The min size of the cable shall be 3 C x 185 sq.mm. of type A2XFY for XLPE insulated cables
as per IS : 7098 Part-II, Non-FRLS
Cable size for HT motors shall be selected on the basis of rated nameplate current, starting &
running voltage drop as per specification and short circuit capacity of the system. The cable size
shall be calculated based on the breaker opening time of 0.25 seconds
%VDROP =
where,
IRATED
Amps
RCAB|900C
= Resistance of Cable at 90 C
Ohms/KM
XCAB
= Reactance of Cable
Ohms/KM
Lr
mts
Volts
= No of parallel path/run
Cos r
%VDIP =
where,
IStart
Amps
RCAB|900C
Ohms/KM
XCAB
= Reactance of Cable
Ohms/KM
Ls
mts
Volts
= No of parallel path/run
Cos s
Page 1 of 8
K2S2
where
K=
Qc( + 20)
------------20
x Loge 1 +
f - i
--------i +
where,
I
Amps
sqmm
sec
= Constant
Qc
J/OCmm3
20
mm
3.1
Remarks
Supply Voltage
6.6
kV
Fault Level
40
kA
0.25
sec
Al , XLPE
90
(From Manufacturer)
250
(From Manufacturer)
228
(From Manufacturer)
0.000028264
(From Manufacturer)
mm
O
94.6
211
(Calculated)
sqmm
(Calculated)
Page 2 of 8
Running Conditions
(From Layout)
750
mts
240
sqmm
(Selected)
Amps
@ 6.6
260
0.91
395
(Calculated)
257
(Calculated)
No of Runs required
No
(Calculated)
0.48
(Calculated)
kV
(Typical Data)
Starting Conditions
(From Layout)
750
mts
240
sqmm
(Selected)
1.5
times
( VFD Driven)
390
(Calculated)
No of Runs required
No
(Calculated)
0.60
(Calculated)
Rcab at 90
degC
Ohms/km
35
1.1100
0.144
3.3
125
0.65
81
50
0.8200
0.137
4.7
150
0.65
98
70
0.5670
0.129
6.6
190
0.65
124
95
0.4100
0.123
230
0.65
150
120
0.3240
0.117
11.3
260
0.65
169
150
0.2640
0.114
14.2
295
0.65
192
185
0.2110
0.105
17.39
335
0.65
218
240
0.1600
0.106
22.6
395
0.65
257
300
0.1300
0.103
28.3
450
0.65
293
400
0.1000
0.099
37.7
520
0.65
338
Page 3 of 8
Running Conditions
Cable Route Length
200
mts
240
sqmm
Amps
(From Layout)
(Selected)
415
0.91
395
(Calculated)
257
(Calculated)
No of Runs required
No
(Calculated)
0.33
(Calculated)
@ 4.16 kV
(Typical Data)
Starting Conditions
(From Layout)
200
mts
240
sqmm
(Selected)
1.5
times
( VFD Driven)
623
(Calculated)
No of Runs required
No
(Calculated)
0.40
(Calculated)
Rcab at 90
degC
Ohms/km
35
1.1100
0.144
3.3
125
0.65
81
50
0.8200
0.137
4.7
150
0.65
98
70
0.5670
0.129
6.6
190
0.65
124
95
0.4100
0.123
230
0.65
150
120
0.3240
0.117
11.3
260
0.65
169
150
0.2640
0.114
14.2
295
0.65
192
185
0.2110
0.105
17.39
335
0.65
218
240
0.1600
0.106
22.6
395
0.65
257
300
0.1300
0.103
28.3
450
0.65
293
400
0.1000
0.099
37.7
520
0.65
338
Page 4 of 8
Running Conditions
Cable Route Length
750
mts
240
sqmm
Amps
(From Layout)
(Selected)
160
0.91
395
(Calculated)
257
(Calculated)
No of Runs required
