Sie sind auf Seite 1von 48

Standard Technical Specifications for Electrical Works

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


( Data Sheets )

Panels, Cubicles, Marshalling Boxes & Enclosures for


Control, Protection, Communication & Auxiliary Equipment

____________________________________________________________________________________
____

305661956.xls

Page 1 of 45

ADWEA/ADDC/AADC STANDARD : D-AAA-CUB


(Rev.0-2011)

____________________________________________________________________________________
____

305661956.xls

Page 2 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication
& Auxiliary Equipment

Table of Content
Page

1.00

GENERAL

A.

Protection (Free Standing Panels/Cubicles)

B.

Local (LCC) / Remote Control Panels/Cubicles

C.

Transformer AVR Panels/Cubicles

D.

Tele-Communication Panels/Cubicles, incl. Optic Heads/Termination Boxes

18

E.

Fire Fighting System Panels/Cubicles

20

F.

Air Conditioning System Panels/Cubicles

22

G.

Interface Panels/Cubicles

23

H.

Other Free-Standing Panels/Cubicles

25

I.

Other Wall-Mounted Cubicle / Marshalling Boxes

25

CONSTRUCTION DATA

26

A.

Indoor Type Panels/Cubicles, Marshalling Boxes

26

B.

Outdoor Type Cubicles/Panels, Marshalling Boxes

28

C.

Wiring

29

D.

Terminal Blocks

30

E.

Contactor

32

F.

Auxiliary Contactor

33

G.

MCB

33

H.

Strip Fuse Ways

33

I.

Indicator Lamps

34

J.

Push Buttons

34

K.

Selector Switch

34

L.

Ventilation *

35

M.

Anticondensing Heater

36

N.

Lighting (if applicable)

36

O.

Socket (if applicable)

37

P.

Cubicle Vermin Proof?

37

2.00

_________________________________________________________________________________________________________
____
305661956.xls

Page 2 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication
& Auxiliary Equipment

Table of Content
Page

Q.

Corrosion Protection Details

37

R.

Earthing Arrangement

38

S.

Danger Sign Details

38

T.

Identification Sign Details

39

U.

Lifting Devices Details (if applicable)

40

V.

Provision of Safety Equipment

40

W.

Pocket on Door for Drawings

40

X.

Door Fixing Devices Provided (to keep door in open position in case of
maintenance)

41

Y.

Door Locks and Keys

41

Z.

Stainless steel used for handles, hinges, signs,bolts, nuts, etc.

41

ELECTRICAL DATA

41

A.

Wiring

41

B.

Terminal Blocks

41

C.

Contactor

43

D.

Auxiliary Contactor

43

E.

MCB

43

F.

Fuses

44

G.

Indicator Lamps

44

H.

Push Buttons

44

I.

Selector Switch

44

J.

Ventilation Motor (if applicable)

44

K.

Anticondensing Heater

45

L.

Lighting (if applicable)

45

M.

Socket (if applicable)

45

3.00

_________________________________________________________________________________________________________
____
305661956.xls

Page 3 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication
& Auxiliary Equipment

Table of Content
Page

4.00

SUPPORTING DOCUMENTS

45

_________________________________________________________________________________________________________
____
305661956.xls

Page 4 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

1.00

GENERAL

A.

Protection (Free Standing Panels/Cubicles)

1.01

Manufacturer

1.01.1

name

1.01.2

country of manufacturing

1.02

Applicable standards

1.03

Housing material type

1.03.1

protection class (IEC 60529)

1.03.2

anti-corrosion treatment

1.03.3

hardware and metallic parts

1.03.4

walls

IEC

IP

54

inside

1.03.4.1
1.03.4.1.1

color

RAL

1.03.4.1.2

thickness

mm

outside

1.03.4.2
1.03.4.2.1

color

RAL

1.03.4.2.2

thickness

mm

1.04

Swing frame provided

1.05

Heat dissipation

yes/no

1.05.1

natural convection

yes/no

1.01.2

air flow

yes/no

1.06

TENDERED

7032/7035

yes

Panel access

1.06.1

front

yes/no

yes

1.06.2

rear (if applicable)

yes/no

yes

1.06.3

front door

1.06.3.1

opening minimum angle

deg

120

1.06.3.2

door switch

yes/no

yes

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 5 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

1.06.4

Internal lighting with socket

1.07

Dimensions

yes/no

TENDERED
yes

1.07.1

height

mm

2200

1.07.2

width

mm

800

1.07.3

depth

mm

800

1.07.3

wall thickness

mm

1.08

Cable entries

1.08.1

numbers

1.08.2

type

1.09

No.

Gland plate
material

1.09.1

hot-dip galvanised steel

1.09.1.1

min. thickness

1.09.1.1.1

aluminium

1.09.1.2

min. thickness

1.09.1.2.1

yes/no
mm
yes/no
mm

1.09.2

length

mm

1.09.3

width

mm

1.10

Gland

1.10.1

material

1.10.2

grade

1.11

brass

MCB`s (supervised) provided for:


AC

1.11.1
1.11.1.1

each Panel

Nos.

DC

1.11.2
1.11.2.1

each Panel at Main DC Board

Nos.

1.11.2.2

alarm / supervision

Nos.

1.11.2.3

each DC supply unit inside the Panel

Nos.

1.12

Reset button

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 6 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
location

1.12.1
1.12.1.1

TENDERED

outside the access door

Alarm Annunciators installed


16 windows for each bay

1.12.2

yes/no

yes

1.13

Weight

kg

1.14

Floor load (maximum)

daN/m2

600

1.15

Heater with thermostat provided

yes/no

yes

1.17

Earth plate with screw terminal connection

yes/no

yes

1.18

Lifting lugs

yes/no

yes

1.19

Electrical interference environment

1.19.2

insulation class

1.19.3

insulation resistance

1.19.4

dielectric strength, 50Hz, 1min.

B.

Local (LCC) / Remote Control Panels/Cubicles

1.20

Free-standing

1.20.1

Manufacturer

1.20.1.1

name

1.20.1.2

country of manufacturing

1.20.2

Applicable standards

1.20.3

Housing material type

1.20.3.1

protection class (IEC 60529)

1.20.3.2

anti-corrosion treatment

1.20.3.2.1

hardware and metallic parts

1.20.3.2.2

walls

1.20.3.2.2.

