Beruflich Dokumente
Kultur Dokumente
Emergency Model:CC500S
3P4W
ISO 9001:2000
QUALITY STANDARDS
Rating Range
Standby:
kW
k VA
RPM1500 50Hz
400
500
Prime:
kW
k VA
360
450
ALTERNATOR RATINGS
HCI544C(STAMFORD)
Alternator Model
50Hz
1500rpm
Cont.H -125K/40
380
400
415
440
Voltage parallel
190
200
208
220
220
230
240
254
Rating capacity(kVA)
450
500
450
450
Rating power(kW)
360
400
360
360
Power efficiency(%)
94.0
93.8
94.4
94.6
383
426
381
381
star
Input power(kW)
RATINGS: All three-phase units are rated at 0.8 power factor. Standby ratings : Standby
ratings apply to installations served by a reliable utility source. The standby rating is for
this rating. Ratings are in according with ISO-3046/1,BS 5514 ,AS 2789 , and DIN 6271.
Prime Power Ratings: Prime power ratings apply to installations where utility power is
unavailable or unreliable. At varying load, the number of generator set operating hours
is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in
accordance with IS0-8528/1, overload capacity in accordance with ISO-3046/1,BS 5514,
AS 2789, and DIN 6271. For limited running time and base load ratings, consult the
factory. The generator set manufacturer reserves the right to change the design or
specifications without notice and without any obligation or liability whatsoever.
GENERAL GUIDELINES FOR DERATING: Altitude: Derate 4.0% per 300m(1000 ft.)
elevation above 760m(2500ft.) up to a maximum elevation of 2450m(8000 ft.).More than
2450m(8000ft), please contacts
the help.
Standby.H -150K/40
Standby.H -150K/40
380
400
415
440
380
400
415
Voltage parallel
190
200
208
220
190
200
208
220
230
240
254
220
230
240
471
star
478
512
478
478
471
471
Rating power(kW)
382
410
382
382
377
377
377
Power efficiency(%)
93.8
93.7
94.2
94.4
93.5
93.5
93.5
408
437
406
405
404
404
404
Input power(kW)
ALTERNATOR
Specification
Type
Exciter type
Voltage regulator(AS440 or MX321)
Voltage regulation
Insulation
Protection
Rated power factor
Stator winding
Winding pitch
Winding leads
Maximum overspeed
Sustained short circuit
Waveform distortion
1500RPM
50HZ
1.5%
Class H
IP23
The 2/3 pitch design avoids excessive neutral currents. With the
2/3 pitch and carefully selected pole and tooth designs,
ensures very low waveform distortion.
0.8
Double layer concentric
Two thirds
12
2250 Rev/min
Self excited machines do not
sustain a short circuit current
Altitude
DIESEL ENGINE
Engine Electrical
Engine Electrical
Application Data
Engine Specifications
Manufacturer
Number of cylinders
Cylinder arrangement
Cycle
Aspiration
Compression ratio
Bore Stroke
Displacement
Direction of rotation
Max. Power at rated rpm
Negative
24V
24V
In-line
Four stroke
Battery voltage
12V
35A
Turbocharged,
After cooled
0.002 ohm
600 CCA
640 CCA
900 CCA
CUMMINS
14.5:1
159 mm 159mm
18.9 litres (1150 In3 )
Clockwise viewed from front
448kW
Fuel System
0.25%
7.9 m/s
Type of injection
Exhaust
1500RPM 50HZ
1489 litre/s
532
(992
Oil Pressure
At idle speed
At governed speed
Maximum Oil Temperature
Total System Capacity
(with Combo Filter)
1500RPM
50HZ
Maximum restriction at PT
fuel injection pump
with clean fuel filter
with dirty fuel filter
13.6kPa
27.1kPa
307 litre/hour
Fuel consumption
1500RPM
6.0 in Hg
Lubrication
Lubrication system
50HZ
Fuel
2076 kg
Exhaust System
1500RPM
Volts(DC)
Starter motor rated voltage(DC)
1500RPM 50HZ
System
1500RPM
50HZ
138kPa
345-483kPa
121 (250 )
50litre( 13.2 US gal)
50HZ
Standby power
US gals/hr )
Continuous power
Application Data
Cooling System
1500RPM 50HZ
Cooling System
30.0 litres
71.0 litres
29950 m 3 /hr
82 - 93
69kPa
104
100
(220 )
(212 )
NOTE:
All data is based on:
1. Engine operating with fuel system, water pump, lubricating oil pump, air cleaner and
exhaust silencer; not included are battery charging alternator, fan, and optional driven
components.
2. Engine operating with fuel corresponding to grade No. 2-D per ASTM D975.
3. ISO 3046, Part 1, Standard Reference Conditions of:
Barometric Pressure : 100 kPa (29.53 in Hg)
Air Temperature : 25 (77 )
Altitude : 110 m (361 ft)
Relative Humidity : 30%
Air Intake Restriction: 254 mm H2O (10 in H2O)
Exhaust Restriction : 51 mm Hg (2 in Hg)
Protection:
Over Speed Shutdown.
Low Oil Pressure Shutdown.
High Engine Temp Shutdown.
Charger failure alarm.
Mains failure alarm.
Optional Under speed Protection.
TBA: To Be Determined
DC Supply: 8 to 35 V Continuous.
Paralleling System
Voltage Regulator
Relocation Kit
Controller System
paper
Maintenance card
Accessories
Enclosed Unit
Miscellaneous Accessories
Sound Enclosure
Weather Enclosure (with enclosed critical silencer)
Weather Housing (with roof-mounted critical silencer)
Trailer(Causes the genset easily to move)
Open Unit
Exhaust Silencer, Critical kit
Cooling System
Open Style
Block Heater
(recommended for ambient temperatures below 0 )
Overall Size, L W H
mm
Weight(radiator model),net,Kg
Fuel System
Auxiliary Fuel Pump
Soundproof Style
Overall Size, L W H
Weight(radiator model),net,Kg
mm
Electrical System
Battery Charger, Equalize/Float Type
NOTE : This drawing is provided for reference only and should not be used for planning
installation. Contact your local distributor for more detailed information.
Manufactured by:
Shenzhen
Superwatt
Shirakawa
Denki
Pte LtdPower Co., Ltd.
Huachang Road,Dalang Street,baoan
Blk 1002,Toa Payoh Industrial Park #06-1477
District,shenzhen.
Tel: (65)
Tel: 83320518
86-755-28175239