Beruflich Dokumente
Kultur Dokumente
AND INVESTIGATIONS
By S. W. MELSOM, Member.*
(Paper
first received 2ndJ January, and in revised form 10th February, 1940; read before the TRANSMISSION SECTION
V y
J
\Zth March, 1940.)
SUMMARY
Section (1) sets out the means to be taken by way of external
protection to ensure that mains cables entering a power or
distribution station will not be destroyed by an oil fire of
short duration or help the spread of an extraneous fire. The
means favoured for new installations is the use of a moulded
asbestos material which has in the best degree obtainable the
thermal characteristics required.
To meet the case where cables are run without exterior
metal protection, for positions having special fire risks and
for such special uses as for switchboard connections, a new
type of cable dielectric [described in Section (2)] has been
developed which of itself possesses a high degree of fire
resistance. The material is of a rubber-like nature, and the
dimensions of the cable and the technique of installation are
the same as for rubber-insulated cables.
Section (3) describes a highly important series of tests made
generally under conditions as nearly as possible simulating
those obtaining in coal minesan investigation made in close
collaboration with H.M. Electrical Inspector of Mines. The
experiments show that, in the great majority of cases, the
cables withstand any transient flames such as would arise
from an explosion of fire-damp, and generally that it is very
difficult to set fire to a cable under conditions held fairly to
simulate working conditions in a pit. In the case of trailing
cables the tests have been carried through in some cases under
conditions much more severe than can occur in practice.
These tests have indicated that, to secure the maximum
degree of safety from fire due to internal faults, a fire-resisting
type of dielectric may be desirable, and that special provision
may be necessary as regards both screening of the cable and
the provision of earth-leakage protection.
Section (4) is a note on the cold-pouring, cold-setting type of
compound recently brought into prominence for emergency
repairs which may have to be made under conditions both of
urgency and of atmosphere that would preclude the use of
heaters of the flame type and also would not allow of the
ordinary long time for cooling and topping-up on contraction.
The main features of the compound are: (a) That certain
ingredients mixed immediately before pouring cause the
compound to set after a short period from the time of mixing;
(b) that there is little or no contraction on setting; (c) that the
electrical characteristics, although not so high as those of the
best pitch compounds, are sufficiently good for service conditions; and (d) that the compound has proved to have ample
stability for emergency joints under all conditions likely to
be encountered.
INTRODUCTION
During the last 4 years there has been general concentration on the problem of fire risks in electrical
installations and on the precautions necessary to elimi Cable Makers' Association.
[521
522
problem was clarified, and for the resultant proper provision for protection against fire.
It may be assumed from the published recommendations of the Commission that the main problems to be
faced so far as cables are concerned arise from extraneous
fires mainly due to flowing burning oil in a station or
substation.
As a result of the measures taken for protection against
oil fires it is expected that, if and when such fires do
occur, they will be of comparatively short duration so
that the protection necessary for the cable is something
which will withstand a fire for a short time without
damage to the cable, or, at the very worst, ensure that
any danger is kept within bounds so that the dielectric
of the cable does not contribute to the general conflagration.
The recommendations of the Commissioners were made
after full consultation with the industry, and with them
the cable makers are in full agreement. It may, however, be of interest to discuss the manner of giving effect
to these recommendations and the effect that the protection may have on the performance of the cables under
normal operating conditions.
The essential requirement for the fireproofing of leadsheathed paper-impregnated cables is that the fireproofing should be sufficiently heat-resisting fully to
protect the cable, of sufficiently low thermal resistivity
so as not to decrease unduly the current rating of the
cable, and either be of such composition as not to set up
corrosion of the lead sheath or, alternatively, be provided with protection against such corrosion.
A combination of all these properties was not very
easy to find, and a good deal of investigation was required
before the best materials were found. Also in some
cases the use of the best method was not possible on
systems already installed, and alternative methods had
to be sought.
Dealing with the question of cables emerging from the
floor and going upwards to connect to switchgear, etc.,
or to other cables run in the vicinity of such gear, the
method selected for new installations and for existing
installations where space was available was to use
moulded asbestos supplied by the makers in the form of
split tubes which could be clamped around the exposed
length of the cable. Apart from ease of fitting and
the comparatively pleasing finish of the job, this material
represents the nearest approach to the ideal characteristics mentioned above. Magnesia has probably a
higher degree of resistance to fire than the asbestos
mouldings, but the thermal resistivity of the material
is so high that the current rating of the cable would be
greatly reduced.