IEC

IP

inside

1.20.3.2.2

color

RAL

1.20.3.2.2

thickness

mm

1.20.3.2.2.

41

outside

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 7 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

1.20.3.2.2

color

RAL

1.20.3.2.2

thickness

mm

1.20.4

Swing frame provided

1.20.5

Heat dissipation

yes/no

1.20.5.1

natural convection

yes/no

1.20.5.2

air flow

yes/no

1.20.6

TENDERED

7032/7035

yes

Panel access

1.20.6.1

front

yes/no

yes

1.20.6.2

rear (if applicable)

yes/no

yes

1.20.6.3

front door

1.20.3.1

opening minimum angle

deg

120

1.20.3.2

door switch

yes/no

yes

yes/no

yes

1.20.6.4

Internal lighting with socket

1.20.7

Dimensions

1.20.7.1

height

mm

2200

1.20.7.2

width

mm

800

1.20.7.3

depth

mm

800

1.20.7.4

wall thickness

mm

1.20.8

Cable entries

1.20.8.1

numbers

1.20.8.2

type

1.20.9
1.20.9.1
1.20.1.1
1.20.1.1.1
1.20.1.2
1.20.1.2.1
1.20.9.2

No.

Gland plate
material
hot-dip galvanised steel
min. thickness
aluminium
min. thickness
length

yes/no
mm

yes/no
mm

mm

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 8 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
width

1.20.9.3

TENDERED

mm

Gland

1.20.10
1.20.10.1

material

1.20.10.2

grade

brass

MCB`s (supervised) provided for:

1.20.11

AC

1.20.11.1

each Panel

1.20.11.1.1

Nos.

DC

1.20.11.2
1.20.11.2.1

each Panel at Main DC Board

Nos.

1.20.11.2.2

alarm / supervision

Nos.

1.20.11.2.3

each DC supply unit inside the Panel

Nos.

Reset button

1.20.12

location

1.20.12.1

outside the access door

Alarm Annunciators installed

1.20.13

16 windows for each bay

1.20.13.1

yes/no

yes

1.20.14

Weight

kg

1.20.15

Floor load (maximum)

daN/m2

600

1.20.16

Heater with thermostat provided

yes/no

yes

1.20.17

Earth plate with screw terminal connection

yes/no

yes

1.20.18

Lifting lugs

yes/no

yes

1.20.19

Electrical interference environment

1.20.19.2

insulation class

1.20.19.3

insulation resistance

1.20.19.4

dielectric strength, 50Hz, 1min.

C.

Transformer AVR Panels/Cubicles

1.21

Free-standing

1.21.1

Manufacturer

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 9 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

1.21.1.1

name

1.21.1.2

country of manufacturing

1.21.2

Applicable standards

1.21.3

Housing material type

1.21.3.1

protection class (IEC 60529)

1.21.3.2

anti-corrosion treatment

1.21.3.2.1

hardware and metallic parts

1.21.3.2.2

walls

1.21.3.2.2.

IEC

IP

color

RAL

1.21.3.2.2

thickness

mm

outside

1.21.3.2.2

color

RAL

1.21.3.2.2

thickness

mm

1.21.4

Swing frame provided

1.21.5

Heat dissipation

yes/no

1.21.5.1

natural convection

yes/no

1.21.5.2

air flow

yes/no

1.21.6

54

inside

1.21.3.2.2

1.21.3.2.2.

TENDERED

7032/7035

yes

Panel access

1.21.6.1

front

yes/no

yes

1.21.6.2

rear (if applicable)

yes/no

yes

1.21.6.3

front door

1.21.3.1

opening minimum angle

deg

120

1.21.3.2

door switch

yes/no

yes

yes/no

yes

1.21.6.4

Internal lighting with socket

1.21.7

Dimensions

1.21.7.1

height

mm

2200

1.21.7.2

width

mm

800

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 10 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

1.21.7.3

depth

mm

1.21.7.4

wall thickness

mm

1.21.8

numbers

1.21.8.2

type

1.21.9.1
1.21.1.1

No.

Gland plate
material
hot-dip galvanised steel
min. thickness

1.21.1.1.1
1.21.1.2

aluminium
min. thickness

1.21.1.2.1

yes/no
mm

mm

length

mm

1.21.9.3

width

mm

material

1.21.10.2

grade

1.21.11.1
1.21.11.1.1

1.21.11.2

Gland

1.21.10.1

1.21.11

yes/no

1.21.9.2

1.21.10

800

Cable entries

1.21.8.1

1.21.9

TENDERED

brass

MCB`s (supervised) provided for:


AC
each Panel

Nos.

DC

1.21.11.2.1

each Panel at Main DC Board

Nos.

1.21.11.2.2

alarm / supervision

Nos.

1.21.11.2.3

each DC supply unit inside the Panel

Nos.

1.21.12
1.21.12.1
1.21.13
1.21.13.1
1.21.14

Reset button
location

outside the access door

Alarm Annunciators installed


16 windows for each bay
Weight

yes/no

yes

kg

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 11 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

TENDERED

1.21.15

Floor load (maximum)

daN/m2

600

1.21.16

Heater with thermostat provided

yes/no

yes

1.21.17

Earth plate with screw terminal connection

yes/no

yes

1.21.18

Lifting lugs

yes/no

yes

1.21.19

Electrical interference environment

1.21.19.2

insulation class

1.21.19.3

insulation resistance

1.21.19.4

dielectric strength, 50Hz, 1min.

1.22

Cubicles mounted at transformers

1.22.1

manufacturer

1.22.1.1

name

1.22.1.2

country of manufacturing

1.22.2

applicable standards

IEC

1.22.3

color

RAL

7032

1.22.4

dimensions

1.22.4.1

height

mm

800

1.22.4.2

width

mm

600

1.22.4.3

depth

mm

250

1.22.5

cable entries

1.22.6

gland plate

No.

1.22.6.1

material

1.22.6.2

length

mm

1.22.6.3

width

mm

1.22.6.4

min. thickness

mm

1.22.7

gland

1.22.7.1

material

1.22.7.2

grade

1.22.8

Hot-Dip galcanised steel

MCB`s provided for transformer control equipment

brass

yes/no

yes

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 12 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
reset button

1.22.9

location

1.22.9.1

outside the access door

1.22.10

Alarm Annunciators installed

yes/no

1.22.11

weight

kg

D.

