
890

620
710
770
830
880

540
640
720
790
850

490
600
690
760
830

460
570
650
720
780

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 3

2.3
2.4
2.6
2.7
2.7

2.1
2.3
2.4
2.6
2.7

2.0
2.2
2.4
2.5
2.7

2.0
2.2
2.4
2.5
2.6

1.9
2.1
2.3
2.5
2.6

1.6
1.9
2.2
2.4
2.5

1.5
1.8
2.1
2.3
2.5

1.4
1.7
1.9
2.2
2.3

(C)

T
WATER

YORK Overhead Active Chilled Beam 4 (1200mm)


COOLING (TRC - TCHS = 10C)

0.02
0.02
0.02
0.02
0.02

0.02
0.02
0.02
0.02
0.02

0.02
0.02
0.02
0.02
0.02

0.02
0.02
0.02
0.02
0.02

0.02
0.02
0.02
0.02
0.02

0.02
0.02
0.02
0.02
0.02

0.02
0.02
0.02
0.02
0.02

0.02
0.02
0.02
0.02
0.02

(l/s)

WATER
FLOW

1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

(KPa)

WATER
P

1160
1230
1290
1350
1400

1110
1190
1270
1330
1390

1080
1180
1270
1350
1420

1070
1170
1260
1340
1410

950
1080
1190
1280
1370

910
1050
1170
1280
1370

830
1000
1140
1260
1360

660
880
1060
1200
1320

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 1

13.9
14.7
15.4
16.1
16.7

13.3
14.3
15.1
15.9
16.5

12.9
14.1
15.2
16.1
16.9

12.8
14.0
15.0
16.0
16.8

11.4
12.9
14.2
15.3
16.3

10.9
12.6
14.0
15.3
16.4

9.9
11.9
13.6
15.0
16.3

7.9
10.6
12.6
14.3
15.8

(C)

T
WATER

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

(l/s)

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

3.5
3.5
3.5
3.5
3.5

(KPa)

WATER
P

1470
1560
1640
1710
1770

1410
1510
1600
1680
1750

1370
1500
1610
1710
1790

1360
1480
1590
1690
1780

1210
1370
1510
1630
1730

1150
1330
1490
1620
1740

1040
1260
1440
1590
1720

840
1120
1340
1520
1670

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 2

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

(l/s)

WATER
FLOW

6.1
6.1
6.1
6.1
6.1

6.1
6.1
6.1
6.1
6.1

6.1
6.1
6.1
6.1
6.1

6.1
6.1
6.1
6.1
6.1

6.1
6.1
6.1
6.1
6.1

6.1
6.1
6.1
6.1
6.1

6.1
6.1
6.1
6.1
6.1

6.1
6.1
6.1
6.1
6.1

(KPa)

WATER
P

1620
1710
1800
1880
1950

1550
1660
1760
1850
1930

1510
1650
1770
1880
1970

1490
1630
1750
1860
1960

1330
1510
1660
1790
1910

1270
1470
1630
1780
1910

1150
1390
1580
1750
1900

930
1230
1470
1670
1840

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 3

4) Performance ratings are subject to tolerances of plus/minus 5%.

3) Water heating capacities are based on 4-pipe chilled beams with THWS-TRW = 35C. For other conditions, multiply the table water heating capacity by the required (THWS-TRW) divided by 35C.

2) Water cooling capacities are based on TRC-TCHS = 10C. For other conditions multiply the table water cooling capacity by the required (TRC-TCHS) divided by 10C.

11.7
12.4
13.0
13.6
14.1

11.2
12.0
12.8
13.4
14.0

10.9
11.9
12.8
13.6
14.3

10.8
11.8
12.7
13.5
14.2

9.6
10.9
12.0
12.9
13.8

9.2
10.6
11.8
12.9
13.8

8.3
10.0
11.5
12.7
13.7

6.7
8.9
10.7
12.1
13.3

(C)

T
WATER

HEATING (THWS - TRH = 35C)


WATER
FLOW

1) Air cooling capacities are based on TAC = TRC-TCSA = 10C. For other conditions, multiply the table air cooling capacity by the required (TRC-TCSA) divided by 10C.
Alternatively, air cooling capacity can be calculated from the formula: Air cooling capacity W = 1.213 x Airflow (l/s) x (TRC-TCSA).

31
37
41
43
46

25
30
34
38
41

22
27
30
34
37

146
182
218
255
291

15
15
18
22
26

50
70
93
119
148

97
121
146
170
194

15
15
15
15
18

291
340
388
437
485

73
97
121
146
170

15
15
15
15
17

20
24
28
31
33

(W)

AIR COOLING
CAPACITY
T=10C

(NC)

NOISE CRITERIA

58
79
103
130
160

57
85
119
158
203

47
73
105
143
186

42
66
95
129
169

8
10
12
14
16

A1

36
64
100
144
196

(Pa)

(l/s)

6
8
10
12
14

PLENUM
PRESSURE

PRIMARY
AIRFLOW

A0

NOZZLE

2-Way Air Flow / 4-Pipe

Performance Data

9.6
10.2
10.8
11.2
11.6

9.3
9.9
10.5
11.0
11.5

9.0
9.8
10.6
11.2
11.8

8.9
9.7
10.5
11.1
11.7

7.9
9.0
9.9
10.7
11.4

7.6
8.8
9.8
10.6
11.4

6.9
8.3
9.4
10.4
11.3

5.5
7.3
8.8
10.0
11.0

(C)

T
WATER

YORK OVERHEAD ACTIVE CHILLED BEAM

42
51
59
68
76

117
163
216
278
345

81
93
106
119
131

93
110
127
144
161

114
131
148
165
182

153
178
203
229
254

B1

C1

E1

F1

G1

H1

0.20
0.28
0.36
0.46
0.57

0.24
0.31
0.39
0.49
0.60

0.20
0.28
0.37
0.48
0.59

0.23
0.31
0.41
0.51
0.62

0.22
0.31
0.41
0.53
0.65

0.21
0.30
0.41
0.53
0.67

0.18
0.27
0.39
0.52
0.67

598
736
874
1012
1150

920
1104
1287
1471
1655

2529
3541
4690
6024
7495

15
15
15
15
18

15
15
18
22
26

15
20
25
28
31

31
37
41
43
46

25
30
34
38
41

22
27
30
34
37

3311
3862
4414
4966
5518

2483
2851
3219
3587
3954

2023
2391
2759
3127
3495

1747
2023
2299
2575
2851

460
598
736
874
1012

15
15
15
15
17

20
24
28
31
33

(Btu/hr)

AIR COOLING
CAPACITY
T=20F

(NC)

NOISE CRITERIA

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

(gpm)

WATER
FLOW

1.61
1.61
1.61
1.61
1.61

1.61
1.61
1.61
1.61
1.61

1.61
1.61
1.61
1.61
1.61

1.61
1.61
1.61
1.61
1.61

1.61
1.61
1.61
1.61
1.61

1.61
1.61
1.61
1.61
1.61

1.61
1.61
1.61
1.61
1.61

1.61
1.61
1.61
1.61
1.61

(ft. w.c.)

WATER
P

3207
3378
3515
3617
3753

2934
3139
3344
3515
3685

2798
3037
3276
3446
3617

2798
3037
3242
3412
3583

2730
2969
3173
3378
3549

2491
2764
3003
3207
3378

2081
2491
2832
3105
3378

1945
2354
2696
2934
3173

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 1

10
11
11
11
12

9
10
11
11
12

9
10
10
11
11

9
10
10
11
11

9
9
10
11
11

8
9
9
10
11

7
8
9
10
11

6
7
9
9
10

(F)

T
WATER

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

(gpm)

WATER
FLOW

3.61
3.61
3.61
3.61
3.61

3.61
3.61
3.61
3.61
3.61

3.61
3.61
3.61
3.61
3.61

3.61
3.61
3.61
3.61
3.61

3.61
3.61
3.61
3.61
3.61

3.61
3.61
3.61
3.61
3.61

3.61
3.61
3.61
3.61
3.61

3.61
3.61
3.61
3.61
3.61

(ft. w.c.)

