Data sheet

Solenoid valve
Types EVR 2 - EVR 40
EVR is a direct or servo operated solenoid
valve for liquid, suction, and hot gas lines with
HCFC and HFC refrigerants.
EVR valves are supplied complete or as separate
components, i.e. valve body, coil and flanges, if
required, can be ordered separately.

Features

yy A complete range of solenoid valves


forrefrigeration, freezing and air
conditioningsystems

yy Use with any fluorinated refrigerant

yy Normally closed (NC) and normally open (NO)


versions available

yy Flare connections up to 5/8 in

yy AC and DC coils are interchangeable on all


valve body versions

Approvals

Danfoss | DCS (rja) | 2016.01

UL listed, file MH 7648

yy Designed for media temperatures up to 220 F

yy Solder connections up to 2 1/8 in


yy Solder versions have extended connections;
there is no need to dismantle the valve
whensoldering

Note:
These approvals are only recognized when one
of the EVR series of solenoid valves found in
thisleaflet is combined with a GP general
purposecoil.

DKRCC.PD.BB0.A8.22 | 1

Data sheet

Solenoid valve, types EVR 2 EVR 40

Table of contents

Technical data.............................................................................................................................................................................2
Rated capacity [kW]..................................................................................................................................................................3
Ordering........................................................................................................................................................................................4
Capacity, Liquid..........................................................................................................................................................................8
Capacity, Suction vapor........................................................................................................................................................ 12
Capacity, Hot gas..................................................................................................................................................................... 19
Identification............................................................................................................................................................................ 25
Design / Function.................................................................................................................................................................... 27
Dimensions and weights...................................................................................................................................................... 29
Spare parts................................................................................................................................................................................. 35

Technical data

Temperature of medium: -40 220 F


Maximum 265 F during defrosting

Refrigerant
R22/R407C, R404A/R507, R134a, R407A, R23, R32,
R290, R600, R600a
For other refrigerants, please contact Danfoss.

Maximum working pressure


EVR 2 EVR 8:
MWP = 655 psig
EVR 10:
MWP = 500 psig
EVR 15 EVR 40: MWP = 460 psig

Note:
Only EVR 2 - EVR 20 with solder connections and
without manual stem are suitable for R32, R290,
R600 and R600a.

Enclosure of coil
~ NEMA 2 or ~ NEMA 4

Opening differential pressure


p [psi]
Valve type

Maximum
working
pressure
MWP

Cv value1)

2)

Minimum

Metric conversions
5
/9 (t1 F - 32) = t2 C
1 in = 25.4 mm

Maximum (= MOPD) liquid

Medium
temperature

AC

DC

[F]

[psig]

[gal/min]

EVR 2

0.0

350

260

-40 220

655

0.19

EVR 3

0.0

300

260

-40 220

655

0.32

EVR 4

0.7

300

260

-40 220

655

0.66

EVR 6

0.7

300

2603)

-40 220

655

0.93

EVR 8

0.7

300

260

EVR 10

0.7

EVR 15

-40 220

655

1.3

300

3)

260

-40 220

500

2.2

0.7

300

2603)

-40 220

460

3.0

EVR 18

0.7

300

260

-40 220

460

3.9

EVR 20

0.7

3004)

190

-40 220

460

5.8

EVR 22

0.7

300

190

-40 220

460

6.9

EVR 25

1.0

300

260

-40 220

460

12.0

EVR 32

1.0

300

260

-40 220

460

18.0

EVR 40

1.0

300

260

-40 220

460

29.0

1)

2)

4)

Cv value is the water flow in [gal/min] at a pressure drop


across valve p = 1 psi. = 10 lbs/gal
MOPD (Max. Opening Pressure Differential) for media in gas
form is approximately 14 psi greater

2 DKRCC.PD.BB0.A8.22

3)
4)

EVR (NO): 300 psig


EVR (NO): 275 psig

Data sheet

Solenoid valve, types EVR 2 EVR 40

Rated capacities [kW]

R22/R407C

R134a

R404A/R507

R32

R290

R600

EVR 2

1.17

0.89

EVR 3

2.03

1.55

R600a

0.80

1.34

1.09

1.29

1.13

1.40

2.26

1.85

2.17

1.91

Liquid

EVR 4

4.15

3.16

2.86

4.68

3.83

4.50

3.96

EVR 6

5.83

4.43

4.01

6.69

5.47

6.43

5.66

EVR 8

8.01

6.09

5.52

9.37

7.66

9.01

7.93

EVR 10

13.8

10.5

9.53

15.89

12.99

15.28

13.45
18.4

EVR 15

18.9

14.4

13.0

21.7

17.8

20.9

EVR 18

24.6

18.7

17.0

28.4

23.2

27.3

24.1

EVR 20

36.4

27.7

25.1

41.8

34.2

40.2

35.4

EVR 22

43.7

33.3

30.1

EVR 25

72.8

55.4

50.2

EVR 32

116.5

88.7

80.3

EVR 40

182.0

138.5

125.4

0.10

0.07

0.09

0.13

0.10

0.05

0.06

Suction vapour
EVR 2
EVR 3

0.17

0.13

0.15

0.22

0.17

0.09

0.10

EVR 4

0.34

0.26

0.30

0.45

0.35

0.19

0.21

EVR 6

0.48

0.37

0.43

0.65

0.50

0.27

0.31

EVR 8

0.66

0.51

0.58

0.90

0.70

0.38

0.43

EVR 10

1.15

0.88

1.01

1.53

1.18

0.65

0.73

EVR 15

1.57

1.20

1.38

2.10

1.62

0.88

0.99

EVR 18

2.04

1.56

1.80

2.74

2.11

1.16

1.30

EVR 20

3.02

2.31

2.66

4.04

3.11

1.70

1.91

EVR 22

3.62

2.78

3.19

EVR 25

6.04

4.63

5.32

EVR 32

9.66

7.40

8.51

EVR 40

16.1

11.6

13.3

Hot gas

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW
1 in = 25.4 mm
US gal/min = 0.86 m3/h

EVR 2

0.22

0.18

0.17

0.32

0.26

0.15

0.17

EVR 3

0.38

0.31

0.30

0.54

0.43

0.26

0.28

EVR 4

0.77

0.63

0.62

1.11

0.90

0.54

0.59

EVR 6

1.08

0.88

0.87

1.59

1.29

0.76

0.84

EVR 8

1.49

1.21

1.19

2.23

1.80

1.07

1.17

EVR 10

2.57

2.10

2.06

3.78

3.05

1.82

1.99

EVR 15

3.52

2.87

2.82

5.17

4.18

2.48

2.72

EVR 18

4.57

3.73

3.67

6.76

5.47

3.25

3.55

EVR 20

6.76

5.51

5.43

9.94

8.04

4.78

5.23

EVR 22

8.11

6.62

6.52

EVR 25

13.5

11.0

10.9

EVR 32

21.6

17.7

17.4

EVR 40

33.8

27.6

27.2

1)

Rated liquid and suction vapor capacity are based on:


Evaporating temperature te= 40 F
Liquid temperature ahead of valve tl= 100 F
Pressure drop p across valve
with liquid
p = 3 psi
with suction vapor p = 1 psi (EVR 25, 32, 40 = 2 psi)

DKRCC.PD.BB0.A8.22

Rated hot gas capacity is based on:


Condensing temperature tc= 100 F
Hot gas temperature th= 140 F
Pressure drop across valve p = 3 psi

Data sheet

Solenoid valve, types EVR 2 EVR 40

Ordering

EVR solder ODF connections, Normally Closed (NC) - separate valve bodies

Connection
[in]
EVR 2

EVR 4

/8

No

0.32

032F7105

/8

/8

No

0.32

032F1157

/8

/32

No

0.66

032F7110

/8

15

/64

No

0.93

032F7115

/8

15

/64

Yes

0.93

032F7116

/2

15

/64

No

0.93

032F1162

/2

15

/64

No

0.93

032F7144

/8

15

/64

No

0.93

032F7117

/2

/16

No

1.3

032F7121

/2

/16

Yes

1.3

032F7148

/8

/16

No

1.3

032F7122

/8

/8

No

2.2

032F7125

/2

/8

No

2.2

032F1166

/2

/8

Yes

2.2

032F1188

/8

/8

No

2.2

032F1168

/8

/8

Yes

2.2

032F7149

/8

/16

No

3.0

032F1171

/8

/16

Yes

3.0

032F1172

/8

/16

No

3.0

032F7130

/8

19

/32

Yes

3.9

032F1004

/8

/8

No

5.8

032F1176

/8

/8

Yes

5.8

032F1177

1 /8

15

/16

No

6.9

032F7145

11/8

15

/16

Yes

6.9

032F7137

13/8

15

/16

No

6.9

032F7146

EVR 18

EVR 20

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW
1 in = 25.4 mm
US gal/min = 0.86 m3/h

EVR 22

032F7100

EVR 15

0.19

/4

EVR 10

No

EVR 8

/32

/4

EVR 6

Code nos.
valve body
excl. coil

1
1

EVR 3

Manual stem

Cvvalue
[gal/min]

Port size
[in]

4 DKRCC.PD.BB0.A8.22

Data sheet
Ordering
(continued)

Solenoid valve, types EVR 2 EVR 40


EVR solder ODF connections, Normally Closed (NC) - separate valve bodies

EVR 25

Manual stem

Cvvalue
[gal/min]

Code nos.
valve body
excl. coil

No

12.0

032F1189

11/8

Yes

12.0

032F1190

13/8

No

12.0

032F1193

Yes

12.0

032F1194

/8

No

18.0

042H1176

/8

Yes

18.0

042H1177

/8

No

18.0

042H1178

/8

Yes

18.0

042H1179

/8

No

18.0

042H1180

/8

Yes

18.0

042H1181

Yes

29.0

042H1188

Connection
[in]

Port size
[in]

1 /8

13/8

EVR 32

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW
1 in = 25.4 mm
US gal/min = 0.86 m3/h

EVR 40

1 /8

13/8

15/8

1 /8

21/8

21/8

2 /8
1

EVR solder ODF connections, Normally Open (NO) - separate valve bodies
Connection
[in]
EVR 6

EVR 10

EVR 15

Port size
[in]

Cvvalue
[gal/min]

Code nos.
valve body excl. coil

/4

0.93

032F1164

/8

/2

/8

2.2

032F1169

/8

/16

3.0

032F1174

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW
1 in = 25.4 mm
US gal/min = 0.86 m3/h
EVR flare connections, Normally Closed (NC) - separate valve bodies
Connection
[in]
EVR 3

EVR 3

EVR 6

Manual stem

Cvvalue
[gal/min]

Code nos.
valve body
excl. coil

No

0.32

032F8106

/8

No

0.32

032F8115

/64

No

0.93

032F8071

Port size
[in]
/8

/4

/8

/8

15

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW
1 in = 25.4 mm
US gal/min = 0.86 m3/h