TENDERED

yes

Tele-Communication Panels/Cubicles, incl. Optic Heads/


Termination Boxes

1.23

Free-standing

1.23.1

Manufacturer

1.23.1.1

name

1.23.1.2

country of manufacturing

1.23.2

Applicable standards

1.23.3

Housing material type

1.23.3.1

protection class (IEC 60529)

1.23.3.2

anti-corrosion treatment

1.23.3.2.1

hardware and metallic parts

1.23.3.2.2

walls

1.23.3.2.2.

IEC

IP

inside

1.23.3.2.2

color

RAL

1.23.3.2.2

thickness

mm

1.23.3.2.2.

outside

1.23.3.2.2

color

RAL

1.23.3.2.2

thickness

mm

1.23.4

Swing frame provided

1.23.5

Heat dissipation

yes/no

1.23.5.1

natural convection

yes/no

1.23.5.2

air flow

yes/no

1.23.6

54

7032/7035

yes

Panel access

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 13 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

TENDERED

1.23.6.1

front

yes/no

yes

1.23.6.2

rear (if applicable)

yes/no

yes

1.23.6.3

front door

1.23.3.1

opening minimum angle

deg

120

1.23.3.2

door switch

yes/no

yes

yes/no

yes

1.23.6.4

Internal lighting with socket

1.23.7

Dimensions

1.23.7.1

height

mm

2200

1.23.7.2

width

mm

800

1.23.7.3

depth

mm

800

1.23.7.4

wall thickness

mm

1.23.8

Cable entries

1.23.8.1

numbers

1.23.8.2

type

1.23.9
1.23.9.1
1.23.1.1

Gland plate
material
hot-dip galvanised steel
min. thickness

1.23.1.1.1
1.23.1.2

No.

aluminium
min. thickness

1.23.1.2.1

yes/no
mm
yes/no
mm

1.23.9.2

length

mm

1.23.9.3

width

mm

1.23.10

material

1.23.10.2

grade

1.23.11.1
1.23.11.1.1

Gland

1.23.10.1

1.23.11

brass

MCB`s (supervised) provided for:


AC
each Panel

Nos.

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 14 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

TENDERED

DC

1.23.11.2
1.23.11.2.1

each Panel at Main DC Board

Nos.

1.23.11.2.2

alarm / supervision

Nos.

1.23.11.2.3

each DC supply unit inside the Panel

Nos.

Reset button

1.23.12

location

1.23.12.1

outside the access door

1.23.13

Weight

kg

1.23.14

Floor load (maximum)

daN/m2

600

1.23.15

Heater with thermostat provided

yes/no

yes

1.23.16

Earth plate with screw terminal connection

yes/no

yes

1.23.17

Lifting lugs

yes/no

yes

1.23.18

Electrical interference environment

1.23.18.2

insulation class

1.23.18.3

insulation resistance

1.23.18.4

dielectric strength, 50Hz, 1min.

E.

Fire Fighting System Panels/Cubicles

1.24

Free-standing

1.24.1

Manufacturer

1.24.1.1

name

1.24.1.2

country of manufacturing

1.24.2

Applicable standards

1.24.3

Housing material type

1.24.3.1

protection class (IEC 60529)

1.24.3.2

anti-corrosion treatment

1.24.3.2.1

hardware and metallic parts

1.24.3.2.2

walls

1.24.3.2.2.

IEC

IP

54

inside

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 15 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

1.24.3.2.2

color

RAL

1.24.3.2.2

thickness

mm

outside

1.24.3.2.2.
1.24.3.2.2

color

RAL

1.24.3.2.2

thickness

mm

1.24.4

Swing frame provided

1.24.5

Heat dissipation

yes/no

1.24.5.1

natural convection

yes/no

1.24.5.2

air flow

yes/no

1.24.6

TENDERED

7032/7035

yes

Panel access

1.24.6.1

front

yes/no

yes

1.24.6.2

rear (if applicable)

yes/no

yes

1.24.6.3

front door

1.24.3.1

opening minimum angle

deg

120

1.24.3.2

door switch

yes/no

yes

yes/no

yes

1.24.6.4

Internal lighting with socket

1.24.7

Dimensions

1.24.7.1

height

mm

2200

1.24.7.2

width

mm

800

1.24.7.3

depth

mm

800

1.24.7.4

wall thickness

mm

1.24.8

Cable entries

1.24.8.1

numbers

1.24.8.2

type

1.24.9
1.24.9.1
1.24.1.1
1.24.1.1.1

No.

Gland plate
material
hot-dip galvanised steel
min. thickness

yes/no
mm

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 16 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
aluminium

1.24.1.2

min. thickness

1.24.1.2.1

TENDERED

yes/no
mm

1.24.9.2

length

mm

1.24.9.3

width

mm

Gland

1.24.10
1.24.10.1

material

1.24.10.2

grade

brass

MCB`s (supervised) provided for:

1.24.11

AC

1.24.11.1

each Panel

1.24.11.1.1

Nos.

DC

1.24.11.2
1.24.11.2.1

each Panel at Main DC Board

Nos.

1.24.11.2.2

alarm / supervision

Nos.

1.24.11.2.3

each DC supply unit inside the Panel

Nos.

Reset button

1.24.12

location

1.24.12.1

outside the access door

1.24.13

Weight

kg

1.24.14

Floor load (maximum)

daN/m2

600

1.24.15

Heater with thermostat provided

yes/no

yes

1.24.16

Earth plate with screw terminal connection

yes/no

yes

1.24.17

Lifting lugs

yes/no

yes

1.24.18

Electrical interference environment

1.24.18.2

insulation class

1.24.18.3

insulation resistance

1.24.18.4

dielectric strength, 50Hz, 1min.

F.

Air Conditioning System Panels/Cubicles

1.25

Free-standing

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 17 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.
1.25.1

REQUIRED
Manufacturer

1.25.1.1

name

1.25.1.2

country of manufacturing

1.25.2

Applicable standards

1.25.3

Housing material type

1.25.3.1

protection class (IEC 60529)

1.25.3.2

anti-corrosion treatment

1.25.3.2.1

hardware and metallic parts

1.25.3.2.2

walls

1.25.3.2.2.