WATER
P

3685
3856
4026
4163
4299

3344
3617
3822
4026
4197

3207
3515
3753
3958
4163

3207
3480
3719
3924
4129

3139
3412
3651
3856
4060

2866
3173
3446
3651
3856

2388
2832
3242
3583
3856

2252
2696
3071
3378
3651

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 2

8
8
8
9
9

7
8
8
8
9

7
7
8
8
9

7
7
8
8
9

7
7
8
8
9

6
7
7
8
8

5
6
7
8
8

5
6
6
7
8

(F)

T
WATER

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

1.27
1.27
1.27
1.27
1.27

(gpm)

WATER
FLOW

6.46
6.46
6.46
6.46
6.46

6.46
6.46
6.46
6.46
6.46

6.46
6.46
6.46
6.46
6.46

6.46
6.46
6.46
6.46
6.46

6.46
6.46
6.46
6.46
6.46

6.46
6.46
6.46
6.46
6.46

6.46
6.46
6.46
6.46
6.46

6.46
6.46
6.46
6.46
6.46

(ft. w.c.)

WATER
P

3924
4095
4265
4436
4572

3583
3822
4060
4265
4470

3753
3719
3992
4231
4436

3378
3685
3958
4163
4368

3344
3617
3890
4095
4299

3037
3378
3651
3890
4129

2525
3037
3446
3787
4095

2388
2866
3276
3583
3856

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 3

6
6
7
7
7

6
6
6
7
7

6
6
6
7
7

5
6
6
7
7

5
6
6
6
7

5
5
6
6
7

4
5
5
6
6

4
5
5
6
6

(F)

T
WATER

YORK Overhead Active Chilled Beam6 (6')


COOLING (TRC - TCHS = 18F)

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

0.48
0.48
0.48
0.48
0.48

(gpm)

WATER
FLOW

1.47
1.47
1.47
1.47
1.47

1.47
1.47
1.47
1.47
1.47

1.47
1.47
1.47
1.47
1.47

1.47
1.47
1.47
1.47
1.47

1.47
1.47
1.47
1.47
1.47

1.47
1.47
1.47
1.47
1.47

1.47
1.47
1.47
1.47
1.47

1.47
1.47
1.47
1.47
1.47

(ft. w.c.)

WATER
P

6931
7348
7726
8067
8332

6666
7120
7575
7916
8257

6477
7083
7613
8067
8446

6401
7007
7537
7992
8408

6325
6893
7423
7878
8257

5643
6401
7045
7613
8105

4924
5946
6780
7499
8143

3977
5265
6325
7158
7916

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 1

29
31
32
34
35

28
30
32
33
35

27
30
32
34
36

27
29
32
34
35

27
29
31
33
35

24
27
30
32
34

21
25
29
32
34

17
22
27
30
33

(F)

T
WATER

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

(gpm)

2.61
2.61
2.61
2.61
2.61

2.61
2.61
2.61
2.61
2.61

2.61
2.61
2.61
2.61
2.61

2.61
2.61
2.61
2.61
2.61

2.61
2.61
2.61
2.61
2.61

2.61
2.61
2.61
2.61
2.61

2.61
2.61
2.61
2.61
2.61

2.61
2.61
2.61
2.61
2.61

(ft. w.c.)

WATER
P

8787
9317
9772
10188
10567

8408
9014
9582
10037
10453

8181
8938
9620
10188
10681

8105
8863
9507
10113
10643

7992
8711
9393
9961
10453

7158
8105
8901
9620
10264

6249
7537
8598
9507
10302

28
29
31
32
33

27
28
30
32
33

26
28
30
32
34

26
28
30
32
34

25
27
30
31
33

23
26
28
30
32

20
24
27
30
32

16
21
25
29
32

(F)

T
WATER

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

(gpm)

WATER
FLOW

4.05
4.05
4.05
4.05
4.05

4.05
4.05
4.05
4.05
4.05

4.05
4.05
4.05
4.05
4.05

4.05
4.05
4.05
4.05
4.05

4.05
4.05
4.05
4.05
4.05

4.05
4.05
4.05
4.05
4.05

4.05
4.05
4.05
4.05
4.05

4.05
4.05
4.05
4.05
4.05

(ft. w.c.)

WATER
P

9658
10226
10756
11211
11628

9279
9923
10529
11059
11514

9014
9847
10567
11211
11779

8901
9734
10453
11097
11703

8787
9582
10302
10946
11514

7878
8901
9810
10567
11287

6855
8295
9469
10453
11325

5530
7348
8787
9999
10984

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 3

4) Performance ratings are subject to tolerances of plus/minus 5%.

3) Water heating capacities are based on 4-pipe chilled beams with THWS-TRW = 70F. For other conditions, multiply the table water heating capacity by the required (THWS-TRW) divided by 70F.

2) Water cooling capacities are based on TRC-TCHS = 18F. For other conditions multiply the table water cooling capacity by the required (TRC-TCHS) divided by 18F.

5037
6666
7992
9090
9999

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 2

HEATING (T HWS - TRH = 70F)


WATER
FLOW

1) Air cooling capacities are based on TAC = TRC-TCSA = 20F. For other conditions, multiply the table air cooling capacity by the required (TRC-TCSA) divided by 20F.
Alternatively, air cooling capacity can be calculated from the formula: Air cooling capacity QS = 1.085 x Airflow (cfm) x (TRC-TCSA).

28
34
40
47
53

A1

0.16
0.27
0.41
0.58
0.78

(in. w.c.)

(cfm)

21
28
34
40
47

PLENUM
PRESSURE

PRIMARY
AIRFLOW

A0

NOZZLE

2-Way Air Flow / 4-Pipe

Performance Data

24
26
27
28
29

23
25
27
28
29

23
25
27
28
30

22
25
26
28
30

22
24
26
28
29

20
22
25
27
28

17
21
24
26
29

14
19
22
25
28

(F)

T
WATER

YORK OVERHEAD ACTIVE CHILLED BEAM

10

20
24
28
32
36

55
77
102
131
163

38
44
50
56
62

44
52
60
68
76

54
62
70
78
86

72
84
96
108
120

B1

C1

E1

F1

G1

H1

51
69
90
114
141

59
77
98
122
149

50
69
93
119
148

58
78
101
126
155

55
77
102
131
163

52
75
102
133
168

45
68
96
129
166

158
194
230
267
303

15
15
18
22
26

41
43
46
48
51

35
39
42
44
46

31
35
39
42
45

29
33
35
39
42

23
27
31
34
36

873
1019
1164
1310
1456

655
752
849
946
1043

534
631
728
825
922

461
534
607
679
752

340
400
461
522
582

243
291
340
388
437

121
158
194
230
267

15
15
15
21
24

16
21
25
29
32

(W)

AIR COOLING
CAPACITY
T=10C

(NC)

NOISE CRITERIA

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

(l/s)

WATER
FLOW

4.8
4.8
4.8
4.8
4.8

4.8
4.8
4.8
4.8
4.8

4.8
4.8
4.8
4.8
4.8

4.8
4.8
4.8
4.8
4.8

4.8
4.8
4.8
4.8
4.8

4.8
4.8
4.8
4.8
4.8

4.8
4.8
4.8
4.8
4.8

4.8
4.8
4.8
4.8
4.8

(KPa)

WATER
P

940
990
1030
1060
1100

860
920
980
1030
1080

820
890
960
1010
1060

820
890
950
1000
1050

800
870
930
990
1040

730
810
880
940
990

610
730
830
910
990

570
690
790
860
930

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 1

5.6
5.9
6.1
6.4
6.6

5.1
5.5
5.8
6.1
6.4

4.9
5.3
5.7
6.1
6.4

4.9
5.3
5.7
6.0
6.3

4.8
5.2
5.6
5.9
6.2

4.4
4.8
5.2
5.6
5.9

3.6
4.3
4.9
5.4
5.9

3.4
4.1
4.7
5.2
5.6

(C)

T
WATER

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

(l/s)