DKRCC.PD.BB0.A8.22

Data sheet

Solenoid valve, types EVR 2 EVR 40

BJ and BX coils for


EVR valves

Approvals

Listed with EVR. MH7648


Low Voltage Directive (LVD) 2006/95/EC

Ordering

Wire length

Danfoss
18F67.10

Danfoss
18F66.10

Coil type

Conduit boss NEMA 4


BX024CS
BX024CS AKV / EVR EVRH
BX024CS / EVRA EVRAT
/ EVRS EVRST
BX120CS / EVM
BX120CS EV220B 6-50
BX120CS EV210B
EV215B
BX120CS EV225B
BX240CS EV250B
BX240CS
BX120BS
BX208BS
BX240BS

Technical data

Valve type

Junction box NEMA 2


AKV / EVR EVRH
BJ024CS / EVRA EVRAT
/ EVRS EVRST
/ EVM
BJ120CS EV220B 6-50
EV210B
EV215B
BJ240CS EV225B
EV250B
BJ120BS
BJ208BS AKVH / EVRH
BJ240BS

AKVH / EVRH

Frequency
[Hz]

Power
consumption
[Hz]

[in]

[cm]

Voltage [V]
AC

18

24

50 / 60

14

018F4100

18

110
120

50 / 60
60

16
15

018F4110

18

208 240
230

60
50

14
17

018F4120

7
7
7

18
18
18

120
208
240

60
60
60

16
16
16

018F4130
018F4132
018F4134

18
71
98
18
36
71
98
18

46
180
250
46
91
180
250
46

24
24
24

50 / 60
50 / 60
50 / 60

14
14
14

110
120

50 / 60
60

16
15

98
98
98
98

250
250
250
250

208 240
230

60
50

14
17

018F4102
018F4103
018F4104
018F4112
018F4113
018F4114
018F4115
018F4122

120
208
240

60
60
60

16
16
16

Design
In accordance with UL 429

Insulation of coil wire


Class H according to IEC 85

Power supply
Alternating current (AC)

Connection
Junction box or Conduit boss

Permissible voltage variation


Alternating current (AC):
50 Hz and 60 Hz: -10% +15%
50/60 Hz: +/- 10%

Enclosure. IEC 60529


Junction box NEMA 2 ~ IP 1232
Conduit boss NEMA 4 ~ IP 54

Power consumption
Alternating current (AC): Inrush: 49 VA;
Holding: 28 VA. 16 W
6 DKRCC.PD.BB0.A8.22

Ambient temperature
-40 F 122 F (-40 C 50 C)

Code no.

018F4123
018F4131
018F4133
018F4135

Data sheet

Solenoid valve, types EVR 2 EVR 40

BG coils for EVR valves


(continued)

yy For high temperatures class H insulated wire

Features

yy Encapsulated coils with long life time


yy Wide range of coils
from 12 V 200 V DC
with terminal box IP67 ~ NEMA 6
Approvals

Low Voltage Directive (LVD) 2006/95/EC


Valve type

Danfoss
18F61

Ordering

EVR 2 to 15 (NC)
EVR 25 to 40 (NC/NO)
EVR 6 to 15 (NO)
EVRC 10 to 15
EVRA 3 to 15 (NC)
EVRA 25 to 40 (NC)
EVRAT 10 to 15 (NC)
EVRS/EVRST 3 to 15
EVM (NC/NO)
EVR 20 to 22 (NC/NO)
EVRC 20
EVRA 20
EVRAT 20
EVRST 20

Technical data

Voltage [V] DC

Power consumption [W]

12

20

018F6856

Code no.

24

20

018F6857

48

20

018F6859

110

20

018F6860

115

20

018F6861

220

20

018F6851

12

20

018F6886

24

20

018F6887

48

20

018F6889

110

20

018F6890

220

20

018F6881

Design
In accordance with VDE 0580

Connection
Terminal box

Power supply
Direct current (DC)

Enclosure. IEC 529


IP 67 NEMA 6

Permissible voltage variation


-10 15%

Ambient temperature
-40 F 122 F (-40 C 50 C)

Power consumption
20 W
Insulation of coil wire
Class H according to IEC 85

DKRCC.PD.BB0.A8.22

Data sheet
Capacity
Liquid

Solenoid valve, types EVR 2 EVR 40


Liquid capacity Q0 [TR]
at a pressure drop across valve p [psi]

Type
1

R22/R407C
EVR 2

0.58

0.82

1.01

1.16

1.30

1.43

1.54

EVR 3

0.98

1.39

1.70

1.97

2.20

2.41

2.60

EVR 4

2.04

2.88

3.53

4.08

4.56

4.99

5.39

EVR 6

2.91

4.12

5.04

5.82

6.51

7.13

7.71

EVR 8

4.08

5.77

7.06

8.15

9.12

9.99

10.79

EVR 10

6.92

9.78

11.98

13.83

15.47

16.94

18.30

EVR 15

9.46

13.39

16.39

18.93

21.16

23.18

25.04

EVR 18

12.38

17.50

21.44

24.75

27.68

30.32

32.75

EVR 20

18.20

25.74

31.53

36.40

40.70

44.59

48.16

EVR 22

21.84

30.89

37.83

43.68

48.84

53.50

57.79

EVR 25

0.28

34.15

63.05

72.81

81.40

89.17

96.31

EVR 32

0.44

54.63

100.88

116.49

130.24

142.67

154.10

EVR 40

0.67

85.35

157.63

182.02

203.50

222.93

240.79

R134a

Capacities are based on:


Liquid temperature tl= 100 F
Evaporating
temperature te = 40 F
Superheat
temperature (te+ 10 F) = 50 F
Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 2

0.54

0.77

0.94

1.09

1.22

1.33

1.44

EVR 3

0.92

1.30

1.59

1.84

2.05

2.25

2.43

EVR 4

1.90

2.69

3.30

3.81

4.26

4.66

5.04

EVR 6

2.72

3.85

4.71

5.44

6.08

6.66

7.20

EVR 8

3.81

5.38

6.59

7.61

8.51

9.33

10.07

EVR 10

6.46

9.13

11.19

12.92

14.44

15.82

17.09

EVR 15

8.84

12.50

15.31

17.68

19.76

21.65

23.38

EVR 18

11.56

16.35

20.02

23.12

25.84

28.31

30.58

EVR 20

17.00

24.04

29.44

33.99

38.01

41.63

44.97

EVR 22

20.40

28.84

35.33

40.79

45.61

49.96

53.96

EVR 25

0.26

31.89

58.88

67.99

76.01

83.27

89.94

EVR 32

0.41

51.02

94.21

108.78

121.62

133.23

143.90

EVR 40

0.63

79.70

147.20

169.97

190.03

208.17

224.85

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.
Correction factors for liquid temperature tl
tl [F]

80

90

100

110

120

Factor

1.10

1.05

1.00

0.95

0.90

8 DKRCC.PD.BB0.A8.22

Data sheet
Capacity
Liquid
(continued)

Solenoid valve, types EVR 2 EVR 40


Liquid capacity Q0 [TR]
at a pressure drop across valve p [psi]

Type
1

R404A and R507

Capacities are based on:


Liquid temperature tl= 100 F
Evaporating
temperature te = 40 F
Superheat
temperature (te+ 10 F) = 50 F
Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 2

0.38

0.54

0.66

0.77

0.86

0.94

1.01

EVR 3

0.65

0.91

1.12

1.29

1.45

1.58

1.71

EVR 4

1.34

1.90

2.32

2.68

3.00

3.28

3.55

EVR 6

1.92

2.71

3.32

3.83

4.28

4.69

5.07

EVR 8

2.68

3.79

4.65

5.36

6.00

6.57

7.10

EVR 10

4.55

6.43

7.88

9.10

10.17

11.14

12.04

EVR 15

6.23

8.80

10.78

12.45

13.92

15.25

16.47

EVR 18

8.14

11.51

14.10

16.28

18.20

19.94

21.54

EVR 20

11.97

16.93

20.74

23.94

26.77

29.33

31.68

EVR 22

14.37

20.32

24.88

28.73

32.13

35.19

38.01

EVR 25

0.28

22.46

41.47

47.89

53.54

58.65

63.35

EVR 32

0.44

35.94

66.36

76.62

85.67

93.84

101.36

EVR 40

0.67

56.14

103.68

119.72

133.86

146.63

158.38

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.
Correction factors for liquid temperature tl

tl [F]

80

90

100

110

120

Factor

1.10

1.05

1.00

0.95

0.90

DKRCC.PD.BB0.A8.22

Data sheet
Capacity
Liquid
(continued)

Solenoid valve, types EVR 2 EVR 40


Liquid capacity Q0 [TR]
at a pressure drop across valve p [psi]

Type
1

R32
EVR 2

0.79

1.12

1.38

1.59

1.78

1.95

2.10

EVR 3

1.34

1.90

2.32

2.68

3.00

3.28

3.55

EVR 4

2.78

3.93

4.82

5.56

6.22

6.81

7.36

EVR 6

3.97

5.62

6.88

7.94

8.88

9.73

10.51

EVR 8

5.56

7.87

9.63

11.12

12.44

13.62

14.71

EVR 10

9.43

13.34

16.34

18.87

21.10

23.11

24.96

EVR 15

12.91

18.26

22.36

25.82

28.87

31.62

34.16

EVR 18

16.88

23.88

29.24

33.77

37.75

41.35

44.67

EVR 20

24.83

35.11

43.00

49.66

55.52

60.82

65.69

R290

Capacities are based on:


Liquid temperature tl= 100 F
Evaporating
temperature te = 40 F
Superheat
temperature (te+ 10 F) = 50 F
Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 2

0.65

0.93

1.13

1.31

1.46

1.60

1.73

EVR 3

1.11

1.56

1.91

2.21

2.47

2.71

2.92

EVR 4

2.29

3.24

3.97

4.58

5.13

5.62

6.07

EVR 6

3.27

4.63

5.67

6.55

7.32

8.02

8.66

EVR 8

4.58

6.48

7.94

9.17

10.25

11.23

12.13

EVR 10

7.78

11.00

13.47

15.56

17.39

19.05

20.58

EVR 15

10.64

15.05

18.43

21.29

23.80

26.07

28.16

EVR 18

13.92

19.68

24.11

27.84

31.12

34.09

36.82

EVR 20

20.47

28.95

35.45

40.94

45.77

50.14

54.15

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.
Correction factors for liquid temperature tl
tl [F]

80

90

100

110

120

Factor

1.10

1.05

1.00

0.95

0.90

10 DKRCC.PD.BB0.A8.22

Data sheet
Capacity
Liquid
(continued)

Solenoid valve, types EVR 2 EVR 40


Liquid capacity Q0 [TR]
at a pressure drop across valve p [psi]