The thermal resistivity of moulded asbestos is of the
order of 700 thermal ohms, a value which, with the
thickness oi material used, would normally decrease
the current rating of the cables by about 20%. Against
this, however, may be offset the normal increase of rating
due to the fact that the cables in the ground are probably
grouped, whereas when they are taken to switchgear they
are separated by a distance sufficient to free them
from " proximity heating." This generalization, however, must not be carried too far, since if the cables in
the run were separated throughout and operated at or
INVESTIGATIONS
523
reasons such cables have a restricted use, and the standard types of rubber-insulated cables retain their popularity for general purposes.
For a number of years the research staffs of the
associated] firms of cable makers have been attempting
to produce fire-resisting or self-extinguishing rubber compounds, and quite a fair degree of success has been
obtained in imparting these properties to rubber. The
fundamental difficulty, however, has been that raw
rubber is not self-extinguishing when once ignited, and
the other materials which it is necessary to incorporate
in the mix to overcome the lack of self-extinguishing
properties greatly modify its other desirable properties.
What is required for the basis of a successful self-extinguishing dielectric is a material which, in the raw state,
has rubber-like properties with the addition of fireresisting properties, since irt is-xtear that, although it
might prove necess,ary to incorporate other materials in
much the same way as is done with rubber, it would not
be necessary to sacrifice the rubber-like properties in
order to obtain the fire-resistance.
Several synthetic materials having generally the properties outlined above have been produced over the past
5-10 years and have naturally received very close
investigation in order to assess their suitability for
application to cables. Not all proved so useful as their
initial examination suggested, but one of them proved
extremely promising. Without entering into any very
involved chemistry, it may be said that this material is
obtained by the polymerization of 2-chlorobutadiene,
which is represented by the formula CH2 = C Cl CH
= CH2. It thus belongs to the same general chemical
group as " rubber," which is 2-methylbutadiene CH2
= C CH3 CH = CH2. This similarity in molecular
constitution between the synthetic material and natural
rubber is reflected in the fact that in the raw state
the material is very similar in its physical properties
to raw rubber. The raw material is unsuited to the
manufacture of cables and has to be converted into a
suitable " mix." However, as pointed out earlier, since
the material is already fire-resisting it is not necessary
to obtain the fire-resistance at the expense of other properties. Extensive tests have shown that this synthetic
material is more resistant than rubber to deleterious
influences such as heat, oxygen, light, oil, etc., and
although observations regarding its life under natural
conditions are necessarily restricted to some 5 to 6 years,
these observations have fully confirmed the conclusions,
drawn from laboratory tests, that a satisfactory life may
be anticipated from cable in which the synthetic material
is used. Its electrical properties are interesting, but in
one respect unfortunate, for while the breakdown value
is comparable with that of rubber the insulation resistance
is so low that the material would be unacceptable if used
alone as a dielectric for general wiring work.
A large number of experiments were carried out in
which cables were made with dielectrics using different
" mixes " derived from the basic material, and also in
which different types of mix were combined with natural
rubber with the object of maintaining a high degree of
self-extinguishing properties and combining these with
satisfactory electrical properties. As a result it has been
possible to arrive at a construction of dielectric which,
524
MELSOM: ELECTRIC
RISKS
mineral dielectrics is that so far as installation is concerned the new fire-resisting insulated cable can be
regarded as identical with the standard rubber-insulated
type, since the cable is just as flexible and requires no
more protection at ends than is normally given to
rubber-insulated cables.
So far development has been restricted to the sizes
and types of cable normally used in ordinary wiring
work, i.e. braided and compounded or metal-sheathed,
but development is proceeding on other types.
(3) THE FIRE-RESISTING PROPERTIES OF
CABLES USED IN COAL MINES
Fires which have occurred in coal mines during recent
years with deplorable loss of life have raised in some
minds the question as to how far the electrical cables
have been responsible either for initiating a fire or for
conveying an existing fire from one part of the mine to
another. Some time ago H.M. Electrical Inspector of
Mines (Mr. Horsley) inquired whether the cable makers
would be willing to carry out experiments with a view
to obtaining data which would answer certain specific
questions. This co-operation was willingly afforded, and
this Section of the paper deals with the work which was
carried out as the result of a research programme drawn
up after discussion between a suitable Research Committee and Mr. Horsley, whose close co-operation and
keen interest has been most highly appreciated.
It will of course be clear that the most important
feature of the co-operation has been the correlation of
the methods of test with the conditions in a coal mine,
the type of fire which occurs there, and the mechanical
usage to which cables are subjected as part of the normal
working of a coal mine.
Cables used for permanent installation in shafts and
" in-bye " normally have a single wire armouring for
external mechanical protection. The armouring generally
has a further textile covering thoroughly impregnated
with a pitch type of compound to give the maximum
protection against corrosion. It was natural, therefore,
that the first question that arose was whether the
external wrappings would be capable of being set on
fire, and, if so, under what conditions; and further,
assuming they could be set on fire, to what extent were
they likely to convey flame.
