interchanger, it warms the cold water proceeding from the pipeline attack of
distribution net and returns to realize its tour towards the solar collectors. Due to
the fact that the water will be destined for human consumption, the necessary
conditions will be born in mind as for quality and temperature. The installation
will have accumulators stored in warehouses to 60C, and later there will be
cooled even 45C that is the average temperature of consumption. In case of not
reaching the suitable temperature due to the fact that the solar warming is
insufficient, since it can happen in the winter months, it will be endowed to the
installation of a gas boiler of 64kW of power.
The building will have a water evacuation net that will evacuate all the waste
water and rain. The waste water is formed by secondhand waters (proceeding
from wash-basins, bidets, showers ) and fecal waters. These will go towards
the vertical pipelines across the boat siphons. To gather the rain waters there
will be installed a set of 6 sinks in the cover of the building and one in the
terrace that they will go direct to the vertical pipeline of rain water.
Once gathered all the waters will be mixed in the placed sinks contiguous to the
pilars of the building under the basement and by the horizontal collectors they
will be proceed to the total evacuation towards the municipal sewer net.
The installation of heating will realize using of thermal issuers that there will be
calculated depending on the thermal demand of every dependence of the
building depending on the types of closings that they shape them according to
the CTE DB-SU, and the RITE. The water will warm up in a gas boiler of 96
kW (20 superior % to the necessary one to suppose possible losses or
unexpected) and it will be distributed to every radiator realizing an installation
in bitubular circuit to avoid losses in its tour.
The electric power supply will be realized by the company Sevillana-Endesa to
a tension of 400 V and 50 Hz, in BT due to the fact that the total power of the
building is of 200 kW. It will be installed a General Box of Protection in the
front of the building, from where the lines of nourishment will depart to the
General Pictures of the basement, the first and second floor. Each of them are
provided with differential protections and thermical breakers, for the
distribution lines to every secondary picture.
MEMORIA
249
Junio 2008
248
Junio 2008
247
Junio 2008
246
Junio 2008
245
http://www.soliclima.com
http://www.asif.org/
http://www.top50solar.nl/solar_es
http://www.alfalaval.com/digitalassets/2/file35087_8_PC68209
ES.pdf
http://www.uib.es/facultat/ciencies/prof/victor.martinez/assig
natures/ofitec/practiques/IT-TYFOCOR-LS_es.pdf
Junio 2008
244
Direcciones de Internet:
www.merlingerin.es/
www.ebara.es
www.voltium.es
www.viessmann.es
www.wagner-solar.com
www.ferrolli.es
www.solarweb.net/forosolar/solar-termica/
www.grundfos.es
www.geoteknia.es
www.roca.es
http://www.codigotecnico.org/index.php?id=33
www.lapesa.es
http://www.construnario.com/diccionario/
http://rj-ingenieros.com
Junio 2008
243
3.2.- Bibliografa
Cdigo Tcnico de la Edificacin Febrero de 2008. Texto
modificado por RD 1371/2007, de 19 de octubre (BOE 23/10/2007) y
correccin de errores (BOE 25/01/2008)
Junio 2008
242
Tabla 5- 16: Seccin mnima del conductor de neutro en funcin de la seccin de los conductores
de fase.[ITC-BT-07]
Tabla 5- 17.- Dimetro mnimo del tubo en funcin de la seccin de los conductores de fase. [ITCBT-14]
Junio 2008
241
3.1.- Tablas
Tabla 5- 15.- Intensidad mxima admisible, en amperios, en servicio permanente para cables con
conductores de cobre en instalacin al aire en galeras ventiladas (temperatura ambiente 40C).
[ITC-BT-07]
Junio 2008
240
3.- ANEXOS
Junio 2008
239
Junio 2008
238
RT =
a
L
a
V
= 2
= 0,2
500
=2,13
47
500
= 4,65
215
RH RC
2,13 4,65
=
= 1,46
RH + RC 2,13 + 4,65
Junio 2008
237
200000
3 400 0.9
= 320 A
u (V ) =
PL
K S U
P: potencia kW
L: longitud en metros
K.: conductividad del cobre (56)
S: seccin del conductor ( mm 2 )
U: tensin (400 V)
Se considerar una cada de tensin mxima del 0,5%.
2.3.- Protecciones:
El interruptor magneto-trmico y diferencial estarn ubicados lo
ms cerca posible del punto de entrada de la derivacin individual, en la
dependencia a la que suministra.
Para determinar su intensidad nominal se utilizar potencia
elctrica del circuito y la intensidad mxima admisible de la canalizacin
segn la Norma UNE 460/5-523.
Se debe cumplir:
I SC I N I CA
Icd 1,45I CA
Junio 2008
236
Cada de tensin
u (V ) =
PL
K S U
u (%) =
u 100
U
P: potencia kW
L: longitud en metros
K.: conductividad del cobre (56)
S: seccin del conductor ( mm 2 )
U: tensin (400 V)
a transportar.
Junio 2008
235
P
U cos
P: Potencia kW
U: tensin (230 V)
cos : factor de potencia
Cada de tensin:
u (V ) =
2PL
K S U
u (%) =
u 100
U
P: potencia kW
L: longitud en metros
K.: conductividad del cobre (56)
S: seccin del conductor ( mm 2 )
U: tensin (230 V)
Circuitos trifsicos
Intensidad:
I=
P
3 U cos
P: Potencia kW
U: tensin (400 V)
cos : factor de potencia
Junio 2008
234
2.- CLCULOS
JUSTIFICATIVOS
Junio 2008
233
1.9.- Conclusin
Con la presente Memoria, Clculos y Planos que se acompaan,
doy por concluido el estudio de la Instalacin, que ser ejecutada por el
Instalador Autorizado, segn lo indicado y de acuerdo a las Normas
vigentes.
Junio 2008
232
Junio 2008
231
Consideraciones generales:
Los conductores de proteccin se fabricarn de cobre al igual que
el material empleado para las fases de conexin.
En los casos en que el conductor de proteccin es comn a varios
circuitos, la seccin del mismo se dimensiona teniendo en cuenta la mayor
seccin de los conductores de fase.
Estarn dotados de una proteccin contra deterioros mecnicos,
qumicos y electroqumicos y contra los esfuerzos electrodinmicos.
Las conexiones sern accesibles para la verificacin y ensayos.
Ningn aparato deber ser intercalado en el conductor de
proteccin, aunque para los ensayos podrn utilizarse conexiones
desmontables mediante tiles adecuados.
Las masas de los equipos a unir con los conductores de
proteccin no se conectarn en serie en serie en un circuito de proteccin.
1.8.5.-Resistencia de tierra
Los electrodos se dimensionarn de tal forma que su resistencia de
tierra, en cualquier circunstancia previsible, no sea superior al valor
especificado para ella, en cada caso, tal y como se indica en la Instruccin
ITC-BT-18, en su apartado 9.
Este valor de resistencia de tierra ser tal que cualquier masa no
pueda dar lugar a tensiones de contacto superior a:
- 24 V en local o emplazamiento conductor.
- 50 V en los dems caso.
Junio 2008
230
Junio 2008
229
Junio 2008
228
Junio 2008
227
Junio 2008
STANO
226
CZC SOT
alumbrado1
3x 1,5
XLPE
alumbrado2
3x 1,5
XLPE
emergencia
3x 1,5
XLPE
fuerza1
3x 2,5
XLPE
C ACS
caldera (ACS)
3x 1,5
XLPE
intercambiador (ACS)
3x 1,5
XLPE
Bomba llenado(x2)
(ACS)
3x 1,5
XLPE
bombas(x3) (ACS)
3x 1,5
XLPE
C, EVAC
bomba(evac)
3x 1,5
XLPE
C . VENT
bomba(ventilac)
3x 1,5
XLPE
C. CALEF
bomba(calef)
3x 1,5
XLPE
caldera(calef)
3x 1,5
XLPE
C,.PUERTA
puerta
3x 1,5
XLPE
Tabla 5- 11.- Tubos empotrados cuadros stano
16
16
16
20
16
16
16
16
16
16
16
16
16
CUADROS
GENERALES
P.2
S
TUBOS
conductor
mm^2
mm
CH2-CG2
3x 6
XLPE
25
CZC2-CG2
3x 4
XLPE
25
P.1
CH1-CG1
3x 6
XLPE
25
ch16/CH16-CG1
3x 2,5
XLPE
20
CH17-CG2
3x 4
XLPE
25
CZC1-CG1
3x 10
XLPE
75
P.baja
CZC1-Cgbaja
3x 16
XLPE
75
CZC2-Cgbaja
3x 6
XLPE
20
cocina-Cgbaja
3x 16
XLPE
75
Stano
C.ACS-Cgsot
3x 4
XLPE
25
Tabla 5- 12.- Tubos empotrados de lneas de alimentacin cuadros generales
ASCEN.
CONDUCTOR
S(mm^2)
6
aislam
XLPE
TUBOS
diam
25
CG2-CGBT
5x50
XLPE
125
CG1-CGBT
5x 35
XLPE
110
CGbaja-CGBT
5x 16
XLPE
75
CG sot-CGBT
5x 6
XLPE
25
ASC-CGBT
5x 10
XLPE
75
Tabla 5- 13.- Tubos empotrados de cuadros generales a CGBT
Junio 2008
PLANTA 1
CH1
alumbrado
fuerza(x7)
CH15
alumbrado
fuerza(x7)
CH16
alumbrado
fuerza(x3)
CH17
alumbrado
fuerza(x5)
CZC1
alumbrado1
alumbrado2
fuerza(x7)
fuerza (x6)
emergencia
225
3x 1,5
3x 2,5
XLPE
XLPE
16
20
3x 1,5
3x 2,5
XLPE
XLPE
16
20
3x 1,5
3x 2,5
XLPE
XLPE
16
20
3x 1,5
3x 2,5
XLPE
XLPE
16
20
3x 2,5
3x 2,5
3x 2,5
3x 2,5
3x 1,5
XLPE
XLPE
XLPE
XLPE
XLPE
20
20
20
20
16
PLANTA
BAJA
CZC B1
alumbrado 1
alumbrado2
fuerza1(x7)
fuerza2(x6)
fuerza3(x5)
CZC B2
alumbrado1
alumbrado2
fuerza(x6)
fuerza(x5)
emergencia
COCINA
coc/horno
lavadora/lavavj
secadora
alumbrado
fuerza(x6)
fuerza(x5)
3x 2,5
3x 2,5
3x 2,5
3x 2,5
3x 2,5
XLPE
XLPE
XLPE
XLPE
XLPE
20
20
20
20
20
3x 1,5
3x 1,5
3x 2,5
3x 2,5
3x 1,5
XLPE
XLPE
XLPE
XLPE
XLPE
16
16
20
20
16
3x 6
3x 6
3x 6
3x 1,5
3x 2,5
3x 2,5
XLPE
XLPE
XLPE
XLPE
XLPE
XLPE
25
25
25
16
20
20
Junio 2008
CUADROS
GENERALES
P.2
P.1
P.baja
Stano
224
Pot
Int
k
S
Imax long
conductor
kW
A
mm^2
A
m
CH2-CG2
3.902 18,85 56
3x 6
37
30
CZC2-CG2
5.512 26,63 56
3x 4
30
0,5
CH1-CG1
3.937 19,02 56
3x 6
22
30
ch16/CH16-CG1 1.666 8,05
56 3x 2,5
22
30
CH17-CG2
2.737 13,22 56
3x 4
30
30
CZC1-CG1
7.700 37,20 56
3x 10
52
0,5
CZC1-Cgbaja
11.200 54,11 56
3x 16
70
0,5
CZC2-Cgbaja
6.864 33,16 56
3x 6
37
0,5
cocina-Cgbaja 12.710 61,40 56
3x 16
70
4,5
C.ACS-Cgsot
6.000 28,99 56
3x 4
30
0,5
Tabla 5- 6.- Lneas de alimentacin a cuadros parciales
u
V
3,03
0,11
3,06
3,10
3,19
0,06
0,05
0,09
0,56
0,12
u
%
1,32
0,05
1,33
1,35
1,39
0,03
0,02
0,04
0,24
0,05
CIRCUITOS TRIFSICOS:
S
Imax long u
mm^2
A
m
V
5x 6
30 15,5 2,13
u
%
0,93
CG2-CGBT
77.674 124,72 56 5x 50 125
42 2,91
CG1-CGBT
55.109 88,49
56 5x35 110
39 2,74
Cgbaja-CGBT 30.774 49,41
56 5x16
66 37,5 3,22
CG sot-CGBT 10.607 17,03
56
5x6
22
35 2,76
ASC-CGBT
25.900 41,59
56 5x10
50
1
0,12
Tabla 5- 7.- Lneas de alimentacin a cuadros generales
1,27
1,19
1,40
1,20
0,05
ASCEN.
Pot
Int
kW
A
18.500 29,70
k
56
TUBOS
diam
PLANTA 2
CH2
alumbrado
3x1,5
XLPE
16
fuerza(x7)
3x 2,5
XLPE
20
CZC2
alum
3x 2,5
XLPE
20
fuerza(x6)
3x 2,5
XLPE
20
fuerza(x5)
3x 2,5
XLPE
20
emerg
3x 1,5
XLPE
16
Tabla 5- 8.- Tubos empotrados cuadro planta segunda
Junio 2008
PLANTA
BAJA
CZC B1
alumbrado1
alumbrado2
fuerza1(x7)
fuerza2(x6)
fuerza3(x5)
CZC B2
alumbrado1
alumbrado2
fuerza(x6)
fuerza(x5)
emergencia
COCINA
coc/horno
lavad/lavavj
secadora
alumbrado
fuerza(x6)
fuerza(x5)
Pot
kW
Int
A
S
Imax long
mm^2
A
m
u
V
u
%
1.950
1.900
3.500
3.000
2.500
9,42
9,18
16,91
14,49
12,08
56
56
56
56
56
3x 2,5
3x 2,5
3x 2,5
3x 2,5
3x 2,5
22
22
22
22
22
48
48
48
48
48
5,81
5,66
10,43
8,94
7,45
2,53
2,46
4,54
3,89
3,24
1.880
1.450
3.000
2.500
280
9,08
7,00
14,49
12,08
1,35
56
56
56
56
56
3x 1,5
3x 1,5
3x 2,5
3x 2,5
3x 1,5
16
16
22
22
16
30
30
30
30
30
5,84
4,50
5,59
4,66
0,87
2,54
1,96
2,43
2,03
0,38
4.050
19,57
56
3x 6
37
3.105
15,00
56
3x 6
37
2.587,5 12,50
56
3x 6
37
450
2,17
56 3x 1,5 16
3.000
14,49
56 3x 2,5 22
2.500
12,08
56 3x 2,5 22
Tabla 5- 4.- Cuadro secundario planta baja
9
9
9
8
8
8
0,94
0,72
0,60
0,37
1,49
1,24
0,41
0,31
0,26
0,16
0,65
0,54
u
V
u
%
Pot
kW
STANO
223
CZC SOT
alumbrado1
1.404
alumbrado2
950
emergencia
240
fuerza1
3.000
C ACS
caldera (ACS)
1.000
intercambiador
(ACS)
1.000
bomballenado(x2)
(ACS)
500
bombas(x3)
(ACS)
1.000
C, EVAC
bomba(evac)
1.000
C . VENT
bomba(ventilac) 1.000
C. CALEF
bomba(calef)
1.000
caldera(calef)
1.000
C,.PUERTA
puerta
1.000
Tabla 5- 5.-
Int
A
S
mm^2
6,78
4,59
1,16
14,49
56
56
56
56
3x 1,5
3x 1,5
3x 1,5
3x 2,5
16
16
16
22
42
42
42
42
6,10
4,13
1,04
7,83
2,65
1,80
0,45
3,40
4,83
56
3x 1,5
16
15
1,55
0,68
4,83
56
3x 1,5
16
15
1,55
0,68
2,42
56
3x 1,5
16
15
0,78
0,34
4,83
56
3x 1,5
16
15
1,55
0,68
4,83
56
3x 1,5
37
25
2,59
1,13
4,83
56
3x 1,5
37
30
3,11
1,35
4,83
4,83
56
56
3x 1,5
3x 1,5
37
37
25
25
2,59
2,59
1,13
1,13
4,83 56 3x 1,5
37
Cuadro secundario stano
30
3,11
1,35
Imax long
A
m
Junio 2008
222
CIRCUITOS MONOFSICOS:
Pot
kW
PLANTA
2
CH2
alumbrado
402
fuerza(x7)
3.500
CZC2
alum
1.950
fuerza(x6)
3.000
fuerza(x5)
2.500
emergencia
330
Tabla 5- 2.Pot
kW
PLANTA
1
CH1
alumbrado
437
fuerza(x7)
3.500
CH15
alumbrado
166
fuerza(x7)
1.500
CH16
alumbrado
166
fuerza(x3)
1.500
CH17
alumbrado
237
fuerza(x5)
2500
CZC1
alumbrado1 1.600
alumbrado2 1.800
fuerza(x7)
3.500
fuerza (x6) 3.000
emergencia
320
Tabla 5- 3.-
Int
A
1,94
16,91
S
Imax long
mm^2
A
m
56 3x1,5
56 3x 2,5
16
22
6
6
9,42
56 3x 2,5 22
48
14,49 56 3x 2,5 22
48
12,08 56 3x 2,5 22
48
1,59
56 3x 1,5 16
48
Cuadro secundario planta segunda
Int
A
S
Imax long
mm^2
A
m
u
V
u
%
0,25
1,30
0,11
0,57
5,81
8,94
7,45
1,64
2,53
3,89
3,24
0,71
u
V
u
%
2,11
16,91
56 3x 1,5
56 3x 2,5
16
22
6
6
0,27
1,30
0,12
0,57
0,80
7,25
56 3x 1,5
56 3x 2,5
16
22
6
6
0,10
0,56
0,04
0,24
0,80
7,25
56 3x 1,5
56 3x 2,5
16
22
6
6
0,10
0,56
0,04
0,24
1,14
12,08
56 3x 1,5
56 3x 2,5
16
22
6
6
0,15
0,93
0,06
0,41
7,73
56 3x 2,5 22
48
8,70
56 3x 2,5 22
48
16,91 56 3x 2,5 22
48
14,49 56 3x 2,5 22
48
1,55
56 3x 1,5 16
48
Cuadro secundario planta primera
4,77
5,37
10,43
8,94
1,59
2,07
2,33
4,54
3,89
0,69
Junio 2008
221
= 10.607,2 W
Junio 2008
220
Cuadro cocina
Potencia= PALUMB + PFUERZA + 2 PLAV + 2 PSEC + PCOCINA = = 22.420 W
Potencia total= 450+2.000+4.050+3.105+3.105=12.710 W
Cuadro Planta 2
Potencia total= P(czc1) + P(czc 2) + PCOCINA = 30.774 W
Cuadro de climatizacin
Potencia= PACS + PCALEF = 8.000 W
F.S.= 0,8
Potencia total= ( PACS + PCALEF ) 0,8 = 6.400 W
Cuadro stano
Potencia=
PALUM + PFUERZA + PCLIMAT + PEVAC + PEVAC + PPUERTA =17.789 W
Potencia total=
PALUM 0.8 + PFUERZA 0.3 + PCLIMAT 0.8 + PEVAC + PEVAC + PPUERTA
Junio 2008
219
Junio 2008
218
Junio 2008
217
con
Junio 2008
216
1.7.4.- Contador
El contador se instalar en el cuarto de contadores elctricos
situado junto a la CGP del edificio, cumpliendo con las normas UNE
20.324 y UNE 50.102. El equipo est constituido por una serie de
elementos:
- Unidad funcional de interruptor general de maniobra de 250 A
en funcin de la previsin de la carga, que deja fuera de servicio
todo el suministro del edificio en los casos que es necesario. Se
instala entre la Lnea General de Alimentacin y el contador.