Type
1

R600
EVR 2

0.77

1.08

1.33

1.53

1.71

1.88

2.03

EVR 3

1.29

1.83

2.24

2.58

2.89

3.17

3.42

EVR 4

2.68

3.79

4.64

5.36

5.99

6.57

7.09

EVR 6

3.83

5.42

6.63

7.66

8.56

9.38

10.13

EVR 8

5.36

7.58

9.29

10.72

11.99

13.13

14.18

EVR 10

9.10

12.86

15.75

18.19

20.34

22.28

24.06

EVR 15

12.45

17.60

21.56

24.89

27.83

30.49

32.93

EVR 18

16.28

23.02

28.19

32.55

36.39

39.87

43.06

EVR 20

23.93

33.85

41.46

47.87

53.52

58.63

63.33

R600a

Capacities are based on:


Liquid temperature tl= 100 F
Evaporating
temperature te = 40 F
Superheat
temperature (te+ 10 F) = 50 F
Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 2

0.68

0.96

1.17

1.35

1.51

1.66

1.79

EVR 3

1.14

1.61

1.98

2.28

2.55

2.80

3.02

EVR 4

2.37

3.35

4.10

4.73

5.29

5.80

6.26

EVR 6

3.38

4.78

5.86

6.76

7.56

8.28

8.95

EVR 8

4.73

6.69

8.20

9.47

10.59

11.60

12.52

EVR 10

8.03

11.36

13.91

16.06

17.96

19.67

21.25

EVR 15

10.99

15.54

19.03

21.98

24.57

26.92

29.07

EVR 18

14.37

20.32

24.89

28.74

32.13

35.20

38.02

EVR 20

21.13

29.89

36.60

42.27

47.25

51.76

55.91

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.
Correction factors for liquid temperature tl

tl [F]

80

90

100

110

120

Factor

1.10

1.05

1.00

0.95

0.90

DKRCC.PD.BB0.A8.22

11

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Suction vapor

Type

Pressure drop
across valve
p [psi]

-40

-20

Suction vapor capacity Q0 [TR]


at evaporating temperature te [F]
0
10
20
30

40

50

R22/R407C
EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

EVR 20

EVR 22

EVR 25

EVR 32

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 40

1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3

0.03
0.04
0.05
0.05
0.07
0.09
0.11
0.15
0.18
0.16
0.22
0.25
0.22
0.30
0.35
0.38
0.51
0.60
0.52
0.70
0.82
0.68
0.92
1.08
0.99
1.35
1.58
1.19
1.62
1.90
0.01
1.72
3.17
0.02
2.76
5.07
0.03
4.31
7.92

0.04
0.06
0.07
0.07
0.10
0.12
0.15
0.20
0.24
0.21
0.29
0.35
0.29
0.41
0.49
0.50
0.69
0.82
0.68
0.94
1.13
0.89
1.23
1.47
1.31
1.81
2.17
1.58
2.18
2.60
0.02
2.35
4.34
0.03
3.77
6.94
0.05
5.88
10.84

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.

0.05
0.08
0.09
0.09
0.13
0.15
0.19
0.26
0.32
0.27
0.38
0.45
0.38
0.53
0.63
0.64
0.89
1.08
0.88
1.22
1.47
1.15
1.60
1.93
1.69
2.35
2.83
2.02
2.82
3.40
0.02
3.07
5.67
0.04
4.92
9.07
0.06
7.68
14.17

0.06
0.08
0.10
0.10
0.14
0.17
0.21
0.30
0.36
0.30
0.42
0.51
0.42
0.59
0.72
0.72
1.00
1.22
0.98
1.38
1.66
1.29
1.80
2.18
1.89
2.64
3.20
2.27
3.17
3.84
0.03
3.47
6.40
0.04
5.55
10.24
0.07
8.67
15.99

0.07
0.09
0.11
0.11
0.16
0.19
0.24
0.33
0.40
0.34
0.47
0.57
0.47
0.66
0.80
0.80
1.12
1.36
1.10
1.54
1.87
1.44
2.01
2.44
2.11
2.96
3.59
2.54
3.55
4.30
0.03
3.89
7.17
0.05
6.22
11.48
0.08
9.72
17.94

0.08
0.11
0.13
0.13
0.18
0.22
0.26
0.37
0.45
0.38
0.53
0.64
0.53
0.74
0.90
0.89
1.25
1.52
1.22
1.71
2.08
1.60
2.24
2.72
2.35
3.29
4.00
2.82
3.95
4.80
0.03
4.34
8.00
0.06
6.94
12.80
0.09
10.84
20.00

0.08
0.12
0.14
0.14
0.20
0.24
0.29
0.41
0.50
0.42
0.58
0.71
0.58
0.82
0.99
0.99
1.39
1.69
1.35
1.90
2.31
1.77
2.48
3.02
2.60
3.65
4.44
3.12
4.38
5.32
0.04
4.81
8.87
0.06
7.69
14.19
0.09
12.02
22.18

0.09
0.13
0.16
0.15
0.22
0.26
0.32
0.45
0.55
0.46
0.64
0.78
0.64
0.90
1.10
1.09
1.53
1.86
1.49
2.09
2.55
1.94
2.73
3.33
2.86
4.02
4.90
3.43
4.83
5.88
0.04
5.31
9.79
0.07
8.49
15.67
0.10
13.26
24.48

The table values refer to evaporator capacity


and are given as a function of evaporating
temperature te and pressure drop p across
the valve. Capacities are based on liquid
temperature tl= 100 F ahead of the expansion
valve and superheat ts= 7 F.
For each additional 10 F of superheat,
the table capacities must be reduced by 2%.

Correction factors for liquid temperature tl


tl [F]
Factor

80
1.10

90
1.05

12 DKRCC.PD.BB0.A8.22

100
1.00

110
0.95

120
0.90

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Suction vapor
(continued)

Type

Pressure drop
across valve
p [psi]

-40

-20

Suction vapor capacity Q0 [TR]


at evaporating temperature te [F]
0
10
20
30

40

50

R134a
EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

EVR 20

EVR 22

EVR 25

EVR 32

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 40

1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3

0.02
0.02
0.03
0.03
0.04
0.05
0.07
0.09
0.10
0.10
0.12
0.14
0.14
0.17
0.19
0.23
0.30
0.33
0.32
0.41
0.45
0.41
0.53
0.58
0.61
0.78
0.86
0.73
0.93
1.03
0.01
0.94
1.71
0.01
1.50
2.74
0.02
2.35
4.28

0.03
0.04
0.04
0.05
0.06
0.07
0.10
0.13
0.15
0.14
0.19
0.22
0.19
0.26
0.30
0.33
0.44
0.51
0.45
0.60
0.70
0.59
0.79
0.92
0.87
1.16
1.35
1.04
1.39
1.62
0.01
1.47
2.69
0.02
2.35
4.31
0.03
3.66
6.73

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.

0.04
0.05
0.06
0.06
0.09
0.10
0.13
0.18
0.21
0.19
0.26
0.31
0.26
0.36
0.43
0.45
0.61
0.73
0.61
0.84
1.00
0.80
1.10
1.30
1.18
1.61
1.92
1.41
1.94
2.30
0.02
2.08
3.83
0.03
3.33
6.13
0.04
5.20
9.58

0.04
0.06
0.07
0.07
0.10
0.12
0.15
0.21
0.25
0.22
0.30
0.36
0.30
0.42
0.50
0.51
0.71
0.85
0.70
0.97
1.16
0.92
1.27
1.52
1.35
1.87
2.23
1.63
2.24
2.68
0.02
2.43
4.47
0.03
3.88
7.15
0.05
6.06
11.17

0.05
0.07
0.08
0.08
0.12
0.14
0.17
0.24
0.29
0.25
0.34
0.41
0.35
0.48
0.58
0.59
0.82
0.98
0.80
1.12
1.34
1.05
1.46
1.75
1.55
2.15
2.58
1.86
2.58
3.09
0.02
2.80
5.16
0.04
4.48
8.25
0.06
7.00
12.90

0.06
0.08
0.09
0.09
0.13
0.16
0.20
0.27
0.33
0.28
0.39
0.47
0.39
0.55
0.66
0.67
0.93
1.12
0.91
1.27
1.53
1.20
1.66
2.01
1.76
2.45
2.95
2.11
2.94
3.54
0.03
3.20
5.90
0.04
5.12
9.44
0.06
8.00
14.75

0.06
0.09
0.11
0.11
0.15
0.18
0.22
0.31
0.38
0.32
0.44
0.54
0.44
0.62
0.75
0.75
1.05
1.27
1.03
1.44
1.74
1.35
1.88
2.28
1.98
2.77
3.35
2.38
3.32
4.02
0.03
3.63
6.70
0.05
5.81
10.72
0.07
9.08
16.75

0.07
0.10
0.12
0.12
0.17
0.20
0.25
0.35
0.42
0.36
0.50
0.60
0.50
0.70
0.85
0.85
1.19
1.44
1.16
1.62
1.97
1.52
2.12
2.57
2.23
3.12
3.78
2.67
3.74
4.54
0.03
4.10
7.56
0.05
6.56
12.10
0.08
10.24
18.90

The table values refer to evaporator capacity


and are given as a function of evaporating
temperature te and pressure drop Dp across
the valve. Capacities are based on liquid
temperature tl= 100 F ahead of the expansion
valve and superheat ts = 7 F.
For each additional 10 F of superheat,
the table capacities must be reduced by 2%.

Correction factors for liquid temperature tl


tl [F]
Factor

80
1.10

90
1.05

DKRCC.PD.BB0.A8.22

100
1.00

110
0.95

120
0.90

13

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Suction vapor
(continued)

Type

Pressure drop
across valve
p [psi]

-40

-20

Suction vapor capacity Q0 [TR]


at evaporating temperature te [F]
0
10
20
30

40

50

R404A and R507


EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

EVR 20

EVR 22

EVR 25

EVR 32

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 40

1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3

0.02
0.03
0.04
0.04
0.06
0.07
0.08
0.11
0.14
0.12
0.16
0.19
0.17
0.23
0.27
0.28
0.39
0.46
0.39
0.53
0.63
0.51
0.70
0.82
0.75
1.03
1.21
0.90
1.23
1.46
0.01
1.32
2.43
0.02
2.11
3.88
0.03
3.30
6.06

0.03
0.05
0.05
0.06
0.08
0.09
0.11
0.16
0.19
0.16
0.23
0.27
0.23
0.32
0.38
0.39
0.54
0.65
0.53
0.74
0.89
0.70
0.96
1.16
1.02
1.42
1.70
1.23
1.70
2.04
0.01
1.85
3.40
0.02
2.96
5.45
0.04
4.62
8.51

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.