WATER
FLOW

10.8
10.8
10.8
10.8
10.8

10.8
10.8
10.8
10.8
10.8

10.8
10.8
10.8
10.8
10.8

10.8
10.8
10.8
10.8
10.8

10.8
10.8
10.8
10.8
10.8

10.8
10.8
10.8
10.8
10.8

10.8
10.8
10.8
10.8
10.8

10.8
10.8
10.8
10.8
10.8

(KPa)

WATER
P

1080
1130
1180
1220
1260

980
1060
1120
1180
1230

940
1030
1100
1160
1220

940
1020
1090
1150
1210

920
1000
1070
1130
1190

840
930
1010
1070
1130

700
830
950
1050
1130

660
790
900
990
1070

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 2

4.3
4.5
4.7
4.9
5.0

3.9
4.2
4.5
4.7
4.9

3.7
4.1
4.4
4.6
4.9

3.7
4.0
4.3
4.6
4.8

3.7
4.0
4.3
4.5
4.7

3.3
3.7
4.0
4.3
4.5

2.8
3.3
3.8
4.2
4.5

2.6
3.2
3.6
3.9
4.2

(C)

T
WATER

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

0.08
0.08
0.08
0.08
0.08

(l/s)

WATER
FLOW

19.3
19.3
19.3
19.3
19.3

19.3
19.3
19.3
19.3
19.3

19.3
19.3
19.3
19.3
19.3

19.3
19.3
19.3
19.3
19.3

19.3
19.3
19.3
19.3
19.3

19.3
19.3
19.3
19.3
19.3

19.3
19.3
19.3
19.3
19.3

19.3
19.3
19.3
19.3
19.3

(KPa)

WATER
P

1150
1200
1250
1300
1340

1050
1120
1190
1250
1310

1100
1090
1170
1240
1300

990
1080
1160
1220
1280

980
1060
1140
1200
1260

890
990
1070
1140
1210

740
890
1010
1110
1200

700
840
960
1050
1130

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 3

3.4
3.6
3.7
3.9
4.0

3.1
3.4
3.6
3.7
3.9

3.0
3.3
3.5
3.7
3.9

3.0
3.2
3.4
3.6
3.8

2.9
3.2
3.4
3.6
3.8

2.7
2.9
3.2
3.4
3.6

2.2
2.6
3.0
3.3
3.6

2.1
2.5
2.9
3.1
3.4

(C)

T
WATER

YORK Overhead Active Chilled Beam6 (1800mm)


COOLING (T RC - TCHS = 10C)

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

0.03
0.03
0.03
0.03
0.03

(l/s)

WATER
FLOW

4.4
4.4
4.4
4.4
4.4

4.4
4.4
4.4
4.4
4.4

4.4
4.4
4.4
4.4
4.4

4.4
4.4
4.4
4.4
4.4

4.4
4.4
4.4
4.4
4.4

4.4
4.4
4.4
4.4
4.4

4.4
4.4
4.4
4.4
4.4

4.4
4.4
4.4
4.4
4.4

(KPa)

WATER
P

1830
1940
2040
2130
2200

1760
1880
2000
2090
2180

1710
1870
2010
2130
2230

1690
1850
1990
2110
2220

1670
1820
1960
2080
2180

1490
1690
1860
2010
2140

1300
1570
1790
1980
2150

1050
1390
1670
1890
2090

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 1

14.6
15.5
16.2
16.9
17.5

14.0
15.0
15.9
16.7
17.4

13.6
14.9
16.0
16.9
17.8

13.5
14.7
15.8
16.8
17.6

13.3
14.5
15.6
16.5
17.4

11.9
13.4
14.8
16.0
17.0

10.4
12.5
14.3
15.8
17.1

8.3
11.1
13.3
15.1
16.6

(C)

T
WATER

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

(l/s)

WATER
FLOW

7.8
7.8
7.8
7.8
7.8

7.8
7.8
7.8
7.8
7.8

7.8
7.8
7.8
7.8
7.8

7.8
7.8
7.8
7.8
7.8

7.8
7.8
7.8
7.8
7.8

7.8
7.8
7.8
7.8
7.8

7.8
7.8
7.8
7.8
7.8

7.8
7.8
7.8
7.8
7.8

(KPa)

WATER
P

2320
2460
2580
2690
2790

2220
2380
2530
2650
2760

2160
2360
2540
2690
2820

2140
2340
2510
2670
2810

2110
2300
2480
2630
2760

1890
2140
2350
2540
2710

1650
1990
2270
2510
2720

1330
1760
2110
2400
2640

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 2

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

(l/s)

WATER
FLOW

12.1
12.1
12.1
12.1
12.1

12.1
12.1
12.1
12.1
12.1

12.1
12.1
12.1
12.1
12.1

12.1
12.1
12.1
12.1
12.1

12.1
12.1
12.1
12.1
12.1

12.1
12.1
12.1
12.1
12.1

12.1
12.1
12.1
12.1
12.1

12.1
12.1
12.1
12.1
12.1

(KPa)

WATER
P

2550
2700
2840
2960
3070

2450
2620
2780
2920
3040

2380
2600
2790
2960
3110

2350
2570
2760
2930
3090

2320
2530
2720
2890
3040

2080
2350
2590
2790
2980

1810
2190
2500
2760
2990

1460
1940
2320
2640
2900

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 3

4) Performance ratings are subject to tolerances of plus/minus 5%.

3) Water heating capacities are based on 4-pipe chilled beams with THWS-TRW = 35C. For other conditions, multiply the table water heating capacity by the required (THWS-TRW) divided by 35C.

2) Water cooling capacities are based on TRC-TCHS = 10C. For other conditions multiply the table water cooling capacity by the required (TRC-TCHS) divided by 10C.

13.8
14.7
15.4
16.1
16.6

13.3
14.2
15.1
15.8
16.5

12.9
14.1
15.2
16.1
16.9

12.8
14.0
15.0
15.9
16.8

12.6
13.8
14.8
15.7
16.5

11.3
12.8
14.0
15.2
16.2

9.8
11.9
13.5
15.0
16.2

7.9
10.5
12.6
14.3
15.8

(C)

T
WATER

HEATING (T HWS - TRH = 35C)

1) Air cooling capacities are based on TAC = TRC-TCSA = 10C. For other conditions, multiply the table air cooling capacity by the required (TRC-TCSA) divided by 10C.
Alternatively, air cooling capacity can be calculated from the formula: Air cooling capacity W = 1.213 x Airflow (l/s) x (TRC-TCSA).

13
16
19
22
25

A1

40
68
103
145
195

(Pa)

(l/s)

10
13
16
19
22

PLENUM
PRESSURE

PRIMARY
AIRFLOW

A0

NOZZLE

2-Way Air Flow / 4-Pipe

Performance Data

12.2
12.9
13.6
14.1
14.7

11.7
12.5
13.3
13.9
14.5

11.4
12.4
13.3
14.1
14.8

11.2
12.3
13.2
14.0
14.7

11.1
12.1
13.0
13.8
14.5

9.9
11.2
12.3
13.3
14.2

8.7
10.4
11.9
13.2
14.3

7.0
9.3
11.1
12.6
13.9

(C)

T
WATER

YORK OVERHEAD ACTIVE CHILLED BEAM

59
70
81
91
102

78
93
108
123
138

102
123
144
161
186

127
153
178
203
229

148
174
199
225
250

191
233
275
318
360

B1

C1

E1

F1

G1

H1

0.17
0.26
0.36
0.48
0.61

0.21
0.29
0.38
0.49
0.60

0.20
0.29
0.39
0.51
0.65

0.20
0.29
0.40
0.53
0.67

0.21
0.29
0.40
0.51
0.64

0.22
0.31
0.41
0.52
0.65

0.20
0.30
0.42
0.55
0.70

874
1058
1241
1425
1609

1287
1517
1747
1977
2207

1701
2023
2345
2667
2989

15
15
15
15
18

15
15
18
22
26

15
20
25
28
31

31
37
41
43
46

25
30
34
38
41

22
27
30
34
37

4138
5058
5978
6897
7817

3219
3770
4322
4874
5426

2759
3311
3862
4414
4966

2207
2667
3127
3495
4046

644
828
1012
1196
1379

15
15
15
15
17

20
24
28
31
33

(Btu/hr)

AIR COOLING
CAPACITY
T=20F

(NC)

Noise Criteria

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

(gpm)

WATER
FLOW

1.14
1.14
1.14
1.14
1.14

1.14
1.14
1.14
1.14
1.14

1.14
1.14
1.14
1.14
1.14

1.14
1.14
1.14
1.14
1.14

1.14
1.14
1.14
1.14
1.14

1.14
1.14
1.14
1.14
1.14

1.14
1.14
1.14
1.14
1.14

1.14
1.14
1.14
1.14
1.14

(ft. w.c.)