IEC

IP

color

RAL

1.25.3.2.2

thickness

mm

outside

1.25.3.2.2

color

RAL

1.25.3.2.2

thickness

mm

1.25.4

Swing frame provided

1.25.5

Heat dissipation

yes/no

1.25.5.1

natural convection

yes/no

1.25.5.2

air flow

yes/no

1.25.6

54

inside

1.25.3.2.2

1.25.3.2.2.

TENDERED

7032/7035

yes

Panel access

1.25.6.1

front

yes/no

yes

1.25.6.2

rear (if applicable)

yes/no

yes

1.25.6.3

front door

1.25.3.1

opening minimum angle

deg

120

1.25.3.2

door switch

yes/no

yes

yes/no

yes

1.25.6.4

Internal lighting with socket

1.25.7

Dimensions

1.25.7.1

height

mm

2200

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 18 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

TENDERED

1.25.7.2

width

mm

800

1.25.7.3

depth

mm

800

1.25.7.4

wall thickness

mm

1.25.8

Cable entries

1.25.8.1

numbers

1.25.8.2

type

1.25.9
1.25.9.1
1.25.1.1

Gland plate
material
hot-dip galvanised steel
min. thickness

1.25.1.1.1
1.25.1.2

No.

aluminium
min. thickness

1.25.1.2.1

yes/no
mm
yes/no
mm

1.25.9.2

length

mm

1.25.9.3

width

mm

1.25.10

material

1.25.10.2

grade

1.25.11.1
1.25.11.1.1

1.25.11.2

Gland

1.25.10.1

1.25.11

brass

MCB`s (supervised) provided for:


AC
each Panel

Nos.

DC

1.25.11.2.1

each Panel at Main DC Board

Nos.

1.25.11.2.2

alarm / supervision

Nos.

1.25.11.2.3

each DC supply unit inside the Panel

Nos.

1.25.12
1.25.12.1

Reset button
location

outside the access door

1.25.13

Weight

kg

1.25.14

Floor load (maximum)

daN/m2

600

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 19 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

TENDERED

1.25.15

Heater with thermostat provided

yes/no

yes

1.25.16

Earth plate with screw terminal connection

yes/no

yes

1.25.17

Lifting lugs

yes/no

yes

1.25.18

Electrical interference environment

1.25.18.2

insulation class

1.25.18.3

insulation resistance

1.25.18.4

dielectric strength, 50Hz, 1min.

1.26

Wall-mounted (if applicable)

1.26.1

manufacturer

1.26.1.1

name

1.26.1.2

country of manufacturing

1.26.2

applicable standards

NFPA

1.26.3

color

RAL

7032

1.26.4

dimensions

1.26.4.1

height

mm

800

1.26.4.2

width

mm

600

1.26.4.3

depth

mm

250

1.26.5

cable entries

1.26.6

gland plate

No.

1.26.6.1

material

1.26.6.2

length

mm

1.26.6.3

width

mm

1.26.6.4

min. thickness

mm

1.26.7

Hot-Dip galcanised steel

gland

1.26.7.1

material

1.26.7.2

grade

1.26.8

MCCB`s provided for HVAC equipment

1.26.9

reset button

brass

yes/no

yes

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 20 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
location

1.26.9.1

weight

1.26.9

Interface Panels/Cubicles

1.27

Free-standing
Manufacturer

1.27.1.1

name

1.27.1.2

country of manufacturing

1.27.2

Applicable standards

1.27.3

Housing material type

1.27.3.1

protection class (IEC 60529)

1.27.3.2

anti-corrosion treatment

1.27.3.2.1

hardware and metallic parts

1.27.3.2.2

walls

1.27.3.2.2.

outside the access door


kg

G.

1.27.1

IEC

IP

color

RAL

1.27.3.2.2.

thickness

mm

outside

1.27.3.2.3.

color

RAL

1.27.3.2.3.

thickness

mm

1.27.4

Swing frame provided

1.27.5

Heat dissipation

yes/no

1.27.5.1

natural convection

yes/no

1.27.5.2

air flow

yes/no

1.27.6

54

inside

1.27.3.2.2.

1.27.3.2.3

TENDERED

7032/7035

yes

Panel access

1.27.6.1

front

yes/no

yes

1.27.6.2

rear (if applicable)

yes/no

yes

1.27.7

front door
deg

120

1.27.7.1

opening minimum angle

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 21 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.
1.27.7.2

REQUIRED
door switch

1.27.8

Internal lighting with socket

1.27.9

Dimensions

TENDERED

yes/no

yes

yes/no

yes

1.27.9.1

height

mm

2200

1.27.9.2

width

mm

800

1.27.9.3

depth

mm

800

1.27.9.4

wall thickness

mm

1.27.10

Cable entries

1.27.10.1

numbers

1.27.10.2

type

1.27.11
1.27.11.1
1.27.11.1.1

Gland plate
material
hot-dip galvanised steel
min. thickness

1.27.11.1.1
1.27.11.1.2

No.

aluminium
min. thickness

1.27.11.1.

yes/no
mm
yes/no
mm

1.27.11.2

length

mm

1.27.11.3

width

mm

1.27.12

Gland

1.27.12.1

material

1.27.12.2

grade

brass

1.27.13

Weight

kg

1.27.14

Floor load (maximum)

daN/m2

600

1.27.15

Heater with thermostat provided

yes/no

yes

1.27.16

Earth plate with screw terminal connection

yes/no

yes

1.27.17

Lifting lugs

yes/no

yes

1.27.18

Electrical interference environment

1.27.18.1

insulation class

1.27.18.2

insulation resistance

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 22 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
dielectric strength, 50Hz, 1min.

1.27.18.3
1.28

TENDERED

Wall-mounted
manufacturer

1.28.1
1.28.1.1

name

1.28.1.2

country of manufacturing

1.28.2

applicable standards

IEC

1.28.3

color

RAL

7032

1.28.4

dimensions

1.28.4.1

height

mm

800

1.28.4.2

width

mm

600

1.28.4.3

depth

mm

250

1.28.5

cable entries

1.28.6

gland plate

No.

1.28.6.1

material

1.28.6.2

length

mm

1.28.6.3

width

mm

1.28.6.4

min. thickness

mm

Hot-Dip galcanised steel

gland

1.28.7
1.28.7.1

material

1.28.7.2

grade
weight

1.28.8

H.