0.04
0.06
0.07
0.07
0.10
0.12
0.15
0.21
0.26
0.22
0.30
0.37
0.30
0.42
0.51
0.51
0.72
0.87
0.70
0.98
1.19
0.92
1.28
1.55
1.35
1.89
2.28
1.62
2.27
2.74
0.02
2.48
4.57
0.03
3.96
7.31
0.05
6.19
11.42

0.05
0.07
0.08
0.08
0.12
0.14
0.17
0.24
0.29
0.25
0.34
0.42
0.34
0.48
0.58
0.59
0.82
0.99
0.80
1.12
1.36
1.05
1.47
1.78
1.54
2.15
2.61
1.85
2.59
3.13
0.02
2.83
5.22
0.04
4.53
8.36
0.06
7.08
13.06

0.06
0.08
0.09
0.09
0.13
0.16
0.20
0.27
0.33
0.28
0.39
0.47
0.39
0.55
0.66
0.66
0.93
1.13
0.91
1.27
1.54
1.18
1.66
2.02
1.74
2.44
2.97
2.09
2.93
3.56
0.03
3.22
5.93
0.04
5.15
9.49
0.06
8.04
14.83

0.06
0.09
0.11
0.11
0.15
0.18
0.22
0.31
0.38
0.31
0.44
0.54
0.44
0.62
0.75
0.75
1.05
1.27
1.02
1.43
1.74
1.33
1.87
2.28
1.96
2.75
3.35
2.35
3.31
4.02
0.03
3.63
6.70
0.05
5.81
10.72
0.07
9.07
16.75

0.07
0.10
0.12
0.12
0.17
0.20
0.25
0.35
0.42
0.35
0.49
0.60
0.49
0.69
0.84
0.83
1.17
1.43
1.14
1.61
1.96
1.49
2.10
2.56
2.20
3.09
3.76
2.64
3.71
4.51
0.03
4.08
7.52
0.05
6.52
12.04
0.08
10.19
18.81

0.08
0.11
0.13
0.13
0.19
0.23
0.27
0.39
0.47
0.39
0.55
0.67
0.55
0.77
0.94
0.93
1.31
1.60
1.27
1.79
2.19
1.67
2.35
2.86
2.45
3.45
4.20
2.94
4.14
5.05
0.04
4.56
8.41
0.06
7.29
13.45
0.09
11.39
21.02

The table values refer to evaporator capacity


and are given as a function of evaporating
temperature te and pressure drop p across
the valve. Capacities are based on liquid
temperature tl= 100 F ahead of the expansion
valve and superheat ts= 7 F.
For each additional 10 F of superheat, the table
capacities must be reduced by 2%.

Correction factors for liquid temperature tl


tl [F]
Factor

80
1.10

90
1.05

14 DKRCC.PD.BB0.A8.22

100
1.00

110
0.90

120
0.90

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Suction vapor
(continued)

Type

Pressure drop
across valve
p [psi]

-40

-20

Suction vapor capacity Q0 [TR]


at evaporating temperature te [F]
0
10
20
30

40

50

R32
EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 20

1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3

0.05
0.07
0.09
0.09
0.13
0.15
0.19
0.26
0.31
0.27
0.37
0.44
0.38
0.52
0.62
0.64
0.88
1.06
0.87
1.21
1.45
1.14
1.58
1.89
1.68
2.32
2.78

0.07
0.10
0.12
0.12
0.16
0.20
0.24
0.34
0.41
0.35
0.48
0.58
0.49
0.68
0.82
0.82
1.15
1.39
1.13
1.57
1.90
1.47
2.06
2.48
2.17
3.02
3.65

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.

0.09
0.12
0.15
0.15
0.21
0.25
0.31
0.43
0.52
0.44
0.61
0.74
0.61
0.86
1.04
1.04
1.45
1.76
1.42
1.99
2.41
1.85
2.60
3.16
2.72
3.82
4.64

0.10
0.14
0.17
0.16
0.23
0.28
0.34
0.48
0.58
0.48
0.68
0.83
0.68
0.95
1.16
1.15
1.62
1.97
1.58
2.21
2.69
2.06
2.90
3.52
3.03
4.26
5.18

0.11
0.15
0.18
0.18
0.25
0.31
0.38
0.53
0.64
0.54
0.76
0.92
0.75
1.06
1.29
1.28
1.79
2.19
1.75
2.45
2.99
2.28
3.21
3.91
3.36
4.72
5.75

0.12
0.17
0.20
0.20
0.28
0.34
0.41
0.58
0.71
0.59
0.83
1.02
0.83
1.17
1.42
1.41
1.98
2.41
1.92
2.71
3.30
2.52
3.54
4.32
3.70
5.21
6.35

0.13
0.18
0.22
0.22
0.31
0.38
0.45
0.64
0.78
0.65
0.92
1.12
0.91
1.28
1.56
1.54
2.17
2.65
2.11
2.98
3.63
2.76
3.89
4.75
4.06
5.72
6.98

0.14
0.20
0.24
0.24
0.34
0.41
0.50
0.70
0.86
0.71
1.00
1.22
0.99
1.40
1.71
1.69
2.38
2.91
2.31
3.26
3.98
3.02
4.26
5.20
4.44
6.26
7.65

The table values refer to evaporator capacity


and are given as a function of evaporating
temperature te and pressure drop p across
the valve. Capacities are based on liquid
temperature tl= 100 F ahead of the expansion
valve and superheat ts= 7 F.
For each additional 10 F of superheat, the table
capacities must be reduced by 2%.

Correction factors for liquid temperature tl


tl [F]
Factor

80
1.10

90
1.05

DKRCC.PD.BB0.A8.22

100
1.00

110
0.90

120
0.90

15

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Suction vapor
(continued)

Type

Pressure drop
across valve
p [psi]

-40

-20

Suction vapor capacity Q0 [TR]


at evaporating temperature te [F]
0
10
20
30

40

50

R290
EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 20

1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3

0.04
0.05
0.06
0.06
0.09
0.10
0.13
0.18
0.21
0.19
0.26
0.30
0.27
0.36
0.42
0.45
0.61
0.72
0.62
0.84
0.98
0.81
1.09
1.29
1.18
1.61
1.89

0.05
0.07
0.08
0.08
0.12
0.14
0.18
0.24
0.29
0.25
0.35
0.41
0.35
0.49
0.58
0.60
0.82
0.98
0.82
1.13
1.35
1.07
1.47
1.76
1.57
2.17
2.59

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.

0.06
0.09
0.11
0.11
0.15
0.18
0.23
0.32
0.38
0.32
0.45
0.54
0.45
0.63
0.76
0.77
1.07
1.29
1.05
1.46
1.76
1.38
1.91
2.31
2.02
2.82
3.39

0.07
0.10
0.12
0.12
0.17
0.21
0.26
0.36
0.43
0.36
0.51
0.61
0.51
0.71
0.86
0.87
1.21
1.46
1.18
1.65
2.00
1.55
2.16
2.61
2.28
3.18
3.84

0.08
0.11
0.14
0.14
0.19
0.23
0.29
0.40
0.48
0.41
0.57
0.69
0.57
0.80
0.97
0.97
1.36
1.64
1.33
1.85
2.25
1.73
2.43
2.94
2.55
3.57
4.32

0.09
0.13
0.15
0.15
0.22
0.26
0.32
0.45
0.54
0.45
0.64
0.77
0.64
0.89
1.08
1.08
1.51
1.84
1.48
2.07
2.51
1.93
2.71
3.29
2.84
3.98
4.83

0.10
0.14
0.17
0.17
0.24
0.29
0.35
0.50
0.60
0.50
0.71
0.86
0.71
0.99
1.21
1.20
1.68
2.04
1.64
2.30
2.80
2.14
3.01
3.66
3.15
4.43
5.38

0.11
0.16
0.19
0.19
0.26
0.32
0.39
0.55
0.67
0.56
0.78
0.95
0.78
1.10
1.34
1.33
1.86
2.27
1.81
2.55
3.10
2.37
3.33
4.05
3.49
4.90
5.96

The table values refer to evaporator capacity


and are given as a function of evaporating
temperature te and pressure drop p across
the valve. Capacities are based on liquid
temperature tl= 100 F ahead of the expansion
valve and superheat ts= 7 F.
For each additional 10 F of superheat, the table
capacities must be reduced by 2%.

Correction factors for liquid temperature tl


tl [F]
Factor

80
1.10

90
1.05

16 DKRCC.PD.BB0.A8.22

100
1.00

110
0.90

120
0.90

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Suction vapor
(continued)

Type

Pressure drop
across valve
p [psi]

-40

-20

Suction vapor capacity Q0 [TR]


at evaporating temperature te [F]
0
10
20
30

40

50

R600
EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 20

1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3

0.01
0.01
0.01
0.02
0.02
0.02
0.05
0.05
0.05
0.07
0.07
0.07
0.09
0.09
0.09
0.16
0.16
0.16
0.22
0.22
0.22
0.28
0.29
0.29
0.42
0.42
0.42

0.02
0.02
0.03
0.04
0.04
0.04
0.07
0.09
0.09
0.11
0.12
0.13
0.15
0.17
0.18
0.25
0.30
0.30
0.35
0.40
0.41
0.45
0.53
0.53
0.67
0.78
0.78

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.

0.03
0.04
0.04
0.05
0.07
0.07
0.11
0.14
0.15
0.15
0.20
0.21
0.22
0.28
0.30
0.37
0.47
0.51
0.50
0.64
0.70
0.65
0.84
0.91
0.96
1.23
1.34

0.04
0.05
0.05
0.06
0.08
0.09
0.13
0.17
0.19
0.18
0.24
0.27
0.25
0.33
0.37
0.43
0.56
0.63
0.59
0.77
0.87
0.77
1.01
1.13
1.13
1.48
1.66

0.04
0.06
0.06
0.07
0.09
0.11
0.15
0.20
0.22
0.21
0.28
0.32
0.29
0.39
0.45
0.50
0.66
0.76
0.68
0.91
1.04
0.89
1.19
1.36
1.31
1.75
2.01

0.05
0.07
0.08
0.08
0.11
0.13
0.17
0.23
0.27
0.24
0.33
0.38
0.34
0.46
0.53
0.57
0.77
0.90
0.79
1.06
1.23
1.03
1.38
1.61
1.51
2.04
2.37

0.06
0.08
0.09
0.09
0.13
0.15
0.19
0.26
0.31
0.28
0.38
0.44
0.39
0.53
0.62
0.66
0.89
1.05
0.90
1.22
1.44
1.17
1.60
1.88
1.72
2.35
2.76

0.06
0.09
0.10
0.11
0.14
0.17
0.22
0.30
0.36
0.31
0.43
0.51
0.44
0.60
0.71
0.74
1.02
1.21
1.02
1.39
1.65
1.33
1.82
2.16
1.96
2.68
3.18

The table values refer to evaporator capacity


and are given as a function of evaporating
temperature te and pressure drop p across
the valve. Capacities are based on liquid
temperature tl= 100 F ahead of the expansion
valve and superheat ts= 7 F.
For each additional 10 F of superheat, the table
capacities must be reduced by 2%.