-Unidad funcional de embarrado general y fusibles de seguridad.
Se instalarn en cada uno de los hilos de fase o polares que van al
mismo. Estarn precintados por la compaa suministradora.
-Unidad funcional de medida:
Contador de medida.
- Unidad funcional de embarrado de proteccin y bornes de salida:
Contiene el embarrado donde se conectan los conductores de
proteccin de cada derivacin individual y los bornes de salida de
las citadas derivaciones
Junio 2008
215
Junio 2008
214
de
alimentacin,
previa
comunicacin
la
empresa
suministradora.
Junio 2008
213
contenido
de
componentes
clorados
otros
contaminantes.
Junio 2008
212
Junio 2008
211
Lnea
General
de
alimentacin
5.-
Interruptor
general
de
maniobra
9.- Fusible de seguridad
10.- Contador
11.- Interruptor control de
potencia
12.- Dispositivos generales de
mando y proteccin.
13.- Instalacin interior
Junio 2008
210
comercializacin,
suministro
procedimiento
de
Junio 2008
209
Junio 2008
Por
208
iluminacin:
Junio 2008
207
la
1.4.- Iluminacin
El alumbrado de cada una de las zonas se distribuir entre varios
circuitos, de manera que el fallo de uno de ello no afecte a ms de 1/3 del
alumbrado general.
Segn el uso y la decoracin, el alumbrado de cada ambiente
combinar equipos para lmparas compactas de bajo consumo, tubos
fluorescentes, lmparas incandescentes y halgenas.
Junio 2008
206
Junio 2008
205
1.- MEMORIA
DESCRIPTIVA
Junio 2008
204
Captulo 5:
Instalacin de
electricidad
Junio 2008
203
Junio 2008
202
Junio 2008
201
Junio 2008
200
3.1.- Catlogos
3.1.1.-Radiadores FERROLI, modelo Europa 800C
Junio 2008
199
3.- ANEXOS
Junio 2008
198
C=
24 z (Ta TEM ) a b c Q
(Ta Tem min ) PCI
Junio 2008
codo 90
tubera
3/8''
1/2''
3/4''
1''
n elem
7
8
5
1
m
0,3
0,6
0,75
0,9
Le
2,1
4,8
3,75
0,9
giro T
tubera
3/8''
1/2''
3/4''
1''
n elem
1
7
3
1
m
0,45
0,9
1,2
1,5
Le
0,45
6,3
3,6
1,5
197
Reducciones
tubera
1 1/2''-1 1/4''
1 1/4''-1''
3/4''-1/2''
1/2''-3/8''
3/8''-1/4''
n elem
2
2
4
13
1
m
0,5
0,39
0,22
0,18
0,12
Le
1
0,78
0,88
2,34
0,12
T paso recto
tubera
3/8''
1/2''
3/4''
n elem
47
7
8
m
0,1
0,2
0,25
Le
4,7
1,4
2
Tabla 4- 18.- Longitud equivalente en metros de los accesorios de las tuberas de cobre.
tubera
3/8''
1/2''
3/4''
1''
1 1/4''
1 1/2''
L
240,72
133,79
62,04
32,275
18,615
13,73
Le
7,25
12,5
9,35
2,4
L+Le mmca/m
247,97
15
146,29
10
71,39
8
34,675
8
18,615
6
13,73
5
mca
3,720
1,463
0,571
0,277
0,112
0,069
mca/ud n elem
radiador 0,0358
111
3,974
TOTAL
10,185
Tabla 4- 19.- Prdida de carga total del circuito primario
Junio 2008
196
q:
Q
C e Pe T 3600
caudal(litros/seg)
Junio 2008
195
VU = VI %
VU : volumen o capacidad til
Pf Pi
Pf
3 2.2
= 0.266
3
VV =
VU
7.155
= 26.9 litros
0.266
Junio 2008
194
PRDIDAS
Transmisin Ventilacin Suplementos
5.328,18
937,34
987,15
1.428,44
405,89
381,86
2.135,44
427,64
519,16
0,00
0,00
0,00
163,88
203,91
26,88
186,51
470,17
56,04
0,00
0,00
0,00
93,15
304,32
18,50
258,48
313,45
28,35
328,37
0,00
28,35
230,44
313,45
28,29
230,44
0,00
56,58
388,12
313,45
28,35
200,71
313,45
30,09
195,69
139,50
82,28
211,26
119,70
58,80
188,58
313,47
30,66
265,01
313,47
56,58
TOTAL
Sala 1
7.252,67
Sal2
2.216,19
Sala3
3.082,24
Aseo1
0,00
Aseo2
394,67
Aseo3
712,72
B1
0,00
B2
415,97
H1norte
600,28
H1 sur
356,72
H2 sur
572,18
H2 norte
287,02
H3
729,92
H4
544,25
H5
417,47
H6
389,76
H7
532,71
H8
635,06
Despacho
1
419,84
143,64
216,28
779,76
Despahco
2
84,29
0,00
0,00
84,29
Tabla 4- 15.- Prdidas calorficas totales locales planta primera
PRDIDAS
Transmisin Ventilacin Suplementos
TOTAL
Aseo1
322,26
602,44
32,82
957,52
Aseo2
201,45
470,17
66,46
738,08
H1
404,74
153,28
37,74
595,76
H2 sur
372,74
153,28
32,94
558,96
H2 norte
372,74
153,28
65,88
591,90
H3
490,13
153,28
50,55
693,96
H sur
675,25
153,28
50,55
879,08
H4 norte
704,96
61,16
137,78
903,90
h5
404,74
153,27
69,36
627,37
h6
373,13
153,28
69,36
595,77
B1 este
61,16
137,78
8,45
207,39
B1 oeste
61,16
137,78
6,76
205,70
B2
101,12
0,00
0,00
101,12
B3
94,44
137,79
6,74
238,97
Tabla 4- 16.- Prdidas calorficas totales locales planta segunda
Junio 2008
193
PRDIDAS
Transmisin Ventilacin Suplementos
743,49
428,42
89,42
TOTAL
Cocina
1.261,18
Despacho
1
825,73
149,88
128,51
1.104,12
Despacho
2
708,70
140,82
25,20
874,72
Sala1
675,32
145,41
33,80
854,53
Sala2
1.427,24
213,24
189,63
1.830,11
Sala3
954,50
106,73
64,76
1.125,90
Sala4
380,13
67,03
31,15
478,31
Sala5
1.653,58
416,62
83,95
2.154,14
Sala6
927,48
194,46
17,45
1.139,40
Sala7
3.039,79
966,13
456,27
4.462,20
Sala8
675,70
435,13
34,15
1.144,98
Sala9
2.289,94
1.018,66
513,14
3.821,74
Aseo1
74,54
0,00
0,00
74,54
Aseo2
238,88
203,91
26,01
468,80
Aseo3
205,59
210,29
18,93
434,81
Aseo4
63,11
0,00
0,00
63,11
Aseo5
127,51
0,00
0,00
127,51
Peluquera
667,40
183,99
41,04
2.269,25
Gimnasio
1.774,20
428,22
68,84
892,42
Vestuario
448,99
975,18
25,32
1.449,49
Tabla 4- 14.- Prdidas calorficas totales locales planta baja
Junio 2008
192
kcal
m3 C
Sur
SurOeste
0%
2,50%
Sur-Este
Oeste
Este
Noroeste
5%
5%
10%
10%
Tabla 4- 13.- Coeficientes de orientacin
Noreste
Norte
12,50%
15%
Junio 2008
191
Qt = K S (Ti Te )
K: coeficiente de transmisin
S: superficie ( m 2 )
Ti : temperatura en el interior del habitculo
Te : temperatura en el exterior del habitculo
Junio 2008
CERRAMIENTO
N
190
INTERIOR BAO-BAO
Elemento constructivo
e(m)
Alicatado azulejo
CERRAMIENTO
(m^3 c/kcal)
R(m^2C/kcal)
0,06
1,9
0,03
0,05
0,42
0,12
Alicatado azulejo
0,01
1,9
0,005
Resistencia exterior
Re=1/he
0,13
Resistencia interior
0,13
Resistencia total
Ri=1/hi
Rt=sum
Ri
0,42
K= 1/Rt
2,38
Elemento constructivo
e(m)
(m^3 c/kcal)
R(m^2C/kcal)
Enlucido de yeso
0,02
0,26
0,08
ladrillo hueco
0,05
0,42
0,11
Enlucido de yeso
0,02
0,26
0,08
Resistencia exterior
Re=1/he
0,13
Resistencia interior
0,13
Resistencia total
Ri=1/hi
Rt=sum
Ri
K= 1/Rt
1,88
Elemento constructivo
e(m)
0,53
CUBIERTA
N
Baldosa cermica
0,01
0,9
0,01
0,04
0,04
0,035
Mortero de agarre
Panel de poliestireno
extrusionado
0,05
0,028
1,8
Lmina bituminosa
0,006
0,16
0,037
Bovedilla cermica
Ri=1/hi
Enlucido de yeso
0,02
0,026
0,08
Resistencia exterior
Re=1/he
0,11
Resistencia interior
0,06
Resistencia total
Ri=1/hi
Rt=sum
Ri
K= 1/Rt
0,43
0,2
2,33
CERRAMIENTO
INTERIOR
BAO-HAB
( cocina hab)
N
Elemento constructivo
e(m)
(m^3 c/kcal)
R(m^2C/kcal)
Enlucido de yeso
0,02
0,26
0,08
0,05
0,42
0,12
Alicatado azulejo
0,01
1,9
0,005
Resistencia exterior
Re=1/he
0,13
Resistencia interior
0,13
Resistencia total
Ri=1/hi
Rt=sum
Ri
K= 1/Rt
2,13
0,47
Junio 2008
FORJADO SOBRE
189
ESPACIO EXTERIOR
Elemento constructivo
e(m)
(m^3 c/kcal)
R(m^2C/kcal)
0,3
0,9
0,4
Aislamiento Roofmate
0,03
0,028
1,07
Capa de mortero
0,04
0,04
0,04
Pavimento de terrazo
0,03
0,03
Resistencia exterior
Re=1/he
0,06
Resistencia interior
Ri=1/hi
0,2
Resistencia total
Rt=sum Ri
1,8
K= 1/Rt
0,56
FORJADO SOBRE
Elemento constructivo
0,3
0,9
0,4
Aislamiento Roofmate
0,03
0,028
1,07
Capa de mortero
0,04
0,04
Pavimento de terrazo
0,03
Resistencia exterior
Re=1/he
0,2
Resistencia interior
0,2
Resistencia total
Ri=1/hi
Rt=sum
Ri
1,94
K= 1/Rt
0,52
FORJADO
e(m)
(m^3 c/kcal)
R(m^2C/kcal)
0,04
0,03
e(m)
ENTRE PLANTAS
Elemento
constructivo
Forjado bovedilla
cermica
0,3
0,9
0,4
Capa de mortero
0,04
0,04
0,04
Pavimento de terrazo
0,03
0,03
Resistencia exterior
Re=1/he
0,2
Resistencia interior
Ri=1/hi
Rt=sum
Ri
0,2
0,8
K= 1/Rt
1,15
Resistencia total
Coeficiente K(kcal/m^2
hC)
(m^3 c/kcal)
R(m^2C/kcal)
Elemento constructivo
e(m)
(m^3 c/kcal)
R(m^2C/kcal)
0,12
0,65
0,18
0,05
0,022
2,27
0,09
0,42
0,22
alicatado azulejo
0,01
1,9
0,005
Resistencia exterior
Re=1/he
0,07
Resistencia interior
0,13
Resistencia total
Ri=1/hi
Rt=sum
Ri
2,87
K= 1/Rt
0,34
Junio 2008
188
Elemento constructivo
e(m)
(m^3 c/kcal)
0,12
0,658
R(m^2C/kcal)
0,18
Enfoscado de mortero
0,01
1,2
0,01
Porexpan
0,04
0,022
1,38
0,07
0,42
0,39
Enlucido de yeso
0,01
0,26
0,04
Resistencia exterior
Re=1/he
0,07
Resistencia interior
Ri=1/hi
0,13
Resistencia total
Rt=sum Ri
2,2
K= 1/Rt
0,45
Elemento constructivo
e(m)
MURO MEDIANIL
AL EXTERIOR
N
(m^3 c/kcal)
R(m^2C/kcal)
0,42
0,27
Enfoscado de mortero
0,01
1,2
0,01
Porexpan
0,04
0,022
0,69
0,07
0,42
0,09
Enlucido de yeso
0,01
0,26
Resistencia exterior
Re=1/he
0,07
Resistencia interior
Ri=1/hi
0,13
Resistencia total
Rt=sum Ri
1,3
K= 1/Rt
0,77
Elemento constructivo
e(m)
(m^3 c/kcal)
Enlucido de yeso
0,01
0,26
0,04
Termoarcilla
0,1
0,14
0,68
Enlucido de yeso
0,01
0,26
Resistencia exterior
Re=1/he
0,13
Resistencia interior
Ri=1/hi
0,13
Resistencia total
Rt=sum Ri
1,3
K= 1/Rt
0,98
0,04
R(m^2C/kcal)
0,04
Junio 2008
187
2.- CLCULOS
JUSTIFICATIVOS
Junio 2008
186
1.15.- Conclusin
Con la presente Memoria, Clculos y Planos que se acompaan, se
da por concluido el estudio de la Instalacin, que ser ejecutada por el
Instalador Autorizado, segn lo indicado y de acuerdo a las Normas
vigentes.
Junio 2008
185
Junio 2008
184
PLANTA SOTANO
CIRCUITO TRAMO
IDA
dimetro
vel real(m/s)
caudal(l/s)
0,41611
1.040,27
36,40
0,520
0,28059
1010,14
701,49
29,89
0,351
0,69670
2508,13
1.741,76
47,10
1 1/4
0,557
0,32920
1185,13
823,01
32,38
0,412
0,17645
635,22
441,13
23,71
3/4''
0,360
0,15275
549,91
381,88
22,06
3/4''
0,312
1,02591
3693,26
2.564,76
57,16
1 1,2
0,540
dimetro(mm) dimetro
vel
real(m/s)
CIRCUITO
TRAMO
caudal(l/s)
caudal(l/h)
area(mm^2)
VUELTA
0,41611
1497,99
832,22
32,56
1''
0,28059
1010,14
561,19
26,74
3/4''
0,573
10
0,69670
2508,13
1393,41
42,13
1 1/4
0,557
11
0,17645
635,22
352,90
21,20
3/4''
0,360
12
0,87315
3143,35
1746,31
47,17
1 1/2''
0,460
0,520
caudal (l/s)
caudal(l/h)
area (mm^2)
diametro(mm)
diameto
vel real(m/s)
0,06471
232,96
129,42
12,84
1/2''
0,298
0,10594
381,39
211,89
16,43
1/2''
0,488
0,15276
549,92
305,51
19,73
3/4''
0,312
0,15276
549,92
305,51
19,73
3/4''
0,312
0,06519
234,68
130,38
12,89
1/2''
0,300
0,08896
320,25
177,91
15,05
1/2''
0,410
0,13577
488,77
271,54
18,60
1/2''
0,277
0,13577
488,77
271,54
18,60
1/2''
0,277
0,07801
280,85
156,03
14,10
1/2''
0,360
0,16454
592,33
329,07
20,47
1/2''
0,758
0,30060
1.082,14
601,19
27,67
3/4''
0,613
0,30060
1.082,14
601,19
27,67
3/4''
0,613
0,07390
266,04
147,80
13,72
1/2''
0,341
0,24230
872,27
484,60
24,85
3/4''
0,494
0,35395
1.274,22
707,90
30,03
1''
0,442
0,35395
1.274,22
707,90
30,03
1''
0,442
Junio 2008
TRAMO
kcal/h
caudal(l/s)
183
caudal(l/h) area(mm^2)
dimetro(mm)
dimetro
vel real(m/s)
19
2.216,19
0,03078
110,81
76,95
9,90
3/8 ''
0,251
20
1.108,095
0,01539
55,40
38,48
7,00
3/8 ''
0,126
21
12.124,67
0,16840
606,23
421,00
23,16
3/4''
0,344
22
867,68
0,01205
43,38
30,13
6,20
3/8 ''
0,098
23
580,66
0,00806
29,03
20,16
5,07
3/8 ''
0,066
24
11.256,99
0,15635
562,85
390,87
22,31
3/4''
0,319
25
10.969,97
0,15236
548,50
380,90
22,03
3/4''
0,311
26
10.334,91
0,14354
516,75
358,85
21,38
3/4''
0,293
27
9307,5
0,12927
465,38
323,18
20,29
3/4''
0,264
28
8.280,09
0,11500
414,00
287,50
19,14
3/4''
0,235
29
7.252,68
0,10073
362,63
251,83
17,91
3/4''
0,206
30
5.439,52
0,07555
271,98
188,87
15,51
1/2''
0,348
31
3.612,11
0,05017
180,61
125,42
12,64
1/2''
0,231
32
2.584,7
0,03590
129,24
89,75
10,69
3/8 ''
0,293
kcal/h
5.160,4
caudal(l/s) caudal(l/h)
0,07167
258,02
area(mm^2)
179,18
dimetro(mm) dimetro
15,11
1/2''
vel real(m/s)
0,330
4.044,86
0,05618
202,24
140,45
13,38
1/2''
0,259
2.595,37
0,03605
129,77
90,12
10,71
3/8 ''
0,294
1.144,98
0,01590
57,25
39,76
7,12
3/8 ''
0,130
3.370,5
0,04681
168,53
117,03
12,21
3/8 ''
0,382
2.254,95
0,03132
112,75
78,30
9,99
3/8 ''
0,255
1.139,4
0,01583
56,97
39,56
7,10
3/8 ''
0,129
10
9.796,2
0,13606
489,81
340,15
20,82
3/4''
0,278
11
2.269,2
0,03152
113,46
78,79
10,02
3/8 ''
0,257
12
1.134,6
0,01576
56,73
39,40
7,08
3/8 ''
0,129
13
7.527
0,10454
376,35
261,35
18,25
3/4''
0,213
14
6.449,94
0,08958
322,50
223,96
16,89
3/4''
0,183
15
5.372,87
0,07462
268,64
186,56
15,42
1/2''
0,344
16
4.767,05
0,06621
238,35
165,52
14,52
1/2''
0,305
17
4.269,13
0,05929
213,46
148,23
13,74
1/2''
0,273
18
497,62
0,00691
24,88
17,28
4,69
3/8 ''
0,014
19
3.800,33
0,05278
190,02
131,96
12,97
1/2''
0,243
20
3.725,79
0,05175
186,29
129,37
12,84
1/2''
0,238
21
2.871,26
0,03988
143,56
99,70
11,27
3/8 ''
0,081
22
1.104,12
0,01534
55,21
38,34
6,99
3/8 ''
0,031
23
8.039,01
0,11165
401,95
279,13
18,86
3/4''
0,228
24
2.535,09
0,03521
126,75
88,02
10,59
3/8 ''
0,072
25
1.261,18
0,01752
63,06
43,79
7,47
3/8 ''
0,036
26
5.503,92
0,07644
275,20
191,11
15,60
1/2''
0,352
27
4.230,016
0,05875
211,50
146,88
13,68
1/2''
0,271
28
2.956,1
0,04106
147,81
102,64
11,43
3/8 ''
0,084
29
18.30,11
0,02542
91,51
63,55
9,00
3/8 ''
0,052
30
915,058
0,01271
45,75
31,77
6,36
3/8 ''
0,026
Junio 2008
182
TRAMO
kcal/h
caudal(l/s)
caudal(l/h)
area(mm^2)
dimetro(mm)
dimetro
vel
real(m/s)
12
5.617,03
0,07801
280,85
195,04
15,76
1/2''
0,360
13
5.515,91
0,07661
275,80
191,52
15,62
1/2''
0,353
14
2.634,33
0,03659
131,72
91,47
10,79
3/8''
0,298
15
2.075,37
0,02882
103,77
72,06
9,58
3/8''
0,235
16
1.163,41
0,01616
58,17
40,40
7,17
3/8''
0,132
17
3.839,30
0,05332
191,97
133,31
13,03
3/8''
0,435
18
3.179,22
0,04416
158,96
110,39
11,86
3/8''
0,360
19
2.620,26
0,03639
131,01
90,98
10,77
3/8''
0,297
20
2.519,14
0,03499
125,96
87,47
10,56
3/8''
0,285
21
1.859,06
0,02582