Other Free-Standing Panels/Cubicles

1.29

Applicable standards

1.30

Housing material type

1.30.1

protection class (IEC 60529)

1.30.2

anti-corrosion treatment

1.30.3

hardware and metallic parts

1.30.4

walls

brass

kg

IEC

IP

54

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 23 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
inside

1.30.4.1
1.30.4.1.1

color

RAL

1.30.4.1.2

thickness

mm

outside

1.30.4.2
1.30.4.2.1

color

RAL

1.30.4.2.2

thickness

mm

1.31

Swing frame provided

1.32

Heat dissipation

yes/no

1.32.1

natural convection

yes/no

1.32.2

air flow

yes/no

1.33

TENDERED

7032/7035

yes

Panel access

1.33.1

front

yes/no

yes

1.33.2

rear (if applicable)

yes/no

yes

1.33.3

front door

1.33.3.1

opening minimum angle

deg

120

1.33.3.2

door switch

yes/no

yes

yes/no

yes

1.34

Internal lighting with socket

1.35

Dimensions

1.35.1

height

mm

2200

1.35.2

width

mm

800

1.35.3

depth

mm

800

1.35.4

wall thickness

mm

1.35

Cable entries

1.35.1

numbers

1.35.2

type

1.36

No.

Gland plate

1.36.1
1.36.1.1

material
hot-dip galvanised steel

yes/no

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 24 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
min. thickness

1.36.1.1.1

aluminium

1.36.1.2

min. thickness

1.36.1.2.1

mm

mm

length

mm

1.36.3

width

mm

Gland

1.37.1

material

1.37.2

grade

1.38

yes/no

1.36.2

1.37

TENDERED

brass

MCB`s (supervised) provided for:


AC

1.38.1
1.38.1.1

each Panel

Nos.

DC

1.38.2
1.38.2.1

each Panel at Main DC Board

Nos.

1.38.2.2

alarm / supervision

Nos.

1.38.2.3

each DC supply unit inside the Panel

Nos.

1.39

Reset button
location

1.39.1
1.39.1.1

outside the access door

Alarm Annunciators installed


16 windows for each bay

1.39.2

yes/no

yes

1.40

Weight

kg

1.41

Floor load (maximum)

daN/m2

600

1.42

Heater with thermostat provided

yes/no

yes

1.43

Earth plate with screw terminal connection

yes/no

yes

1.44

Lifting lugs

yes/no

yes

1.45

Electrical interference environment

1.45.2

insulation class

1.45.3

insulation resistance

1.45.4

dielectric strength, 50Hz, 1min.

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 25 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

I.

Other Wall-Mounted Cubicle / Marshalling Boxes

1.46

Application

1.47

Manufacturer

1.47.1

name

1.47.2

country of manufacturing

1.48

Applicable standards

1.49

Color

1.50

Dimensions

TENDERED

RAL

7032

1.50.1

height

mm

800

1.50.2

width

mm

600

1.50.3

depth

mm

250

1.51

Cable entries

1.52

Gland plate

No.

1.52.1

material

1.52.2

length

mm

1.52.3

width

mm

1.52.4

min. thickness

mm

1.53

Gland

1.53.1

material

1.53.2

grade

1.54

Hot-Dip galcanised steel

brass

Reset button
location

1.54.1
1.54.2

Weight

2.00

CONSTRUCTION DATA

A.

Indoor Type Panels/Cubicles, Marshalling Boxes

2.01

Degree of protection

outside the access door


kg

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 26 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

TENDERED

2.01.1

Battery Chargers

IP

41

2.01.2

LVAC Distribution Board

IP

41

2.01.3

DC Distribution Board

IP

41

2.02

Corner posts

2.02.1

material

2.02.2

grade

2.02.3

applicable standards

IEC

60439-1

2.02.4

minimum thickness

mm

2.03

galvanised steel

Walls
material

2.03.1

galvanised steel

grade

2.03.1.1
2.03.2

applicable standards

IEC

60439-1

2.03.3

minimum thickness

mm

2.04

Roof
material

2.04.1

galvanised steel

grade

2.04.1.1
2.04.2

applicable standards

IEC

60349-1

2.04.3

minimum thickness

mm

2.05

Doors

2.05.1
2.05.1.1

material

galvanised steel

grade

2.05.2

applicable standards

IEC

6039-1

2.05.3

minimum thickness

mm

2.05.4

transparent glass window provided

2.05.4.1

yes

seize

2.05.4.1.1

length

mm

1600

2.05.4.1.2

width

mm

450

2.05.5

door stoppers provided

yes

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 27 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
door opening minimum angle

2.05.6
2.06

deg

TENDERED
120

Equipment mounting plates


material

2.06.1

galvanised steel sheet

grade

2.06.1.1
2.06.2

applicable standards

IEC

60439-1

2.06.3

minimum thickness

mm

2.07

Partition (if applicable)


material

2.07.1

galvanised steel sheet

grade

2.07.1.1
2.07.2

applicable standards

IEC

60349-1

2.07.3

minimum thickness

mm

2.08

Panel access

2.08.1

front

yes/no

yes

2.08.2

rear (if applicable)

yes/no

yes

2.09

Maximum inside temperature of cubicle

2.10

Lifting lugs provided

yes/no

B.

Outdoor Type Cubicles/Panels, Marshalling Boxes

2.10

Applicable Standards

IEC

2.11

Degree of protection

IP

2.12

Corner posts
material

2.11.1

minimum thickness

2.11.2

yes

61069
55W

galvanised steel sheet

mm

Walls

2.13.1
2.13.1.1

material

stainless steel

grade

1.4301 (V2A)

minimum thickness

2.13.2
2.14

55

grade

2.11.1.1

2.13

mm

1.5

Roof

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 28 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

2.14.1
2.14.1.1

2.15

material

stainless steel

grade

1.4301 (V2A)

minimum thickness

2.14.2

TENDERED

mm

1.5

Doors

2.15.1
2.15.1.1

material

stainless steel

grade

1.4301 (V2A)

2.15.2

minimum thickness

mm

2.15.3

door stoppers provided

yes/no

yes

2.15.4

door opening angle

deg

120

2.16

Sun shade

2.16.1
2.16.1.1

material

stainless steel

grade

1.4301 (V2A)

2.16.2

minimum thickness

mm

2.16.3

minimum clearance to cubicle wall

mm

15

2.17

Equipment mounting plates


material

2.17.1

grade

2.17.1.1
2.17.2

applicable standards

2.17.3

minimum thickness

2.18

mm

Partition (if applicable)


material

2.18.1

galvanised steel sheet

grade

2.18.1.1

minimum thickness

2.18.2
2.19

galvanised steel sheet

mm

1.5

Panel access

2.09.1

front

yes

2.09.2

rear (if applicable)

yes

2.20

Maximum inside temperature of cubicle

2.21

Lifting lugs provided

yes/no

55
yes

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 29 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

C.