WATER
P

4402
4709
4948
5152
5357

4026
4368
4675
4948
5186

3958
4333
4675
4982
5221

3753
4197
4572
4879
5152

3685
4129
4504
4811
5084

3446
3856
4197
4504
4743

3105
3651
4095
4470
4811

2832
3378
3787
4163
4470

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 1

9
10
10
11
11

8
9
10
10
11

8
9
10
10
11

8
9
10
10
11

8
9
9
10
11

7
8
9
9
10

7
8
9
9
10

6
7
8
9
9

(F)

T
WATER

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

(gpm)

WATER
FLOW

2.58
2.58
2.58
2.58
2.58

2.58
2.58
2.58
2.58
2.58

2.58
2.58
2.58
2.58
2.58

2.58
2.58
2.58
2.58
2.58

2.58
2.58
2.58
2.58
2.58

2.58
2.58
2.58
2.58
2.58

2.58
2.58
2.58
2.58
2.58

2.58
2.58
2.58
2.58
2.58

(ft. w.c.)

WATER
P

5016
5323
5630
5869
6074

4572
4982
5323
5630
5903

4470
4948
5323
5630
5937

4265
4777
5186
5528
5869

4197
4675
5118
5459
5767

3924
4368
4777
5084
5391

3549
4163
4641
5084
5494

3207
3822
4333
4743
5084

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 2

7
7
8
8
9

6
7
7
8
8

6
7
7
8
8

6
7
7
8
8

6
7
7
8
8

6
6
7
7
8

5
6
7
7
8

4
5
6
7
7

(F)

T
WATER

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

(gpm)

WATER
FLOW

4.62
4.62
4.62
4.62
4.62

4.62
4.62
4.62
4.62
4.62

4.62
4.62
4.62
4.62
4.62

4.62
4.62
4.62
4.62
4.62

4.62
4.62
4.62
4.62
4.62

4.62
4.62
4.62
4.62
4.62

4.62
4.62
4.62
4.62
4.62

4.62
4.62
4.62
4.62
4.62

(ft. w.c.)

WATER
P

5221
5562
5869
6108
6347

4777
5186
5562
5869
6142

4675
5152
5528
5869
6176

4436
4982
5391
5767
6108

4368
4879
5323
5698
6039

4095
4572
4982
5323
5630

3685
4333
4845
5323
5698

3344
3992
4504
4948
5323

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 3

YORK Overhead Active Chilled Beam8 (8')


COOLING (T RC - TCHS = 18F)

5
6
6
6
7

5
5
6
6
6

5
5
6
6
6

5
5
6
6
6

5
5
6
6
6

4
5
5
6
6

4
5
5
6
6

4
4
5
5
6

(F)

T
WATER

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

(gpm)

WATER
FLOW

1.77
1.77
1.77
1.77
1.77

1.77
1.77
1.77
1.77
1.77

1.77
1.77
1.77
1.77
1.77

1.77
1.77
1.77
1.77
1.77

1.77
1.77
1.77
1.77
1.77

1.77
1.77
1.77
1.77
1.77

1.77
1.77
1.77
1.77
1.77

1.77
1.77
1.77
1.77
1.77

(ft. w.c.)

WATER
P

9469
10037
10567
10984
11400

9090
9734
10340
10832
11287

8825
9658
10378
10984
11552

8749
9544
10264
10908
11476

8598
9431
10113
10756
11287

7726
8711
9620
10378
11059

6742
8105
9279
10264
11097

5416
7196
8635
9810
10794

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 1

30
32
33
35
36

29
31
33
34
36

28
30
33
35
36

28
30
32
34
36

27
30
32
34
36

24
27
30
33
35

21
26
29
32
35

17
23
27
31
34

(F)

T
WATER

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

(gpm)

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

(ft. w.c.)

WATER
P

11968
12726
13370
13938
14430

11514
12347
13067
13711
14317

11173
12234
13143
13900
14620

11059
12120
12991
13786
14506

10908
11931
12802
13597
14317

9772
11059
12158
13143
13976

8522
10264
11741
12991
14052

6855
9128
10908
12385
13673

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 2

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

(gpm)

WATER
FLOW

4.92
4.92
4.92
4.92
4.92

4.92
4.92
4.92
4.92
4.92

4.92
4.92
4.92
4.92
4.92

4.92
4.92
4.92
4.92
4.92

4.92
4.92
4.92
4.92
4.92

4.92
4.92
4.92
4.92
4.92

4.92
4.92
4.92
4.92
4.92

4.92
4.92
4.92
4.92
4.92

(ft. w.c.)

WATER
P

13180
13976
14695
15301
15870

12650
13559
14355
15074
15718

12309
13446
14430
15301
16059

12158
13294
14317
15188
15983

12006
13105
14089
14961
15718

10719
12158
13370
14430
15377

9355
11325
12915
14279
15453

7537
10037
12006
13635
15036

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 3

4) Performance ratings are subject to tolerances of plus/minus 5%.

3) Water heating capacities are based on 4-pipe chilled beams with THWS-TRW = 70F. For other conditions, multiply the table water heating capacity by the required (THWS-TRW) divided by 70F.

2) Water cooling capacities are based on TRC-TCHS = 18F. For other conditions multiply the table water cooling capacity by the required (TRC-TCHS) divided by 18F.

30
32
34
35
36

29
31
33
35
36

28
31
33
35
37

28
31
33
35
37

28
30
32
34
36

25
28
31
33
35

22
26
30
33
35

17
23
28
31
35

(F)

T
WATER

HEATING (T HWS - TRH = 70F)


WATER
FLOW

1) Air cooling capacities are based on TAC = TRC-TCSA = 20F. For other conditions, multiply the table air cooling capacity by the required (TRC-TCSA) divided by 20F.
Alternatively, air cooling capacity can be calculated from the formula: Air cooling capacity QS = 1.085 x Airflow (cfm) x (TRC-TCSA).

40
49
57
66
74

A1

0.17
0.28
0.42
0.59
0.79

(in. w.c.)

(cfm)

30
38
47
55
64

PLENUM
PRESSURE

PRIMARY
AIRFLOW

A0

NOZZLE

2-Way Air Flow / 4-Pipe

Performance Data

28
29
31
32
33

27
29
30
32
33

26
28
30
32
34

26
28
30
32
34

25
28
30
31
33

23
26
28
30
32

20
24
27
30
32

16
21
25
29
32

(F)

T
WATER

YORK OVERHEAD ACTIVE CHILLED BEAM

11

12

28
33
38
43
48

37
44
51
58
65

48
58
68
76
88

60
72
84
96
108

70
82
94
106
118

90
110
130
150
170

B1

C1

E1

F1

G1

H1

43
64
90
119
153

53
73
95
121
150

50
72
97
127
161

50
72
99
131
166

52
73
99
127
160

55
76
101
129
161

51
75
104
137
174

230
379
328
376
425

15
15
20
23
27

37
42
46
50
55

34
38
41
44
47

30
35
39
42
46

26
31
35
39
42

22
27
30
34
37

1092
1334
1577
1820
2062

849
995
1140
1286
1431

728
873
1019
1164
1310

582
704
825
946
1067

449
534
619
704
788

340
400
461
522
582

170
218
267
315
364

15
15
16
20
24

17
21
25
28
31

(W)

AIR COOLING
CAPACITY
T=10F

(NC)

Noise Criteria

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

(l/s)