Correction factors for liquid temperature tl


tl [F]
Factor

80
1.10

90
1.05

DKRCC.PD.BB0.A8.22

100
1.00

110
0.90

120
0.90

17

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Suction vapor
(continued)

Type

Pressure drop
across valve
p [psi]

-40

-20

Suction vapor capacity Q0 [TR]


at evaporating temperature te [F]
0
10
20
30

40

50

R600a
EVR 2

EVR 3

EVR 4

EVR 6

EVR 8

EVR 10

EVR 15

EVR 18

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 20

1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3

0.02
0.02
0.02
0.03
0.03
0.03
0.06
0.07
0.07
0.09
0.10
0.10
0.12
0.14
0.14
0.21
0.24
0.24
0.29
0.33
0.33
0.37
0.43
0.43
0.55
0.64
0.64

0.03
0.03
0.04
0.04
0.06
0.06
0.09
0.12
0.13
0.13
0.17
0.18
0.18
0.23
0.25
0.31
0.39
0.43
0.42
0.54
0.59
0.55
0.70
0.77
0.81
1.04
1.13

Correction factors
When liquid temperature tl ahead of the
expansion valve is other than 100 F, adjust
the table capacities by multiplying them
by the appropriate correction factor found
in the following table.

0.04
0.05
0.06
0.06
0.08
0.09
0.13
0.17
0.19
0.18
0.24
0.28
0.25
0.34
0.39
0.43
0.57
0.65
0.59
0.78
0.90
0.77
1.02
1.17
1.13
1.50
1.72

0.04
0.06
0.07
0.07
0.10
0.11
0.15
0.20
0.23
0.21
0.28
0.33
0.29
0.39
0.46
0.50
0.67
0.78
0.68
0.92
1.07
0.89
1.20
1.40
1.31
1.76
2.05

0.05
0.07
0.08
0.08
0.11
0.13
0.17
0.23
0.27
0.24
0.33
0.39
0.34
0.46
0.54
0.57
0.78
0.91
0.78
1.06
1.25
1.02
1.39
1.64
1.50
2.04
2.41

0.05
0.08
0.09
0.09
0.13
0.15
0.19
0.26
0.31
0.27
0.38
0.45
0.38
0.53
0.62
0.65
0.89
1.06
0.89
1.22
1.45
1.16
1.60
1.89
1.71
2.35
2.79

0.06
0.09
0.10
0.10
0.14
0.17
0.22
0.30
0.36
0.31
0.43
0.51
0.43
0.60
0.72
0.74
1.02
1.21
1.01
1.39
1.66
1.32
1.82
2.17
1.94
2.68
3.19

0.07
0.10
0.12
0.12
0.16
0.20
0.24
0.34
0.41
0.35
0.48
0.58
0.49
0.68
0.81
0.83
1.15
1.38
1.14
1.57
1.89
1.49
2.06
2.47
2.19
3.03
3.63

The table values refer to evaporator capacity


and are given as a function of evaporating
temperature te and pressure drop p across
the valve. Capacities are based on liquid
temperature tl= 100 F ahead of the expansion
valve and superheat ts= 7 F.
For each additional 10 F of superheat, the table
capacities must be reduced by 2%.

Correction factors for liquid temperature tl


tl [F]
Factor

80
1.10

90
1.05

18 DKRCC.PD.BB0.A8.22

100
1.00

110
0.90

120
0.90

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Hot gas
Type

Pressure
drop
across
valve
p
[psi]
2

EVR 2

EVR 3

EVR 4

EVR 6

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

Hot gas capacity Qh [TR]


Evaporating temp. te= 40 F, hot gas temp. th=tc+40 F, subcooling tu= 10 F
R22/R407C

R134a

R404A/R507

Condensing temp. tc
[F]

Condensing temp. tc
[F]

Condensing temp. tc
[F]

70

100

140

70

100

140

70

100

140

0.15

0.16

0.17

0.12

0.14

0.14

0.14

0.14

0.13

0.24

0.26

0.27

0.19

0.21

0.22

0.22

0.23

0.21

10

0.33

0.36

0.38

0.26

0.29

0.30

0.31

0.32

0.29

15

0.39

0.43

0.46

0.31

0.35

0.37

0.37

0.38

0.35

20

0.44

0.49

0.52

0.34

0.39

0.42

0.42

0.44

0.40

25

0.48

0.54

0.58

0.36

0.43

0.46

0.46

0.48

0.44

0.26

0.28

0.29

0.21

0.23

0.23

0.24

0.24

0.22

0.40

0.43

0.45

0.32

0.36

0.37

0.38

0.38

0.35

10

0.55

0.61

0.64

0.44

0.49

0.51

0.52

0.53

0.49

15

0.66

0.73

0.77

0.52

0.59

0.62

0.62

0.65

0.59

20

0.74

0.83

0.88

0.57

0.66

0.70

0.71

0.74

0.68

25

0.81

0.91

0.98

0.61

0.72

0.78

0.77

0.81

0.75

0.53

0.57

0.60

0.44

0.47

0.49

0.50

0.51

0.46

0.83

0.90

0.94

0.67

0.74

0.76

0.78

0.79

0.72

10

1.14

1.26

1.32

0.92

1.02

1.06

1.08

1.11

1.01

15

1.37

1.52

1.60

1.08

1.22

1.28

1.30

1.34

1.22

20

1.54

1.72

1.83

1.19

1.37

1.46

1.47

1.53

1.40

25

1.68

1.90

2.03

1.27

1.49

1.61

1.60

1.68

1.56

0.76

0.82

0.86

0.62

0.68

0.69

0.71

0.72

0.65

1.18

1.29

1.35

0.96

1.05

1.09

1.11

1.13

1.03

10

1.63

1.79

1.89

1.31

1.46

1.52

1.54

1.58

1.44

15

1.95

2.16

2.29

1.54

1.74

1.83

1.85

1.91

1.75

20

2.20

2.46

2.62

1.70

1.96

2.09

2.09

2.18

2.00

25

2.40

2.71

2.90

1.82

2.13

2.30

2.29

2.41

2.22

For each additional 10 F of superheat above


40 F, the table capacities must be reduced by 1%.
When the valve is used in a hot gas defrost
circuit. evaporator temperature affects the
capacity. When the evaporator temperature
differs from 40 F, adjust the table capacities
by multiplying them by the appropriate
correction factor found in the following table.

Correction factors
The table values refer to hot gas capacity
and are given as a function of condensing
temperature tc and pressure drop p across
the valve. Capacities are based on a hot gas
temperature superheated 40 F above
condensing temperature (th= tc+ 40 F).

Correction factors for th and te


te [F]
Factor

-40
1.18

-20
1.14

DKRCC.PD.BB0.A8.22

0
1.09

20
1.04

40
1

50
0.97

19

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Hot gas
(continued)
Type

EVR 8

EVR 10

EVR 15

EVR 18

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

Pressure
drop
across
valve
p
[psi]

Hot gas capacity Qh [TR]


Evaporating temp. te= 40 F, hot gas temp. th= tc+40 F, subcooling tu= 10 F
R22/R407C

R134a

R404A/R507

Condensing temp. tc
[F]

Condensing temp. tc
[F]

Condensing temp. tc
[F]

70

100

140

70

100

140

70

100

140

1.06

1.15

1.20

0.87

0.95

0.97

1.00

1.01

0.91

1.65

1.80

1.88

1.35

1.48

1.52

1.56

1.59

1.44

10

2.29

2.51

2.64

1.83

2.04

2.12

2.16

2.22

2.01

15

2.74

3.03

3.21

2.15

2.43

2.57

2.59

2.68

2.45

20

3.08

3.45

3.67

2.38

2.74

2.92

2.93

3.05

2.81

25

3.36

3.80

4.07

2.54

2.99

3.22

3.21

3.37

3.11

1.80

1.95

2.03

1.48

1.61

1.65

1.69

1.72

1.55

2.81

3.06

3.19

2.29

2.50

2.58

2.64

2.69

2.44

10

3.88

4.26

4.48

3.11

3.46

3.60

3.66

3.76

3.42

15

4.64

5.14

5.44

3.65

4.13

4.35

4.40

4.55

4.15

20

5.23

5.85

6.23

4.03

4.65

4.96

4.97

5.18

4.76

25

5.71

6.44

6.90

4.31

5.07

5.47

5.44

5.72

5.28

2.46

2.67

2.78

2.02

2.20

2.25

2.31

2.35

2.12

3.84

4.18

4.37

3.13

3.43

3.53

3.62

3.69

3.33

10

5.31

5.83

6.13

4.25

4.73

4.93

5.01

5.15

4.68

15

6.35

7.03

7.44

4.99

5.65

5.96

6.02

6.22

5.68

20

7.16

8.00

8.52

5.52

6.36

6.79

6.81

7.09

6.51

25

7.81

8.81

9.44

5.90

6.93

7.48

7.45

7.82

7.23

3.22

3.49

3.63

2.65

2.87

2.95

3.03

3.07

2.77

5.02

5.47

5.72

4.09

4.48

4.62

4.73

4.82

4.36

10

6.94

7.62

8.02

5.56

6.18

6.45

6.56

6.73

6.12

15

8.30

9.20

9.73

6.53

7.39

7.79

7.87

8.14

7.43

20

9.36

10.46

11.14

7.22

8.32

8.87

8.90

9.27

8.52

25

10.21

11.52

12.34

7.71

9.06

9.78

9.74

10.23

9.45

Correction factors
The table values refer to hot gas capacity
and are given as a function of condensing
temperature tc and pressure drop p across
the valve. Capacities are based on a hot gas
temperature superheated 40 F above
condensing temperature (th=tc+ 40 F).
For each additional 10 F of superheat above
40 F, the table capacities must be reduced by 1%.

When the valve is used in a hot gas defrost


circuit. evaporator temperature affects the
capacity. When the evaporator temperature
differs from 40 F, adjust the table capacities
by multiplying them by the appropriate
correction factor found in the following table.