92,95
64,55
9,07
3/8''
0,211
22
1.165,10
0,01618
58,26
40,45
7,18
3/8''
0,132
23
5.665,59
0,07869
283,28
196,72
15,83
1/2''
0,363
24
5.564,47
0,07728
278,22
193,21
15,69
1/2''
0,356
36
5.421,90
0,07530
271,10
188,26
15,49
1/2''
0,347
37
5.320,78
0,07390
266,04
184,75
15,34
1/2''
0,341
38
2.026,87
0,02815
101,34
70,38
9,47
3/8''
0,230
39
1.434,97
0,01993
71,75
49,83
7,97
3/8''
0,163
0,084
40
738,08
0,01025
36,90
25,63
5,71
3/8''
41
3.293,91
0,04575
164,70
114,37
12,07
3/8''
0,373
42
2.600,89
0,03612
130,04
90,31
10,73
3/8''
0,295
43
2.008,99
0,02790
100,45
69,76
9,43
3/8''
0,228
44
1.907,87
0,02650
95,39
66,25
9,19
3/8''
0,216
45
1.214,85
0,01687
60,74
42,18
3,66
3/8''
0,138
46
207,38
0,00288
10,37
7,20
1,51
3/8''
0,023
kcal/h
caudal(l/s)
caudal(l/h) area(mm^2)
2.968,74
0,04123
148,44
103,08
11,46
3/8 ''
0,336
2.552,67
0,03545
127,63
88,63
10,63
3/8 ''
0,289
1.772,90
0,02462
88,65
61,56
8,86
3/8 ''
0,201
1.228,65
0,01706
61,43
42,66
7,37
3/8 ''
0,139
1.144,36
0,01589
57,22
39,73
7,11
3/8 ''
0,130
572,18
0,00795
28,61
19,87
5,03
3/8 ''
0,065
1.711,25
0,02377
85,56
59,42
8,70
3/8 ''
0,194
1.293,78
0,01797
64,69
44,92
7,56
3/8 ''
0,147
904,02
0,01256
45,20
31,39
6,32
3/8 ''
0,102
10
819,73
0,01139
40,99
28,46
6,02
3/8 ''
0,093
11
532,71
0,00740
26,64
18,50
4,85
3/8 ''
0,060
12
6.229,64
0,08652
311,48
216,31
16,60
1/2''
0,399
13
729,92
0,01014
36,50
25,34
5,68
3/8 ''
0,083
14
4.927,64
0,06844
246,38
171,10
14,76
1/2''
0,315
15
4.355,46
0,06049
217,77
151,23
13,88
1/2''
0,279
16
3.783,28
0,05255
189,16
131,36
12,94
1/2''
0,242
17
3.211,10
0,04460
160,56
111,50
11,92
3/8 ''
0,364
18
2.610,83
0,03626
130,54
90,65
10,75
3/8 ''
0,296
dimetro(mm)
dimetro
vel real(m/s)
Junio 2008
181
TRAMO
kcal/h
caudal(l/s)
caudal(l/h)
area(mm^2)
dimetro(mm)
dimetro
vel
real(m/s)
4.659,31
0,06471
232,97
161,78
14,36
1/2''
0,298
4.558,19
0,06331
227,91
158,27
14,20
1/2''
0,292
1.676,61
0,02329
83,83
58,22
8,61
3/8 ''
0,190
1.117,65
0,01552
55,88
38,81
7,03
3/8 ''
0,127
205,69
0,00286
10,28
7,14
3,02
3/8 ''
0,023
2.881,58
0,04002
144,08
100,05
11,29
3/8 ''
0,326
2.221,50
0,03085
111,08
77,14
9,91
3/8 ''
0,252
1.662,54
0,02309
83,13
57,73
8,58
3/8 ''
0,188
1.561,42
0,02169
78,07
54,22
8,31
3/8 ''
0,177
10
901,34
0,01252
45,07
31,30
6,31
3/8 ''
0,102
11
207,38
0,00288
10,37
7,20
3,03
3/8 ''
0,023
25
4.707,87
0,06539
235,39
163,47
14,43
1/2''
0,301
26
4.606,75
0,06398
230,34
159,96
14,27
1/2''
0,295
27
1.799,19
0,02499
89,96
62,47
8,92
3/8 ''
0,204
28
1.207,29
0,01677
60,36
41,92
7,31
3/8 ''
0,137
29
205,69
0,00286
10,28
7,14
3,02
3/8 ''
0,023
30
2.807,56
0,03899
140,38
97,48
11,14
3/8 ''
0,318
31
2.114,54
0,02937
105,73
73,42
9,67
3/8 ''
0,240
32
1.522,64
0,02115
76,13
52,87
8,21
3/8 ''
0,172
33
1.421,52
0,01974
71,08
49,36
7,93
3/8 ''
0,161
34
728,50
0,01012
36,43
25,30
5,68
3/8 ''
0,083
35
101,12
0,00140
5,06
3,51
2,11
3/8 ''
0,011
Junio 2008
180
q:
Q
C e Pe T 3600
caudal(litros/seg)
Junio 2008
179
Pf Pi
Pf
VV =
VU
Junio 2008
178
P
P.C.I
Junio 2008
habitculo
Elementos
por
(planta 1) calorfica(kcal/h)
radiador
Sala 1
7.252,67
4
10
Sala 2
2.216,19
2
6
Sala 3
3.082,24
3
6
Aseo 1
0
1
0
Aseo 2
394,67
1
3
Aseo 3
712,72
1
5
Bao1
0
1
0
Bao2
416,07
1
3
H1norte
600,27
1
4
H1sur
356,72
1
3
H2 sur
572,18
1
4
H2 norte
287,02
1
2
H3
729,92
1
5
H4
544,25
1
4
H5
417,47
1
3
H6
389,76
1
3
H7
532,71
1
4
H8
635,06
1
4
Despacho1
779,77
1
5
Despacho2
84,29
1
1
Tabla 4- 5.- Mdulos de radiadores de la planta primera
habitculo
(planta 2)
Aseo1
Aseo2
H1
H2 sur
H2 norte
H3
H4 sur
H4 norte
H5
H6
B1 este
B1 oeste
B2
B3
demanda
177
demanda
calorfica
(Kcal/h)
957,52
738,08
595,76
558,96
591,9
693,96
879,08
962,16
627,38
595,77
207,38
205,69
101,12
238,96
n rad
n radiadores
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Elementos
por
radiador
6
5
4
4
4
5
6
6
4
4
2
2
1
2
Junio 2008
176
habitculo
demanda
Elementos
por
(planta baja) calorfica(kcal/h)
radiador
Cocina
1..261,18
1
8
Despacho 1
1.104,12
1
7
Despacho 2
874,72
1
6
Sala1
854,53
1
5
Sala2
1.830,11
2
6
Sala3
1.125,9
1
7
Sala4
478,31
1
3
Sala5
2.154,14
2
6
Sala6
1.139,4
1
7
Sala7
4.462,2
4
7
Sala8
1.144,98
1
7
Sala9
3.821,74
3
8
Aseo1
74,54
1
1
Aseo2
468,8
1
3
Aseo3
434,81
1
3
Aseo4
63,11
1
1
Aseo5
127,51
1
1
Gimnasio
2.269,25
2
7
Peluquera
892,42
1
6
Vestuario
1.449,49
1
9
Tabla 4- 4.- mdulos de radiadores de la planta baja
n rad
Junio 2008
Sur
SurOeste
0%
2,50%
Sur-Este
Oeste
175
Este
Noroeste
5%
5%
10%
10%
Tabla 4- 3.- Coeficientes de orientacin
Noreste
Norte
12,50%
15%
Junio 2008
174
Qt = K S (Ti Te )
-Prdidas por ventilacin: Se calculan debido a la instalacin de
ventilacin primaria en
Junio 2008
173
K =
1
Rt
K=(
kcal
)
m h C
2
Temp. exterior
saln-comedor
habitaciones
cocina
bao
distribuidor-pasillo
gimnasio
temp. local no calef
Temperatura(C)
0
23
22
18
22
20
23
8
Junio 2008
172
1 e 1
+ +
he hi
1
: resistencia trmica superficial exterior
he
kcal
)
m h C
2
Junio 2008
171
Junio 2008
170
36,4
20,12
16,2
13,19
103,66
44,8
47,3
4,86
4,86
4,63
4,73
10,92
15,17
7,5
PLANTA BAJA
m^2
sala 1
16,8
sala 2
23,58
sala 3
11,8
sala 4
7,41
sala 5
46
sala 6
21,5
sala 7
106,8
sala 8
15,33
sala 9
112,21
despacho 1
16,58
despacho2
15,57
aseo1
4,63
aseo2
4,73
aseo3
4,88
aseo4
3,92
aseo5
7,92
vestuario
22,64
cocina
27,64
gimnasio
47,35
peluquera
21,36
Junio 2008
169
Junio 2008
168
Junio 2008
167
1.- MEMORIA
DESCRIPTIVA
Junio 2008
166
Captulo 4:
Instalacin de calefaccin
Junio 2008
165
Junio 2008
164
3.3.2.- Mantenimiento.
Para un correcto funcionamiento de la instalacin de saneamiento,
se debe comprobar peridicamente la estanqueidad general de la red con
Junio 2008
163
Junio 2008
162
Junio 2008
161
Tabla 3- 9.- Nmero de sumideros en funcin de la superficie de cubierta (CTE HS5 Tabla 4.6)
Tabla 3- 10.- Dimetro de las bajantes de aguas pluviales para un rgimen pluviomtrico de 100
mm/h. (CTE HS5 Tabla 4.8
Tabla 3- 11.- Dimetro de los colectores de aguas pluviales para un rgimen pluviomtrico de
100 mm/h(CTE HS5 Tabla 4.9)
Junio 2008
160
Tabla 3- 6.- Dimetro de las bajantes segn el nmero de alturas del edificio y el nmero de
unidades de descarga (CTE HS5 Tabla 4.4)
Tabla 3- 7.- Dimetro de las bajantes segn el nmero de alturas del edificio y el nmero de
unidades de descarga (CTE HS5 Tabla 4.4)
Tabla 3- 8.- Dimetro de los colectores horizontales de aguas residuales en funcin del nmero
mximo de UD y la pendiente adoptada (CTE HS5 Tabla 4.5)
Junio 2008
159
3.1.- Tablas
Tabla 3- 4.- Unidades correspondientes a cada tipo de aparato (CTE HS5 Tabla 4.1)
Junio 2008
158
3.- ANEXOS:
Junio 2008
157
Junio 2008
unidades
de
descarga
ARQUETA
12
13
14
156
superficie
(m^2)
superficie
total(m^2)
dimetro
(mm)
ARQUETA
LxA (cm)
99
297
396
125
50x50
99
561
660
160
60x60
99
396
495
160
60x60
99
660
759
160
60x60
99
99
495
693
160
60x60
12
99
99
90
40x40
13
165
99
693
957
200
60x60
924
200
60x60
250
60x70
baj_pluvial
baj_residual
ARQ10
21
baj_pluvial
baj_residual
ARQ 11
18
baj_pluvial
baj_residual
ARQ12
21
15
baj_pluvial
ARQ
16
17
18
19
20
baj_pluvial
baj_residual
ARQ 17
ARQ 14
baj_pluvial
baj_residual
baj_pluvial
baj_residual
ARQ16
20
10
baj_pluvial
baj_residual
ARQ15
165
759
ARQ19
924
ARQ18
957
1881
Tabla 3- 3.- Dimensionado de bajantes y arquetas
Junio 2008
ARQUETA
3
AUX1
AUX2
10
11
baj_pluvial
baj_residual
155
unidades
de
descarga
superficie
(m^2)
superficie
total(m^2)
dimetro
(mm)
ARQUETA
LxA (cm)
10
99
99
90
40x40
99
478,5
577,5
160
60x60
ARQ4
ARQ2
baj_pluvial
baj_residual
24
99
99
90
40x40
baj_pluvial
baj_residual
99
99
90
40x40
ARQ5
ARQ6
99
264
363
125
50x50
baj_pluvial
baj_residual
165
99
264
110
50x50
99
577,5
676,5
160
60x60
99
99
198
110
50x50
99
363
462
160
60x60
99
198
297
110
50x50
99
462
561
160
60x60
baj_pluvial
baj_residual
ARQ AUX1
14
baj_pluvial
baj_residual
ARQ3
11
baj_pluvial
baj_residual
ARQ AUX2
28
baj_pluvial
baj_residual
ARQ8
10
baj_pluvial
baj_residual
ARQ 9
21
Junio 2008
TRAMO
26-27-28
1 bao
unidades
de
descarga
154
total
dimetro
dimetro
(unidades) propuesto(mm) elegido(mm)
63
110
29
tramo 23
tramo 30
7
10
17
75
110
21
tramo 29
3 lavabos
17
3
20
75
110
31
tramo 25
1 WC
7
4
11
63
110
18
3 lavabos
tramo 31
3
11
14
63
110
32
tramo 27
1 lavabo
1 ducha
7
1
2
10
63
110
20
tramo 32
tramo 26
10
7
17
63
110
19
tramo 28
1 WC
7
4
11
63
Tabla 3- 2.- Dimensionado de bajantes
110
ARQUETA
1
baj_pluvial
baj_residual
baj_pluvial
baj_residual
ARQ1
49
13
superficie
(m^2)
379,5
99
99
478,5
superficie
total(m^2)
dimetro
(mm)
ARQUETA
LxA (cm)
478,5
160
60x60
577,5
160
60x60
Junio 2008
153
BAJANTE
aparatos
unidades
unidades
totales
18
3 lavabos
1 bao
1 WC
3
7
4
14
63
110
1 bao
1 WC
7
4
11
63
110
1 baos
1 lavabo
1 ducha
7
1
2
10
50
110
1bao
1 lavabo
1 ducha
3 lav
7
1
2
3
13
63
110
4 duchas
4 inodoros
8
16
24
75
110
7 baos
49
49
90
110
19
20
21
22
dimetro
dimetro
propuesto(mm) elegido(mm)
f_correccin
i/100
sup corregida
diametro
(m^2)
bajante(mm)
1,1
190,3
90
S3-S6
30
1,1
33
50
S7
150
1,1
165
75
Junio 2008
152
aparatos
unidades
unidades
totales
5 aseos
2 WC
25
8
13
63
110
2 aseos
2 lavabos
10
2
12
63
110
2 aseos
10
10
50
110
peluqueria(2
lavabos)
1 WC
1 bao
2
4
7
13
63
110
1 bao
50
110
1 bao
1 lavabo
1 ducha
7
1
2
10
50
110
1 bao
50
110
8y9
1 WC
1 bao
4
7
11
63
110
1 ducha+1
lavabo
1 bao
3
7
10
50
110
1 WC
1 bao
4
7
11
63
110
cocina
1 ducha+1
lavabo
1 bao
18
3
7
28
90
110
1 ducha+1
lavabo
1 bao
3
7
10
63
110
16
1 aseo
15
15
63
110
17
3 aseos
50
110
10 y 11
12 y 13
14
15
dimetro
dimetro
propuesto(mm) elegido(mm)
Junio 2008
151
dimetro
(mm)
3
3
3
18
Pendiente
min
40
40
40
COCINA
lavavajillas(2)
lavadora(2)
fregadero(2)
total
BAO1
lavabo
inodoro
1
4
Pendiente
min
BAO2
lavabo
ducha
total
inodoro
2.50%
32
100
2%
1
2
3
4
32
40
100
TRAMO
23-24-25
1 bao
30
1 lavabo
1 ducha
tramo 24
unidades
de
descarga
total
dimetro
dimetro
(unidades) propuesto(mm) elegido(mm)
63
1
2
7
10
63
Ilustracin 3- 5.- Dimensionado de derivaciones
110
110
Junio 2008
150
2.- CLCULOS
JUSTIFICATIVOS
Junio 2008
149
1.9.- Conclusin
Con la presente Memoria, Clculos y Planos que se acompaan, se
da por concluido el estudio de la Instalacin, que ser ejecutada por el
Instalador Autorizado, segn lo indicado y de acuerdo a las Normas
vigentes.
Una vez presentado ante los Organismos Oficiales que lo requieran
y realizadas todas las pruebas necesarias en presencia del Instalador
Autorizado, del Representante de la Propiedad y de los Organismos
competentes, se efectuar la recepcin de la Instalacin.
Junio 2008
148
justificativos.
Junio 2008
147
Junio 2008
146
construyen
de
ladrillo,
revocadas
con
mortero
de
cemento
Junio 2008
145
760 110 1
=23,22 l/s
3600
Junio 2008
144
Junio 2008
143
A Im e
3600
Junio 2008
142
Junio 2008
141
Junio 2008
140
BAOS Y ASEOS
La derivacin del inodoro va directamente a la bajante
correspondiente, con el dimetro de sifn indicado en la tabla mostrada en
el apartado anterior segn el nmero de unidades de descarga, con un
dimetro de 100mm y una pendiente mnima del 2%.
Las derivaciones de la ducha y el lavabo en los baos se dirigen
hasta un bote sifnico con un dimetro de 40 mm y 32 mm
respectivamente, con una pendiente del 2%. A partir del bote sifnico, se
realiza una conexin con la bajante dimensionada segn el nmero de
descargas totales y la pendiente.
COCINA
En el caso de la cocina, el bote sifnico consta de un dimetro
equivalente al de 18 descargas con una pendiente del 1%. Y cada uno de
los componentes (fregadero, lavadora, lavavajillas) consta de un ramal de
40mm de dimetro en su conexin con el bote sifnico.
1.5.3.- Bajantes
En los casos en que sea posible, la evacuacin de las aguas
residuales de los baos se realizar por la misma bajante, si stos
coinciden en planta.
Junio 2008
139
Junio 2008
138
COCINA
lavavajillas(2)
lavadora(2)
fregadero(2)
total
BAO1
lavabo
inodoro
unidades de
descarga
dimetro
(mm)
3
3
3
18
Pendiente
min
40
40
40
1
4
Pendiente
min
2.50%
32
100
2%
BAO2
lavabo
1
32
ducha
2
40
total
3
inodoro
4
100
Tabla 3- 1.- Unidades de descarga para aparatos sanitarios de cocina
1.5.2.-Ramales-derivaciones
El dimetro de los ramales colectores entre aparatos sanitarios y la
bajante se obtienen a partir del nmero mximo de unidades de descarga
y la pendiente del ramal, segn la tabla 4.3 del CTE, HS5.
Como se observa en las siguientes figuras, la evacuacin puede
realizarse directamente a la bajante, o a travs de un bote sifnico comn.
Junio 2008
137
parmetro
de
medida,
aplicable
exclusivamente
en
Junio 2008
136
Junio 2008
135
Consideraciones importantes:
Los dimetros de las tuberas son los apropiados para transportar
los caudales previsibles en condiciones seguras
Las redes de tuberas se disean de tal forma que sean accesibles
para su mantenimiento y reparacin, para lo cual deben disponerse a la
vista o alojadas en huecos o patinillos registrables.
El trazado se realizar lo ms sencillo posible para conseguir
circulacin natural por gravedad, evitando los cambios bruscos de
direccin.
Las derivaciones de fregaderos, lavadoras, lavavajillas se harn
con sifn individual. La distancia a la bajante debe ser de 4 metros como
mximo, con pendientes comprendidas entre 2,5% y 5%.
