Philosophy of Cable Sizing Methodology

1 General guideline for selection of Power Cables

The min size of the cable shall be 3 C x 185 sq.mm. of type A2XFY for XLPE insulated cables
as per IS : 7098 Part-II, Non-FRLS

Supply System : 6600 V , +6%, -9% / 50 Hz, +3%, -6%, 3-ph

Cable size for HT motors shall be selected on the basis of rated nameplate current, starting &
running voltage drop as per specification and short circuit capacity of the system. The cable size
shall be calculated based on the breaker opening time of 0.25 seconds

Short circuit capacity of 6.6 kV is 40kA .


AC motors of ratings in excess of 200KW upto 2000 KW shall be connected to 6.6 KV HT
power supply system.

2 Formulae used for calculation


2.1 Voltage Drop Calculation

%VDROP =

3 x IRATED x (RCAB|900C Cos r + XCAB Sin r) x Lr


= ------------------------------------------------------------------------V x n x 10

where,
IRATED

= Rated Motor Current

Amps

RCAB|900C

= Resistance of Cable at 90 C

Ohms/KM

XCAB

= Reactance of Cable

Ohms/KM

Lr

= Length of Cable (run)

mts

= Operating System Voltage

Volts

= No of parallel path/run

Cos r

= Power Factor during running

2.2 Voltage Dip Calculation

%VDIP =

3 x IStart x (RCAB|900C Cos s + XCAB Sin s) x Ls


= -----------------------------------------------------------------------V x n x 10

where,
IStart

= Motor Starting Current

Amps

RCAB|900C

= Resistance of Cable at 900C

Ohms/KM

XCAB

= Reactance of Cable

Ohms/KM

Ls

= Length of Cable (Start)

mts

= Operating System Voltage

Volts

= No of parallel path/run

Cos s

= Power Factor during start

Page 1 of 8

Prep By : Abhijit Mandal


I-MT OP PEP-EA2

2.3 Minimum Crossection of Cable

As per IEC - 60724 recomendation


I2t =

K2S2

where
K=

Qc( + 20)
------------20

x Loge 1 +

f - i
--------i +

where,
I

= Short Circuit Current

Amps

= Cross Section of Cable

sqmm

= Duration of Short Circuit

sec

= Final temp after Short Circuit

= Initial temp before Short Circuit

= Reciprocal of temp co-efficient of resistance of current carrying component

= Constant

Qc

= Volumetric heat capacity of conductor material at 20OC

J/OCmm3

20

= Electrical resistivity of conductor material at 20OC

mm

3 Sample calculations for selection of Aluminium XLPE cable


System Parameters / Conductor Parameters

3.1

Remarks

Supply Voltage

6.6

kV

(From CTS / GS03)

Fault Level

40

kA

(From CTS / GS03)

Fault Clearing Time

0.25

sec

(From CTS / GS03)

Conductor Material , Insulation

Al , XLPE

Initial Temp of Cable Conductor

90

(From Manufacturer)

250

(From Manufacturer)

228

(From Manufacturer)

0.000028264

Final Temp of Cable Conductor

Recipro. of temp co-eff. of resistance


O

Resistivity of conductor Mat. at 20 C


O

(From CTS / GS03)


O

(From Manufacturer)

mm
O

0.0025 J/ Cmm (From Manufacturer)

Vol. heat cap. of cond. Mat. at 20 C

94.6

Required Min.Cross Section of Cable

211

(Calculated)
sqmm

(Calculated)

Selected Cable 240 sqmm Al, XLPE

Page 2 of 8

Prep By : Abhijit Mandal


I-MT OP PEP-EA2

Primary Dedusting ID Fan Motor (HTSS to VFD Transformer)


Calculations & Selected Cable Parameters (from Table - 1)
Remarks

Running Conditions

(From Layout)

Cable Route Length

750

mts

Cable Size Selected

240

sqmm

(Selected)