WATER
FLOW

3.4
3.4
3.4
3.4
3.4

3.4
3.4
3.4
3.4
3.4

3.4
3.4
3.4
3.4
3.4

3.4
3.4
3.4
3.4
3.4

3.4
3.4
3.4
3.4
3.4

3.4
3.4
3.4
3.4
3.4

3.4
3.4
3.4
3.4
3.4

3.4
3.4
3.4
3.4
3.4

(KPa)

WATER
P

1290
1380
1450
1510
1570

1180
1280
1370
1450
1520

1160
1270
1370
1460
1530

1100
1230
1340
1430
1510

1080
1210
1320
1410
1490

1010
1130
1230
1320
1390

910
1070
1200
1310
1410

830
990
1110
1220
1310

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 1

5.2
5.5
5.8
6.1
6.2

4.7
5.1
5.4
5.7
6.0

4.6
5.0
5.4
5.7
6.0

4.3
4.9
5.3
5.7
6.0

4.1
4.6
5.0
5.3
5.7

3.9
4.5
4.9
5.3
5.6

3.7
4.4
4.9
5.4
5.8

3.3
4.0
4.5
5.0
5.3

(C)

T
WATER

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

(l/s)

WATER
FLOW

7.7
7.7
7.7
7.7
7.7

7.7
7.7
7.7
7.7
7.7

7.7
7.7
7.7
7.7
7.7

7.7
7.7
7.7
7.7
7.7

7.7
7.7
7.7
7.7
7.7

7.7
7.7
7.7
7.7
7.7

7.7
7.7
7.7
7.7
7.7

7.7
7.7
7.7
7.7
7.7

(KPa)

WATER
P

1470
1560
1650
1720
1780

1340
1460
1560
1650
1730

1310
1450
1560
1650
1740

1250
1400
1520
1620
1720

1230
1370
1500
1600
1690

1150
1280
1400
1490
1580

1040
1220
1360
1490
1610

940
1120
1270
1390
1490

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 2

0.12
0.12
0.12
0.12
0.12
0.12
0.12
0.12
0.12
0.12

3.9
4.2
4.4
4.6
4.8

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

(l/s)

WATER
FLOW

3.5
3.8
4.1
4.3
4.5

3.4
3.8
4.1
4.4
4.6

3.3
3.7
4.0
4.3
4.5

3.1
3.5
3.8
4.1
4.3

3.0
3.4
3.7
4.0
4.2

2.8
3.3
3.7
4.1
4.4

2.5
3.0
3.4
3.8
4.0

(C)

T
WATER

13.8
13.8
13.8
13.8
13.8

13.8
13.8
13.8
13.8
13.8

13.8
13.8
13.8
13.8
13.8

1530
1630
1720
1790
1860

1400
1520
1630
1720
1800

1370
1510
1620
1720
1810

1300
1460
1580
1690
1790

1280
1430
1560
1670
1770

13.8
13.8
13.8
13.8
13.8
13.8
13.8
13.8
13.8
13.8

1200
1340
1460
1560
1650

1080
1270
1420
1560
1670

980
1170
1320
1450
1560

13.8
13.8
13.8
13.8
13.8

13.8
13.8
13.8
13.8
13.8

13.8
13.8
13.8
13.8
13.8

(KPa)

WATER
P

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 3

3.0
3.2
3.4
3.6
3.7

2.8
3.0
3.2
3.4
3.6

2.7
3.0
3.2
3.4
3.6

2.6
2.9
3.2
3.4
3.6

2.6
2.9
3.1
3.3
3.5

2.4
2.7
2.9
3.1
3.3

2.2
2.5
2.8
3.1
3.3

1.9
2.3
2.6
2.9
3.1

(C)

T
WATER

YORK Overhead Active Chilled Beam8 (2400mm)


COOLING (TRC - TCHS = 18F)

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

(l/s)

WATER
FLOW

5.3
5.3
5.3
5.3
5.3

5.3
5.3
5.3
5.3
5.3

5.3
5.3
5.3
5.3
5.3

5.3
5.3
5.3
5.3
5.3

5.3
5.3
5.3
5.3
5.3

5.3
5.3
5.3
5.3
5.3

5.3
5.3
5.3
5.3
5.3

5.3
5.3
5.3
5.3
5.3

(KPa)

WATER
P

2500
2650
2790
2900
3010

14.9
15.8
16.6
17.3
18.0

14.3
15.4
16.3
17.1
17.8

13.9
15.2
16.4
17.3
18.2

2330
2550
2740
2900
3050
2400
2570
2730
2860
2980

13.8
15.1
16.2
17.2
18.1

13.6
14.8
16.0
16.9
17.8

12.2
13.8
15.1
16.4
17.4

10.6
12.8
14.6
16.2
17.5

8.6
11.4
13.6
15.4
17.0

(C)

T
WATER

2310
2520
2710
2880
3030

2270
2490
2670
2840
2980

2040
2300
2540
2740
2920

1780
2140
2450
2710
2930

1430
1900
2280
2590
2850

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 1

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

(l/s)

WATER
FLOW

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

(KPa)

WATER
P

3160
3360
3530
3680
3810

3040
3260
3450
3620
3780

2950
3230
3470
3670
3860

2920
3200
3430
3640
3830

2880
3150
3380
3590
3780

2580
2920
3210
3470
3690

2250
2710
3100
3430
3710

1810
2410
2880
3270
3610

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 2

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

(l/s)

WATER
FLOW

14.7
14.7
14.7
14.7
14.7

14.7
14.7
14.7
14.7
14.7

14.7
14.7
14.7
14.7
14.7

14.7
14.7
14.7
14.7
14.7

14.7
14.7
14.7
14.7
14.7

14.7
14.7
14.7
14.7
14.7

14.7
14.7
14.7
14.7
14.7

14.7
14.7
14.7
14.7
14.7

(KPa)

WATER
P

3480
3690
3880
4040
4190

3340
3580
3790
3980
4150

3250
3550
3810
4040
4240

3210
3510
3780
4010
4220

3170
3460
3720
3950
4150

2830
3210
3530
3810
4060

2470
2990
3410
3770
4080

1990
2650
3170
3600
3970

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 3

4) Performance ratings are subject to tolerances of plus/minus 5%.

3) Water heating capacities are based on 4-pipe chilled beams with THWS-TRW = 35C. For other conditions, multiply the table water heating capacity by the required (THWS-TRW) divided by 35C.

2) Water cooling capacities are based on TRC-TCHS = 10C. For other conditions multiply the table water cooling capacity by the required (TRC-TCHS) divided by 10C.

15.1
16.0
16.8
17.6
18.2

14.5
15.6
16.5
17.3
18.0

14.1
15.4
16.6
17.6
18.4

14.0
15.3
16.4
17.4
18.3

13.8
15.0
16.2
17.1
18.0

12.3
13.9
15.3
16.6
17.6

10.7
13.0
14.8
16.4
17.7

8.7
11.5
13.8
15.6
17.2

(C)

T
WATER

HEATING (T HWS - TRH = 70F)

1) Air cooling capacities are based on TAC = TRC-TCSA = 10C. For other conditions, multiply the table air cooling capacity by the required (TRC-TCSA) divided by 10C.
Alternatively, air cooling capacity can be calculated from the formula: Air cooling capacity W = 1.213 x Airflow (l/s) x (TRC-TCSA).

