Sie sind auf Seite 1von 15

CONCERNED ABOUT YOUR HEALHT AND THE ENVIROMENT

FILTER CARTRIDGE FOR ELECTRICAL


ROOM PRESSURISATION
OBJECTIVE
Prevent the entry of dust and pollutants into the electrical room, with
the aim of achieving longer life for the equipment and instruments
interior room.
TECHNICAL CHARACTERISTICS
Models
Nominal Capacity:
Filtering Area:
Filtration speed
Arrangement of Cartridge:
Number of Cartridge:
Cartridge Material:
Material structure:

: FC-2/200ST, FC-2/250ST Y FC-2/350ST


: 1500, 2500 Y 3500 MT3/HR
: 20 m2
: 0,7 m/min.
: 2x1
: 2 Units
: Polyester 275 gr/m2
: Carbon Steel A37 24 ES

FILTER CARTRIDGE FOR ELECTRICAL


ROOM PRESSURISATION

EQUIPMENT DESCRIPTION
It consists of two Catridge Filters with jet pulse cleaning system and
high pressure centrifugal fan.
Equipment manufactured in steel plate, which has an income of dirty
air, dirty chamber where the Cartridge, a clean chamber where the
air filter, where the automatic cleaning system and an air outlet filter
is reached are located.

To decrease the saturation level of the Cartridge, the computer has


a pneumatic cleaning, which allows Cartridge cleaning during
operation, which is composed by a Manifold Solenoid Valves
discharge air cleaning and Timer that controls the opening
valves.
Cleaning is to download a certain amount of air pressure on a
Catridge. Allows the generated impact peel the layers of particulate
material adhered onto the outside of Cartridge, which are deposited
in the bottom hopper of the filter. This shot is regularly performed in
the following Catridge, repeating the cycle indefinitely.
An electronic board (Timer) controls the frequency and duration of
the shooting, which basically depend on the degree of saturation of
the Cartridge.

FAN

MANOMETER

FILTERS

COMPRESSOR

FAN

Model
Type
Flow rate
Engine power
Transmission

: IV-15-L/B
: CBM T/4-270/200 CV.
: 1500 Mt3/hr
: 1 HP
: direct transmission.

FILTER
Use

Based composite filter media


pore size
Efficiency (Class)
Gramature
Filtration Area
structure.

Maximum air flow

:air intake and filter


dust collection.
:10% Cellulose 90% Polyester
:1 micron
:99.9%
:140 [g / m 2]
: 20 [m 2]
:Metal Roofs. Inner and
outer mantle perforated metal.
:3200 [L / s @ 37 mm H2O]]

COMPRESSOR
Work pressure
Engine power
Electrical feeding

: 6 Bar
: 3 HP.
: 380 Volt 60hz

MANOMETER
Housing: Die cast aluminum case and bezel, with acrylic cover.
Exterior finish is coated gray to withstand 168 hour
salt spray corrosion test.
Accuracy: 2% of full scale (3% on - 0, -100 Pa, -125 Pa,
10MM and 4% on - 00, -60 Pa, -6MM ranges),
throughout range at 70F (21.1C).
Pressure Limits: -20 Hg. to 15 psig. (-0.677 bar to 1.034
bar);MP option: 35 psig (2.41 bar), HP option:80
psig (5.52 bar).
Overpressure: Relief plug opens at approximately 25 psig
(1.72 bar), standard gages only.
Temperature Limits: 20 to 140F.* (-6.67 to 60C).
Process Connections: 1/8 female NPT duplicate high and low
pressure taps - one pair side and one pair back.
Weight: 1 lb 2 oz (510 g), MP & HP 2 lb 2 oz (963 g)

VALVES
Model
Work Pressure
Electrical Feeding:

: AE 1440 R 225:
:90 PSI
:220V

Pressure Differential
Service: Air and non-combustible, compatible gases
Temperature Limits: Process and ambient temperature from -4
to 185F (-20 to 85C)
Pressure Limits: Max. Operating Pressure: 40' w.c. (10 kPa)
for all pressure ranges
Switch Type: Single-pole double-throw (SPDT)
Electrical Rating: Max., 1.5A/250 VAC, max. switching rate: 6
cycles/min.; Gold Contact Option: 0.4 A/ 250 VAC
Electrical Connections: Push-on screw terminals. M20x1.5
with cable strain relief or optional 1/2' NPT connection
Process Connections: 5/16' (7.94 mm) outside diameter
tubing, 1/4' (6.0 mm) inside diameter tubing
Enclosure Rating: NEMA 13, IP54
Mounting Orientation: Vertically, with pressure connections
pointing downwards
Mechanical Working Life: Over 106 switching operations
Weight: 5.6 oz (160 g)

Control System
It has a control system which through a pressure differential
marker actuates the valves, in order to clean the filter catridge.

MANUFACTURER: INGECOAT
PRESSURIZER INSTRUCTIONS
FC-2/200 PRESSURIZER

Pressurizer FC-2/ 200 is a filtering equipment and pressurized ambient air,


connected directly to the site. Providing clean air injection.
Among its main features are its high degree of purification of air injection,
equivalent to less than 5 milligrams of particles per cubic meter of air filter
and powerful pressurized enclosure to which it is dedicated.

For the proper functioning of the FC-2/200, is recommended that the air
injection is made to the enclosure through an injection grid double deflection
(horizontal and vertical), with control damper to compensate manually last
air resistance increased by filters. A second control can made by opening
the damper, located off the pipeline of FC-2/200. This damper has been
factory-set to 55 open, suitable for use with completely clean filters.
The pressurizer FC- 2/200 is fully automatic in function of purifying and
pressurizing. Cleaning of filters is performed through a discharge of
compressed air, for which has its own air compressor.
It has 2 electric motors protected by thermal overload relays.

For proper operation has an electric charge and control board.

The starting and stopping is done by activating the command switch "A",
black, opening the door panel. The "B" button, green, can run a manual
download each time it is pressed, for voluntary cleaning cartridge filters.
The operation of the pressurizer FC- 2/200 is managed by a small PLC,
brand Lobato. With an open program that can be changed according to the
user's convenience, for which simply seek Ingecoat permission.
For the command cleaning, FC - 2/200 has a DIFFERENTIAL PRESSURE,
identified with the letter "C" in the board. This switch has been set at 2.5 "
wg , or 63 mm water column , so that when the pressure drop of the filter
reaches the specified value , the switch will give way to regular cleaning of
the filters through pulse of

18

17

19
20

14

15
7

13

12

11

10

Equipo Jetpulse

Primera Etapa de Filtrado


Jet Pulse

Equipo Jet Pulse

Evita Ingreso de Aire


Contaminado con Polvo o
Gases cidos o Alcalinos.

Segunda Etapa de Filtrado


Filtro Catridge

Circulacin de Aire limpio


Al interior de Sala.
Inyeccin de Aire

Equipo Aire
Acondicionado Marvair

Retorno de Aire

WWW.INGECOAT.CL
Saturno 1490, Quinta Normal, Santiago - (+56 2) 27271442 - ventas@ingecoat.cl

Das könnte Ihnen auch gefallen