Correction factors for th and te


te [F]
Factor

-40
1.18

-20
1.14

20 DKRCC.PD.BB0.A8.22

0
1.09

20
1.04

40
1

50
0.97

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Hot gas
(continued)
Type

Pressure
drop
across
valve
p
[psi]
2

EVR 20

EVR 22

EVR 25

EVR 32

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 40

Hot gas capacity Qh [TR]


Evaporating temp. te= 40 F, hot gas temp. th=tc+ 40 F, subcooling tu= 10 F
R22/R407C

R134a

R404A/R507

Condensing temp. tc
[F]
70
100
140

Condensing temp. tc
[F]
70
100
140

Condensing temp. tc
[F]
70
100
140

4.73

5.34

3.89

4.45

5.13

4.23

4.33

4.52

4.07

7.39

8.04

8.41

6.01

6.59

6.80

6.95

7.09

6.41

10

10.21

11.21

11.79

8.17

9.09

9.48

9.64

9.90

8.99

15

12.21

13.53

14.31

9.60

10.87

11.46

11.57

11.96

10.93

20

13.77

15.39

16.38

10.62

12.23

13.05

13.09

13.63

12.53

25

15.02

16.94

18.15

11.34

13.33

14.39

14.33

15.04

13.90

5.68

6.16

6.41

4.67

5.07

5.20

5.34

5.42

4.89

8.86

9.65

10.09

7.22

7.90

8.16

8.35

8.50

7.69

10

12.25

13.45

14.14

9.81

10.91

11.38

11.57

11.87

10.79

15

14.65

16.23

17.17

11.52

13.04

13.75

13.89

14.36

13.12

20

16.52

18.47

19.66

12.74

14.68

15.66

15.71

16.36

15.03

25

18.02

20.33

21.79

13.61

15.99

17.26

17.19

18.05

16.67

6.26

6.79

7.08

5.13

5.58

5.74

5.88

5.98

5.39

14.77

16.09

16.81

12.03

13.17

13.59

13.91

14.17

12.82

10

20.42

22.42

23.57

16.34

18.19

18.97

19.28

19.79

17.99

15

24.42

27.06

28.62

19.20

21.73

22.92

23.14

23.93

21.86

20

27.53

30.78

32.76

21.23

24.47

26.10

26.18

27.27

25.05

25

30.04

33.89

36.31

22.69

26.66

28.77

28.66

30.08

27.79

10.01

10.86

11.33

8.20

8.93

9.17

9.41

9.56

8.63

23.63

25.74

26.90

19.24

21.08

21.75

22.25

22.68

20.51

10

32.66

35.87

37.72

26.15

29.10

30.35

30.85

31.67

28.78

15

39.08

43.29

45.80

30.72

34.77

36.66

37.03

38.28

34.98

20

44.05

49.24

52.42

33.97

39.15

41.76

41.89

43.63

40.08

25

48.06

54.22

58.09

36.30

42.65

46.04

45.85

48.14

44.46

15.63

16.97

17.69

12.82

13.95

14.33

14.70

14.94

13.48

36.93

40.22

42.04

30.07

32.94

33.98

34.77

35.44

32.04

10

51.04

56.05

58.94

40.86

45.47

47.42

48.21

49.48

44.97

15

61.06

67.64

71.56

48.01

54.33

57.29

57.86

59.82

54.65

20

68.84

76.94

81.91

53.08

61.17

65.24

65.45

68.17

62.63

25

75.09

84.72

90.77

56.72

66.64

71.93

71.64

75.21

69.48

Correction factors
The table values refer to hot gas capacity
and are given as a function of condensing
temperature tc and pressure drop p across
the valve. Capacities are based on a hot gas
temperature superheated 40 F above
condensing temperature (th= tc+40 F).
For each additional 10 F of superheat above
40 F, the table capacities must be reduced by 1%.

When the valve is used in a hot gas defrost


circuit. evaporator temperature affects the
capacity. When the evaporator temperature
differs from 40 F, adjust the table capacities
by multiplying them by the appropriate
correction factor found in the following table.

Correction factors for th and te


te [F]
Factor

-40
1.18

-20
1.14

0
1.09

DKRCC.PD.BB0.A8.22

20
1.04

40
1

50
0.97

21

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Hot gas
Type

EVR 2

EVR 3

EVR 4

EVR 6

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

Hot gas capacity Qh [TR]


Evaporating temp. te= 40 F, hot gas temp. th=tc+40 F, subcooling tu= 10 F
Pressure
drop
across
R32
R290
R600
R600a
valve
Condensing temp. tc Condensing temp. tc Condensing temp. tc Condensing temp. tc
p
[F]
[F]
[F]
[F]
[psi]
70

100

140

70

100

140

70

100

140

70

100

140

0.23

0.25

0.26

0.19

0.20

0.19

0.11

0.12

0.13

0.12

0.13

0.14

0.36

0.40

0.41

0.29

0.31

0.31

0.16

0.18

0.20

0.18

0.20

0.21

10

0.51

0.55

0.58

0.40

0.43

0.43

0.20

0.24

0.28

0.24

0.27

0.29

15

0.61

0.67

0.70

0.48

0.52

0.52

0.21

0.27

0.32

0.27

0.32

0.35

20

0.70

0.77

0.81

0.54

0.59

0.59

0.21

0.29

0.36

0.28

0.35

0.39

25

0.77

0.86

0.90

0.59

0.64

0.65

0.21

0.30

0.38

0.28

0.37

0.43

0.39

0.42

0.44

0.32

0.33

0.33

0.18

0.20

0.22

0.20

0.22

0.23

0.61

0.67

0.69

0.49

0.52

0.52

0.27

0.31

0.34

0.31

0.34

0.36

10

0.86

0.94

0.98

0.68

0.72

0.72

0.33

0.41

0.46

0.40

0.46

0.50

15

1.04

1.14

1.19

0.81

0.87

0.87

0.35

0.46

0.55

0.45

0.54

0.59

20

1.18

1.30

1.37

0.91

0.99

1.00

0.35

0.49

0.61

0.47

0.59

0.66

25

1.30

1.44

1.52

0.99

1.09

1.10

0.35

0.50

0.65

0.47

0.62

0.72

0.81

0.88

0.91

0.66

0.69

0.68

0.37

0.42

0.46

0.42

0.46

0.48

1.27

1.38

1.44

1.02

1.08

1.07

0.55

0.64

0.71

0.64

0.71

0.75

10

1.78

1.94

2.02

1.41

1.50

1.50

0.69

0.85

0.96

0.83

0.96

1.03

15

2.15

2.36

2.47

1.68

1.81

1.81

0.73

0.96

1.13

0.93

1.11

1.22

20

2.45

2.70

2.83

1.89

2.05

2.07

0.73

1.02

1.26

0.97

1.22

1.37

25

2.70

2.99

3.15

2.05

2.25

2.29

0.73

1.04

1.35

0.98

1.28

1.49

1.16

1.26

1.30

0.94

0.99

0.97

0.54

0.60

0.65

0.60

0.66

0.69

1.82

1.98

2.05

1.46

1.54

1.53

0.79

0.92

1.01

0.91

1.01

1.07

10

2.54

2.77

2.89

2.02

2.15

2.14

0.99

1.21

1.38

1.19

1.37

1.47

15

3.07

3.37

3.52

2.40

2.58

2.59

1.05

1.37

1.62

1.33

1.59

1.75

20

3.50

3.86

4.05

2.70

2.93

2.96

1.05

1.46

1.80

1.39

1.74

1.96

25

3.86

4.28

4.50

2.93

3.22

3.27

1.05

1.49

1.92

1.40

1.84

2.13

Correction factors
The table values refer to hot gas capacity
and are given as a function of condensing
temperature tc and pressure drop p across
the valve. Capacities are based on a hot gas
temperature superheated 40 F above
condensing temperature (th= tc+ 40 F).
For each additional 10 F of superheat above
40 F, the table capacities must be reduced by 1%.

When the valve is used in a hot gas defrost


circuit. evaporator temperature affects the
capacity. When the evaporator temperature
differs from 40 F, adjust the table capacities
by multiplying them by the appropriate
correction factor found in the following table.

Correction factors for th and te


te [F]
Factor

-40
1.18

-20
1.14

22 DKRCC.PD.BB0.A8.22

0
1.09

20
1.04

40
1

50
0.97

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Hot gas
(continued)
Type

EVR 8

EVR 10

EVR 15

EVR 18

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

Hot gas capacity Qh [TR]


Pressure
Evaporating temp. te= 40 F, hot gas temp. th= tc+40 F, subcooling tu= 10 F
drop
R32
R290
R600
R600a
across
valve
Condensing temp. tc Condensing temp. tc Condensing temp. tc Condensing temp. tc
p
[F]
[F]
[F]
[F]
[psi]
70
100
140
70
100
140
70
100
140
70
100
140
2

1.62

1.76

1.82

1.32

1.38

1.36

0.75

0.85

0.92

0.85

0.92

0.96

2.55

2.77

2.88

2.05

2.16

2.14

1.11

1.28

1.42

1.28

1.42

1.49

10

3.56

3.88

4.05

2.82

3.00

2.99

1.38

1.69

1.93

1.66

1.91

2.05

15

4.30

4.72

4.93

3.36

3.61

3.62

1.46

1.92

2.27

1.86

2.23

2.45

20

4.90

5.40

5.67

3.78

4.10

4.14

1.46

2.04

2.51

1.95

2.43

2.74

25

5.41

5.99

6.30

4.10

4.50

4.58

1.46

2.08

2.69

1.96

2.57

2.98

2.76

2.99

3.09

2.23

2.34

2.31

1.27

1.44

1.55

1.43

1.57

1.63

4.32

4.70

4.88

3.48

3.67

3.62

1.88

2.18

2.40

2.17

2.41

2.53

10

6.04

6.59

6.86

4.79

5.10

5.07

2.34

2.87

3.27

2.82

3.25

3.48

15

7.30

8.00

8.37

5.71

6.13

6.15

2.48

3.26

3.85

3.16

3.78

4.15

20

8.31

9.16

9.61

6.41

6.96

7.02

2.48

3.46

4.27

3.31

4.13

4.65

25

9.17

10.15

10.69

6.96

7.64

7.77

2.48

3.54

4.57

3.33

4.36

5.05

3.77

4.08

4.23

3.06

3.21

3.16

1.74

1.96

2.12

1.96

2.15

2.23

5.92

6.43

6.67

4.76

5.02

4.96

2.57

2.98

3.29

2.96

3.30

3.47

10

8.26

9.01

9.39

6.55

6.97

6.94

3.20

3.93

4.47

3.86

4.44

4.77

15

9.98

10.95

11.45

7.81

8.39

8.41

3.40

4.46

5.27

4.32

5.17

5.68

20

11.38

12.53

13.15

8.77

9.52

9.61

3.40

4.74

5.84

4.53

5.65

6.37

25

12.55

13.90

14.63

9.53

10.45

10.63

3.40

4.84

6.25

4.55

5.96

6.91

4.93

5.34

5.54

4.00

4.19

4.13

2.28

2.57

2.78

2.57

2.81

2.91

7.74

8.40

8.73

6.22

6.56

6.49

3.36

3.90

4.30

3.87

4.31

4.53

10

10.80

11.79

12.28

8.57

9.12

9.08

4.19

5.14

5.85

5.05

5.81

6.23

15

13.06

14.32

14.97

10.21

10.97

11.00

4.44

5.83

6.89

5.65

6.76

7.42

20

14.88 16.39

17.20

11.47

12.45

12.57

4.45

6.20

7.63

5.92

7.39

8.33

25

16.41

19.14

12.46

13.66

13.90

4.45

6.33

8.18

5.96

7.80

9.04

18.17

Correction factors
The table values refer to hot gas capacity
and are given as a function of condensing
temperature tc and pressure drop p across
the valve. Capacities are based on a hot gas
temperature superheated 40 F above
condensing temperature (th=tc+ 40 F).
For each additional 10 F of superheat above
40 F, the table capacities must be reduced by 1%.