19
23
27
31
35

A1

43
70
105
147
196

(Pa)

(l/s)

14
18
22
26
30

PLENUM
PRESSURE

PRIMARY
AIRFLOW

A0

NOZZLE

2-Way Air Flow / 4-Pipe

Performance Data

13.8
14.7
15.4
16.1
16.7

13.3
14.3
15.1
15.9
16.5

12.9
14.1
15.2
16.1
16.9

12.8
14.0
15.0
16.0
16.8

12.6
13.8
14.8
15.7
16.5

11.3
12.8
14.1
15.2
16.2

9.8
11.9
13.6
15.0
16.3

7.9
10.6
12.6
14.3
15.8

(C)

T
WATER

YORK OVERHEAD ACTIVE CHILLED BEAM

72
87
102
117
131

106
123
140
157
174

131
157
182
208
233

159
191
222
254
286

182
220
259
297
335

254
307
360
413
466

B1

C1

E1

F1

G1

H1

0.19
0.28
0.38
0.50
0.64

0.20
0.29
0.40
0.53
0.67

0.19
0.28
0.38
0.50
0.63

0.21
0.29
0.40
0.52
0.65

0.24
0.32
0.41
0.52
0.64

0.20
0.29
0.40
0.53
0.67

0.20
0.30
0.41
0.54
0.69

993
1201
1406
1614
1822

1406
1696
1986
2276
2566

2071
2402
2733
3064
3395

15
15
15
15
18

15
15
18
22
26

15
20
25
28
31

31
37
41
43
46

25
30
34
38
41

22
27
30
34
37

4968
6002
7036
8070
9107

3559
4306
5050
5794
6541

3105
3726
4347
4968
5589

2566
3064
3559
4057
4552

703
911
1119
1324
1532

15
15
15
15
17

20
24
28
31
33

(Btu/hr)

AIR COOLING
CAPACITY
T=50F

(NC)

NOISE CRITERIA

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

(gpm)

WATER
FLOW

1.41
1.41
1.41
1.41
1.41

1.41
1.41
1.41
1.41
1.41

1.41
1.41
1.41
1.41
1.41

1.41
1.41
1.41
1.41
1.41

1.41
1.41
1.41
1.41
1.41

1.41
1.41
1.41
1.41
1.41

1.41
1.41
1.41
1.41
1.41

1.41
1.41
1.41
1.41
1.41

(ft. w.c.)

WATER
P

5186
5528
5801
6039
6244

4572
5084
5494
5869
6176

4538
5016
5391
5732
6039

4402
4879
5289
5630
5971

4333
4811
5221
5562
5869

4197
4572
4913
5221
5494

3617
4231
4743
5186
5562

3173
3822
4333
4777
5152

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 1

11
12
12
13
13

10
11
12
12
13

10
11
11
12
13

9
10
11
12
13

9
10
11
12
12

9
10
10
11
12

8
9
10
11
12

7
8
9
10
11

(F)

T
WATER

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

1.43
1.43
1.43
1.43
1.43

(gpm)

WATER
FLOW

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

3.14
3.14
3.14
3.14
3.14

(ft. w.c.)

WATER
P

6005
6381
6722
6995
7234

5323
5869
6381
6790
7131

5255
5801
6244
6620
6961

5084
5664
6108
6517
6893

5016
5562
6039
6449
6790

4845
5289
5698
6039
6381

4163
4879
5494
6005
6449

3651
4402
5016
5528
5937

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 2

8
9
9
10
10

7
8
9
10
10

7
8
9
9
10

7
8
9
9
10

7
8
8
9
10

7
7
8
8
9

6
7
8
8
9

5
6
7
8
8

(F)

T
WATER

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

1.90
1.90
1.90
1.90
1.90

(gpm)

WATER
FLOW

5.59
5.59
5.59
5.59
5.59

5.59
5.59
5.59
5.59
5.59

5.59
5.59
5.59
5.59
5.59

5.59
5.59
5.59
5.59
5.59

5.59
5.59
5.59
5.59
5.59

5.59
5.59
5.59
5.59
5.59

5.59
5.59
5.59
5.59
5.59

5.59
5.59
5.59
5.59
5.59

(ft. w.c.)

WATER
P

6517
6927
7268
7575
7848

5767
6381
6893
7370
7746

5698
6278
6756
7200
7575

5528
6142
6654
7097
7473

5459
6039
6551
6961
7370

5255
5732
6176
6551
6893

4538
5289
5937
6483
6995

3958
4777
5425
5971
6449

WATER
COOLING
CAPACITY
(Btu/hr)

COOLING WATER FLOW 3

YORK Overhead Active Chilled Beam10 (10')


COOLING (TRC - TCHS = 18F)

7
7
8
8
8

6
7
7
8
8

6
7
7
8
8

6
6
7
7
8

6
6
7
7
8

6
6
6
7
7

5
6
6
7
7

4
5
6
6
7

(F)

T
WATER

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63

(gpm)

WATER
FLOW

2.07
2.07
2.07
2.07
2.07

2.07
2.07
2.07
2.07
2.07

2.07
2.07
2.07
2.07
2.07

2.07
2.07
2.07
2.07
2.07

2.07
2.07
2.07
2.07
2.07

2.07
2.07
2.07
2.07
2.07

2.07
2.07
2.07
2.07
2.07

2.07
2.07
2.07
2.07
2.07

(ft. w.c.)

WATER
P

12006
12726
13370
13938
14430

11514
12347
13105
13749
14317

11211
12271
13143
13938
14620

11097
12120
13029
13824
14544

10908
11931
12840
13597
14317

9772
11059
12196
13143
14014

8522
10302
11741
12991
14089

6893
9128
10946
12423
13673

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 1

38
40
42
44
46

36
39
41
43
45

35
39
41
44
46

35
38
41
44
46

34
38
41
43
45

31
35
38
41
44

27
32
37
41
44

22
29
35
39
43

(F)

T
WATER

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

0.79
0.79
0.79
0.79
0.79

(gpm)

WATER
FLOW

3.68
3.68
3.68
3.68
3.68

3.68
3.68
3.68
3.68
3.68

3.68
3.68
3.68
3.68
3.68

3.68
3.68
3.68
3.68
3.68

3.68
3.68
3.68
3.68
3.68

3.68
3.68
3.68
3.68
3.68

3.68
3.68
3.68
3.68
3.68

3.68
3.68
3.68
3.68
3.68

(ft. w.c.)

WATER
P

15188
16135
16930
17650
18294

14582
15642
16551
17385
18142

14165
15529
16665
17650
18521

14052
15339
16476
17498
18407

13824
15112
16248
17233
18142

12385
14014
15415
16665
17725

10794
13029
14885
16438
17839

8711
11590
13824
15718
17309

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 2

HEATING (THWS - TRH = 70F)

38
41
43
45
46

37
39
42
44
46

36
39
42
45
47

35
39
42
44
46

35
38
41
43
46

31
35
39
42
45

27
33
38
41
45

22
29
35
40
44

(F)

T
WATER

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

0.95
0.95
0.95
0.95
0.95

(gpm)

WATER
FLOW

5.75
5.75
5.75
5.75
5.75

5.75
5.75
5.75
5.75
5.75

5.75
5.75
5.75
5.75
5.75

5.75
5.75
5.75
5.75
5.75

5.75
5.75
5.75
5.75
5.75

5.75
5.75
5.75
5.75
5.75

5.75
5.75
5.75
5.75
5.75

5.75
5.75
5.75
5.75
5.75

(ft. w.c.)

WATER
P

16703
17725
18634
19430
20112

16059
17195
18218
19127
17982

15604
17044
18331
19392
20377

15453
16892
18142
19240
20263

15188
16627
17877
18975
19960

13597
15415
16968
18294
19506

11893
14317
16362
18104
19619

9582
12726
15226
17309
19051

WATER
HEATING
CAPACITY
(Btu/hr)

HEATING WATER FLOW 3

4) Performance ratings are subject to tolerances of plus/minus 5%.

3) Water heating capacities are based on 4-pipe chilled beams with THWS-TRW = 70F. For other conditions, multiply the table water heating capacity by the required (THWS-TRW) divided by 70F.

2) Water cooling capacities are based on TRC-TCHS = 18F. For other conditions multiply the table water cooling capacity by the required (TRC-TCHS) divided by 18F.

1) Air cooling capacities are based on TAC = TRC-TCSA = 20F. For other conditions, multiply the table air cooling capacity by the required (TRC-TCSA) divided by 20F.
Alternatively, air cooling capacity can be calculated from the formula: Air cooling capacity QS = 1.085 x Airflow (cfm) x (TRC-TCSA).

51
61
72
83
93

A1

0.16
0.26
0.39
0.55
0.74

(in. w.c.)