Los desages de inodoros irn directamente a la bajante por
medio de un manguetn de acometida de longitud igual o menor que
1metro, siempre que no sea posible dar al tubo la pendiente.
Las derivaciones que acometan al bote sifnico tendrn una
longitud igual o menor que 2,5 metros, con una pendiente comprendida
entre el 2%-4%.
Los restantes aparatos acometern a un bote sifnico comn que
desembarcar directamente a la bajante.
La distancia entre el bote sifnico y la bajante no debe ser mayor
que 2 metros.
Las tuberas horizontales irn siempre situadas a una cota inferior
de la red de distribucin de agua con pendiente supuesta, la ms
desfavorable que corresponde al 1%.
Junio 2008
134
las aguas
Junio 2008
133
Junio 2008
132
Junio 2008
131
1.- MEMORIA
DESCRIPTIVA
Junio 2008
130
Captulo 3:
Instalacin de
Saneamiento
Junio 2008
129
Junio 2008
128
Junio 2008
127
Junio 2008
126
3.4.6.-Vaso de expansin.
Junio 2008
125
Junio 2008
124
Junio 2008
123
Junio 2008
122
Junio 2008
121
3.4.2.-Acumulador de A.C.S
Junio 2008
120
3.4.- Catlogos
3.4.1.- Captador LB Wagner poner todo.
Junio 2008
119
Junio 2008
118
3.3.3.- Pruebas
Todas las pruebas se efectuaran en presencia del director de obra o
persona en quien delegue, quien deber dar su conformidad tanto al
procedimiento seguido como a los resultados.
Las redes de conductos deben someterse a pruebas de resistencia
estructural y estanqueidad.
Junio 2008
117
Junio 2008
116
Junio 2008
115
captacin superior a 20 m 2 .
El plan de mantenimiento debe realizarse por personal tcnico
competente que conozca la tecnologa solar trmica y las instalaciones
Junio 2008
114
3.2.- Mantenimiento
Sin perjuicio de aquellas operaciones de mantenimiento derivadas
de otras normativas, para englobar todas las operaciones necesarias
durante la vida de la instalacin para asegurar el funcionamiento,
aumentar la fiabilidad y prolongar la duracin de la misma, se definen
dos escalones complementarios de actuacin:
1) plan de vigilancia;
2) plan de mantenimiento preventivo.
Junio 2008
113
Tabla 2- 29.- Caudal instantneo mnimo para cada tipo de aparato (CTE HS4 Tabla 2.1)
Junio 2008
112
Altitud(m)
40
Latitud(C)
36,7
Longitud(C)
4,4W
T min(C)
-4
Tabla 2- 27.- Datos de altitud, latitud y temperatura mnima
Junio 2008
111
Tred(C)
T amb(C) H(MJ/m^2 dia)
ENE
8
15
8,3
FEB
9
15
12
MARZO
11
17
15,5
ABRIL
13
19
18,5
MAYO
14
21
23,2
JUNIO
15
25
24,5
JULIO
16
27
26,5
AGOST
15
28
23,2
SEPT
14
26
19
OCT
13
22
13,6
NOV
11
18
9,3
DIC
8
15
8
12,3
20,7
16,8
AO
Tabla 2- 26.- Datos para la provincia de Mlaga (CENSOLAR) Pliego de condiciones Tcnicas
de Instalaciones de Baja Temperatura con Energa Solar Trmica. (referidas a la capital)
Junio 2008
110
3.1.-Tablas
Tabla 2- 23.- Contribucin solar mnima en %. Caso general (Tabla 2.1 del CTE HE4 Ahorro de
energa)
Tabla 2- 24.- Contribucin solar mnima en %. Caso efecto Joule (Tabla 2.2 del CTE HE4
Ahorro de energa)
Tabla 2- 25.- Demanda de referencia a 60C (Tabla 3.1 del CTE HE4 Ahorro de energa)
Junio 2008
109
3.- ANEXOS:
Junio 2008
108
Junio 2008
107
2.14.- Bomba
Clculo de la potencia de la bomba de circulacin en funcin de la
prdida de carga:
Potencia de la bomba= caudal ( m3 /seg)*prdida de carga(N/ m 2 )
Potencia de la bomba = 0.00092 76048 =70 W
Prdida de carga (7.76 9800
Caudal =
N
) / 1mca =76.048 N/ m 2
2
m
3314 / 1000 3
m / seg
3600
depsito
de
expansin
interviene
un
nmero
adimensional
ku =
p f pi
pf
Junio 2008
106
perdida unit
perdida unit
perdida
perdida total
mbar
9 capt(mbar)
18 capt(mbar)
mca
126,95
1.142,98
1.714,479
17,48
Tabla 2- 22.- Prdida de carga en colectores serie-paralelo
Junio 2008
105
portador
utilizado:
propilenglicol
con
inhibidores,
Junio 2008
104
2850.59
= 325 J
365 24
m=
Q
77.77
=
= 29.31 kg / m 2 h
ce T 0.8843 3
cm
115.2 29.31
= 3313.55 litros/hora 3.314 litros hora
1.019
3314
= 28.76l/ h m 2 30l/ h m 2
115.2
Junio 2008
103
area
colector
- Sustitucin energtica(%) =
V
< 180
A
Junio 2008
102
2
2.6.- Energa disponible por m superficie colectora.
NEi ( MJ )
Aportacioni ( MJ / m 2 )
Sup.colectora
m2
colector
Junio 2008
101
[ MJ/ m 2 ]
E
t
[ W/ m 2 ]
Junio 2008
100
m 2 -dia])
Junio 2008
99
2.- CLCULOS
JUSTIFICATIVOS
Junio 2008
98
1.16.-Conclusin
Con la presente Memoria, Clculos y Planos que se acompaan, se
da por concluido el estudio de la Instalacin, que ser ejecutada por el
Instalador Autorizado, segn lo indicado y de acuerdo a las Normas
vigentes.
Una vez presentado ante los Organismos Oficiales que lo requieran
y realizadas todas las pruebas necesarias en presencia del Instalador
Autorizado, del Representante de la Propiedad y de los Organismos
competentes, se efectuar la recepcin de la Instalacin.
Junio 2008
97
caudal
litros/seg
0,065
0,1
lavabo
ducha
lavavajillas
industrial
0,2
lavadora industrial
0,4
Tabla 2- 20: Caudales de aparatos sanitarios para ACS
Junio 2008
96
depsito
de
expansin
interviene
un
nmero
adimensional
0,67*0,045 = 0,301 m 3
0,301*0,7 = 0,021 m 3 = 21 litros
En la instalacin se colocar un vaso de expansin VASOFLEX/S,
de 25 litros que es volumen normalizado inmediatamente superior. Sus
caractersticas se adjuntan en el anexo de catlogos.
Junio 2008
95
Tramo
1
2
3
4
Tramo
1
2
3
4
colectores
l/colector
total (litros)
colectores
6
3
1
2
Dext(mm)
42
35
18
28
18
3,00
54
Q(l/h)
3.314,00
1.657,00
552,33
1.104,67
Dint(mm)
39
32
16
25
long(m)
98,56
24,24
21,66
23,76
Dint(m)
0,039
0,032
0,016
0,025
intercambiador
canales
litros/canal
total (litros)
Vol(m^3)
0,00
0,01
0,00
0,01
TOTAL(m^3)
Tabla 2- 19.- Clculo del volumen del circuito primario
18
0,059
1,062
0,67
Junio 2008
94
- Vlvulas antirretorno:
Las vlvulas antirretorno impiden el paso del fluido absolutamente
en un sentido de la tubera.
Junio 2008
93
1.14.-Elementos auxiliares:
1.14.1.- Vlvulas
La eleccin de las vlvulas se realizar de acuerdo con la funcin
que desempeen:
-Vlvulas de corte de esfera a la entrada y salida de cada
dispositivo para poder aislarlo en caso de mantenimiento, sustitucin o
reparacin.
Junio 2008
92
Junio 2008
91
prdida
unitaria
mca
1,5
total
mca
depsitos
3
4,5
intercambiador
1
2,23
tuberas
17,754
TOTAL
24,48
Tabla 2- 18.- Prdida de carga del circuito secundario
Junio 2008
90
TRAMO
1
2
3
4
Dimetro
mm
42
35
28
18
long total
m
163,46
82,48
25,96
23,76
Intercambiador CB 26 -H
Colector
LB 6,4
perdida unit
mmca
22,95
15,92
24,71
27,45
perdida
total
mca
3,75
1,31
0,64
0,65
24 placas
2,23
17,48
TOTAL
26,07
Junio 2008
89
elemento
"te" derivacin
a ramal
curva 90
reduccin
vlvula de
retencin
vlvula de bolas
vlvula
mezcladora
vlvula de
seguridad
diametro
mm
42
long
unit
m
0,5
35
numero elem
1
total
m
0,5
0,4
1,6
28
0,3
0,6
diametro
mm
42
35
long
unit
m
4,6
4,1
numero elem
total
m
4,1
42
35
28
42-35
35-28
28-18
42
0,96
0,84
0,6
1
0,85
0,65
10
5
1
4
2
2
2
2
4,8
0,84
2,4
2
1,7
1,3
20
42
30
30
42
42
1,8
1
2
4
3,6
4
TOTAL(42 mm)
TOTAL(35 mm)
TOTAL(28 mm)
64,9
58,24
4,3
Junio 2008
88
1.12.-Grupo de presin
La instalacin de produccin de A.C.S. es un sistema de circulacin
forzada, que transportar los fluidos por las tuberas mediante la accin
de bombas.
Las bombas empleadas sern centrfugas montadas en lnea con eje
horizontal. Para evitar el dao producido por averas y garantizar el
correcto funcionamiento de las mismas, se recomienda situar dos bombas
en paralelo por ser un sistema de ms de 50 m 2 .
Para la eleccin correcta de la potencia de las bombas se deben
conocer las prdidas de carga totales de cada uno de los circuitos, que
incluyen las lineales y las prdidas ocasionadas por la introduccin de
Junio 2008
87
Tramo
1
2
3
4
grupos
D
colect
proporcin Q (l/hora) Q(m^3/h) D(mm) Dnom(mm) int(mm)
6
Q
3314,00
3,314
33,46
42
39
3
Q/2
1657,00
1,657
26,25
35
32
1
Q/6
552,33
0,552
17,87
18
16
2
Q/3
1104,67
1,105
22,78
28
25
Tabla 2- 15.- Caudales y secciones del circuito segundario
Tramo
1
2
3
4
Q (l/hora)
Radio_int (m)
vel(m/s)
hPa
3314,00
0,0195
0,77
2,25
1657,00
0,016
0,57
1,45
552,33
0,008
0,76
2,25
1104,67
0,0125
0,63
2,50
Tabla 2- 16.- Prdidas de carga del circuito primario
mmca
22,95
15,92
24,71
27,45
Junio 2008
86
3314
= 28.76l/ h m 2 30l/ h m 2
115.2
0 .5 v 1 .5
H< 30 mmca
Junio 2008
85
kcal/kg k
calor especfico
3,7
0,8843
densidad(g/cm^3)
1,019
Tabla 2- 14.- Calor especfico y densidad del fluido-calorportador
Junio 2008
84
Junio 2008
83
potencia
sup.
Intercambio
(MW)
(kcal/h)
mxima
57,6
49.560,76
mnima
83,2
71.587,77
m^2
38,4
28,8
Junio 2008
82
Junio 2008
81
Junio 2008
80
Consideraciones generales:
- La conexin de entrada de agua caliente procedente del
intercambiador o de los captadores al cumulador se realizar a una altura
comprendida entre el 50% y 75% de la altura total del mismo.
- La conexin de salida de agua fra del acumulador hacia el
intercambiador o los captadores se realizar por la parte inferior de ste.
Junio 2008
79
un volumen de
V
< 180 ( Vmax = 20.736 litros Vmin = 5.760 litros)
A
V
6320
=
= 54.86 comprendido entre 50-180
A 115.2
Junio 2008
78
1.9.-Subconjunto almacenamiento
1.9.1.- Dimensionado
El almacenamiento de agua se realiza por medio de depsitos
acumuladores. Estos elementos permiten solucionar el problema de
indisponibilidad energtica en ciertos meses del ao por la ausencia de
produccin. Su funcin consiste en almacenar agua que va a ser calentada
hasta la temperatura de utilizacin. Debido al aumento de temperatura de
la misma y a la falta de movimiento de aire en el interior del depsito se
un fenmeno de estratificacin trmica. De esta manera, los mayores niveles
trmicos se encontrarn en la parte ms elevada del depsito.
La eleccin del depsito garantiza la durabilidad del equipo y
proteccin frente a la corrosin debido a que el agua a la temperatura
obtenida va a ser utilizada para el consumo humano. El dimensionado de
los mismos se debe realizar en funcin de los siguientes parmetros:
- superficie captacin
- la demanda energtica
- la temperatura de utilizacin
Junio 2008
77
1.8.6.- Purgador
Con objeto de eliminar los gases contenidos en el fluido
calorportador, se dispondr al sistema de un purgador cada grupo de tres
colectores
Junio 2008
76
sin
sin 45
+ cos ) = 4.785 (
+ cos 45) = 9,17 m
tg (h0 )
tg 30.3
Junio 2008
75
Junio 2008
74
Junio 2008
73
Junio 2008
72
Necesidades energticas
Aportacin solar
Energa (MJ)
50000,00
40000,00
30000,00
20000,00
10000,00
DI
C
EN
E
FE
M B
AR
ZO
AB
R
IL
M
AY
O
JU
NI
O
JU
LI
AG O
O
ST
SE
PT
O
C
T
NO
V
0,00
mes
Sustitucin energtica
120,00
100,00
(%)
80,00
60,00
40,00
20,00
DI
C
V
NO
O
C
SE
P
JU
L
AG
O
JU
N
EN
E
FE
B
M
AR
AB
R
M
AY
0,00
meses
Junio 2008
71
Nec
energticas
Energa disp
Dficit
Cob. mensual
(MJ)
(MJ)
(MJ)
(%)
ENE
32.812,68
18.455,67
14.357,01
56,25
FEB
39.137,06
22.438,13
16.698,93
57,33
MARZO
40.195,53
27.855,03
12.340,50
69,30
ABRIL
37.311,19
27.555,69
9.755,50
73,85
MAYO
37.734,58
29.916,63
7.817,95
79,28
JUNIO
35.723,48
28.199,67
7.523,81
78,94
JULIO
36.093,95
34.345,06
1.748,89
95,15
AGOST
36.914,27
35.191,29
1.722,97
95,33
SEPT
36.517,34
34.960,79
1.556,55
95,74
OCT
38.554,90
30.328,52
8.226,38
78,66
NOV
38.898,90
21.324,27
17.574,63
54,82
DIC
42.656,49
17.817,43
24.839,06
41,77
452.550,39
328.388,21
TOTAL
Tabla 2- 9.- Cobertura mensual para 18 colectores solares
mes
n colectores cobertura
25
100,78(%)
20
80,63(%)
18
72,56(%)
Tabla 2- 10.- Cobertura anual para 25, 20 y 18 colectores solares
Junio 2008
70
mes
ENE
FEB
MARZO
ABRIL
MAYO
JUNIO
JULIO
AGOST
SEPT
OCT
NOV
DIC
TOTAL
mes
ENE
FEB
MARZO
ABRIL
MAYO
JUNIO
JULIO
AGOST
SEPT
OCT
NOV
DIC
TOTAL
Junio 2008
69
50
55
60
1,6
1,4
1,2
1
0,8
0,6
0,4
0,2
EN
E
FE
B
M
A
R
AB
R
M
A
Y
JU
N
JU
L
AG
O
SE
P
O
C
T
N
O
V
0
m es
Junio 2008
68
Junio 2008
67
Junio 2008
Mes
ENE
FEB
MARZO
ABRIL
MAYO
JUNIO
JULIO
AGOST
SEPT
OCT
NOV
DIC
Sup colect
terica(m^2)
204,82
200,93
166,24
155,98
145,30
145,94
121,07
120,84
120,33
146,45
210,14
275,80
Sup colectora
(m^2)
n colectores
Superficie colec
real(m^2)
160,00
160,00
160,00
160,00
160,00
160,00
160,00
160,00
160,00
160,00
160,00
160,00
66
n colec
terico
32,00
31,40
25,97
24,37
22,70
22,80
18,92
18,88
18,80
22,88
32,83
43,09
n colect
real
25,00
25,00
25,00
25,00
25,00
25,00
25,00
25,00
25,00
25,00
25,00
25,00
158,76
24,81
Tabla 2- 5.- Superficie colectora necesaria/ n colectores solares
Junio 2008
Sustitucin
energtica
(%)
78,12
79,63
96,25
102,57
110,11
109,64
132,16
132,41
132,97
109,25
76,14
58,01
Frac solar
(%)
78,12
79,63
96,25
100,00
100,00
100,00
100,00
100,00
100,00
100,00
76,14
58,01
Dficit
energtico
(MJ)
7.179,80
7.972,99
1.507,99
-960,60
-3.816,30
-3.442,73
-11.607,52
-11.962,53
-12.039,31
-3.568,04
9.281,86
17.910,06
Mes
ENE
FEB
MARZO
ABRIL
MAYO
JUNIO
JULIO
AGOST
SEPT
OCT
NOV
DIC
AO
I
(w/m^2)
528,01
647,91
652,39
615,40
522,88
475,22
506,60
547,53
653,70
674,20
617,73
567,55
Tamb
c
15
15
17
19
21
25
27
28
26
22
18
15
20,7
65
Junio 2008
EN disponible(mes)
(MJ/m^2 mes)
160,21
194,78
241,80
239,20
259,69
244,79
298,13
305,48
303,48
263,27
185,11
154,67
2.850,59
64
A continuacin se presentan los resultados obtenidos para captadores LB 6.4 del fabricante Wagner.
Mes
das/mes
% ocupacin
consumo (mes)
ENE
31
100%
195,92
Tred
Salto trmico
NE mensual
NE diaria
H correg
(C)
Tm-Tred
MJ
MJ
(MJ/m^2 dia)
(k=1)
40
32.812,68
1.058,47
8,3
8,3
k(latitud)
1,34
n horas sol
(MJ/m^2)
(h)
10,45
5,5
FEB
29
100%
183,28
51
39.137,06
1.349,55
12
12
1,22
13,76
5,9
MARZO
31
100%
195,92
11
49
40.195,53
1.296,63
15,5
15,5
1,08
15,74
6,7
ABRIL
30
100%
189,6
13
47
37.311,19
1.243,71
18,5
18,5
0,93
16,17
7,3
MAYO
31
100%
195,92
14
46
37.734,58
1.217,24
23,2
23,2
0,82
17,88
9,5
JUNIO
30
100%
189,6
15
45
35.723,48
1.190,78
24,5
24,5
0,78
17,96
10,5
JULIO
31
100%
195,92
16
44
36.093,95
1.164,32
26,5
26,5
0,82
20,43
11,2
AGOST
31
100%
195,92
15
45
36.914,27
1.190,78
23,2
23,2
0,94
20,50
10,4
SEPT
30
100%
189,6
14
46
36.517,34
1.217,24
19
19
1,12
20,00
8,5
OCT
31
100%
195,92
13
47
38.554,90
1.243,71
13,6
13,6
1,31
16,75
6,9
NOV
30
100%
189,6
11
49
38.898,90
1.296,63
9,3
9,3
1,45
12,68
5,7
DIC
31
100%
195,92
52
42.656,49
1.376,02
1,44
10,83
5,3
AO
365
100%
2.313,12
12,3
47,7
452.550,39
16,8
16,8
Junio 2008
15,71
63
los clculos de
36,7
inclinacin
50
correcin H
n camas
79
l/da
80
rea colector
6,4
rendimiento
79,40%
k1(W/m^2 *k)
2,49
k2(W/m^2 k)
0,018
Tm
48
Junio 2008
62
n
personas
79
30
30
10
total
n camas
4.345
vestuarios
450
gimnasio
600
peluquera
100
5.495
<--Total
Tabla 2- 1.- Consumo en litros del edificio
litros/dia
55
15
20
10
Junio 2008
61
Junio 2008
60
Junio 2008
59
Ilustracin 2- 6.- Esquema de flujos de energa en los colectores planos de alto rendimiento
Junio 2008
58
Junio 2008
57
Junio 2008
56
Junio 2008
55
Junio 2008
54
1.4.-Introduccin a la tecnologa.