Amps

@ 6.6

Motor FL Current ( at 6.6 kV )

260

Power Factor (Run)

0.91

Cable Rating (at 40 0 C per run)

395

(Calculated)

Cable Ampacity (with DF = 0.65)

257

(Calculated)

No of Runs required

No

(Calculated)

0.48

(Calculated)

Calculated Voltage Drop (Run)

kV

(Typical Data)

Starting Conditions
(From Layout)

Cable Route Length

750

mts

Cable Size Selected

240

sqmm

(Selected)

Locked Rotor Current/Nominal Current

1.5

times

( VFD Driven)

Motor Starting Current ( at 6.6 kV )

390

(Calculated)

No of Runs required

No

(Calculated)

0.60

(Calculated)

Calculated Voltage Drop (Start)

Table - 1 : Cable Data from Manufacturer


3C x 6.6/11 kV (UE) Al XLPE
Conductor
Size
(sqmm)

Rcab at 90
degC
Ohms/km

35

1.1100

0.144

3.3

125

0.65

81

50

0.8200

0.137

4.7

150

0.65

98

70

0.5670

0.129

6.6

190

0.65

124

95

0.4100

0.123

230

0.65

150

120

0.3240

0.117

11.3

260

0.65

169

150

0.2640

0.114

14.2

295

0.65

192

185

0.2110

0.105

17.39

335

0.65

218

240

0.1600

0.106

22.6

395

0.65

257

300

0.1300

0.103

28.3

450

0.65

293

400

0.1000

0.099

37.7

520

0.65

338

Xcab at 90 degC STC (kA) Icab at 40 degC Derating


IcabD (A)
for 1 Sec
Factor
ohms/km
in air (A)

Page 3 of 8

Prep By : Abhijit Mandal


I-MT OP PEP-EA2

Primary Dedusting ID Fan Motor (VFD Transformer to Motor via VFD)


Calculations & Selected Cable Parameters (from Table - 1)
Remarks

Running Conditions
Cable Route Length

Cable Size Selected

200

mts

240

sqmm
Amps

(From Layout)
(Selected)

Motor FL Current ( at 4.16 kV )

415

Power Factor (Run)

0.91

Cable Rating (at 40 0 C per run)

395

(Calculated)

Cable Ampacity (with DF = 0.65)

257

(Calculated)

No of Runs required

No

(Calculated)

0.33

(Calculated)

Calculated Voltage Drop (Run)

@ 4.16 kV
(Typical Data)

Starting Conditions
(From Layout)

Cable Route Length

200

mts

Cable Size Selected

240

sqmm

(Selected)

Locked Rotor Current/Nominal Current

1.5

times

( VFD Driven)

Motor Starting Current ( at 4.16 kV )

623

(Calculated)

No of Runs required

No

(Calculated)

0.40

(Calculated)

Calculated Voltage Drop (Start)

Table - 1 : Cable Data from Manufacturer


3C x 6.6/11 kV (UE) Al XLPE
Conductor
Size
(sqmm)

Rcab at 90
degC
Ohms/km

35

1.1100

0.144

3.3

125

0.65

81

50

0.8200

0.137

4.7

150

0.65

98

70

0.5670

0.129

6.6

190

0.65

124

95

0.4100

0.123

230

0.65

150

120

0.3240

0.117

11.3

260

0.65

169

150

0.2640

0.114

14.2

295

0.65

192

185

0.2110

0.105

17.39

335

0.65

218

240

0.1600

0.106

22.6

395

0.65

257

300

0.1300

0.103

28.3

450

0.65

293

400

0.1000

0.099

37.7

520

0.65

338

Xcab at 90 degC STC (kA) Icab at 40 degC Derating


IcabD (A)
for 1 Sec
Factor
ohms/km
in air (A)

Page 4 of 8

Prep By : Abhijit Mandal


I-MT OP PEP-EA2

Secondary Dedusting ID Fan Motor (HTSS to VFD Transformer)