(cfm)

36
47
57
68
78

PLENUM
PRESSURE

PRIMARY
AIRFLOW

A0

NOZZLE

2-Way Air Flow / 4-Pipe

Performance Data

35
37
39
41
42

34
36
38
40
70

33
36
39
41
43

32
36
38
40
43

32
35
38
40
42

29
32
36
38
41

25
30
34
38
41

20
27
32
36
40

(F)

T
WATER

YORK OVERHEAD ACTIVE CHILLED BEAM

13

14

34
41
48
55
62

50
58
66
74
82

62
74
86
98
110

75
90
105
120
135

86
104
122
140
158

120
145
170
195
220

B1

C1

E1

F1

G1

H1

48
69
95
125
160

50
72
100
131
167

48
70
95
124
157

52
73
99
129
162

59
79
103
129
159

50
73
100
131
167

51
75
102
135
172

291
352
412
473
534

15
19
23
27
30

44
48
51
53
58

36
42
46
49
53

34
40
44
47
50

30
36
40
44
47

28
31
35
38
42

1456
1759
2062
2365
2669

1043
1262
1480
1698
1917

910
1092
1274
1456
1638

752
898
1043
1189
1334

607
704
801
898
995

412
497
582
667
752

206
267
328
388
449

15
15
19
24
28

20
25
29
32
36

(W)

AIR COOLING
CAPACITY
T=10F

(NC)

NOISE CRITERIA

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

(l/s)

WATER
FLOW

4.2
4.2
4.2
4.2
4.2

4.2
4.2
4.2
4.2
4.2

4.2
4.2
4.2
4.2
4.2

4.2
4.2
4.2
4.2
4.2

4.2
4.2
4.2
4.2
4.2

4.2
4.2
4.2
4.2
4.2

4.2
4.2
4.2
4.2
4.2

4.2
4.2
4.2
4.2
4.2

(KPa)

WATER
P

1520
1620
1700
1770
1830

1340
1490
1610
1720
1810

1330
1470
1580
1680
1770

6.1
6.4
6.8
7.0
7.3

5.4
5.9
6.4
6.8
7.2

5.3
5.8
6.3
6.7
7.0

5.1
5.7
6.2
6.6
7.0

5.1
5.6
6.1
6.5
6.8

1270
1410
1530
1630
1720
1290
1430
1550
1650
1750

4.9
5.3
5.7
6.1
6.4

4.2
4.9
5.5
6.0
6.5

3.7
4.5
5.1
5.6
6.0

(C)

T
WATER

1230
1340
1440
1530
1610

1060
1240
1390
1520
1630

930
1120
1270
1400
1510

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 1

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

0.09
0.09
0.09
0.09
0.09

(l/s)

WATER
FLOW

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

9.4
9.4
9.4
9.4
9.4

(KPa)

WATER
P

1760
1870
1970
2050
2120

1560
1720
1870
1990
2090

1540
1700
1830
1940
2040

1490
1660
1790
1910
2020

1470
1630
1770
1890
1990

1420
1550
1670
1770
1870

1220
1430
1610
1760
1890

1070
1290
1470
1620
1740

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 2

4.7
5.0
5.2
5.4
5.6

4.1
4.6
5.0
5.3
5.6

4.1
4.5
4.9
5.2
5.4

4.0
4.4
4.8
5.1
5.4

3.9
4.3
4.7
5.0
5.3

3.8
4.1
4.4
4.7
5.0

3.2
3.8
4.3
4.7
5.0

2.8
3.4
3.9
4.3
4.6

(C)

T
WATER

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

0.12
0.12
0.12
0.12
0.12

(l/s)

WATER
FLOW

16.7
16.7
16.7
16.7
16.7

16.7
16.7
16.7
16.7
16.7

16.7
16.7
16.7
16.7
16.7

16.7
16.7
16.7
16.7
16.7

16.7
16.7
16.7
16.7
16.7

16.7
16.7
16.7
16.7
16.7

16.7
16.7
16.7
16.7
16.7

16.7
16.7
16.7
16.7
16.7

(KPa)

WATER
P

1910
2030
2130
2220
2300

1690
1870
2020
2160
2270

1670
1840
1980
2110
2220

1620
1800
1950
2080
2190

1600
1770
1920
2040
2160

1540
1680
1810
1920
2020

1330
1550
1740
1900
2050

1160
1400
1590
1750
1890

WATER
COOLING
CAPACITY
(W)

COOLING WATER FLOW 3

3.8
4.0
4.2
4.4
4.6

3.4
3.7
4.0
4.3
4.5

3.3
3.7
3.9
4.2
4.4

3.2
3.6
3.9
4.1
4.4

3.2
3.5
3.8
4.1
4.3

3.1
3.4
3.6
3.8
4.0

2.6
3.1
3.5
3.8
4.1

2.3
2.8
3.2
3.5
3.8

(C)

T
WATER

YORK Overhead Active Chilled Beam8 (3000mm)


COOLING (TRC - TCHS = 10C)

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

0.04
0.04
0.04
0.04
0.04

(l/s)

WATER
FLOW

6.2
6.2
6.2
6.2
6.2

6.2
6.2
6.2
6.2
6.2

6.2
6.2
6.2
6.2
6.2

6.2
6.2
6.2
6.2
6.2

6.2
6.2
6.2
6.2
6.2

6.2
6.2
6.2
6.2
6.2

6.2
6.2
6.2
6.2
6.2

6.2
6.2
6.2
6.2
6.2

(KPa)

WATER
P

3170
3360
3530
3680
3810

3040
3260
3460
3630
3780

2960
3240
3470
3680
3860

2930
3200
3440
3650
3840

2880
3150
3390
3590
3780

2580
2920
3220
3470
3700

2250
2720
3100
3430
3720

1820
2410
2890
3280
3610

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 1

18.9
20.1
21.1
22.0
22.8

18.2
19.5
20.6
21.7
22.6

17.7
19.3
20.7
22.0
23.1

17.5
19.1
20.5
21.8
22.9

17.2
18.8
20.2
21.5
22.6

15.4
17.4
19.2
20.7
22.1

13.5
16.2
18.5
20.5
22.2

10.8
14.4
17.2
19.6
21.6

(C)

T
WATER

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

0.05
0.05
0.05
0.05
0.05

(l/s)

WATER
FLOW

11
11
11
11
11

11
11
11
11
11

11
11
11
11
11

11
11
11
11
11

11
11
11
11
11

11
11
11
11
11

11
11
11
11
11

11
11
11
11
11

(KPa)

WATER
P

4010
4260
4470
4660
4830

3850
4130
4370
4590
4790

3740
4100
4400
4660
4890

3710
4050
4350
4620
4860

3650
3990
4290
4550
4790

3270
3700
4070
4400
4680

2850
3440
3930
4340
4710

2300
3060
3650
4150
4570

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 2

0.06
0.06
0.06
0.06
0.06

17.2
17.2
17.2
17.2
17.2

17.2
17.2
17.2
17.2
17.2

17.2
17.2
17.2
17.2
17.2

17.2
17.2
17.2
17.2
17.2

17.2
17.2
17.2
17.2
17.2

17.2
17.2
17.2
17.2
17.2

17.2
17.2
17.2
17.2
17.2

17.2
17.2
17.2
17.2
17.2

(KPa)

WATER
P

4410
4680
4920
5130
5310

4240
4540
4810
5050
5270

4120
4500
4840
5120
5380

4080
4460
4790
5080
5350

4010
4390
4720
5010
5270

3590
4070
4480
4830
5150

3140
3780
4320
4780
5180

2530
3360
4020
4570
5030

WATER
HEATING
CAPACITY
(W)

HEATING WATER FLOW 3

4) Performance ratings are subject to tolerances of plus/minus 5%.

3) Water heating capacities are based on 4-pipe chilled beams with THWS-TRW = 35C. For other conditions, multiply the table water heating capacity by the required (THWS-TRW) divided by 35C.

2) Water cooling capacities are based on TRC-TCHS = 10C. For other conditions multiply the table water cooling capacity by the required (TRC-TCHS) divided by 10C.