La energa solar trmica consiste en el aprovechamiento del calor
solar mediante el uso de colectores o paneles solares trmicos. No genera
energa elctrica, al contrario que la energa solar fotovoltaica.
Existen varias tecnologas para el aprovechamiento de la energa
solar, pero las principales son: la circulacin natural y la forzada.
no
hay
elementos en el
sistema
de
tipo
Junio 2008
53
INTA.
- Norma UNE de obligado cumplimiento.
- Norma UNE 100030 Gua para la prevencin y control de la
proliferacin y diseminacin de legionela en instalaciones.
- Procedimiento bsico para la certificacin de eficiencia energtica
de edificios de nueva construccin. REAL DECRETO 47/2007, de 19 de
enero, por el que se aprueba el Procedimiento bsico para la certificacin
de eficiencia energtica de edificios de nueva construccin.
-Conservacin de la Energa ley 82/1980, de 30 de diciembre, sobre
Conservacin de la Energa.
- Homologacin de los Paneles Solares REAL DECRETO 891/1980,
de 14 de abril, sobre Homologacin de los Paneles Solares.
Junio 2008
52
Junio 2008
51
Junio 2008
50
1.- MEMORIA
DESCRIPTIVA
Junio 2008
49
Captulo 2:
Produccin de ACS
mediante energa solar
trmica
Junio 2008
48
Junio 2008
47
para
la
prevencin
control
de
la
legionelosis,
equipos
que
necesiten
operaciones
peridicas
de
Junio 2008
46
Junio 2008
45
Junio 2008
44
Tabla 1- 19. - Relacin entre dimetro de tuberas y caudal recirculado de ACS (CTE 4.4.1)
Tabla 1- 20.- valores del dimetro nominal de la vlvula reductora de presin en funcin del
caudal mximo simultneo
Junio 2008
43
Tabla 1- 16: Dimetros mnimos de derivaciones a los aparatos (CTE HS4 Tabla 4.2 )
Junio 2008
42
3.1.- Tablas
Tabla 1- 14: CTE HS4 Tabla 2.1.-Caudal instantneo mnimo para cada tipo de aparato
0,75
Espesor nominal mm
1,2
1,5 2
2,5
Dimetro
nominal(mm)
Presiones de trabajo
kg/cm^2
6
8
10
12
15
18
22
28
35
42
54
63
80
100
147
102
78
63
49
40
220
146
110
88
68
55
44
33
27
22
69
53
41
34
26
22 29
17 23
18
Tabla 1- 15.- Presin de Trabajo en tuberas de cobre UNE 37.141-76
53
41
32
27
20
23
Junio 2008
41
3.- ANEXOS
Junio 2008
40
Junio 2008
39
Junio 2008
TRAMO
caudal
(litros
seg)
n ap
0,875
9,000
0,545
D12-E
E-F
D10D11
D11D12
"k"
caudal
38
diametro velocidad
Le
Pi
Pi-J
(mca)
(mca)
(m)
(litros/seg)
(mm)
(m/s)
mca/m)
(m)
(m)
(mca)
0,354
0,309
25
0,630
0,025
5,380
0,000
0,135
-13,499 -13,634
5,000
0,500
0,273
25
0,555
0,020
2,200
0,000
0,044
-13,634 -13,678
0,215
1,000
1,000
0,215
20
0,685
0,038
6,130
1,260
0,284
-13,678 -13,962
0,260
4,000
0,577
0,150
15
0,849
0,080
3,500
0,150
0,293 -13,962 -14,254
Tabla 1- 12.- Dimetros y prdidas de carga de tuberas en la planta segunda para agua caliente
Junio 2008
Pr
(mca)
0,000 13,634
0,000 13,678
0,000 13,962
-3,500 17,754
TRAMO
C7-C6
C6-C5
C5-C
C-C1
C1-C2
C2-C3
C3-C4
C-D
TRAMO
D5-D6
D4-D5
D3-D4
D2-D3
D1-D2
D0-D1
D-D0
D7-D
D8-D7
D9-D8
D10-D9
caudal
(litros
seg)
0,165
0,495
0,560
0,955
0,625
0,295
0,130
caudal
(litros
seg)
0,330
0,660
0,990
1,320
1,650
1,980
2,045
2,195
1,865
1,535
1,205
n ap
"k"
caudal
37
diametro velocidad
Le
Pi
(litros/seg)
(mm)
(m/s)
mca/m)
(m)
(m)
(mca)
(mca)
2,000 1,000
0,165
20
0,525
0,024
4,870
0,000
0,117 -10,033
6,000 0,447
0,221
20
0,705
0,040 11,570
0,500
0,487 -9,546
7,000 0,408
0,229
20
0,728
0,043
0,780
3,000
0,161 -9,385
15,000 0,267
0,255
20
0,812
0,052
1,770
3,000
0,247 -9,385
10,000 0,333
0,208
20
0,663
0,036
7,580
0,500
0,293 -9,632
6,000 0,447
0,132
15
0,747
0,064
7,380
0,000
0,472 -9,925
2,000 1,000
0,130
15
0,736
0,062 11,300
0,800
0,754 -10,397
0,866
40
0,689
0,016
3,500
4,600
0,132 -9,385
Tabla 1- 10.- Dimetros y prdidas de carga de tuberas en la planta primera para agua caliente
n ap
4,000
8,000
12,000
16,000
20,000
24,000
25,000
25,000
21,000
17,000
13,000
"k"
caudal
diametro velocidad
Le
Pi
(litros/seg)
(mm)
(m/s)
mca/m)
(m)
(m)
(mca)
(mca)
0,577
0,191
20
0,606
0,031
2,200
0,000
0,068 -13,566
0,378
0,249
25
0,508
0,017
5,300
0,650
0,103 -13,464
0,302
0,298
25
0,608
0,024
2,200
0,000
0,052 -13,412
0,258
0,341
25
0,694
0,030
5,300
0,000
0,158 -13,254
0,229
0,379
25
0,771
0,036
2,200
0,650
0,102 -13,152
0,209
0,413
32
0,513
0,013
8,810
0,000
0,113 -13,039
0,204
0,417
40
0,332
0,005
0,180
4,600
0,022 -13,017
0,204
0,448
32
0,557
0,015
2,880
4,100
0,104 -13,017
0,224
0,417
25
0,850
0,042
2,200
0,000
0,093 -13,121
0,250
0,384
25
0,782
0,037
5,380
0,000
0,197 -13,214
0,289
0,348
25
0,709
0,031
2,200
0,650
0,088 -13,411
Tabla 1- 11.- Dimetros y prdidas de cargas de tuberas en la planta primera para agua caliente
Junio 2008
Pi-J
(mca)
(m)
-10,151 0,000
-10,033 0,000
-9,546 0,000
-9,632 0,000
-9,925 0,000
-10,397 0,000
-11,151 0,000
-9,517 -3,500
Pr
(mca)
-10,151
-10,033
-9,546
-9,632
-9,925
-10,397
-11,151
-13,017
Pi-J
Pr
(mca)
-13,634
-13,566
-13,464
-13,412
-13,254
-13,152
-13,039
-13,121
-13,214
-13,411
-13,499
(m)
0,000
0,000
0,000
0,000
0,000
0,000
0,000
0,000
0,000
0,000
0,000
(mca)
-13,634
-13,566
-13,464
-13,412
-13,254
-13,152
-13,039
-13,121
-13,214
-13,411
-13,499
TRAMO
O-A
A-A1
A-B
TRAMO
B2-B3
B1-B2
B-B1
B4-B5
B-B4
B-C
caudal
(litros
seg)
n ap
0,130
2,000
caudal
(litros
seg)
0,260
0,325
2,425
0,395
0,790
n ap
4,000
5,000
11,000
5,000
10,000
"k"
caudal
36
diametro velocidad
Le
Pi
(litros/seg)
(mm)
(m/s)
mca/m)
(m)
(m)
(mca)
(mca)
2,510
65
0,756
0,010 29,410
1,940
0,328
0,000
1,000
0,130
15
0,736
0,062
0,750
2,400
0,196 -1,828
2,380
65
0,717
0,010
3,900
2,100
0,057 -1,828
Tabla 1- 8.- Dimetros y prdidas de carga de tuberas en la planta stano para agua caliente
"k"
caudal
diametro velocidad
Le
Pi
(litros/seg)
(mm)
(m/s)
mca/m)
(m)
(m)
(mca)
(mca)
0,577
0,150
15
0,849
0,080 11,860
0,500
0,991 -6,205
0,500
0,163
20
0,517
0,023 13,160
0,500
0,321 -5,884
0,316
0,767
40
0,610
0,013
2,880
4,600
0,099 -5,785
0,500
0,198
32
0,246
0,004
0,600
0,850
0,005 -5,867
0,333
0,263
32
0,327
0,006
9,770
4,100
0,081 -5,785
1,349
50
0,687
0,012
3,500
4,600
0,100 -5,785
Tabla 1- 9.- Dimetros y prdidas de carga de tuberas en la planta baja para agua caliente
Junio 2008
Pi-J
Pr
(mca)
-0,328
-2,024
-1,885
(m)
-1,500
0,000
-3,900
(mca)
-1,828
-2,024
-5,785
Pi-J
Pr
(mca)
-7,196
-6,205
-5,884
-5,872
-5,867
-5,885
(m)
0,000
0,000
0,000
0,000
0,000
-3,500
(mca)
-7,196
-6,205
-5,884
-5,872
-5,867
-9,385
TRAMO
C7-C6
C6-C5
C5-C
C-C1
C1-C2
C2-C3
C3-C4
caudal
(litros seg)
0,40
1,20
1,40
2,40
1,60
0,80
0,40
C-D
TRAMO
n ap
"k"
3
9
11
19
13
7
4
0,707
0,354
0,316
0,236
0,289
0,408
0,577
Pi
(mca)
-8,632
-8,090
-7,926
-7,926
-8,200
-8,627
-8,835
Pi-J
(mca)
-8,736
-8,632
-8,090
-8,200
-8,627
-8,835
-9,373
2,40
65
0,723
0,010 3,50 6,20 0,094 -7,926
Tabla 1- 6.- Dimetros y prdidas de carga de tuberas en la planta primera para agua fra
-8,020
caudal
n ap
(litros seg)
D11-D12
1,30
D12-E
0,50
E-F
0,80
35
"k"
caudal
diametro velocidad
j
L
Le
(litros/seg)
(mm)
(m/s)
mca/m) (m)
(m)
0,28
25
0,576
0,021 4,87 0,00
0,42
25
0,864
0,044 11,57 0,85
0,44
32
0,550
0,015 0,78 10,50
0,57
32
0,703
0,022 1,77 10,50
0,46
25
0,941
0,051 7,58 0,85
0,33
25
0,665
0,028 7,53 0,00
0,23
20
0,735
0,043 11,30 1,10
L
(m)
Junio 2008
Le
(m)
J
(mca)
Pi
(mca)
Pi-J
(mca)
H
Pr
(m)
(mca)
0,000 -8,736
0,000 -8,632
0,000 -8,090
0,000 -8,200
0,000 -8,627
0,000 -8,835
0,000 -9,373
3,500 11,520
Pr
(mca)
8
0,378
0,49
32
0,612
0,018 2,20 0,00 0,039 -12,324 -12,363 0,000 12,363
2
1,000
0,50
32
0,625
0,018 6,13 1,68 0,142 -12,363 -12,505 0,000 12,505
8
0,378
0,30
25
0,616
0,024 3,50 1,25 0,115 -12,505 -12,619 3,500 16,119
Tabla 1- 7.- Dimetros y prdidas de carga de tuberas en la planta segunda y cubierta para agua fra
caudal
diametro velocidad
j
(litros/seg)
(mm)
(m/s)
mca/m)
J
(mca)
0,105
0,542
0,164
0,274
0,427
0,208
0,539
H
(m)
TRAMO
caudal
(litros seg)
N ap
0,40
O-A
A-A1
A-B
TRAMO
B2-B3
B1-B2
B-B1
B4-B5
B-B4
B-C
"k"
caudal
(litros/seg)
4,94
0,577
0,23
34
diam.
(mm)
80
20
vel.
j
L
(m/s) (mca/m) (m)
0,983
0,013 23,90
0,735
0,043
3,38
Le
(m)
0,00
8,55
J
(mca)
0,305
0,518
Pi
(mca)
0,000
-0,305
Pi-J
(mca)
-0,305
-0,823
4,71
80
0,937
0,012
3,90 2,40 0,074 -0,305 -0,379
Tabla 1- 4.- Dimetros y prdidas de carga de tuberas en la planta stano para agua fra
caudal
(litros seg)
0,80
1,00
3,10
0,90
1,80
n ap
"k"
8
10
16
7
14
0,378
0,333
0,258
0,408
0,277
Pi
(mca)
-5,297
-4,896
-4,279
-4,673
-4,279
Pi-J
(mca)
-5,597
-5,297
-4,896
-4,722
-4,673
3,41
65
1,027
0,018 3,50 4,70 0,147 -4,279
Tabla 1- 5.- Dimetros y prdidas de carga de tuberas en la planta baja para agua fra
-4,426
caudal
diametro velocidad
j
L
Le
(litros/seg)
(mm)
(m/s)
mca/m) (m)
(m)
0,30
25
0,616
0,024 11,86 0,60
0,33
25
0,679
0,029 13,16 0,85
0,80
32
0,995
0,041 2,88 12,15
0,37
25
0,749
0,034 0,60 0,85
0,50
32
0,621
0,018 9,77 12,15
Junio 2008
J
(mca)
0,301
0,401
0,617
0,049
0,394
H
(m)
0,000
0,000
3,900
Pr
(mca)
-0,305
-0,823
-4,279
H
(m)
0,000
0,000
0,000
0,000
0,000
3,500
Pr
(mca)
-5,597
-5,297
-4,896
-4,722
-4,673
-7,926
33
Junio 2008
32
Junio 2008
31
Ilustracin 1- 4.- Distribucin del bao de aseo de uso comn ubicado en los pasillos
Junio 2008
30
Junio 2008
29
Siendo:
J: prdida de carga en mca/m
L: longitud en tramo recto
Junio 2008
28
b=
Dv 4
Con lo que:
v
J = 4
5
4
D v
1
4
= 4
7
4
5
D4
Llamando m al producto 4
7
J= m
v4
D
5
4
Siendo:
m: constante del material de la tubera
J: prdida de carga por m de tubera en mca
v: velocidad media circulante en m/s
D: dimetro de la tubera en metros.
m: constante del material (en el caso de cobre 0,00056)
las
Junio 2008
27
Junio 2008
26
Siendo:
A: rea transversal de la tubera
v: velocidad de la tubera
lavabo
ducha
inodoro
fregadero
lavavajillas
industrial
lavadora industrial
Tubo de cobre
(mm)
12
12
12
12
20
25
20
Montante/descendente
20
(montante)
Tabla 1- 3.- Dimetros mnimos para baos y montantes
Junio 2008
25
Procedimiento de clculo:
1.- Determinacin del caudal instantneo total, realizando el
sumatorio de los caudales de cada uno de los aparatos a los que va a
alimentar la tubera.
2.- Clculo del coeficiente de simultaneidad y aplicacin al caudal
instantneo, obteniendo el consumo punta.
3.- Clculo del dimetro interior partiendo de un valor de velocidad
prefijado,
aproximacin
al
valor
del
dimetro
normalizado
inmediatamente superior.
rea= r 2
Q = Av
Junio 2008
24
k=
1
N 1
Junio 2008
23
agua
fra(l/s)
0,1
0,2
0,2
0,1
0,6
agua
caliente(l/s)
0,065
0,1
0,1
lavabo
fregadero
ducha
inodoro
lavadora industrial
0,4
lavavajillas
industrial
0,25
0,2
Tabla 1- 1.- Caudales de aparatos sanitarios litros/seg.
Junio 2008
22
2.- CLCULOS
JUSTIFICATIVOS
Junio 2008
21
1.6.- Conclusin
Con la presente Memoria, Clculos y Planos que se acompaan, se
da por concluido el estudio de la Instalacin, que ser ejecutada por el
Instalador Autorizado, segn lo indicado y de acuerdo a las Normas
vigentes.
Una vez presentado ante los Organismos Oficiales que lo requieran
y realizadas todas las pruebas necesarias en presencia del Instalador
Autorizado, del Representante de la Propiedad y de los Organismos
competentes, se efectuar la recepcin de la Instalacin.
Junio 2008
20
Junio 2008
19
Junio 2008
18
Junio 2008
17
Junio 2008
16
instalaciones particulares.
Est formada por los siguientes elementos:
Acometida: es la tubera y elementos que enlaza la red de
distribucin con la instalacin interior general.
Toma: La toma se encuentra colocada sobre la tubera de
distribucin y sirve de enlace entre la acometida y la red. Debe permitir la
conexin con la red para realizar maniobras o manteniendo con facilidad,
sin que la tubera deje de estar en servicio.