No
(Calculated)
0.60
(Calculated)
@ 6.6 kV
(Typical Data)
Starting Conditions
(From Layout)
750
mts
240
sqmm
(Selected)
1.5
times
( VFD Driven)
240
(Calculated)
No of Runs required
No
(Calculated)
0.73
(Calculated)
Rcab at 90
degC
Ohms/km
35
1.1100
0.144
3.3
125
0.65
81
50
0.8200
0.137
4.7
150
0.65
98
70
0.5670
0.129
6.6
190
0.65
124
95
0.4100
0.123
230
0.65
150
120
0.3240
0.117
11.3
260
0.65
169
150
0.2640
0.114
14.2
295
0.65
192
185
0.2110
0.105
17.39
335
0.65
218
240
0.1600
0.106
22.6
395
0.65
257
300
0.1300
0.103
28.3
450
0.65
293
400
0.1000
0.099
37.7
520
0.65
338
Page 5 of 8
Running Conditions
Cable Route Length
90
mts
240
sqmm
Amps
(From Layout)
(Selected)
260
0.91
395
(Calculated)
257
(Calculated)
No of Runs required
No
(Calculated)
0.09
(Calculated)
@ 4.16 kV
(Typical Data)
Starting Conditions
(From Layout)
90
mts
240
sqmm
(Selected)
1.5
times
( VFD Driven)
390
(Calculated)
No of Runs required
No
(Calculated)
0.11
(Calculated)
Rcab at 90
degC
Ohms/km
35
1.1100
0.144
3.3
125
0.65
81
50
0.8200
0.137
4.7
150
0.65
98
70
0.5670
0.129
6.6
190
0.65
124
95
0.4100
0.123
230
0.65
150
120
0.3240
0.117
11.3
260
0.65
169
150
0.2640
0.114
14.2
295
0.65
192
185
0.2110
0.105
17.39
335
0.65
218
240
0.1600
0.106
22.6
395
0.65
257
300
0.1300
0.103
28.3
450
0.65
293
400
0.1000
0.099
37.7
520
0.65
338
Page 6 of 8
Running Conditions
Cable Route Length
1000
mts
(From Layout)
(Selected)
240
sqmm
29
Amps
0.91
395
(Calculated)
257
(Calculated)
No of Runs required
No
(Calculated)
0.15
(Calculated)
@ 6.6 kV
(Typical Data)
Starting Conditions
(From Layout)
1000
mts
240
sqmm
(Selected)
times
( DOL)
175
No of Runs required
(Calculated)
No
(Calculated)
0.71
(Calculated)
Rcab at 90
degC
Ohms/km
35
1.1100
0.144
3.3
125
0.65
81
50
0.8200
0.137
4.7
150
0.65
98
70
0.5670
0.129
6.6
190
0.65
124
95
0.4100
0.123
230
0.65
150
120
0.3240
0.117
11.3
260
0.65
169
150
0.2640
0.114
14.2
295
0.65
192
185
0.2110
0.105
17.39
335
0.65
218
240
0.1600
0.106
22.6
395
0.65
257
300
0.1300
0.103
28.3
450
0.65
293
400
0.1000
0.099
37.7
520
0.65
338
Page 7 of 8
Running Conditions
Cable Route Length
750
mts
240
sqmm
Amps
(From Layout)
(Selected)
175
0.80
395
(Calculated)
257
(Calculated)
No of Runs required
No
(Calculated)
0.66
(Calculated)
@ 6.6 kV
(Typical Data)
Rcab at 90
degC
Ohms/km
35
1.1100
0.144
3.3
125
0.65
81
50
0.8200
0.137
4.7
150
0.65
98
70
0.5670
0.129
6.6
190
0.65
124
95
0.4100
0.123
230
0.65
150
120
0.3240
0.117
11.3
260
0.65
169
150
0.2640
0.114
14.2
295
0.65
192
185
0.2110
0.105
17.39
335
0.65
218
240
0.1600
0.106
22.6
395
0.65
257
300
0.1300
0.103
28.3
450
0.65
293
400
0.1000
0.099
37.7
520
0.65
338
Page 8 of 8