19.2
20.3
21.4
22.3
23.1

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

17.9
19.6
21.0
22.3
23.4
18.4
19.7
20.9
21.9
22.9

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

0.06
0.06
0.06
0.06
0.06

(l/s)

WATER
FLOW

17.7
19.3
20.8
22.1
23.2

17.4
19.1
20.5
21.7
22.9

15.6
17.7
19.4
21.0
22.4

13.6
16.4
18.8
20.8
22.5

11.0
14.6
17.5
19.8
21.8

(C)

T
WATER

HEATING (T HWS - TRH = 35C)

1) Air cooling capacities are based on TAC = TRC-TCSA = 10C. For other conditions, multiply the table air cooling capacity by the required (TRC-TCSA) divided by 10C.
Alternatively, air cooling capacity can be calculated from the formula: Air cooling capacity W = 1.213 x Airflow (l/s) x (TRC-TCSA).

24
29
34
39
44

A1

39
65
98
138
185

(Pa)

(l/s)

17
22
27
32
37

PLENUM
PRESSURE

PRIMARY
AIRFLOW

A0

NOZZLE

2-Way Air Flow / 4-Pipe

Performance Data

17.6
18.6
19.6
20.4
21.1

16.9
18.1
19.2
20.1
21.0

16.4
17.9
19.2
20.4
21.4

16.2
17.7
19.1
20.2
21.3

16.0
17.5
18.8
19.9
21.0

14.3
16.2
17.8
19.2
20.5

12.5
15.1
17.2
19.0
20.6

10.1
13.4
16.0
18.2
20.0

(C)

T
WATER

YORK OVERHEAD ACTIVE CHILLED BEAM

YORK OVERHEAD ACTIVE CHILLED BEAM

Selection Example
Specified Data
Office (LxWxH):
Occupants:
Occupant Load Per Person:

25 x 20 x 9 Area = 500 ft2


4
250 Btu/h Sensible / 155 Btu/h Latent

Summer Room Design Condition (TRS ):


Summer Primary Air Temperature (TCSA ):
Chilled Water Supply Temperature (TCHS ):
Summer Room Sensible Load:

75F db / 50% RH / 55F dp / W=0.00924 lbs/lb


55F db / 51F dp / W=0.00793 lbs/lb
57F
8189 Btu/h

Winter Room Design Condition (TRW):


Heating Water Supply Temperature (THWS):
Winter Supply Air Temperature (TAIR,H ):
Winter Room Heating Requirement:

70F db / 50% RH
140F db
55F db
9212 Btu/h

Cooling Calculations
1. Quantify ventilation requirements according to ASHRAE 62-2010:
(4 people x 5 cfm) + (0.06 cfm/ft2 x 500 ft2) = 50 cfm
2. Calculate primary airflow rate to handle the latent cooling demand:
QLatent = Primary Air CFM (4840)(WRoom - WPrimary)
QLatent
Primary Air CFM =
4840 x (WRoom - WPrimary)
q = 500 gpm T
=
500 (gpm)

620 Btu/h
4840 x (0.00924 - 0.00793)

= 97.8 cfm

Primary air flow rate needed to condition latent load = 98 cfm.


3. Sensible load of primary air:
QS = 1.085 (98) (75F - 55F) = 2126 Btu/h
4. Temperature differences required to make cooling selection:
TAC = TRC - TCHS = 75F - 55F = 20F
TWC = TRC - TCHS = 75F - 57F = 18F
5. Capacities needed (two (2) units):
Primary Air = 49 cfm ea.
Total Capacity Needed = 8189 Btu/h / 2 = 4049 Btu/h ea.
Air Sensible Cooling = 2126 Btu/h / 2 = 1063 Btu/h ea.

15

YORK OVERHEAD ACTIVE CHILLED BEAM

Heating Calculations
1. Using two (2) 8 units:
Primary Air = 49 cfm ea. @ 55F db
Total Heating Needed = 9212 Btu/h / 2 = 4606 Btu/h
2. Deficit due to primary air:
QS = 1.085 (49 cfm)(55-70) = -797 Btu/h
3. Total heating needed from chilled beam:
QT = 4606 Btu/h + 797 Btu/h = 5403 Btu/h
4. Unit selection:
YK-OHACB-8 with A1 air nozzle will deliver cooling capacity of:
1241 Btu/h air side @ 57 cfm / 4095 Btu/h water side @ 0.95 gpm
YK-OHACB-8 with A1 air nozzle will deliver heating capacity of:
8105 Btu/h water side @ 0.95 gpm

Selection Summary
YORK Overhead Active Chilled Beam8
Unit Size
Length x Width:

8 x 24 / (2) 5 Connection

Room Conditions
Cooling:
Heating:

75F db / 50% RH
70F db / 50% RH

Primary Air
Cooling EAT:
Heating EAT:
Air Volume Needed:
Unit Air Pressure Drop:
Sound Level:

55F db / 55F dp
55 F db
98 cfm total / 49 cfm ea. unit
0.3 in. w.g.
15 NC

Cooling
Chilled Water EWT:
Chilled Water LWT:
Water Volume:
Water Pressure Drop:
Air Sensible Cooling:
Water Sensible Cooling:
Total Sensible Cooling:

57F
66F
0.95 gpm
1.14 ft. w.g.
1214 Btu/h
4095 Btu/h
5336 Btu/h

Heating
Hot Water EWT:
Hot Water LWT:
Water Flow:
Water Pressure Drop:
Air Heating Capacity:
Water Heating Capacity:
Total Heating Capacity:

140F
111F
0.63 gpm
1.8 ft. w.g.
-797 Btu/h
9279 Btu/h
8482 Btu/h

16

YORK OVERHEAD ACTIVE CHILLED BEAM

Guide Specifications
YORK Overhead Active Chilled Beams series active
chilled beams shall be used to compensate for external
and internal heat loads of a building, and shall maintain
thermal comfort in a room within specified comfort and
noise criteria.

Functional Description
Primary air will be supplied by the central air handling
unit to the chilled beam air plenum box. The primary
air shall then pass through the induction nozzles into
the mixing section to mix with the induced room air
before being distributed into the room by two slot
supply diffusers.
Induction nozzles shall induce air from the room
through the inlet air diffuser and then through the fin
and tube cooling/heating exchanger before mixing with
the primary air and being supplied to the room. The
size and quantity of induction nozzles shall be factory
installed to provide the required unit capacity with the
specified primary air flow, air inlet pressure and noise
level.
Heat exchangers shall be 2-pipe type for cooling only
or cooling/heating changeover systems or 4 pipe type
for systems with separate cooling and heating circuits.
The units shall incorporate two linear slot air supply
diffusers and shall be designed so that the supply
air is discharged horizontally across the ceiling using
the Coanda effect to increase air throw of the units
and ensure air mixing with the room air above the
occupied zone. The inlet air diffuser for the room
air shall be perforated or provided with linear bar air
inlet grille and shall be easily removable for cleaning
the heat exchanger and shall be provided with safety
hanging wires.

Construction of the Chilled Beam


The primary air plenum box shall be manufactured
from galvanized sheet steel and shall have one or
more round air connections. The plenum should
be internally insulated to prevent condensation if
the primary supply air temperature is less than the
surrounding air dew point.
The nozzle plate and chilled beam body shall be
manufactured from galvanized steel with a minimum
thickness of 22 ga. (0.8mm).
The heat exchangers shall be made from seamless
copper tubes with aluminum fins and shall have 1/2
or 5/8 (12mm or 15mm) diameter water connections
depending on unit size and connections. Heat
exchangers shall be suitable to operate at 250 psi
working pressure and shall be factory pressure tested
at 300 psi pressure.
The supply air diffuser and room air inlet diffuser
shall be manufactured from galvanized steel with
a minimum thickness of 20 ga. (1mm) and shall be
finished with polyester powder paint to RAL9010 with
20% gloss or with an alternative finish to be specified.
The active chilled beams shall be tested and rated in
accordance with Standard EN15116.

Installation
The active chilled beam shall include 9/32 (7mm)
diameter mounting holes for suspension by 1/4 (6mm)
diameter threaded rod or suspension wires.

17

Printed on recycled paper.