The cables used for this section of the work consisted
of 0-06-sq. in. standard rubber-insulated, single-wirearmoured cable, and paper-insulated lead-covered cable
of the same conductor size but lead-sheathed and singlewire armoured. The testing procedure consisted in
laying 1-yard lengths of the cable horizontally about 1 ft.
above a laboratory bench and subjecting them to the
action of three bunsen burners (adjusted so as to melt a
piece of 0-028 in. copper wire in 5 seconds) spaced equally
round the cable at one place. There was no sign of
ignition for about 15 seconds, after which the cable
began to drop burning compound, which was self-extinguished almost immediately on reaching the bench.
Fig. 2 (Plate 1) shows a typical test about 30 seconds
after commencement. The compound is reasonably well
alight. In several instances the cable was removed from
the burners when in this condition in order to ascertain
whether the wrappings would continue to burn, but in
MELSOM:
ELECTRIC CABLES
AND
FlRE
RISKS
Ti me, days
Fig. 11.-Curve
Fig. 12.-66-kV
MELSOM:
ELECTRIC
CABLES
AND FIRE
RISKS:
Plate 2
Fig. 3.Standard vulcanized-rubber, steel-wire-armoured cable as Fig. 2, but 10 rain, after start.
Fig. 5.Standard vulcanized-rubber mining cable after 10-min. flame test. Three burners, bedding removed.
RECENT
DEVELOPMENTS
AND
INVESTIGATIONS
Plate 3
Fig. 7.Standard paper-insulated, lead-sheathed cable after flame test. Three burners, hessian removed.
MELSOM:
EJ,ECTRIC
CABLES AND F I R E R I S K S
MELSOM: ELECTRIC
RISKS
525
the hessian bedding over the lead was burnt away in the
vicinity of the applied flame and it appeared that the
lead had also been melted. Fig. 7, showing the cable
after removal of the bedding, confirms this, showing the
lead melted away locally. Further examination showed
that the belt papers were charred, but the actual core
insulating papers were unaffected.
While the tests indicated that the wrappings treated
with petroleum pitch compound were appreciably more
fire-resisting than might have been expected, the next
logical step was to investigate the use of compounds
having greater fire resistance on the wrappings. Such
compounds are already used on certain types of cable.
Tests similar to those already described were applied to
rubber cables which were of standard construction apart
from the replacement of the pitch type of compound by
the fire-resisting compound. Fig. 8 (Plate 3) shows a
sample of cable 30 seconds after application of the burners,
and it will be seen that there is complete absence of
burning compound; even continued application failed to
ignite the wrappings. It would seem that the wrappings
can for practical purposes be rendered non-ignitable b}'
the use of' fire-resisting paint compounds. These are
not so resistant to the passage of water as are the standard
petroleum pitch type which, as mentioned earner, are
used specifically to give protection against corrosion.
Consequently the use of these fire-resisting compounds
in place of the present standard types would render the
armouring wires more liable to corrosion from acid
waters, etc. The author is not in a position to say
whether the trouble which may arise from this source
would more than offset any advantage which might be
gained from increased fire resistance.
Generally the results draw attention to the extraordinary fire-protective qualities of the armour wires.
Not only are the exterior wrappings and their impregnating compound rendered fire-resisting to a high degree,
but the inside of the cable is almost completely protected.
The work so far described concerns the possible
tendency of the armoured cable to spread an already
existing fire. The next question which arises is whether
a core-to-core arc, which might arise, for instance, as a
result of mechanical damage to the cable, would set the
latter on fire, this in its turn initiating a larger fire.
The cables for this part of the investigation consisted of
0- 1-sq. in. 3-core, single-wire-armoured, rubber-insulated,
impregnated paper-insulated, and vulcanized-bitumeninsulated cables with standard petroleum pitch finish.
As a result of a number of preliminary tests made to
obtain a rough idea of the magnitude of the possible
effects, artificial short-circuits were made by driving
0-064-in. copper wire through two of the three cores
prior to completion of the cable. To prevent vapour,
etc., being forced out at the end of the cable as the
result of the arc, the test pieces were made 10 to 12 ft.
long, the artificial short-circuit being in the middle of the
length. For the actual test the pieces of cable were
laid on a concrete floor and the two short-circuited conductors connected to a 600-volt supply obtained from a
250-kVA, single-phase, 50-cycle alternator, giving a
short-circuit current of between 1 200 and 2 000 amperes.
Under the worst conditions the short-circuit caused a
relatively violent explosion, burst the cable, burnt away
34
526
RECENT DEVELOPMENTS
for use as dielectrics and for sheathing. Work on dielectrics has resulted in the development of a special
type of dielectric already in use for certain types of
cables [see Section (2)].