When the valve is used in a hot gas defrost


circuit. evaporator temperature affects the
capacity. When the evaporator temperature
differs from 40 F, adjust the table capacities
by multiplying them by the appropriate
correction factor found in the following table.

Correction factors for th and te


te [F]
Factor

-40
1.18

-20
1.14

DKRCC.PD.BB0.A8.22

0
1.09

20
1.04

40
1

50
0.97

23

Data sheet

Solenoid valve, types EVR 2 EVR 40

Capacity
Hot gas
(continued)
Type

Hot gas capacity Qh [TR]


Pressure
Evaporating temp. te= 40 F, hot gas temp. th=tc+ 40 F, subcooling tu= 10 F
drop
across
R32
R290
R600
R600a
valve
Condensing temp. tc Condensing temp. tc Condensing temp. tc Condensing temp. tc
p
[F]
[F]
[F]
[F]
[psi]
70
100
140
70
100
140
70
100
140
70
100
140
2

Metric conversions
1 psi = 0.07 bar
5
/9 (t1 F - 32) = t2 C
1 TR = 3.5 kW

EVR 20

7.25

7.86

8.14

5.88

11.38

12.36

12.84

9.15

10

15.88

17.33

18.06

12.60

6.16

6.07

3.35

3.78

4.08

3.77

4.13

4.28

9.65

9.54

4.94

13.41

13.35

6.16

5.74

6.32

5.70

6.34

6.66

7.56

8.60

7.42

8.54

9.17

15

19.20

21.05

22.01

15.02

16.14

16.18

6.53

8.57

10.13

8.32

9.94

10.92

20

21.88

24.11

25.29

16.87

18.30

18.48

6.54

9.11

11.23

8.70

10.87

12.25

25

24.13

26.72

28.14

18.32

20.09

20.44

6.54

9.31

12.03

8.76

11.47

13.29

Correction factors
The table values refer to hot gas capacity
and are given as a function of condensing
temperature tc and pressure drop p across
the valve. Capacities are based on a hot gas
temperature superheated 40 F above
condensing temperature (th= tc+40 F).
For each additional 10 F of superheat above
40 F, the table capacities must be reduced by 1%.

When the valve is used in a hot gas defrost


circuit. evaporator temperature affects the
capacity. When the evaporator temperature
differs from 40 F, adjust the table capacities
by multiplying them by the appropriate
correction factor found in the following table.

Correction factors for th and te


te [F]
Factor

-40
1.18

-20
1.14

24 DKRCC.PD.BB0.A8.22

0
1.09

20
1.04

40
1

50
0.97

Data sheet

Solenoid valve, types EVR 2 EVR 40

GENERAL
PURPOSE
VALVE 317R.

MADE IN CHINA

Part no: 032F1171

GENERAL PURPOSE VALVE 317R.

SWP: 460psig
MOPD: 350psi
Section of general-purpose valve
assembly. Assembly consisting of
coil: 018F4100,-02,-03,-04,-10,
-12,-13,-14,-15,-20,-22,-23,-30,-31
,-32,-33,-34,-35. UL LISTED, 317R
and body type: EVR 15

MADE IN CHINA

SWP: 460psig
MOPD: 350psi
Section of general-purpose valve
assembly. Assembly consisting of
coil: 018F4100,-02,-03,-04,-10,
-12,-13,-14,-15,-20,-22,-23,-30,-31
,-32,-33,-34,-34. UL LISTED, 317R
and body type: EVR 15

Identification

Example
EVR 8
Valve type and size
SWP Safe Working Pressure
(MWP) in psig
018F4100
Coil group for the EVR
MOPD Maximum Operating Pressure
in psi
S and A
Approvals in USA and Canada

Essential valve data is given on the label.

Valve selection example

Note:
When selecting the appropriate
solenoid valve, it is easier to convert the actual
required capacity to that of the rated capacities
listed in the tables.
Liquid line solenoid valve selection example
Refrigerant R134a
Condensing temperature tc= 100 F
Liquid temperature ahead of valve tl= 90 F
Maximum allowable pressure drop across
valvep = 2 psi
Evaporator capacity Qo= 10 TR (required
valvecapacity)
The table capacity should be corrected by the
corresponding factor as:

Qtable x fliquid = Qo
Step 1:
Determine the correction factor for liquid
temperature. From the correction factor table
found on page 8, a liquid temperature of 90 F
corresponds to a factor of 1.05.
Step 2:
Correct the required valve capacity.
This is done by dividing the evaporator
capacity by the liquid correction factor.
Qcorrected= 10/1.05 = 9.5 TR
Step 3:
Select the appropriate capacity table
and choose the first valve whose capacity
is greater than or equal to Qcorrected at the required
pressure drop. Using the R134a liquid capacity
table found on page 8, the EVR 15 is selected
as it has a capacity of 12.5 TR at a p = 2 psi.

This is done by utilizing various correction


factors in the selection process. The following
examples illustrate how this is done.
Suction line solenoid valve selection example
Refrigerant R134a
Liquid temperature ahead of expansion
valvetl= 90 F
Evaporator temperature te= 30 F
Superheat ahead of valve ts= 17 F
Maximum allowable pressure drop across
valvep = 3 psi
Evaporator capacity Qo= 10 TR
(required valve capacity)
The table capacity should be corrected by the
corresponding factor as:

Qtable x fliquid x fsuperheat = Qo


Step 1:
Determine the correction factor for superheat
ahead of the valve by increasing the required
valve capacity by 2% for each 10 F of actual
superheat above the table rated value of 7 F.
In the example. a superheat of 17 F corresponds
to a 10 F increase above the table value
which is equivalent to a superheat
correction factor of 0.98.
Step 2:
Determine the correction factor for liquid
temperature. From the correction factor table
found on page 13, a liquid temperature of 90 F
corresponds to a factor of 1.05.
Step 3:
Correct the required valve capacity. This is done
by first multiplying the evaporator capacity by
the superheat correction factor and then
dividing it by the liquid correction factor.
Qcorrected= 10/0.98/1.05=9.7
Step 4:
Select the appropriate capacity table
and choose the first valve whose capacity
is greater than or equal to Qcorrected
at the required evaporating temperature
and pressure drop. Using the R134a
suction vapor capacity table found
on page 13, the EVR 40 is selected
as it has a capacity of 14.75 TR
at te= 30 F and p = 3 psi.

DKRCC.PD.BB0.A8.22

25

Data sheet

Solenoid valve, types EVR 2 EVR 40

Valve selection example


(continued)

Hot gas line solenoid valve selection example


With hot gas defrost, pressure in the evaporator
quickly rises to a value near that of the
condensing pressure and remains there
until the defrost cycle has been completed.
Therefore. when selecting valves for hot gas
applications, sizing is based primarily on the
condensing temperature tc and the pressure
drop Dp across the valve.
Example (with heat recovery)
Refrigerant: R134a
Evaporator temperature: te = 0 F
Condensing temperature: tc= 100 F
Hot gas temperature ahead of valve: th= 180 F
Maximum allowable pressure drop across
valve:p = 5 psi
Output of heat recovery condenser: Qh= 15 TR
(required valve capacity)

The table capacity should be corrected by the


correspondig factor as:

Qtable x fevaporator x fsuperheat = Qo


Step 1:
Determine the correction factor for hot gas
temperature (th= tc+ 40 F) by increasing the
required valve capacity by 1% for each 10 F
ofactual superheat above the table rated
superheat value of 40 F.
In the example, an actual hot gas temperature
of180 F is 40 F higher than the calculated table
value of (th= tc+ 40 F = 140 F). This is equivalent
to a hot gas correction factor of 0.96.
Step 2:
Determine the correction factor for evaporator
temperature. From the correction factor table
found on page 19 an evaporator temperature
of0 F corresponds to a factor of 1.09.
Step 3:
Correct the required valve capacity. This is done
by first multiplying the heat recovery capacity by
the hot gas correction factor and then dividing it
by the evaporator correction factor.
Qcorrected= 15 /0.96/1.09=14.3
Step 4:
Select the appropriate capacity table and choose
the first valve whose capacity is greater than
orequal to Qcorrected at the required condensing
temperature and pressure drop. Using the R134a
hot gas capacity table found on pages 19 and 20,
the EVR 32 is selected as it has a capacity of
21.8 TR at tc= 100 F andp = 5 psi.

26 DKRCC.PD.BB0.A8.22

Data sheet

Solenoid valve, types EVR 2 EVR 40

Design / Function

EVR 2 and EVR 3, NC

EVR 4 EVR 22, NC

20

20

40

40

4
16

16
18
29

18
45

43
Danfoss
32F9024.10

83
90

73
83

80

90

49

Danfoss
32F9025.10

45

49

EVR 6 EVR 15, NO


20

54
4
16
18
29
45
43
73
83

80

90

49

Danfoss
32F9026.10

4. Coil
16. Armature
18. Valve plate
20. Earth terminal
29. Pilot orifice
40. Junction box
43. Valve cover
45. Gasket
49. Valve body
54. Spacer ring
73. Equalizing hole
80. Diaphragm
83. Valve seat
90. Fixing hole

40

Note:
The drawings are only representative.

EVR solenoid valves are based on two different


design principles:
1. Direct operation
2. Servo operation
1: Direct operation
EVR 2 and EVR 3 are direct operated. The valves
opens to admit full flow when the armature (16)
is moved up into the magnetic field of the coil.
The valves operates with a minimum differential
pressure of 0 psi.
The valve plate (18) is fitted directly to
thearmature (16).
Inlet pressure and spring forceact to close the
valve when the coil is de-energized.
2a:
EVR 4 EVR 22 are servo-operated with a
floating diaphragm (80). The pilot orifice (29)
islocated in the center of the diaphragm.
The pilot valve plate (18) is fitted directly to the
armature (16).
When the coil is de-energized, the valve port and
pilot orifice are closed and the inlet pressure acts
both above and below the diaphragm.

DKRCC.PD.BB0.A8.22

The valve port and pilot orifice are kept closed by


the armature spring force and the differential
pressure between inlet and outlet sides.
When current is applied to the coil, the armature
is pulled up into the magnetic field and the pilot
orifice opens. This relieves pressure above the
diaphragm because the space above it becomes
connected to the outlet side of the valve.
Thedifferential pressure between inlet and
outlet presses the diaphragm away from the
valve seat (83) and the valve opens to admit full
flow. Aminimum differential pressure (0.7 psi for
EVR 4 EVR 22) is necessary to open the valve
and keep it open.
When the coil is de-energized, the pilot orifice
closes. Then. via the equalizing port (73)
thepressure above the diaphragm rises to the
same value as the inlet pressure, which results in
the valve port being closed by the diaphragm.
EVR 6 EVR 15, NO, function in a manner
opposite to the NC valves; they are open when
the coil is de-energized.
Normally open (NO) EVR valves are available with
servo operation only.