Calculations & Selected Cable Parameters (from Table - 1)
Remarks

Running Conditions
Cable Route Length

750

mts

Cable Size Selected

240

sqmm
Amps

(From Layout)
(Selected)

Motor FL Current ( at 6.6 kV )

160

Power Factor (Run)

0.91

Cable Rating (at 40 0 C per run)

395

(Calculated)

Cable Ampacity (with DF = 0.65)

257

(Calculated)

No of Runs required

No

(Calculated)

0.60

(Calculated)

Calculated Voltage Drop (Run)

@ 6.6 kV
(Typical Data)

Starting Conditions
(From Layout)

Cable Route Length

750

mts

Cable Size Selected

240

sqmm

(Selected)

Locked Rotor Current/Nominal Current

1.5

times

( VFD Driven)

Motor Starting Current ( at 6.6 kV )

240

(Calculated)

No of Runs required

No

(Calculated)

0.73

(Calculated)

Calculated Voltage Drop (Start)

Table - 1 : Cable Data from Manufacturer


3C x 6.6/11 kV (UE) Al XLPE
Conductor
Size
(sqmm)

Rcab at 90
degC
Ohms/km

35

1.1100

0.144

3.3

125

0.65

81

50

0.8200

0.137

4.7

150

0.65

98

70

0.5670

0.129

6.6

190

0.65

124

95

0.4100

0.123

230

0.65

150

120

0.3240

0.117

11.3

260

0.65

169

150

0.2640

0.114

14.2

295

0.65

192

185

0.2110

0.105

17.39

335

0.65

218

240

0.1600

0.106

22.6

395

0.65

257

300

0.1300

0.103

28.3

450

0.65

293

400

0.1000

0.099

37.7

520

0.65

338

Xcab at 90 degC STC (kA) Icab at 40 degC Derating


IcabD (A)
for 1 Sec
Factor
ohms/km
in air (A)

Page 5 of 8

Prep By : Abhijit Mandal


I-MT OP PEP-EA2

Secondary Dedusting ID Fan Motor (VFD Transformer to Motor)


Calculations & Selected Cable Parameters (from Table - 1)
Remarks

Running Conditions
Cable Route Length

Cable Size Selected

90

mts

240

sqmm
Amps

(From Layout)
(Selected)

Motor FL Current ( at 4.16 kV )

260

Power Factor (Run)

0.91

Cable Rating (at 40 0 C per run)

395

(Calculated)

Cable Ampacity (with DF = 0.65)

257

(Calculated)

No of Runs required

No

(Calculated)

0.09

(Calculated)

Calculated Voltage Drop (Run)

@ 4.16 kV
(Typical Data)

Starting Conditions
(From Layout)

Cable Route Length

90

mts

Cable Size Selected

240

sqmm

(Selected)

Locked Rotor Current/Nominal Current

1.5

times

( VFD Driven)

Motor Starting Current ( at 4.16 kV )

390

(Calculated)

No of Runs required

No

(Calculated)

0.11

(Calculated)

Calculated Voltage Drop (Start)

Table - 1 : Cable Data from Manufacturer


3C x 6.6/11 kV (UE) Al XLPE
Conductor
Size
(sqmm)

Rcab at 90
degC
Ohms/km

35

1.1100

0.144

3.3

125

0.65

81

50

0.8200

0.137

4.7

150

0.65

98

70

0.5670

0.129

6.6

190

0.65

124

95

0.4100

0.123

230

0.65

150

120

0.3240

0.117

11.3

260

0.65

169

150

0.2640

0.114

14.2

295

0.65

192

185

0.2110

0.105

17.39

335

0.65

218

240

0.1600

0.106

22.6

395

0.65

257

300

0.1300

0.103

28.3

450

0.65

293

400

0.1000

0.099

37.7

520

0.65

338

Xcab at 90 degC STC (kA) Icab at 40 degC Derating


IcabD (A)
for 1 Sec
Factor
ohms/km
in air (A)