Vlvula de Registro: La vlvula de registro situada en el exterior
del edificio, en la va pblica, junto a su fachada se alojada en un registro
Junio 2008
15
los
equipos
necesarios
(depsitos
de
acumulacin,
Junio 2008
14
Junio 2008
13
1.- MEMORIA
DESCRIPTIVA
Junio 2008
12
Captulo 1:
Instalacin de fontanera
Junio 2008
11
Junio 2008
10
NDICE DE ILUSTRACIONES
Instalacin de fontanera.
llustracin 1- 1: Esquema de acometida de red ............................................ 16
Ilustracin 1- 2: Distribucin de tuberas en los baos................................. 27
Ilustracin 1- 3: Distribucin del bao perteneciente a las habitaciones ... 31
Ilustracin 1- 4: Distribucin del bao de aseo de uso comn ubicado en
los pasillos ........................................................................................................... 31
Ilustracin 1- 5: Distribucin de tuberas en los vestuarios ......................... 32
Ilustracin 1- 6: Distribucin de la cocina ...................................................... 32
Junio 2008
Junio 2008
Instalacin de saneamiento
Tabla 3- 1: Unidades de descarga para aparatos sanitarios de cocina ..... 138
Tabla 3- 2.- Dimensionado de bajantes ......................................................... 154
Tabla 3- 3: Dimensionado de bajantes y arquetas ....................................... 156
Tabla 3- 4.- Unidades correspondientes a cada tipo de aparato (CTE HS5
Tabla 4.1) ........................................................................................................... 159
Tabla 3- 5: Dimetros de ramales colectores entre aparatos sanitarios y
bajante................................................................................................................ 159
Tabla 3- 6.- Dimetro de las bajantes segn el nmero de alturas del
edificio y el nmero de unidades de descarga (CTE HS5 Tabla 4.4)........ 160
Tabla 3- 7.- Dimetro de las bajantes segn el nmero de alturas del
edificio y el nmero de unidades de descarga (CTE HS5 Tabla 4.4)........ 160
Tabla 3- 8.- Dimetro de los colectores horizontales de aguas residuales en
funcin del nmero mximo de UD y la pendiente adoptada (CTE HS5
Tabla 4.5) ........................................................................................................... 160
Tabla 3- 9.- Nmero de sumideros en funcin de la superficie de cubierta
(CTE HS5 Tabla 4.6)......................................................................................... 161
Tabla 3- 10.- Dimetro de las bajantes de aguas pluviales para un rgimen
pluviomtrico de 100 mm/h. (CTE HS5 Tabla 4.8 ...................................... 161
Tabla 3- 11.- Dimetro de los colectores de aguas pluviales para un
rgimen pluviomtrico de 100 mm/h(CTE HS5 Tabla 4.9) ....................... 161
Tabla 3- 12.- Intensidad pluviomtrica I(mm/h) CTE HS5 Anexo B ....... 161
Tabla 3- 13.- Dimensiones de las arquetas (CTE HS5 Tabla 4.13) ............. 161
Instalacin de calefaccin
Tabla 4- 1: Superficies tiles del edificio....................................................... 170
Tabla 4- 2: Temperaturas consideradas en cada local................................. 173
Tabla 4- 3: Coeficientes de orientacin.......................................................... 175
Tabla 4- 4: mdulos de radiadores de la planta baja................................... 176
Tabla 4- 5: Mdulos de radiadores de la planta primera .......................... 177
Tabla 4- 6: mdulos de radiadores de la planta segunda........................... 177
Tabla 4- 7: dimetro de tuberas planta segunda ........................................ 182
Tabla 4- 8: dimetro de tuberas planta primera ......................................... 183
Tabla 4- 9: dimetro de tuberas planta baja ................................................ 183
Tabla 4- 10.- dimetro de tuberas stano..................................................... 184
Tabla 4- 11.- dimetro de tuberas del stano(circuito de ida y vuelta)... 184
Tabla 4- 12: Dimensionamiento de las bajantes........................................... 184
Tabla 4- 13: Coeficientes de orientacin........................................................ 192
Tabla 4- 14: Prdidas calorficas totales locales planta baja ....................... 193
Tabla 4- 15: Prdidas calorficas totales locales planta primera ................ 194
Tabla 4- 16: Prdidas calorficas totales locales planta segunda ............... 194
Junio 2008
Junio 2008
NDICE DE TABLAS
Instalacin de Fontanera
Tabla 1- 1.- Caudales de aparatos sanitarios litros/seg............................... 23
Tabla 1- 2.- Dimetros mnimos para cada aparato sanitario..................... 26
Tabla 1- 3.- Dimetros mnimos para baos y montantes........................... 26
Tabla 1- 4.- Dimetros y prdidas de carga de tuberas en la planta stano
para agua fra...................................................................................................... 34
Tabla 1- 5.- Dimetros y prdidas de carga de tuberas en la planta baja
para agua fra...................................................................................................... 34
Tabla 1- 6.- Dimetros y prdidas de carga de tuberas en la planta
primera para agua fra....................................................................................... 35
Tabla 1- 7.- Dimetros y prdidas de carga de tuberas en la planta
segunda y cubierta para agua fra ................................................................... 35
Tabla 1- 8.- Dimetros y prdidas de carga de tuberas en la planta stano
para agua caliente .............................................................................................. 36
Tabla 1- 9.- Dimetros y prdidas de carga de tuberas en la planta baja
para agua caliente .............................................................................................. 36
Tabla 1- 10.- Dimetros y prdidas de carga de tuberas en la planta
primera para agua caliente .............................................................................. 37
Tabla 1- 11.- Dimetros y prdidas de cargas de tuberas en la planta
primera para agua caliente ............................................................................... 37
Tabla 1- 12.- Dimetros y prdidas de carga de tuberas en la planta
segunda para agua caliente ............................................................................. 38
Tabla 1- 13.- Dimetros de red de acometida................................................. 39
Tabla 1- 14: CTE HS4 Tabla 2.1.-Caudal instantneo mnimo para cada
tipo de aparato.................................................................................................... 42
Tabla 1- 15.- Presin de Trabajo en tuberas de cobre UNE 37.141-76 ...... 42
Tabla 1- 16: Dimetros mnimos de derivaciones a los aparatos (CTE HS4
Tabla 4.2 ) ............................................................................................................ 43
Tabla 1- 17.- Dimetros mnimos de alimentacin (CTE HS4 Tabla 4.3) .. 43
Tabla 1- 18: longitud equivalente de accesorios para tuberas de cobre.... 44
Tabla 1- 19. - Relacin entre dimetro de tuberas y caudal recirculado de
ACS (CTE 4.4.1) ................................................................................................. 44
Tabla 1- 20.- valores del dimetro nominal de la vlvula reductora de
presin en funcin del caudal mximo simultneo ...................................... 44
Instalacin de produccin de ACS mediante energa solar trmica
Tabla 2- 1.- Consumo en litros del edificio.................................................... 62
Tabla 2- 2.- Datos de partida para la instalacin colectores solares........... 63
Tabla 2- 3.- Necesidades energticas mensuales y anual ............................ 64
Junio 2008
3.- ANEXOS................................................................................................................................240
3.1.- Tablas ..........................................................................................................................241
3.2.- Bibliografa ..................................................................................................................243
Junio 2008
CAPTULO 4: .............................................................................................................................166
INSTALACIN DE CALEFACCIN ...................................................................................166
1.- MEMORIA DESCRIPTIVA...............................................................................................167
1.1.- Objeto del proyecto......................................................................................................168
1.2.- Normativa utilizada ....................................................................................................168
1.3.- Descripcin general de la instalacin ..........................................................................168
1.4.- Descripcin de los cerramientos del edificio ................................................................170
1.5.- Determinacin de los coeficientes de transmisin de los cerramientos........................172
1.6.- Condiciones de la instalacin ......................................................................................173
1.7.- Evaluacin de las prdidas de carga consideradas:......................................................174
1.8.- Instalacin de radiadores:............................................................................................175
1.9.- Determinacin de la potencia de la caldera: ................................................................178
1.10.- Seleccin del quemador..............................................................................................178
1.11.- Depsito de expansin...............................................................................................179
1.12.- Distribucin de tuberas............................................................................................180
1.13.- Bombas de circulacin ...............................................................................................185
1.14.- Consumo anual de combustible .................................................................................185
1.15.- Conclusin ................................................................................................................186
2.- CLCULOS JUSTIFICATIVOS........................................................................................187
2.1.-Clculos de los coeficientes de transmisin de los cerramientos del edificio.................188
2.2.-Prdidas calorficas de los cerramientos .......................................................................191
2.3.- Clculo del volumen del depsito de expansin...........................................................195
2.4.- Dimensionado de tuberas ...........................................................................................196
2.5.- Bombas de circulacin .................................................................................................196
2.6.- Consumo anual de combustible...................................................................................198
3.- ANEXOS................................................................................................................................199
3.1.1.-Radiadores FERROLI, modelo Europa 800C ................................................................ 200
3.1.2.- Equipo caldera quemador .............................................................................................. 200
3.1.3.- Bomba circuladota Grundfos, modelo UPS 200 .......................................................... 203
CAPTULO 5: .............................................................................................................................204
INSTALACIN DE ELECTRICIDAD..................................................................................204
1.- MEMORIA DESCRIPTIVA...............................................................................................205
1.1.- Objeto del proyecto......................................................................................................206
1.2.- Reglamentacin aplicable: ...........................................................................................206
1.3.- Descripcin general de la instalacin ..........................................................................206
1.4.- Iluminacin .................................................................................................................207
1.4.1.- Iluminacin general ........................................................................................................ 208
1.4.2.- Iluminacin de emergencia............................................................................................ 208
Junio 2008
3.4.- Catlogos.....................................................................................................................120
3.4.1.- Captador LB Wagner poner todo.................................................................................. 120
3.4.2.-Acumulador de A.C.S...................................................................................................... 121
3.4.3.- Intercambiador de calor.................................................................................................. 122
3.4.4.- Anticongelante TYFOCOR............................................................................................. 123
3.4.5.- Caldera auxiliar Vitolas 200-F (Viessman) ................................................................... 125
3.4.6.-Vaso de expansin............................................................................................................ 126
3.4.7.- Bomba de llenado............................................................................................................ 128
3.4.8.- Bombas de circulacin Ebara: ....................................................................................... 128
CAPTULO 3: .............................................................................................................................130
INSTALACIN DE SANEAMIENTO..................................................................................130
1.- MEMORIA DESCRIPTIVA...............................................................................................131
1.1.- Objeto del proyecto......................................................................................................132
1.2.- Normativa utilizada ....................................................................................................132
1.3.- Descripcin general de la instalacin: .........................................................................133
1.4.- Materiales empleados ..................................................................................................136
1.5.- Red de evacuacin de aguas residuales (aguas fecales y aguas usadas).......................137
1.5.1.- Unidades de descarga..................................................................................................... 137
1.5.2.-Ramales-derivaciones ...................................................................................................... 138
1.5.3.- Bajantes............................................................................................................................. 140
1.3.4.- Ventilacin ....................................................................................................................... 142
Junio 2008
Junio 2008
CAPTULO 1: ...............................................................................................................................12
INSTALACIN DE FONTANERA .......................................................................................12
1.- MEMORIA DESCRIPTIVA.................................................................................................13
1.1.-Objeto del proyecto.........................................................................................................14
1.2.- Descripcin de las necesidades del edificio. ...................................................................14
1.3.- Normativa empleada .....................................................................................................15
1.4.- Descripcin de la instalacin general. ...........................................................................15
1.5.- Materiales empleados ....................................................................................................20
1.6.- Conclusin ....................................................................................................................21
2.- CLCULOS JUSTIFICATIVOS..........................................................................................22
2.1.- Determinacin de los puntos de consumo .....................................................................23
2.2.- Datos de la instalacin ..................................................................................................23
2.3.- Clculo de red de tuberas .............................................................................................24
2.4.- Dimensionado de tuberas .............................................................................................25
2.5.- Posicionamiento de las tuberas.....................................................................................27
2.6.- Prdida de carga ............................................................................................................28
2.7.- Grupo de presin ...........................................................................................................29
2.8.- Vlvulas reductoras de presin .....................................................................................30
2.9.- Disposicin final............................................................................................................30
2.10.- Clculo de la instalacin general de fontanera ...........................................................39
2.11.- Clculo del circuito de retorno (ACS) .........................................................................40
3.- ANEXOS..................................................................................................................................41
3.1.- Tablas ............................................................................................................................42
3.2.- Puesta en Servicio y Pruebas ........................................................................................45
3.2.1.- Consideraciones generales. .............................................................................................. 45
3.2.2.- Pruebas en la instalacin de agua fra. ........................................................................... 45
CAPTULO 2: ...............................................................................................................................49
PRODUCCIN DE ACS MEDIANTE ENERGA SOLAR TRMICA ............................49
1.- MEMORIA DESCRIPTIVA.................................................................................................50
1.1.- Objeto del proyecto........................................................................................................51
1.2.-Descripcin de las necesidades del edificio .....................................................................52
1.3.- Normativa empleada .....................................................................................................53
1.4.-Introduccin a la tecnologa. ..........................................................................................54
1.5.- La radiacin solar ..........................................................................................................55
1.6.- Colectores solares: .........................................................................................................56
1.6.1.- Colectores solares .............................................................................................................. 56
1.6.2.- Interaccin con el circuito hidrulico.............................................................................. 59
Junio 2008
PLIEGO DE
CONDICIONES
Pliego de condiciones
103
Junio 2008
Pliego de condiciones
102
se
estimen
admisibles
por
aqul,
debern
ser
retirados
montaje
responsabilidad
del
ejecutados
contratista
en
con
el
ellos.
Por
cumplimiento
tanto,
de
la
las
24.- Seguridad.
En general, basndonos en la Ley de Prevencin de Riesgos
Laborales y las especificaciones de las normas NTE, se cumplirn,
entre otras, las siguientes condiciones de seguridad:
- Siempre que se vaya a intervenir en una instalacin elctrica,
tanto en la ejecucin de la misma como en su mantenimiento, los
trabajos se realizarn sin tensin, asegurndonos la inexistencia de sta
mediante los correspondientes aparatos de medicin y comprobacin.
- En el lugar de trabajo se encontrar siempre un mnimo de dos
operarios.
- Se utilizarn guantes y herramientas aislantes.
Junio 2008
Pliego de condiciones
101
particular
se
harn
por
lo
menos
las
siguientes
comprobaciones:
- Se medir la resistencia de aislamiento con relacin a tierra y
entre conductores, que tendr un valor de al menos 0,50 Mohm.
- Una prueba de rigidez dielctrica, que se efectuar aplicando
una tensin igual a dos veces la tensin nominal ms 1.000 voltios, con
un mnimo de 1.500 voltios, durante 1 minuto a la frecuencia nominal.
Este ensayo se realizar estando los aparatos de interrupcin
cerrados y los cortocircuitos instalados como en servicio normal.
- Se inspeccionarn visulamente todos los aparatos y se
comprobar el funcionamiento mecnico de todas las partes mviles.
- Se pondr el cuadro de baja tensin y se comprobar que todos
los rels actan correctamente.
- Se calibrarn y ajustarn todas las protecciones de acuerdo con
los valores suministrados por el fabricante.
23.- Control.
Se realizarn cuantos anlisis, verificaciones, comprobaciones,
ensayos, pruebas y experiencias con los materiales, elementos o partes
de la instalacin que se ordenen por el Tcnico Director de la misma,
siendo ejecutados en laboratorio que designe la direccin, con cargo a
la contrata.
Junio 2008
Pliego de condiciones
100
Junio 2008
Pliego de condiciones
99
en especial, que
las
Junio 2008
Pliego de condiciones
98
Junio 2008
Pliego de condiciones
97
Junio 2008
Pliego de condiciones
96
Junio 2008
Pliego de condiciones
95
Junio 2008
Pliego de condiciones
94
donde:
- Ra es la suma de las resistencias de la toma de tierra y de los
conductores de proteccin de masas.
- Ia es la corriente que asegura el funcionamiento automtico del
dispositivo de proteccin. Cuando el dispositivo de proteccin es un
dispositivo de corriente diferencial-residual es la corriente diferencialresidual asignada.
- U es la tensin de contacto lmite convencional (50 24V).
19.5.- Embarrados.
El embarrado principal constar de tres barras para las fases y
una, con la mitad de la seccin de las fases, para el neutro. La barra de
neutro deber ser seccionable a la entrada del cuadro.
Las barras sern de cobre electroltico de alta conductividad y
adecuadas para soportar la intensidad de plena carga y las corrientes
de cortocircuito que se especifiquen en memoria y planos.
Se dispondr tambin de una barra independiente de tierra, de
seccin adecuada para proporcionar la puesta a tierra de las partes
metlicas no conductoras de los aparatos, la carcasa del cuadro y, si los
hubiera, los conductores de proteccin de los cables en salida.
Junio 2008
Pliego de condiciones
93
Junio 2008
Pliego de condiciones
92
Cuando
sea
necesario
suprimir
las
barreras,
abrir
las
Junio 2008
Pliego de condiciones
91
19.3.- Fusibles.
Los fusibles sern de alta capacidad de ruptura, limitadores de
corriente y de accin lenta cuando vayan instalados en circuitos de
proteccin de motores.
Los fusibles de proteccin de circuitos de control o de
consumidores hmicos sern de alta capacidad ruptura y de accin
rpida.
Se dispondrn sobre material aislante e incombustible, y estarn
construidos de tal forma que no se pueda proyectar metal al fundirse.
Llevarn marcadas la intensidad y tensin nominales de trabajo.
No sern admisibles elementos en los que la reposicin del
fusible pueda suponer un peligro de accidente. Estar montado sobre
una empuadura que pueda ser retirada fcilmente de la base.
Junio 2008
Pliego de condiciones
La
proteccin
90
contra
sobreintensidades
para
todos
los
Junio 2008
Pliego de condiciones
89
as
como
dispositivos
de
proteccin
contra
Junio 2008
Pliego de condiciones
88
Junio 2008
Pliego de condiciones
87
cuadros
sern
diseados
para
servicio
interior,
Junio 2008
Pliego de condiciones
86
Junio 2008
Pliego de condiciones
En
los
85
cambios
de
direccin,
los
tubos
estarn
Junio 2008
Pliego de condiciones
84
Junio 2008
Pliego de condiciones
83
Junio 2008
Pliego de condiciones
82
Junio 2008
Pliego de condiciones
81
Junio 2008
Pliego de condiciones
80
Junio 2008
Pliego de condiciones
79
Junio 2008
Pliego de condiciones
78
14.- Mantenimiento.
Cuando sea necesario intervenir nuevamente en la instalacin,
bien sea por causa de averas o para efectuar modificaciones en la
misma, debern tenerse en cuenta todas las especificaciones reseadas
en los apartados de ejecucin, control y seguridad, en la misma forma
que si se tratara de una instalacin nueva. Se aprovechar la ocasin
para comprobar el estado general de la instalacin, sustituyendo o
reparando aquellos elementos que lo precisen, utilizando materiales de
caractersticas similares a los reemplazados.
Junio 2008
Pliego de condiciones
77
12.- Herramientas
El Contratista se supone posee para situar en obra, segn
necesidades, todo el herramental y utillaje necesario para el montaje y
pruebas requeridas, tales como equipo individual y herramientas de
mano para cada operario, equipo de taller con taladradoras, mquinas
de roscar y de doble tubo, andamios, escaleras, etc. Sern necesarios en
obra, instrumentos tales como multitester, ampermetro de pinzas, etc.
13.- Materiales
Los
materiales
suministrar
por
la
propiedad
sern
Junio 2008
Pliego de condiciones
76
Junio 2008
Pliego de condiciones
75
Junio 2008
Pliego de condiciones
74
Junio 2008
Pliego de condiciones
73
Junio 2008
Pliego de condiciones
72
1.- Objeto
El presente pliego, tiene por objeto definir al Adjudicatario de
las instalaciones elctricas, en adelante Contratista, el alcance y
condiciones de ejecucin cualitativa de los trabajos a realizar para
conseguir el funcionamiento de las instalaciones elctricas, as como
ordenar las condiciones tcnicas que han de regir la planificacin,
ejecucin, desarrollo, control y recepcin de la obra correspondiente a
las instalaciones elctricas.
La instalacin de las obras, que se hace a continuacin, tiene
simplemente a facilitar la interpretacin de:
- Los planos.
- Lo representado en los detalles reflejados en los mismos.
- Los restantes documentos.
- Las disposiciones que dicte la Direccin de la obra durante su
ejecucin.
Cada contratista, antes de iniciar su trabajo, examinar todos los
trabajos que, de algn modo, estn relacionados con el suyo, para
lograr una perfecta coordinacin, de acuerdo con la finalidad de este
Pliego.
2.- Planos
Los planos de construccin, que forman parte del Contrato,
muestran las obras a realizar.- Para la construccin se emplearn los
que hayan sido aprobados por la Direccin de la Obra y que estn
marcados con la palabra FINAL y sus eventuales revisiones.
Los
planos
de
construccin,
podrn
ser
entregados
parcialmente.
Junio 2008
Pliego de condiciones
71
Captulo 5: Instalacin
de electricidad
Junio 2008
Pliego de condiciones
70
25.- Subcontratistas
La empresa instaladora, no podr subcontratar los trabajos a ella
encomendados, salvo autorizacin por parte de la direccin de obra y
la Propiedad.
Junio 2008
Pliego de condiciones
69
Junio 2008
Pliego de condiciones
68
vez
realizadas
las
pruebas
finales
con
resultado
Junio 2008
Pliego de condiciones
67
Junio 2008
Pliego de condiciones
66
20.- Pruebas
La empresa instaladora dispondr de los medios humanos y
materiales necesarios para efectuar las pruebas parciales y finales de la
instalacin.
Las pruebas parciales estarn precedidas por una comprobacin
de los materiales en el momento de su recepcin en obra.
Pruebas hidrostticas de redes de tuberas.
Todas las redes de circulacin de fluidos portadores deben ser
probadas hidrostticamente, a fin de asegurar su estanqueidad, antes
de quedar ocultas por obras de albailera, material de relleno o por el
material aislante.