Wiring

2.21

Material
stranded copper wires for cross-sections
>2.5mm2 else solid copper wires

2.21.1
2.22

TENDERED

yes/no

yes

Cross-sections

2.22.1

power circuits (min)

mm2

1.5

2.22.2

control circuits

mm2

2.22.3

CT circuits (min)

mm2

2.5

2.22.4

VT circuits (min)

mm2

1.5

2.22.5

Telecommunication/control/protection connections

2.22.5.1

external wiring

mm2

1.5

2.22.5.2

other wiring

mm2

0.5

2.23

Arrangement
Telecommunication/control/protection connections

2.23.1
2.24

screened pairs

Colors
control circuits

2.24.1
2.24.1.1

black

yes/no

2.24.1.2

grey

yes/no

D.

Terminal Blocks

2.25

Manufacturer

2.25.1

name

2.25.2

country of manufacturing

2.25.3

catalogue number

2.26

Applicable standards or equivalent

2.27

Type

IEC

2.27.1

clamping yoke

yes/no

2.27.2

plu-in spring clamp

yes/no

60947-7-1

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 30 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

2.28

Color

2.29

Dimensions (of one terminal)

beige

2.29.1

length

mm

2.29.2

width

mm

2.29.3

height

2.29.3.1

Type 1

mm

2.29.3.2

Type 2

mm

2.29.3.3

Type 3

mm

2.30

Material

2.30.1

type

2.30.2

UV stabilised
applicable standards

2.30.2.1

TENDERED

polyamide
PA

IEEE

G53/26/23

flammability grade

2.30.3
2.30.3.1

applicable standards

2.30.3.2

class

UL

94
5V or V0

2.31

Maximum continuous working temperature

2.32

Short-time temperature rise (IEC 60216)

2.33

Cable size to be terminated

120

200

2.33.1

minimum

mm2

0.5

2.33.2

maximum

mm2

10

10

2.34

Spare terminals

2.35

Terminal Marking

2.35.1

Color of letters

2.35.2

Power Circuits (motors, etc.)

black on white

2.35.2.1

Phase R

R on red ground

2.35.2.2

Phase Y

Y on yellow ground

2.35.2.3

Phase B

B on blue ground

2.35.2.4

Neutral

NP on black ground

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 31 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
Earthing Conductor

2.35.2.5

TENDERED

PE on green ground

Current Transformer Circuits (according to IEC)

2.35.3
2.35.3.1

Phase R

on red ground

2.35.3.2

Phase Y

on yellow ground

2.35.3.3

Phase B

on blue ground

Voltage Transformer Circuits (according to IEC)

2.35.4
2.35.4.1

Phase R

on red ground

2.35.4.2

Phase Y

on yellow ground

2.35.4.3

Phase B

on blue ground

110 Vdc Circuits

2.35.5
2.35.5.1

Positive

P on green ground

2.35.5.2

Negative

N on grey ground

2.36

Isolation links provided

yes/no

yes

2.37

Testing sockets provided

yes/no

yes

2.38

Arresters are provided

2.38.1

telephone cores

yes/no

yes

2.38.2

protection cores

yes/no

no

2.39

Isolation transformers provided

2.39.1

protection cores

yes/no

2.39.2

control cores

yes/no

2.40

Short-circuit facilities provided for CT terminals

yes/no

yes

2.41

Easily accessible from the floor level

yes/no

yes

2.42

Minimum numbers of terminals

2.42.1

protection cubicle

2.42.1.1

protection

No.

2.40.1.2

control

No.

2.42.2

local/remote control

No.

2.42.3

local/remote control (transformer)

No.

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 32 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

TENDERED

marshalling cubicle for 17 pair protection/


telephone cable

2.42.4

2.42.4.1

protection

No.

12

2.42.4.2

telephone

No.

30

2.42.5

AC Distribution

No.

2.42.6

DC Distribution

No.

2.42.7

battery chargers, voltage control units

No.

2.42.8

uninterruptable power supply (UPS)

No.

2.42.9

tele-communication

No.

2.42.10

fire fighting

No.

2.42.11

air conditioning

No.

2.42.12

interfacings

No.

2.42.13

other free-standing cubicle

No.

2.42.14

other wall-mounted cubicle

No.

2.43

Mounting rail

2.43.1

type

2.43.2

applicable standards

2.44

TS 35 x 15mm
DIN EN

46277

Min. clearances

2.44.1

between two rows of terminal blocks

mm

150

2.44.2

between first row and the cable gland plate

mm

250

No.

E.

Contactor

2.45

Manufacturer

2.45.1

name

2.45.2

country of manufacturing

2.45.3

catalogue number

2.46

Applicable standards or equivalent

2.47

Type

2.48

Number of poles

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 33 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

2.49

Lifetime operation under rated current switching

F.

Auxiliary Contactor

2.50

Manufacturer

2.50.1

name

2.50.2

country of manufacturing

2.50.3

catalogue number

No.

2.51

Applicable standards or equivalent

2.52

Type

2.53

Number of poles

No.

2.54

Lifetime operation under rated current switching

No.

G.

MCB

2.55

Manufacturer

2.55.1

name

2.55.2

country of manufacturing

2.55.3

catalogue number

2.56

Applicable standards

2.57

Type

H.

Strip Fuse Ways

2.58

Manufacturer

2.58.1

name

2.58.2

country of manufacturing

2.58.3

catalogue number

2.59

Applicable standards or equivalent

2.60

Type

2.61

Fuses

2.61.1

IEC

TENDERED

100,000

100,000

60947-2
molded case

IEC

60269-1

Manufacturer

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 34 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

2.61.1.1

name

2.61.1.2

country of manufacturing

2.61.1.3

catalogue number

2.62

Applicable standards or equivalent

2.63

Type

2.64

Fuse supervision provided

I.