One point, however, of especial interest to mining
works may be mentioned here. The major difficulty so
far as sheathings are concerned is the fact that hitherto
fire-resisting properties have been obtained at the expense
of desirable physical properties, such as tensile strength
and resistance to tear. As the result of later developments, it is now possible to produce fire-resisting sheathings which, while not possessing such high tensile strength
or tear resistance as the standard resilient tough-rubber
sheathing, may have sufficiently good mechanical properties to allow of their use for trailing cables used in mines.
It will perhaps be admitted that the results with
trailing cables, showing as they do the great difficulty in
maltreating a cable so badly as to produce an internal arc,
and the comparative ease with which the flame resulting
from such an arc is extinguished, indicate clearly that
the existing standard cables are adequate for their
service. Consideration, however, of the extent to which
the normal overload protection used in mines installations was suitable to clear faults of this kind led to a
further series of interesting experiments, but under
conditions which can hardly occur in practice. Most
certainly there is no record of any such.
Four sets of samples were made up, as follows:
(1) Standard vulcanized-rubber dielectric with standard
sheath.
(2).Standard vulcanized-rubber dielectric with fireresisting sheath.
(3) Fire-resisting dielectric with standard sheath.
(4) Fire-resisting dielectric with fire-resisting sheath.
The conductor was 0-0225 sq. in., insulated with
dielectric 0-062 in. thick and having a sheath 0-15 in.
thick.
The weak places were spaced every 2 ft. and, as the
conductor was semi-broken before the dielectric was
applied, the complete breaks could be made by moving
the cable and without in any way affecting the dielectric
or sheathing. This arrangement also allowed the broken
ends of the conductor to be pressed together and withdrawn to start and continue the arc. In fact, by the
use of the comparatively simple apparatus shown in
Figs. 9 and 10 (Plate 4) the exact position of the cores
could be varied at will.
In order to obtain the most severe result, the current
supply was from a large 500-volt d.c. generator, and
the current was intentionally maintained at low values,
so that disruption, if any, should be due to a continual
arc, rather than a short-duration arc of high current.
The actual currents applied to the cable were therefore
4, 10-5 and 20 amp. respectively.
Three tests were carried out on each type of cable
under each condition, and the results obtained are
summarized below.
(1) In every test at 10-5 amp. and above, and in half
of the tests at 4 amp., the sheathing was burst
by the internal pressure developed from the
thermal decomposition of the dielectric. This
AND
INVESTIGATIONS
527
528
MELSOM:
ELECTRIC
CABLES
AND
FIRE
RISKS:
The setting time of the compound and the final hardness may be varied within considerable limits by slight
(4) A COLD-SETTING JOINT-BOX COMPOUND
modification of the two constituents, and while agreeing
While this new type of compound is not directly that these properties may well be left to the individual
associated with fire resistance, it has been greatly dis- firms interested in one or other of the three or more types
cussed in connection with urgent repairs under emergency of compound now available, it may be stated that as a
conditions, and as one of its important features is that minimum a compound of this type should not set in less
its use does not require heating of any kind, and so is than 20 minutes after the start of mixing, this giving time
particularly safe for gas-laden conditions, it is hoped for filling the joint, and after 24 hours it should have
that a note here and an opportunity for discussing it will set hard. After this time the compound continues to
not be out of place.
harden for a week or two. A typical case, the figures
Publication or part publication of the properties of the on which are not necessarily applicable to all types of
compound itself has already been made. In view of this compound, is illustrated in Fig. 11 (Plate 4).
this, and seeing that the Transmission Section will be
Out of the very large number of laboratory tests made
concerned almost entirely with the operational aspect to prove the quality of this compound for this particular
of the material, this note can well be confined to new type of service, one may be quoted. Eleven 3-core
matter, excluding the question of chemical composition 11-kV joints were inserted in a 250-yard length of cable.
of the compound.
Four of the joints were filled with standard hot-pouring
The use of a cold-pouring and cold-setting box com- box compounds and the remaining seven with cold-filling
pound was first considered some years ago in connection compound. All joints were subjected to a 3-phase
with low-voltage boxes used in collieries and similar voltage test of 33 kV, current heating cycles being applied
RECENT DEVELOPMENTS
at intervals throughout the test. After prolonged application of the voltage, deterioration of the dielectric of
the hot-filled joints could be detected. No such deterioration, however, appeared in the cold-filled joints, neither
did these latter joints show signs of being affected even
after many hundreds of hours of the treatment.
To quote another example, a 66-kV temporary emergency-type joint and terminal were subjected to a step
test the details of which are given below.
kV to earth
Joint
Terminal
min.
min.
60
70
80
90
100
110
120
130
140
150
160
170
180
30
30
12
(breakdown)
190
200
Limit of testing
transformers
AND
INVESTIGATIONS
529