Independientemente de las pruebas parciales a que hayan sido
sometidas las partes de la instalacin a lo largo del montaje, debe
efectuarse una prueba final de estanqueidad de todos los equipos y
conducciones a una presin en fro equivalente a vez y media la de
trabajo, con un mnimo de 6 bar, de acuerdo a UNE 100151.
Las pruebas requieren, inevitablemente, el taponamiento de los
extremos de la red, antes de que estn instaladas las unidades
terminales. Los elementos de taponamiento deben instalarse en el
curso del montaje, de tal manera que sirvan, al mismo tiempo, para
evitar la entrada en la red de materiales extraos.
Posteriormente se realizarn pruebas de circulacin de agua,
poniendo las bombas en marcha, comprobando la limpieza de los
filtros
midiendo
presiones
y,
finalmente,
se
realizar
la
Junio 2008
Pliego de condiciones
65
19.- Vlvulas
Todo tipo de vlvula deber cumplir los requisitos de las
normas correspondientes.
El fabricante deber suministrar la perdida de presin a
obturador abierto y la hermeticidad a obturador cerrado a presin
diferencial mxima.
Junio 2008
Pliego de condiciones
64
17.- Radiadores
Sern todos ellos homologados o autorizados por el Ministerio
de Industria y Energa. Estarn anclados y soportados de forma que no
transmitan esfuerzos a las tuberas que los alimenten.
Junio 2008
Pliego de condiciones
63
Junio 2008
Pliego de condiciones
62
de
purga,
se
instalara
una
vlvula
de
interceptacin,
preferentemente de esfera.
Para el dimensionado, y la disposicin de los soportes de
tuberas se seguirn las prescripciones marcadas en las Normas UNE
correspondientes al tipo de tubera. En particular, para las tuberas de
Junio 2008
Pliego de condiciones
61
14.- Tuberas
Antes del montaje debe comprobarse que las tuberas no estn
rotas, dobladas, aplastadas, oxidadas o daadas de cualquier manera.
Las tuberas se instalaran de forma ordenada, disponindose
siempre que sea posible, paralelamente a tres ejes perpendiculares
entre s y paralelos a los elementos estructurales del edificio, salvo las
pendientes que deben darse a los elementos horizontales.
La separacin entre la superficie exterior del recubrimiento de
una tubera y cualquier otro elemento ser tal que permita la
manipulacin y el mantenimiento del aislante trmico, si existe, as
como las vlvulas, purgados, aparatos de medida y control, etc.
La alineacin de las canalizaciones en uniones, cambios de
seccin y derivaciones se realizaran sin forzar las tuberas, empleando
los correspondientes accesorios o piezas especiales.
Para la realizacin de cambios de direccin se utilizaran
preferentemente piezas especiales, unidas a las tuberas mediante
rosca, soldadura, encolado o bridas.
Junio 2008
Pliego de condiciones
60
Humedad
operativa C
aire m/s
relativa %
Verano
23 a 25
0,18 a 0,24
40 a 60
Invierno
20 a 23
0,15 a 0,20
40 a 60
Estacin
Ruidos y vibraciones
Los ruidos generados por los componentes de las instalaciones
trmicas pueden afectar al bienestar y confort de los ocupantes de los
locales del edificio, as como las vibraciones al ajuste de las mquinas,
a la estanquidad de los conductos y a la estructura del edificio.
Junio 2008
Pliego de condiciones
59
11.- Sealizacin
Las conducciones de la instalacin deben estar sealizadas con
franjas, anillos y flechas dispuestos sobre la superficie exterior de las
mismas o de su aislamiento trmico, de acuerdo con lo indicado en la
UNE 100100.
En las salas de maquinas se dispondr el cdigo de colores,
junto al esquema de principio de la instalacin.
12.- Identificacin
Al final de la obra los aparatos, equipos y cuadros elctricos que
no vengan reglamentariamente identificados con placa de fabrica,
Junio 2008
Pliego de condiciones
58
Junio 2008
Pliego de condiciones
57
Junio 2008
Pliego de condiciones
56
materiales
al
objeto
procedern
de
de
fbrica
protegerlos
contra
convenientemente
los
elementos
Junio 2008
Pliego de condiciones
55
1.- Generalidades
El presente Pliego de Condiciones Tcnicas, tiene por objeto fijar
la calidad de materiales, equipos, aparatos y cualquier elemento que
deba emplearse para la ejecucin de la instalacin, as como las
condiciones de montaje.
Todos aquellos materiales, equipos o aparatos, no expresamente
indicados en esta documentacin, pero que sean necesarios para el
correcto funcionamiento de la instalacin, sern indicados e incluidos
por el instalador en su suministro.
Junio 2008
Pliego de condiciones
54
Captulo 4: Instalacin
de calefaccin
Junio 2008
Pliego de condiciones
53
15.- Planos
Los planos de construccin, que forman parte del Contrato,
muestran las obras a realizar.- Para la construccin se emplearn los
que hayan sido aprobados por la Direccin de la Obra y que estn
marcados con la palabra FINAL y sus eventuales revisiones.
Los
planos
de
construccin,
podrn
ser
entregados
parcialmente.
Junio 2008
Pliego de condiciones
52
12.- Pruebas
Antes de iniciarse el funcionamiento de las instalaciones, la
Empresa instaladora estar obligada a realizar las pruebas de
resistencia mecnica y estanqueidad previstas en el C.T.E., unas vez
realizadas avisar a la direccin facultativa para su comprobacin.
Sern objeto de estas pruebas todas las tuberas, elementos y
accesorios que integran la instalacin.
Las presiones y el modo de realizar las pruebas sern las
indicadas en la memoria de este proyecto.
Junio 2008
Pliego de condiciones
51
Junio 2008
Pliego de condiciones
50
Junio 2008
Pliego de condiciones
49
Junio 2008
Pliego de condiciones
48
5.4.- Canalones
Los canalones se dispondrn con una pendiente mnima de
0,5%, con una ligera pendiente hacia el exterior.
Para la construccin de canalones de zinc, se soldarn las piezas
en todo su permetro, las abrazaderas a las que se sujetar la chapa, se
ajustarn a la forma de la misma y sern de pletina de acero
galvanizado.
En canalones de plstico, se puede establecer una pendiente
mnima de 0,16%. En estos canalones se unirn los diferentes perfiles
con manguito de unin con junta de goma.
La conexin de canalones al colector general de la red vertical
aneja, se har a travs de sumidero sifnico.
Junio 2008
Pliego de condiciones
47
5.3.- Sumideros
Los sumideros de recogida de aguas pluviales sern de tipo
sifnico, capaces de soportar, de forma constante, cargas de 100
kg/cm2.
El sumidero, en su montaje, permitir absorber diferencias de
espesores de suelo, de hasta 90 mm.
El sumidero sifnico se dispondr a una distancia de la bajante
inferior o igual a 5 m, y se garantizar que en ningn punto de la
cubierta se supera una altura de 15 cm de hormign de pendiente. Su
Junio 2008
Pliego de condiciones
Los
embalados
46
materiales
al
objeto
procedern
de
de
protegerlos
fbrica
contra
convenientemente
los
elementos
Junio 2008
Pliego de condiciones
45
Junio 2008
Pliego de condiciones
44
1.- Objeto
El presente pliego, tiene por objeto definir el suministro de toda
la instalacin, mano de obra, equipo, materiales y accesorios, as como
la red de saneamiento del edificio objeto de este proyecto.
Todo ello de acuerdo a las especificaciones e instrucciones
contenidas en las diferentes partes que componen en Proyecto:
Memoria, Planos, Presupuesto y Pliego de Condiciones.
La definicin de las obras, tiene por objeto
simplemente a
2.- Legislacin
La ejecucin de la obra de instalacin, se ajustar a lo
determinado en este proyecto y en las siguientes Normas:
Norma UNE-EN 1329-1, sobre sistemas de canalizacin en
materiales plsticos para evacuacin de aguas residuales.
Recomendaciones del Servicio de aguas Municipal.
Normas UNE de obligado cumplimiento.
Junio 2008
Pliego de condiciones
43
Captulo 3: Instalacin
Saneamiento
Junio 2008
Pliego de condiciones
42
Comprobacin
de
los
intercambiadores
de
calor.
de
regulacin y control
- Comprobacin de las temperaturas y saltos de todos los
circuitos de generacin, distribucin y las unidades terminales el las
condiciones de rgimen
- Comprobacin que los consumos energticos se hallan dentro
de los mrgenes previstos
Junio 2008
Pliego de condiciones
41
materiales
embalados
al
objeto
procedern
de
de
protegerlos
fbrica
convenientemente
contra
los
elementos
8.- Planos
Los planos de construccin, que forman parte del Contrato,
muestran las obras a realizar.- Para la construccin se emplearn los
que hayan sido aprobados por la Direccin de la Obra y que estn
marcados con la palabra FINAL y sus eventuales revisiones.
Los
planos
de
construccin,
podrn
ser
entregados
parcialmente.
9.- Pruebas
La empresa instaladora realizara y documentara las siguientes
pruebas de eficiencia energtica de la instalacin:
- Comprobacin del funcionamiento de la instalacin en las
condiciones de rgimen.
Junio 2008
Pliego de condiciones
40
Junio 2008
Pliego de condiciones
39
Junio 2008
Pliego de condiciones
38
5.8.- Purgadores
En los puntos altos de la salida de bateras de captadores y en
todos aquellos puntos de la instalacin donde pueda quedar aire
acumulado, se colocarn sistemas de purga constituidos por botellines
de desaireacin y purgador manual o automtico. El volumen til del
botelln ser superior
a 100 cm3. Este volumen podr disminuirse si se instala a la
salida del circuito solar y antes del intercambiador un desaireador con
purgador automtico.
En el caso de utilizar purgadores automticos, adicionalmente,
se colocarn los dispositivosnecesarios para la purga manual.
Se evitar el uso de purgadores automticos cuando se prevea la
formacin de vapor en el circuito.
Junio 2008
Pliego de condiciones
37
5.6.-Vlvulas
La eleccin de las vlvulas se realizar, de acuerdo con la
funcin
que
desempeen
las
condiciones
extremas
de
Junio 2008
Pliego de condiciones
36
5.5.- Tuberas
En las tuberas del circuito primario podrn utilizarse como
materiales el cobre y el acero inoxidable, con uniones roscadas,
soldadas o embridadas y proteccin exterior con pintura anticorrosiva.
En el circuito secundario o de servicio de agua caliente sanitaria,
podr utilizarse cobre y acero inoxidable. Podrn utilizarse materiales
plsticos que soporten la temperatura mxima del circuito y que le
sean de aplicacin y est autorizada su utilizacin por las compaas
de suministro de agua potable.
Junio 2008
Pliego de condiciones
35
5.4.-Bombas de circulacin
Si el circuito de captadores est dotado con una bomba de
circulacin, la cada de presin se debera mantener aceptablemente
baja en todo el circuito.
Siempre que sea posible, las bombas en lnea se montarn en las
zonas ms fras del circuito, teniendo en cuenta que no se produzca
ningn tipo de cavitacin y siempre con el eje de rotacin en posicin
horizontal.
En instalaciones superiores a 50 m se montarn dos bombas
idnticas en paralelo, dejando una de reserva, tanto en el circuito
primario como en el secundario. En este caso se prever el
funcionamiento alternativo de las mismas, de forma manual o
automtica.
En instalaciones de climatizacin de piscinas la disposicin de
los elementos ser la siguiente: el filtro ha de colocarse siempre entre la
bomba y los captadores, y el sentido de la corriente ha de ser bombafiltro-captadores; para evitar que la resistencia de este provoque una
sobrepresin perjudicial para los captadores, prestando especial
Junio 2008
Pliego de condiciones
34
Junio 2008
Pliego de condiciones
33
Junio 2008
Pliego de condiciones
32
5.2.- Acumuladores
Cuando el intercambiador est incorporado al acumulador, la
placa de identificacin indicar la superficie de intercambio trmico en
m y la presin mxima de trabajo, del circuito primario.
Cada acumulador vendr equipado de fbrica de los necesarios
manguitos de acoplamiento, soldados antes del tratamiento de
proteccin, para las siguientes funciones:
Manguitos roscados para la entrada de agua fra y la salida de
agua caliente.
Registro embridado para inspeccin del interior del
acumulador y eventual acoplamiento del serpentn.
Manguitos roscados para la entrada y salida del fluido
primario.
Manguitos roscados para accesorios como termmetro y
termostato.
Manguito para el vaciado.
En cualquier caso la placa caracterstica del acumulador indicar
la prdida de carga del mismo.
Junio 2008
Pliego de condiciones
31
Junio 2008
Pliego de condiciones
30
por lo que habr que tomar, en esos casos, las precauciones oportunas
para evitarlo.
Para evitar flujos inversos es aconsejable la utilizacin de
vlvulas antirretorno, salvo que el equipo sea por circulacin natural.
5.- Componentes
5.1.- Captadores solares
El captador seleccionado deber poseer la certificacin emitida
por el organismo competente en la materia segn lo regulado en el RD
891/1980 de 14 de Abril, sobre homologacin de los captadores solares
y en la Orden de 28 de Julio de 1980 por la que se aprueban las normas
e instrucciones tcnicas complementarias para la homologacin de los
captadores solares, o la certificacin o condiciones que considere la
reglamentacin que lo sustituya.
Se recomienda que los captadores que integren la instalacin
sean del mismo modelo, tanto por criterios energticos como por
criterios constructivos.
Junio 2008
Pliego de condiciones
29
Junio 2008
Pliego de condiciones
28
Junio 2008
Pliego de condiciones
27
de
soportar
la
temperatura
especificada
sin
daos
permanentes en el sistema.
Cualquier componente que vaya a ser instalado en el interior de
un recinto donde la temperatura pueda caer por debajo de los 0 C,
deber estar protegido contra las heladas.
La instalacin estar protegida, con un producto qumico no
txico cuyo calor especfico no ser inferior a 3 kJ/kg K, en 5 C por
debajo de la mnima histrica registrada con objeto de no producir
daos
en
el
Adicionalmente
circuito
este
primario
producto
de
captadores
qumico
por
mantendr
heladas.
todas
sus
Junio 2008
Pliego de condiciones
26
Junio 2008
Pliego de condiciones
25
secundario
independientes,
con
producto
qumico
Junio 2008
Pliego de condiciones
24
1.- Objeto
El presente pliego, tiene por objeto definir el suministro de toda
la instalacin, mano de obra, equipo, materiales y accesorios, as como
la instalacin solar del edificio objeto de este proyecto.
Todo ello de acuerdo a las especificaciones e instrucciones
contenidas en las diferentes partes que componen en Proyecto:
Memoria, Planos, Presupuesto y Pliego de Condiciones.
La definicin de las obras, tiene por objeto
simplemente a
2.- Legislacin
La ejecucin de la obra de instalacin, se ajustar a lo
determinado en este proyecto y en las siguientes Normas:
Cdigo Tcnico de la Edificacin aprobado por Real Decreto
314/2006 el 17 de Marzo de 2006, en especial el Documento Bsico HE4.
Reglamento de Instalaciones Trmicas en los Edificios (RITE)
y sus Instrucciones Tcnicas Complementarias, aprobadas por el Real
Decreto 1751/1998 de 31 de Julio.
Normas UNE de obligado cumplimiento.
3.-Dudas y omisiones
Cualquier duda que pueda suscitarse en la interpretacin de los
documentos del Proyecto o diferencia que pueda apreciarse entre unos
Junio 2008
Pliego de condiciones
23
Captulo 2: Produccin
de ACS mediante
energa solar trmica
Junio 2008
Pliego de condiciones
22
abonado
deber
utilizar
de
forma
correcta
las
Junio 2008
Pliego de condiciones
21
Junio 2008
Pliego de condiciones
20
11.- Planos
Los planos de construccin, que forman parte del Contrato,
muestran las obras a realizar.- Para la construccin se emplearn los
que hayan sido aprobados por la Direccin de la Obra y que estn
marcados con la palabra FINAL y sus eventuales revisiones.
Los
planos
de
construccin,
podrn
ser
entregados
parcialmente.
debidamente
Organismo
Territorial
autorizada
Competente
por
en
el
materia
correspondiente
de
Industria,
Junio 2008
Pliego de condiciones
19
Junio 2008
Pliego de condiciones
18
9.- Pruebas
Antes de iniciarse el funcionamiento de las instalaciones, la
Empresa instaladora estar obligada a realizar las pruebas de
resistencia mecnica y estanqueidad previstas en el C.T.E., unas vez
realizadas avisar a la direccin facultativa para su comprobacin.
Sern objeto de estas pruebas todas las tuberas, elementos y
accesorios que integran la instalacin.
Las presiones y el modo de realizar las pruebas sern las
indicadas en la memoria de este proyecto y como mnimo como se
describen a continuacin.
Junio 2008
Pliego de condiciones
17
Junio 2008
Pliego de condiciones
16
Junio 2008
Pliego de condiciones
15
Junio 2008
Pliego de condiciones
14
adecuadamente
la
instalacin
para
evitar
las
Junio 2008
Pliego de condiciones
13
Junio 2008
Pliego de condiciones
12
para
transporte
de
agua
caliente
deben
recubrirse
Junio 2008
Pliego de condiciones
11
5.1.- Conexiones
Las conexiones de los equipos y los aparatos a las tuberas se
realizarn de tal forma que entre la tubera y el equipo o aparato no se
transmita ningn esfuerzo, debido al peso propio y las vibraciones.
Las conexiones cercanas a equipos, deben ser fcilmente
desmontables, a fin de facilitar el acceso al equipo en caso de
reparacin o sustitucin.
5.2.- Uniones
Segn el tipo de tubera empleada y la funcin que sta deba
cumplir, las uniones pueden realizarse por soldadura, encolado, rosca,
brida, compresin mecnica o junta elstica.
Los extremos de las tuberas se prepararn de forma adecuada
al tipo de unin que se debe realizar.
Antes de efectuar una unin, se repasarn y limpiaran los
extremos de los tubos para eliminar las rebabas que se hubieran
formado al cortarlos y cualquier otra impureza que pueda haberse
depositado en el interior o exterior.
Las tuberas se instalarn siempre con el menor nmero posible
de uniones.
Junio 2008
Pliego de condiciones
10
Junio 2008
Pliego de condiciones
Los
equipos
que
necesiten
operaciones
peridicas
de
4.4.-Identificacin de equipos
Al final de la obra, los aparatos, equipos y cuadros elctricos
que no vengan reglamentariamente identificados con placa de fbrica,
deben marcarse mediante una chapa de identificacin, sobre la cual se
indicarn el nombre y las caractersticas tcnicas del elemento.
5.-Montaje
Las tuberas sern perfectamente lisas, uniformes, circulares de
generatriz recta y bien calibrada. Tampoco contendrn ningn defecto
que pueda reducir su resistencia, impermeabilidad o durabilidad.
Todas las vlvulas, motores, aparatos en general se colocarn de
forma que sean fcilmente desmontables y accesibles, sobre todo las
partes de ms fcil rotura, los engrasadores y zonas de control
peridico.
Todas las conducciones estarn identificadas de acuerdo con la
Norma UNE correspondiente, as como se indicar con flechas el
sentido de circulacin de los fluidos.
Las conducciones se instalarn de forma que queden ordenadas
y en lneas paralelas, evitando en lo posible los cruces entre ellas y los
cambios de direccin, sern de 90 o 45 y de acuerdo con los elementos
estructurales del edificio.
Junio 2008
Pliego de condiciones
4.2.- Limpieza
Durante el curso del montaje de las instalaciones se deber
retirar de la obra todos los materiales sobrantes de trabajos efectuados
con anterioridad.
Al final de la obra, se debern limpiar perfectamente de
cualquier suciedad todos los equipos, salas de maquinas, etc.,
dejndolos en perfecto estado.
