Sie sind auf Seite 1von 7

Application Note

Testing 6-phase Synchronizers with two CMC Test Sets


Author
Stephan Geiger | stephan.geiger@omicron.at
Date
Nov 23, 2010
Related OMICRON Products
CMC Test Sets, Test Universe
Application Area
Relay testing
Keywords
Testing, synchronizer, relay
Version
v1.0
Document ID
ANS_10003_ENU

OMICRON

Page 1 of 7

Content
1

Introduction ..................................................................................................................................... 3

Wiring Diagram................................................................................................................................ 3

Software Settings ............................................................................................................................ 4

Please use this note only in combination with the related product manual which contains several important safety
instructions. The user is responsible for every application that makes use of an OMICRON product.
OMICRON electronics GmbH including all international branch offices is henceforth referred to as OMICRON.
OMICRON 2010. All rights reserved. This application note is a publication of OMICRON.
All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical
character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON.
Reprinting, wholly or in part, is not permitted.
The product information, specifications, and technical data embodied in this application note represent the technical
status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this application note is useful, accurate and entirely
reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be present.
OMICRON translates this application note from the source language English into a number of other languages. Any
translation of this document is done for local requirements, and in the event of a dispute between the English and a nonEnglish version, the English version of this note shall govern.
OMICRON 2011

Page 2 of 7

Introduction
Usually for testing 6-phase synchronizer relays six voltage channels are necessary in order to simulate two
independent 3-phase systems. Therefore often external voltage amplifiers like the CMS 156 are connected
to the CMC Test Set. However, instead of an external voltage amplifier also a second CMC Test Set with its
synchronization feature can be used.
This Application Note should provide assistance with testing a 6-phase synchronizer relay without any
additional voltage amplifiers by making use of two CMC Test Sets.
Required Hardware:
> 2 x CMC 256-6 / 256plus / 356 / 353
Required Test Universe modules:
> Synchronizer
> QuickCMC

Wiring Diagram
The devices have to be wired as shown in the wiring diagram below:

Figure 1: Wiring diagram

OMICRON 2011

Page 3 of 7

Software Settings
1. Start the Synchronizer module
2. Choose CMC#1 in the Hardware Configuration and select the configuration as shown in
the figures below.

Figure 2: Output configuration of CMC#1

Figure 3: Analog output configuration of CMC#1

OMICRON 2011

Page 4 of 7

3. Define the relay test in the Synchronizer module. The figure below shows an example.

Figure 4: Test example

4. Open a QuickCMC module parallel to the Synchronizer module and select CMC#2 in the Hardware
Configuration. The output configuration of CMC#2 has to be defined as shown in the figure below.

Figure 5: Output configuration of CMC#2

OMICRON 2011

Page 5 of 7

5. Now define the output voltage in QuickCMC. Enter the voltage which has been defined in the
Synchronizer module for System 1 (figure 6). The phase shift between the voltages has to be 0, -120
and 120.

Figure 6: Transferring the settings

6. As a next step select Synchronize to Input... from the Parameters menu entry in QuickCMC and
activate the button Synchronize.

Figure 7: Synchronize mode

7. Start thereupon QuickCMC by pushing the ON button or F5-key and execute the defined test in the
Synchronizer module subsequently. Now CMC#2 will be synchronized to CMC#1 and a test with six
voltages takes place.
8. As soon as the test in the Synchronizer module is finished, switch off the outputs in the QuickCMC
module and save the results.

OMICRON 2011

Page 6 of 7

OMICRON is an international company serving the electrical power


industry with innovative testing and diagnostic solutions. The application of
OMICRON products provides users with the highest level of confidence in
the condition assessment of primary and secondary equipment on their
systems. Services offered in the area of consulting, commissioning,
testing, diagnosis, and training make the product range complete.
Customers in more than 140 countries rely on the company's ability to
supply leading edge technology of excellent quality. Broad application
knowledge and extraordinary customer support provided by offices in
North America, Europe, South and East Asia, and the Middle East,
together with a worldwide network of distributors and representatives,
make the company a market leader in its sector.

Americas
OMICRON electronics Corp. USA
12 Greenway Plaza, Suite 1510
Houston, TX 77046, USA
Phone: +1 713 830-4660
+1 800-OMICRON
Fax: +1 713 830-4661
info@omicronusa.com

Asia-Pacific
OMICRON electronics Asia Limited
Suite 2006, 20/F, Tower 2
The Gateway, Harbour City
Kowloon, Hong Kong S.A.R.
Phone: +852 3767 5500
Fax: +852 3767 5400
info@asia.omicron.at

For addresses of OMICRON offices with customer service


centers, regional sales offices or offices for training,
consulting and commissioning please visit our web site.

Europe, Middle East, Africa


OMICRON electronics GmbH
Oberes Ried 1
6833 Klaus, Austria
Phone: +43 5523 507-0
Fax: +43 5523 507-999
info@omicron.at

www.omicron.at www.omicronusa.com