Page 6 of 8

Prep By : Abhijit Mandal


I-MT OP PEP-EA2

Gas Holder (GRP) Booster Fan 300 kW


Calculations & Selected Cable Parameters (from Table - 1)
Remarks

Running Conditions
Cable Route Length

Cable Size Selected

Motor FL Current ( at 6.6 kV )


Power Factor (Run)

1000

mts

(From Layout)
(Selected)

240

sqmm

29

Amps

0.91

Cable Rating (at 40 0 C per run)

395

(Calculated)

Cable Ampacity (with DF = 0.65)

257

(Calculated)

No of Runs required

No

(Calculated)

0.15

(Calculated)

Calculated Voltage Drop (Run)

@ 6.6 kV
(Typical Data)

Starting Conditions
(From Layout)

Cable Route Length

1000

mts

Cable Size Selected

240

sqmm

(Selected)

Locked Rotor Current/Nominal Current

times

( DOL)

Motor Starting Current ( at 6.6 kV )

175

No of Runs required

Calculated Voltage Drop (Start)

(Calculated)

No

(Calculated)

0.71

(Calculated)

Table - 1 : Cable Data from Manufacturer


3C x 6.6/11 kV (UE) Al XLPE
Conductor
Size
(sqmm)

Rcab at 90
degC
Ohms/km

35

1.1100

0.144

3.3

125

0.65

81

50

0.8200

0.137

4.7

150

0.65

98

70

0.5670

0.129

6.6

190

0.65

124

95

0.4100

0.123

230

0.65

150

120

0.3240

0.117

11.3

260

0.65

169

150

0.2640

0.114

14.2

295

0.65

192

185

0.2110

0.105

17.39

335

0.65

218

240

0.1600

0.106

22.6

395

0.65

257

300

0.1300

0.103

28.3

450

0.65

293

400

0.1000

0.099

37.7

520

0.65

338

Xcab at 90 degC STC (kA) Icab at 40 degC Derating


IcabD (A)
for 1 Sec
Factor
ohms/km
in air (A)

Page 7 of 8

Prep By : Abhijit Mandal


I-MT OP PEP-EA2

LCSS Dedusting 2000 kVA


Calculations & Selected Cable Parameters (from Table - 1)
Remarks

Running Conditions
Cable Route Length

Cable Size Selected

750

mts

240

sqmm
Amps

(From Layout)
(Selected)

Trafo FL Current ( at 6.6 kV )

175

Power Factor (Run)

0.80

Cable Rating (at 40 0 C per run)

395

(Calculated)

Cable Ampacity (with DF = 0.65)

257

(Calculated)

No of Runs required

No

(Calculated)

0.66

(Calculated)

Calculated Voltage Drop (Run)

@ 6.6 kV
(Typical Data)

Table - 1 : Cable Data from Manufacturer


3C x 6.6/11 kV (UE) Al XLPE
Conductor
Size
(sqmm)

Rcab at 90
degC
Ohms/km

35

1.1100

0.144

3.3

125

0.65

81

50

0.8200

0.137

4.7

150

0.65

98

70

0.5670

0.129

6.6

190

0.65

124

95

0.4100

0.123

230

0.65

150

120

0.3240

0.117

11.3

260

0.65

169

150

0.2640

0.114

14.2

295

0.65

192

185

0.2110

0.105

17.39

335

0.65

218

240

0.1600

0.106

22.6

395

0.65

257

300

0.1300

0.103

28.3

450

0.65

293

400

0.1000

0.099

37.7

520

0.65

338

Xcab at 90 degC STC (kA) Icab at 40 degC Derating


IcabD (A)
for 1 Sec
Factor
ohms/km
in air (A)

Page 8 of 8

Prep By : Abhijit Mandal


I-MT OP PEP-EA2

Das könnte Ihnen auch gefallen