4.3.- Accesibilidad
Los elementos de medida, control, proteccin y maniobra se
deben instalar en lugares visibles y fcilmente accesibles, sin necesidad
de desmontar ninguna parte de la instalacin, y deben cumplir las
funciones de seguridad.
Junio 2008
Pliego de condiciones
sern
productos
normalizados
de
fabricantes
4.1.- Protecciones
Durante el almacenamiento en la obra y una vez instalados se
debern proteger todos los materiales de desperfectos y daos, as
como de la humedad.
Todos los aparatos, accesorios, tuberas, etc. durante el tiempo
que permanezcan en obra sin colocar, debern estar bien protegidos
tanto de la humedad, como del polvo o suciedades varias, propias de
una obra en construccin.
Todos los materiales debern dejarse en un cuarto cerrado que
habitualmente permanezcan con las puertas cerradas no debiendo
tener acceso a l ms que el personal propio que lo va a instalar, ste
cuarto no podr estar en stanos que puedan inundarse as como
tampoco prximos a columnas montantes de agua de obra.
Todos los aparatos y accesorios que tengan tuberas, que vayan
a quedar algn tiempo abiertos, debern protegerse con tapones para
evitar que pueda entrar suciedad en su interior.
Junio 2008
Pliego de condiciones
materiales
al
objeto
procedern
de
de
protegerlos
fbrica
contra
convenientemente
los
elementos
Junio 2008
Pliego de condiciones
1.-Objeto
El presente pliego, incluye las condiciones que deben satisfacer
los materiales, tuberas, accesorios y aparatos complementarios no slo
en
simplemente a
2.- Legislacin
La ejecucin de la obra de instalacin, se ajustar a lo
determinado en este proyecto y en las siguientes Normas:
Cdigo Tcnico de la Edificacin aprobado por Real Decreto
314/2006 el 17 de Marzo de 2006, en especial el Documento Bsico HS4 Suministro de agua.
Reglamento de Instalaciones Trmicas en los Edificios (RITE) y
sus Instrucciones Tcnicas Complementarias, aprobadas por el Real
Decreto 1751/1998 de 31 de Julio.
Recomendaciones del Servicio de aguas Municipal.
Normas UNE de obligado cumplimiento.
Junio 2008
Pliego de condiciones
Captulo 1: Instalacin
de fontanera
Junio 2008
Pliego de condiciones
Junio 2008
Pliego de condiciones
1.- Generalidades.................................................................................. 55
2.- Alcance de los trabajos................................................................... 55
3.- Planificacin y coordinacin ......................................................... 55
4.- Acopio de materiales...................................................................... 56
5.- Proteccin de los materiales en obra............................................ 57
6.- Limpieza de la obra. ....................................................................... 57
7.- Limpieza de canalizaciones........................................................... 58
8.- Andamios y aparejos...................................................................... 58
9.- Obras auxiliares de albailera. .................................................... 59
10.- Proteccin de elementos sometidos a altas temperaturas. ..... 59
11.- Sealizacin ................................................................................... 59
12.- Identificacin ................................................................................. 59
13.- Condiciones interiores. ................................................................ 60
14.- Tuberas.......................................................................................... 61
15.- Generadores de calor.................................................................... 63
16.- Chimeneas y conductos de humos............................................. 63
17.- Radiadores ..................................................................................... 64
18.- Aislamientos trmicos de aparatos y conducciones ................ 65
19.- Vlvulas.......................................................................................... 65
20.- Pruebas ........................................................................................... 66
21.- Recepcin provisional y definitiva............................................. 68
22.- Mantenimiento de la instalacin ................................................ 68
23.- Puesta en funcionamiento ........................................................... 68
24.- Condiciones de seguridad. .......................................................... 69
25.- Subcontratistas .............................................................................. 70
26.- Calidad de obra............................................................................. 70
CAPTULO 5: INSTALACIN DE ELECTRICIDAD ................................................................ 71
Junio 2008
Pliego de condiciones
PLIEGO DE CONDICIONES
CAPTULO 1: INSTALACIN DE FONTANERA ..................................................................... 4
1.-Objeto .................................................................................................. 5
3.- Dudas y omisiones ........................................................................... 6
4.- Condiciones generales de la instalacin........................................ 6
5.-Montaje................................................................................................ 9
6.- Protecciones de las tuberas .......................................................... 12
7.- Condiciones y procedencia ........................................................... 17
8.- Cambios de materiales ................................................................... 18
9.- Pruebas ............................................................................................. 18
10.- Comprobacin de materiales y ejecucin................................. 19
11.- Planos ............................................................................................ 20
12.- Obligaciones del fabricante, empresa suministradora,
instalador y usuario ............................................................................. 20
CAPTULO 2: PRODUCCIN DE ACS MEDIANTE ENERGA SOLAR TRMICA ................... 23
Junio 2008
Resumen de presupuesto
A continuacin se presenta el resumen del coste total de cada
instalacin:
6.236,5
PRESUPUESTO
13
Presupuesto
Junio 2008-06-05
Junio 2008
12
Presupuesto
uds
320
Luminarias
45
180
10
152
215
Puesta a
tierra
ELEMENTO
Luminaria Downlight Optics dela marca
TROLL, serie 0153/33 2x36 W
Luminaria con difusor serie 2/21/236/8
Halgenos Downlight 0139/01 50W
12V, de la marca TROLL
Apliquye pared exterior 6105/33 60W
TROLL
2 Tubos serie 3/108/CP TROLL 1x18 W
Conductor de cobre desnudo de 35
mm2 de seccin, directamente
instalado. Completamente instalado
P.UNIT()
74,85
P.TOTAL()
23.952,00
84,90
65,50
3.820,50
11.790
63,80
638,00
84,90
7,38
12.904,80
1.586,70
12,25
12,25
41,07
41,07
82,15
82,15
TOTAL
76.906,395
Junio 2008
11
Presupuesto
uds
720
0,5
510
30
Lneas de
enlace
4,5
0,5
0,5
0,5
Accesorios
251
88
390
ELEMENTO
Linea de enlace a cuadro de
habitaciones de la segunda planta
con cable de 3x6 mm2, bajo tubo
rgido de 20 mm2.
Linea de enlace a cuadro de zonas
comunes de la segunda planta con
cable de 3x4 mm2, bajo tubo rgido
de 20 mm2.
Linea de enlace a cuadro de
habitaciones de la primera planta con
cable de 3x6 mm2, bajo tubo rgido
de 20 mm2.
Linea de enlace a cuadro de zonas
comunes de la primera planta con
cable ) de 3x4 mm2, bajo tubo rgido
de 20 mm2.
Linea de enlace a cuadro de
cocinade la planta baja con cable de
3x16 mm2, bajo tubo rgido de 32
mm2.
Linea de enlace a cuadro de zonas
comunes 1 de la planta baja, con
cable de 3x6 mm2mm2, bajo tubo
rgido de 20 mm2.
Linea de enlace a cuadro de zonas
comunes 2 de la planta baja, con
cable de 3x16 mm2, bajo tubo rgido
de 32 mm2.
Linea de enlace a cuadro de
climatizacin de la planta baja, con
cable de 3x4 mm2, bajo tubo rgido
de 20 mm2.
Interruptor ALPINO unipolar
Conmutador ALPINO
Toma de corriente 16 A tipo schuko,
incluso lnea general de 2x2,5+2,5
mm2, desde cuadro de proteccin,
bajo tubo empotrado. marca: EUNEA
modelo: UNICA
Toma de corriente 25 A para cocina,
incluso lnea general de 2x6+6 mm2,
bajo tubo empotrado, y base.
P.UNIT()
2,50
P.TOTAL()
1.800,00
2,15
1.075,00
2,50
1.275,00
2,15
64,5
4,13
18,58
2,50
1,25
4,13
2,065
2,15
1.07
4,00
5,00
13,53
1.004,00
440,00
5.276,70
29,84
29,84
Junio 2008
10
Presupuesto
uds
ELEMENTO
P.UNIT()
1 Cuadro de proteccin del stano,
826,09
compuesto por:
7 int. magnetotrmico 2x6 A
1 int. magnetotrmico 2x10 A
2 int. magnetotrmico 2x16 A
1 int. magnetotrmico 2x32 A
4 int. diferencial 30 mA
1 armario para alojamiento
Poderes de Corte, segn esquemas
unifilares
1 Cuadro general de baja tensin,
826,00
compuesto por:
7 int. magnetotrmico 2x6 A
1 int. magnetotrmico 2x10 A
2 int. magnetotrmico 2x16 A
1 int. magnetotrmico 2x32 A
4 int. diferencial 30 mA
1 armario para alojamiento
Poderes de Corte, segn esquemas
unifilares
40 Lnea general de alimentacin de
16,25
cobre unipolar, de 3x240+1x120 mm2
de seccin, tipo RZ1-0'6/1 KV., del
Linea General
tipo no propagador de la llama, con
de
emisin reducida de humos y gases
alimentacin
txicos, del tipo AFUMEX, de
PIRELLI o similar, incluyendo parte
proporcional de terminales para
conexin a bornes. Colocado y
conexionado.
42 Derivacin individual a cuadro
12,53
general planta segunda, con cable
de 5x 50mm2, bajo tubo rgido de 50
mm2.
39 Derivacin individual a cuadro
8,63
general planta primera, con cable de
5x35mm2 , bajo tubo rgido de 50
mm2.
Derivacin
37,5 Derivacin individual a cuadro
4,13
individual
general planta baja, con cable de
5x16 mm2 , bajo tubo rgido de 32
mm2.
35 Derivacin individual a cuadro
4,13
general del stano, con cable de
5x16 mm2 , bajo tubo rgido de 32
mm2.
10 Derivacin individual a cuadro
3,00
general del ascensor, con cable ) de
5x10 mm2 , bajo tubo rgido de 32
mm2.
P.TOTAL()
826,09
826,00
650,00
526,26
336,57
154,875
144,55
30,00
Junio 2008
Presupuesto
Cuadros de
proteccin
uds
ELEMENTO
17 Cuadro de proteccin para
habitaciones de la planta primera,
compuesto por:
1 int. general magnetotrmico 2x6 A
1 int. magnetotrmico 2x16 A
1 armario para alojamiento
Poderes de Corte, segn esquemas
unifilares
1 Cuadro de proteccin para zonas
comunes (1) de la planta primera,
compuesto por:
1 int. general magnetotrmico 2x6 A
2 int. magnetotrmico 2x10 A
9 int. magnetotrmico 2x16 A
1 armario para alojamiento
Poderes de Corte, segn esquemas
unifilares
1 Cuadro de proteccin de la planta
primera, compuesto por:
4 int. general magnetotrmico 2x20 A
1 int. magnetotrmico 2x40 A
18 int. diferencial 30 mA
1 armario para alojamiento
Poderes de Corte, segn esquemas
unifilares
1 Cuadro de proteccin para zonas
comunes de la planta baja(1)
compuesto por:
1 int. general magnetotrmico 2x10 A
12 int. magnetotrmico 2x16 A
1 armario para alojamiento
Poderes de Corte, segn esquemas
unifilares
1 Cuadro de proteccin para zonas
comunes de la planta baja(2),
compuesto por:
1 int. general magnetotrmico 2x6 A
2 int. magnetotrmico 2x10 A
5 int. magnetotrmico 2x16 A
1 armario para alojamiento
Poderes de Corte, segn esquemas
unifilares
1 Cuadro de proteccin de la cocina,
compuesto por:
1 int. magnetotrmico 2x6 A
4 int. magnetototrmico 2x16A
2 int. magnetotrmico 2x20 A
1 int. magnetotrmico 2x25 A
1 armario para alojamiento
Poderes de Corte, segn esquemas
unifilares
P.UNIT()
68,64
P.TOTAL()
1.166,88
401,28
401,28
2.179,21
2.179,21
433,44
433,44
267,72
267,72
272,61
272,61
Junio 2008
Presupuesto
Aparamenta
uds
ELEMENTO
P.UNIT()
1 Caja General de proteccin Uriarte, NI
337,89
7650,01 400 A, con fusible NH tamao
2, Modelo GL-7-BUC
1 Cuadro General de Proteccin
2.167,50
realizado en armario de la serie ART
de 2 salidas de 400 A
1 Interruptor General de corte en carga
409,14
IDT-400 A
1 Panel de 1 contador trifsico
664,38
electrnico con bloque de bornes PLI1-E-BP
1 Armario para un contador trifsico ALI949,46
E-BP
1 Fusible IDT-400-C-FUS(400a)
919,37
14
Cuadros de
proteccin
P.TOTAL()
337,89
2.167,50
409,14
664,38
949,46
919,37
68,64
960,96
268,35
268,35
292,60
292,60
Junio 2008
Presupuesto
vlvulas
unidades
ELEMENTO
108
Vlvulas de escuadra
P.UNIT() P.TOTAL()
5,50
594,00
108
Purgador de aire
1,10
118,8
Reducciones
1 1/2 - 1 1/4
2,30
9,20
1 1/4 - 1
1,22
4,88
8
26
3/4 - 1/2
1/2 - 3/8
0,47
0,44
3,76
11,44
3/8 - 1/4
0,40
0,80
14
3/8
0,37
5,18
16
1/2
0,40
6,40
10
3/4
0,54
5,40
0,81
1,62
3/8
0,54
1,08
14
1/2
0,47
6,58
3/4
0,71
4,26
1,28
2,56
94
3/8
0,54
50,76
14
1/2
0,47
6,58
16
3/4
0,71
11,36
TOTAL()
17.220,92
Codos
Accesorios
Giro en T
T paso recto
Junio 2008
Presupuesto
4.-Instalacin de calefaccin
Desglose del coste del equipo de la instalacin de calefaccin:
unidades
ELEMENTO
23
Radiador Ferrolli
Europa 200 C 1 mdulo
Radiador Ferrolli
Europa 200 C 2 mdulos
Radiador Ferrolli
Europa 200 C 3 mdulos
Radiador Ferrolli
Europa 200 C 4 mdulos
Radiador Ferrolli
Europa 200 C 5 mudlos
Radiador Ferrolli
Europa 200 C 6 mdulos
Radiador Ferrolli
Europa 200 C 7 mdulos
Radiador Ferrolli
Europa 200 C 8 mdulos
Radiador Ferrolli
Europa 200 C 9 mdulos
Radiador Ferrolli
8
8
29
8
Radiadores
9
6
2
1
1
P.UNIT() P.TOTAL()
21,43
492,89
42,86
342,88
64,29
514,32
85,72
2485,88
107,15
857,20
128,58
1.157,22
150,01
900,06
171,44
342,88
192,87
192,87
214,30
214,30
4.700,00
4.700,00
59,40
59,40
495,83
991,66
1,50
727,50
1,90
513,00
Equipos
1
2
270
Bomba circuladora
Tubera de cobre 3/8.
Tubera de cobre 1/2
140
4,03
564,20
80
Tubera de cobre 1
6,00
480,00
40
10,50
420,00
30
14,00
420,00
485
tuberas
Caldera Viessman
Vitrocrossal200.
87-311Kw
Junio 2008
Presupuesto
unidades
35
19
Accesorios
4
5
12
1
7
Partida
alzada
85
36
Tuberas
50
357
Equipos
ELEMENTO
Bote sifnico
(110-40-50)
Bote sifnico
curvo extensible
Arqueta 40x40x40
Arqueta 50x50x50
Arqueta 60x60x60
Arqueta 60x70x60
Sumidero
(20x20x0,75)
Partida alzada
Tuberas PVC
32mm
(p.unit rollo 5 m)
Tuberas PVC
40mm
(p.unit rollo 5 m)
Tuberas PVC
90mm
(p.unit rollo 5 m)
Tuberas PVC
110mm
(p.unit rollo 5 m)
Bomba evacuacin
DRAINBOX
P.UNIT()
6,77
P.TOTAL()
236,95
4,09
77,71
25,07
47,80
65,20
67,35
31,97
100,28
239,00
782,40
67,35
223,79
1,81
300,00
153,85
2,25
81,00
5,13
256,50
6,31
2.252,67
1.465,00
1465,00
TOTAL()
6.236,5
Junio 2008
Presupuesto
colectores
unidades
18
2
acumuladores
1
1
equipos
vlvulas
2
30
3
4
1
accesorios
4
1
6
18
tuberas
120
47
26
25
ELEMENTO
Colectores solares
Wagner LB 6,4
Depsito acumulador
Lapesa, MV- SB 25 litros
Depsito acumulador
Lapesa, MV- SB 2000 litros
Intercambiador de calor
Alpha laval
CB26 H de 24
Caldera Viessman
Vitolass 200 F de
Viessman
Bomba centrfuga horizontal
EBARA 3P
vlvulas mezcladoras
vlvulas de esfera
vlvulas de retencin
vlvula de seguridad
Partida alzada
Vaso de expansin
VASOFLEX 25 litros
Fluido calor-portador
Tyfocor
bidn de 200litros
Estacin de llenado
Glyco-fill
Purgador aire automtico
tubera de cobre 15 mm
circuito secundario
tuberas primario (cobre)
42
35
28
18
P.UNIT()
2.236,00
P.TOTAL()
4.0248,00
3.685,68
7.336,00
3.061,00
3.061,00
4.029,00
4.029,00
2.695,66
2.695,66
2.234,00
8.936,00
58,00
7,00
51,00
10,00
350,00
40,97
116,00
210,00
153,00
40,00
720,00
40,97
824,00
3.296,00
66,00
66,00
4,07
1,50
24,42
27,00
10,50
6,00
4,03
1,90
TOTAL()
1.260
282,00
104,78
47,50
74.412,77
Junio 2008
Presupuesto
unidades
112
28
60
Tuberas
180
1.108
560
1.800
ELEMENTO
Tubera de cobre
dimetro 80 mm
Tubera de cobre
dimetro 65mm
Tubera de cobre
dimetro 40mm
Tubera de cobre
dimetro 32mm
Tubera de cobre
dimetro 25mm
Tubera de cobre
dimetro 20 mm
Tubera de cobre
dimetro 16 mm
P.UNIT()
22,35
P.TOTAL()
2.503,20
18,46
516,88
10,50
630,00
6,00
1.080,00
4,03
4.465,24
1,90
1.064,00
1,50
2.700,00
TOTAL
21.816,73
Junio 2008
Presupuesto
unidades
ELEMENTO
P.UNIT()
P.TOTAL()
80-65
65-40
40-32
32-25
25-20
20-16
4,225
2,30
1,22
0,47
0,44
0,41
50,40
46,00
34,16
13,16
184,8
168
25
20
16
0,54
0,41
0,37
140,4
300,8
153,92
80
65
40
32
25
3,14
2,68
1,78
1,28
0,71
37,20
10,40
21,36
46,08
187,44
32
25
20
1,21
0,71
0,47
31,97
7,00
24,00
181,76
116,56
31,97
1.456,00
7,00
5.320,00
7,00
278,00
5.600,00
278,00
18,00
18,00
11,00
7,00
12,00
7,00
11,00
7,00
12,00
7,00
Reducciones
12
20
28
28
420
420
Codos
260
752
416
Accesorios
Giro en T
12
4
12
36
264
T paso recto
20
256
248
1
208
Vlvulas
760
800
1
Red
acometida
1
1
1
1
sumidero
Vlvulas de corte
20mm
Vlvulas de corte
16 mm
Vlvulas reductoras
Contador individual
homologado, de hierro
fundido
Filtro desmontable
instalado en tubera de
alimentacin
Grifo
vlvula antirretorno
vlvula triple funcin
vlvula de esfera
Junio 2008
Presupuesto
PRESUPUESTO
1.- INSTALACIN DE FONTANERA ..................................................................................2
2.- INSTALACIN PRODUCCIN DE ACS ........................................................................4
3.- INSTALACIN DE SANEAMIENTO ...............................................................................5
4.-INSTALACIN DE CALEFACCIN .................................................................................6
5.- INSTALACIN DE ELECTRICIDAD................................................................................8
Junio 2008