Indicator Lamps

2.65

Manufacturer

2.65.1

name

2.65.2

country of manufacturing

2.65.3

catalogue number

2.66

Applicable standards or equivalent

2.67

Type

2.68

IEC

yes/no

TENDERED

60269-1

yes

IEC

60983, 61554

Minimum diameter

mm

16

2.69

Lamps are panel mounting type

yes/no

yes

2.70

Lamps are filament type

yes/no

yes

2.71

Lamps have translucent covers

yes/no

yes

J.

Push Buttons

2.72

Manufacturer

2.72.1

name

2.72.2

country of manufacturing

2.72.3

catalogue number

2.73

Applicable standards or equivalent

2.74

Type

2.75

IEC

60629, 61554

Minimum diameter

mm

16

2.76

Push button is push to actuate type

yes/no

2.77

Contacts

yes

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 35 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

2.77.1

silver

yes/no

2.77.2

silver alloy

yes/no

K.

Selector Switch

2.78

Manufacturer

2.78.1

name

2.78.2

country of manufacturing

2.78.3

catalogue number

TENDERED

2.79

Applicable standards or equivalent

2.80

Type

2.81

Switch is panel mounted rotary type

yes/no

yes

2.82

Switch is with oval handle

yes/no

yes

2.83

Contacts are spring assisted

yes/no

yes

2.84

Voltmeter switch has 4 stayput positions

yes/no

yes

L.

Ventilation *

2.85

Fans (if applicable)

2.85.1

name

2.85.1.2

country of manufacturing

2.85.1.3

catalogue number

2.85.2

applicable standards or equivalent

2.85.3

type

2.85.4

MCB for fans

IEC

manufacturer

2.85.4.1.1

name

2.85.4.1.2

country of manufacturing

2.85.4.1.3

catalogue number

2.85.4.2

61058, 61554

manufacturer

2.85.1.1

2.85.4.1

IEC

applicable standards or equivalent

IEC

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 36 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

2.85.4.3

type

2.85.4.4

no. of poles

2.86

TENDERED

molded case
1

Louvers (if applicable)


manufacturer

2.86.1
2.86.1.1

name

2.86.1.2

country of manufacturing
* heat dissipation calculation of equipment inside panel/cubicle
shall be submitted for approval!

M.

Anticondensing Heater

2.87

Manufacturer

2.87.1

name

2.87.2

country of manufacturing

2.87.3

catalogue number

2.88

Applicable standards or equivalent

2.89

Type

2.90

Control system
thermostat

2.90.1

setting

2.90.1.1

humidistat

2.90.2

yes/no
C

yes/no

yes
20 to 80
yes

setting

2.90.2.1
2.91

IEC

MCB for anticondensing heater

2.91.1

manufacturer

2.91.1.1

name

2.91.1.2

country of manufacturing

2.91.1.3

catalogue number

2.91.2

applicable standards or equivalent

2.91.3

type

2.91.4

no. of poles

IEC
molded case
1

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 37 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

N.

Lighting (if applicable)

2.92

Manufacturer

2.92.1

name

2.92.2

country of manufacturing

2.92.3

catalogue number

2.93

Applicable standards or equivalent

2.94

Type
electronic/HF switched type

2.94.1

TENDERED

IEC
florescent
yes/no

yes

2.95

Door switch provided

yes/no

yes

2.96

MCB for lighting

yes/no

yes

manufacturer

2.96.1
2.96.1.1

name

2.96.1.2

country of manufacturing

2.96.1.3

catalogue number

2.96.2

applicable standards or equivalent

2.96.3

type

2.96.4

no. of poles

O.

Socket (if applicable)

2.97

Manufacturer

2.97.1

name

2.97.2

country of manufacturing

2.97.3

catalogue number

2.98

Applicable standards or equivalent

2.99

Type

2.100

RCCB for socket

2.100.1

IEC
molded case
1

BS

1363
cubicle mounted

yes/no

yes

manufacturer

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 38 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

2.100.1.1

name

2.100.1.2

country of manufacturing

2.100.1.3

catalogue number

2.100.2

applicable standards or equivalent

2.100.3

type

2.100.4

no. of poles

P.

Cubicle Vermin Proof?

Q.

Corrosion Protection Details

R.

Earthing Arrangement

2.101

Earth bar of each compartment

2.101.1

material

2.101.2

minimum cross-section

2.101.3

dimension

TENDERED

BS
molded case
1
yes/no

yes
as per requirement
specified in standard
technical specification
part: D-AA-CORR

copper
mm2

2.101.3.1

width

mm

2.101.3.2

height

mm

40

2.102

Interconnection between compartments, etc.

2.102.1

material

2.102.2

minimum cross-section

2.103

stranded copper
mm2

70

Door earthing

2.103.1

material

2.103.2

cross-section

2.103.3

color

2.104

Number of connections for external earthing

2.105

Gland earthing

highly flexible
stranded copper
mm2

16
green-yellow

No.

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 39 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

2.105.1

material

2.105.2

minimum cross-section

TENDERED

stranded copper
conductor
mm2

120

S.

Danger Sign Details

2.106

Material

stainless steel

grade

1.4301 (V2A)

2.106.1
2.107

Width

mm

2.108

Height

mm

2.109

Language
Arabic and English

2.109.1
2.110

yes

Letters

2.110.1

quality of paint

2.110.2

height of letters

2.111

yes/no

sun light proof, no fading


mm

75

Colors

2.111.1

MV cubicles

2.111.1.1

background

2.111.1.2

letters

2.111.2

white

AC distribution cubicles

2.111.2.1

background

2.111.2.2

letters

2.111.3

red

yellow
black

DC distribution cubicles

2.111.3.1

background

white

2.111.3.2

letters

black

2.111.4

protection cubicles

2.111.4.1

background

2.111.4.2

letters

2.111.5
2.111.5.1

white
red

emergency system cubicles


background

red

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 40 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
letters

2.111.5.2
2.112

TENDERED

white

Fixing bolts

2.112.1
2.112.1.1

material

stainless steel

grade

1.4301 (V2A)

2.113

Numbers

T.

Identification Sign Details

2.114

Material

stainless steel

grade

1.4301 (V2A)

2.114.1

No.