27

Solenoid valve, types EVR 2 EVR 40

Design / Function
(continued)

EVR 25
54

20

4
16

EVR 32 and EVR 40

28 29 18 4

16 54 20

40

Danfoss
32F9028.10

4. Coil
16. Armature
18. Pilot valve plate
20. Earth screw
28. Gasket
29. Pilot orifice
30. O-ring
31. Piston ring
40. Junction box
43. Valve cover
44. O-ring
45. Valve cover gasket
49. Valve body
51. Protective cap
/blanking plug
53. Manual stem
73. Equalizing hole
74. Main passage
75. Pilot passage
76. Return spring
80. Servo piston
83. Main valve seat
84. Main valve plate

40
Danfoss
32F9027.10

Data sheet

Note:
The drawings are only representative.

2b. Servo operation of EVR 25 EVR 40


EVR 25. EVR 32 and EVR 40 are servo-operated
piston valves.
The valves are closed when the coil
is de-energized. In operation. EVR 25 is the same
as for EVR 4 EVR 22. but the design is different.
The pilot unit is located in the cover and the
servo unit is a piston (80) with a cast iron
piston ring.

28 DKRCC.PD.BB0.A8.22

For EVR 25 EVR 40, piston (80) and valve plate


(84) will close against the valve seat (83) due to
the differential pressure between inlet
and outlet plus the force from the return
spring (76).
When the coil is energized, the pilot orifice (29)
is opened and pressure on the spring side
of the piston is relieved. The pressure differential
now opens the valve. The minimum differential
required to keep the valve fully open is 1 psi.

Data sheet

Solenoid valve, types EVR 2 EVR 40

Dimensions [in]
and weights [lbs]

EVR 2 - EVR 8 NC, EVR 6 - EVR 8 NO, Solder connection


With conduit boss
EVR 2 - EVR 8 NC, EVR 6 - EVR 8 NO
min 29/16

min 29/16

With junction box


EVR 2 - EVR 8 NC, EVR 6 - EVR 8 NO

L5

H3

H1

H3

H1

H2

H2

Danfoss
32F975.10

Danfoss
32F976.10

L5

L2

L2
L

B
B1

B
B1

Coil net weight: 1 lb


Note:
The drawings are only representative.

Connection

Type

Metric conversions:
1 in = 25.4 mm

L5

Normal
size

Oversize

/4

4 5/8

/4

L2

EVR 2
NC

EVR 3
NC

4 5/8

EVR 3
NC

/8

4 5/8

EVR 4
NC

4 3/8

EVR 4
NC

/2

EVR 6
NC/NO

/8

4 3/8

EVR 6
NC/NO

/8

4 3/8

EVR 6
NC

/2

EVR 6
NC

/8

6 1/2

EVR 8
NC

4 5/8

EVR 8
NC

/2

EVR 8
NC

/8

/8

/8

Junction Conduit
box
boss

H1

H2

H3

H4

B1

Net
weight
with
coil

/16

/20

1 5/16

2 1/16

1.3

/16

2 13/16

/20

1 5/16

2 1/16

1.3

/16

2 13/16

/20

1 5/16

2 1/16

1.3

/16

3 1/16

/8

1 7/16

2 1/16

1.4

/16

3 1/16

/8

1 7/16

2 1/16

1.4

/8

/8

/8

/8

/8

/8

/16

3 1/16

/8

1 7/16

2 1/16

1.4

/8

3 1/16

2 3/16

1 7/16

2 1/16

1.4

/8

/16

3 1/16

/8

1 7/16

2 1/16

1.4

/2

/16

3 1/16

/8

1 7/16

2 1/16

1.4

/8

/16

3 1/16

/8

1 7/16

2 1/16

1.4

/8

/16

3 1/16

/8

1 7/16

2 1/16

1.4

/2

/16

3 1/16

/8

1 7/16

2 1/16

1.4

DKRCC.PD.BB0.A8.22

29

Data sheet

Solenoid valve, types EVR 2 EVR 40

Dimensions [in]
and weights [lbs]

EVR 10 NC/NO, Solder connection


With junction box
EVR 10 NC/NO

With conduit boss


EVR 10 NC/NO

Coil net weight: 1 lb


Note:
The drawings are only representative.

Connection
Type

Metric conversions:
1 in = 25.4 mm

L5

Normal
size

Oversize

/8

L2

EVR 10
NC

4 5/8

EVR 10
NC/NO

/2

EVR 10
NC/NO

/2

EVR 10
NC/NO

/8

6 5/16

Junction Conduit
box
boss

H1

H2

/8

3 1/8

B1

1
/16

2 1/16

1.8

1
/16

2 1/16

1.8

2 3/16 1 7/16 2 1/16

1.8

1
/16

1.8

H3

H4

/16

13

/16

13

/8

/8

/8

3 1/8

/8

3 1/8

/2

/8

3 1/8

30 DKRCC.PD.BB0.A8.22

Net
weight
with coil

/16

13

2 1/16

Data sheet

Solenoid valve, types EVR 2 EVR 40

Dimensions [in]
and weights [lbs]

EVR 15 - EVR 22 NC, EVR 15 NO, Solder connection


With junction box
EVR 15 - EVR 22, NC/NO

With conduit boss


EVR 15 - EVR 22, NC/NO

B1

L5

B1

L2

L2

Coil net weight: 1 lb

Danfoss
32F839.10

Danfoss
32F838.10

H1

H1

H2

H2

L5

Note:
The drawings are only representative.

Connection

Type

Metric conversions:
1 in = 25.4 mm

L5

Normal Oversize
size

EVR 15
NC/NO

EVR 15
NC/NO

L2

/8

6 7/8

/8

6 7/8

EVR 15
NC

/8

7 1/8

EVR 18
NC

/8

7 1/8

EVR 18
NC

1 1/8

8 1/2

EVR 20
NC

/8

7 1/2

EVR 20
NC

/8

7 1/2

EVR 20
NC

1 1/8

8 1/2

EVR 22
NC

1 1/8

10 1/16

EVR 22
NC

1 3/8

11 1/16

Junction Conduit
box
boss

H1

H2

H3

H4

B1

Net
weight
with
coil

/2

/4

3 3/8

/4

2 3/16

2 1/16

2.4

/2

3 3/8

2 1/8

2 3/16

2 1/16

2.4

/8

/4

3 3/8

/4

2 3/16

2 1/16

2.4

/8

/4

3 3/8

/4

2 3/16

2 1/16

2.4

/8

/4

3 3/8

/4

2 3/16

2 1/16

2.4

/8

25

/32

3 9/16

2 13/16 2 1/16

3.4

/8

3 9/16

2 3/8

2 13/16 2 1/16

3.4

/8

25

/32

3 9/16

2 13/16 2 1/16

3.4

/8

25

/32

3 9/16

2 13/16 2 1/16

3.4

25

/32

3 9/16

2 13/16 2 1/16

3.4

DKRCC.PD.BB0.A8.22

31

Data sheet

Solenoid valve, types EVR 2 EVR 40

Dimensions [in]
and weights [lbs]

EVR 25 - EVR 40, Solder connection


With conduit boss
EVR 25

With junction box


EVR 25

EVR 32 and EVR 40

EVR 32 and EVR 40

Coil net weight: 1 lb


Note:
The drawings are only representative.

Connection
Normal
size

Oversize

EVR 25

1 1/8

10 1/16

EVR 25

1 3/8

Type

EVR 32

Metric conversions:
1 in = 25.4 mm

L5

1 3/8

L2

Junction Conduit
box
boss

H1

H2

H4

Net weight
with coil

/8

5 7/16

2 13/16

6.9

11 1/16

5 7/16

2 13/16

7.7

11 1/16

1 /8

4 /8

2 /8

3 /16

9.5

EVR 32

1 5/8

11 1/16

1 /8

1 /8

4 /8

2 /8

3 /16

9.7

EVR 40

1 5/8

11 1/16

1 1/8

1 7/8

4 3/8

2 1/8

3 3/16

10.0

EVR 40

2 1/8

11 1/16

1 1/8

1 7/8

4 3/8

2 1/8

3 3/16

10.0

32 DKRCC.PD.BB0.A8.22

Data sheet

Solenoid valve, types EVR 2 EVR 40

Dimensions [in]
and weights [lbs]

EVR 2 - 6 NC, Flare connection


With conduit boss
EVR 2 6 NC
min 29/16

min 29/16

With junction box


EVR 2 6 NC

L5

H1

B
B1

H3

H3

H1

H2

H2

Danfoss
32F974.10

Danfoss
32F973.10

L5

Coil net weight: 1 lb

B1

Note:
The drawings are only representative.

Connection
Type

Metric conversions
1 in = 25.4 mm

Normal
size

Oversize

/4
/4

Junction Conduit
box
boss

H4

B1

/16

1 /16

2 1/16

1.3

/16

1 /16

2 /16

1.3

/16

1 5/16

2 1/16

1.3

/8

1 7/16

2 1/16

1.4

/8

1 /16

2 /16

1.4

/8

1 /16

2 /16

1.4

2 7/8

2 3/16

1 7/16

2 1/16

1.4

2 7/8

/8

1 7/16

2 1/16

1.4

H1

H2

EVR 2 NC

EVR 3 NC

2 /16

EVR 3 NC

/8

2 7/16

EVR 4 NC

2 3/4

EVR 4 NC

/2

EVR 6 NC

/8

2 /4

EVR 6 NC

/8

2 3/4

EVR 6 NC

/2

/8

H3

Net
weight
with
coil

L5

2 /16

DKRCC.PD.BB0.A8.22

/16

13

2 /16

/16

13

2 /16

/16

2 13/16

/16

2 7/8

/16

2 /8

/16

2 /8

/16
/16

33

Code no.

Spare parts

Spare parts, contents

Danfoss | DCS (rja) | 2016.01

Type

Seal kit

Service kit

Piston service kit

Pilot service kit

EVR 2

032F8196

032F0230

EVR 3

032F8196

032F0230

EVR 4

032F8165

EVR 6

032F8165

032F8166

EVR 8

032F8165

032F8166

EVR 10

032F8196

032F0185

EVR 15

032F8196

032F0187

EVR 18

032F8196

032F0187

EVR 20

032F0189

EVR 22

032F0189

EVR 25

032F3236

042H0165

EVR 32

042H0172

042H0165

EVR 40

042H0173

EVR 6 NO

032F8165

EVR 10 NO

032F8196

EVR 15 NO

032F8196

Seal kit

Service kit

Piston service kit

Pilot service kit

O-ring
Gasket

Diaphragm assembly
Armature assembly
Rubber gasket
Screws
Torx key
Snap fastener
Nut

Piston assembly
Plastic block
Spring
Piston ring
Rubber gasket
Snap fastener
Nut

Armature tube
assembly
Snap fastener
Armature
Orifice
Gaskets
Nut

DKRCC.PD.BB0.A8.22 | 34