2.115

Width

mm

2.116

Height

mm

2.117

Language
Arabic and English

2.117.1
2.118

Letters

2.118.1

quality of paint

2.118.2

height of letters

2.119

yes

sun light proof, no fading


mm

75

Colors

2.119.1

MV cubicles

2.119.1.1

background

2.119.1.2

letters

2.119.2

white

AC distribution cubicles

2.119.2.1

background

2.119.2.2

letters

2.119.3

red

yellow
black

DC distribution cubicles

2.119.3.1

background

white

2.119.3.2

letters

black

2.119.4
2.119.4.1

protection cubicles
background

white

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 41 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED
letters

2.119.4.2

red

emergency system cubicles

2.119.5
2.119.5.1

background

2.119.5.2

letters

2.120

TENDERED

red
white

Fixing bolts

2.120.1
2.120.1.1

material

stainless steel

grade

1.4301 (V2A)

2.121

Numbers

U.

Lifting Devices Details (if applicable)

2.122

Free-standing cubicle

No.

number

2.122.1

V.

Provision of Safety Equipment

2.123

Shock treatment chart

yes/no

yes

W.

Pocket on Door for Drawings

yes/no

yes

2.124

Material

X.

Door Fixing Devices Provided (to keep door in


open position in case of maintenance)

yes/no

yes

Y.

Door Locks and Keys

yes/no

yes

2.125

Manufacturer

2.125.1

name

2.125.2

country of manufacturing

2.126

Keys numbers for any lock or padlock

Z.

Stainless steel used for handles, hinges, signs,


bolts, nuts, etc.

2.127

Grade

galvanised steel

YALE or equivalent

No.

1.4301 (V2A)

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 42 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

3.00

ELECTRICAL DATA

A.

Wiring

3.01

Power frequency withstand voltage

B.

Terminal Blocks

3.02

Material

kV ac/1min

3.02.1

applicable standards

IEC
IEC
IEC
DIN VDE

3.02.2

dielectric strength

kV/cm

3.02.3

surface resistance

x cm

3.03

TENDERED

60093
60167
60112
0303-2
8
10^12

Nominal Voltage

3.03.1

type 1

800

3.03.2

type 2

400

3.03.3

type 3

800

3.03.4

type 4

400

3.03.5

type 5

800

3.03.6

type 6

800

3.04

Nominal Currents

3.04.1

type 1

41

3.04.2

type 2

16

3.04.3

type 3

76

3.04.4

type 4

57

3.04.5

type 5

57

3.04.6

type 6

101

3.05

Rated surge voltage

3.05.1

type 1

kVac

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 43 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

TENDERED

3.05.2

type 2

kVac

3.05.3

type 3

kVac

3.05.4

type 4

kVac

3.05.5

type 5

kVac

3.05.6

type 6

kVac

kVac

15

3.06

Power frequency withstand voltage between


terminals

3.06.1

protection cubicle

3.06.2

marshalling cubicle for 17 pair protection/


telephone cable

3.06.2.1

protection terminals

kVac

15

3.06.2.2

telephone terminals

kVac

15

3.06.2.3

surge arrester magazine base and terminals


without arresters

kVac

15

3.06.3

local/remote control cubicle

kVac

3.06.4

local/remote control (transformer) cubicle

kVac

3.06.5

AC distribution cubicle

kVac

3.06.6

DC distribution cubicle

kVac

3.06.7

battery chargers, voltage control cubicle

kVac

3.06.8

uninterruptable Power Supply (UPS) cubicle

kVac

3.06.9

tele-communication cubicle

kVac

3.06.10

fire fighting cubicle

kVac

3.06.11

air conditioning cubicle

kVac

3.06.12

interfacings cubicle

kVac

3.06.13

other free-standing cubicle

kVac

3.06.14

other wall-mounted cubicle

kVac

C.

Contactor

3.07

Rated voltages

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 44 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

TENDERED

3.07.1

main contacts

Vac

400

3.07.2

control contacts

Vdc

110

3.08

Limits of operation

3.08.1

supply voltage variation

+/- 10

3.08.2

supply frequency variation

+/- 5

3.08.3

drop out voltage

3.09

Rated breaking capacity

kA

3.10

Rated making capacity

kA

3.11

Rated thermal capacity

kA

3.12

Coil

3.12.1

rated voltage

Vdc

3.12.2

burden

VA

D.

Auxiliary Contactor

3.13

Coil

3.13.1

rated voltage

Vdc

3.13.2

burden

VA

3.14

Number of contacts

E.

MCB

3.15

Rated voltage

Vac

3.16

Rated current carrying at max. 50 0C

3.17

Rated short-circuit current, 1s

kA

3.18

Rated breaking current

3.19

Rated making current

F.

Fuses

3.20

Rated voltage

3.21

Rated minimum breaking current

2NO+2NC

Vac

230

230

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 45 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

3.21.1

type 1

3.21.2

type 2

3.21.3

type 3

G.

Indicator Lamps

3.22

Rated voltage

H.

Push Buttons

3.23

Rated voltage

TENDERED

110 +10%-15%

3.23.1

AC

230

3.23.2

DC

220

3.24

Rated make, continuously, break current

3.24.1

AC, pf = 0.5

10

3.24.2

DC

10

10

I.

Selector Switch

3.25

Contact ratings for continuos duty, pf = 0.5

3.26

Rated voltage

Vac

230

J.

Ventilation Motor (if applicable)

3.27

Rated voltage

3.27.1

AC

230

3.27.2

DC

110

3.28

Rated power

3.29

MCB for fans


rated current

3.29.1

K.

Anticondensing Heater

3.30

Rated voltage

Vac

3.31

Rated current

230

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 46 of 45

PANELS, CUBICLES, MARSHALLING BOXES & ENCLOSURES


Panels, Cubicles, Marshalling Boxes & Enclosures for Control, Protection, Communication & Auxiliary Equipment
Sl. No.

REQUIRED

3.32

Power

3.33

MCB for anticondensing heater


rated current

3.33.1

TENDERED
70

L.

Lighting (if applicable)

3.34

Rated voltage

Vac

230

3.35

Rated power

40

3.36

MCB for lighting

yes/no

rated current

3.36.1

yes
6

M.

Socket (if applicable)

3.37

Rated voltage

Vac

230

3.38

RCCB for socket

yes/no

yes

rated current

3.38.1

16

4.00

SUPPORTING DOCUMENTS

4.01

Technical literature enclosed

yes/no

yes

4.02

Standard conditions of installation enclosed

yes/no

yes

4.03

Relevant drawings enclosed

yes/no

yes

TENDERER`s STAMP SIGNATURE


___________________________________________________________________________________________________________________
305661956.xls
Page 47 of 45