Beruflich Dokumente
Kultur Dokumente
Comments
Initial release
Ammendments:
Minimum Module
Version Required
V1.0.10
Minimum Configuration
Suite Version Required
2013.79 (v1.133.2)
V1.5.2
2015.5 (v1.237.3)
Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The
numeral 1 has a top serif to avoid this confusion.
TABLE OF CONTENTS
1
BIBLIOGRAPHY .............................................................................................. 4
1.1
1.2
1.3
2
3
4
INSTALLATION INSTRUCTIONS................................................................................................. 4
MANUALS ................................................................................................................................... 4
OTHER ........................................................................................................................................ 4
DESCRIPTION ................................................................................................. 4
INSTALLATION AND USING THE DSE CONFIGURATION SUITE ............... 4
EDIT CONFIGURATION .................................................................................. 5
4.1
CONFIGURATION LOCK ............................................................................................................. 5
4.2
SCREEN LAYOUT ....................................................................................................................... 6
4.3
MODULE ..................................................................................................................................... 7
4.3.1
MODULE OPTIONS .............................................................................................................. 8
4.3.2
CONFIGURABLE STATUS ................................................................................................... 9
4.4
DIGITAL INPUTS ....................................................................................................................... 10
4.5
DIGITAL OUTPUTS ................................................................................................................... 11
4.5.1
OUTPUT SOURCES ........................................................................................................... 11
4.6
TIMERS ..................................................................................................................................... 13
4.7
MAINS ....................................................................................................................................... 14
4.7.1
MAINS OPTIONS................................................................................................................ 14
4.7.1.1 SUPPORTED AC SYSTEM TOPOLOGIES ......................................................................... 15
4.7.2
MAINS VOLTAGE ............................................................................................................... 16
4.7.3
MAINS SEQUENCE ALARMS ............................................................................................. 17
4.7.4
MAINS FREQUENCY ALARMS........................................................................................... 18
4.7.5
MAINS DECOUPLING ........................................................................................................ 19
4.8
COMMUNICATIONS .................................................................................................................. 20
4.8.1
COMMUNICATION OPTIONS ............................................................................................. 20
4.8.2
CONFIGURABLE GENCOMM PAGES ................................................................................ 20
4.9
ALTERNATIVE CONFIGURATION............................................................................................. 21
4.9.1
ALTERNATIVE CONFIGURATION EDITOR ........................................................................ 21
SCADA ........................................................................................................... 22
5.1
MODULE IDENTITY ................................................................................................................... 23
5.2
MIMIC ........................................................................................................................................ 23
5.3
LANGUAGES ............................................................................................................................ 23
5.4
DIGITAL INPUTS ....................................................................................................................... 24
5.5
DIGITAL OUTPUTS ................................................................................................................... 24
5.6
MAINS ....................................................................................................................................... 25
5.7
ALARMS.................................................................................................................................... 26
5.8
STATUS..................................................................................................................................... 26
5.9
EVENT LOG .............................................................................................................................. 27
5.10 MAINTENANCE ......................................................................................................................... 28
5.10.1
TIME .................................................................................................................................. 28
5.10.2
MODULE PIN ..................................................................................................................... 29
Bibliography
1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained from the
DSE website: www.deepseaplc.com
1.1
INSTALLATION INSTRUCTIONS
DSE Part
053-149
1.2
MANUALS
DSE Part
057-151
057-184
1.3
Description
DSEP100 Installation Instructions
Description
DSE Configuration Suite PC Software Installation & Operation Manual
DSEP100 Operator Manual
OTHER
Description
IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device Function Numbers
and Contact Designations. Published by Institute of Electrical and Electronics Engineers
Inc
2 DESCRIPTION
The DSE100 Mains Decoupling Relay configuration suite allows the DSEP100 module to be connected to
a PC via USB A USB B cable. Once connected the various operating parameters within the module can be
viewed or edited as required by the engineer. This software allows easy controlled access to these values.
This manual details the configuration of the DSEP100 Mains Decoupling Relay.
The configuration suite should only be used by competent, qualified personnel, as changes to the operation of
the module may have safety implications on the panel / generating set to which it is fitted. Access to critical
operational sequences and settings for use by qualified engineers, may be barred by a security code set by
the generator provider.
The information contained in this manual should be read in conjunction with the information contained in the
appropriate module documentation. This manual only details which settings are available and how they may
be used.
A separate manual deals with the operation of the individual module (See section entitled Bibliography
elsewhere in this document).
Edit Configuration
4 EDIT CONFIGURATION
This menu allows module configuration, to change the function of Inputs, Outputs and LEDs, system timers
and level settings to suit a particular application.
4.1
CONFIGURATION LOCK
A means of attaching a small padlock or utility company seal is provided that when attached, prevents the
main configuration settings being changed either from the Front Panel Editor or via Configuration Suite PC
Software.
Ensure the
Configuration Lock has
been disabled and is in
the fully open position.
Edit Configuration
4.2
SCREEN LAYOUT
Move to the
Previous or Next
configuration page
The type of
configuration file
being edited.
The coloured
shading shows
the currently
selected page.
Close this
configuration file
Click + or to
show or hide
the sub
settings within
each sections.
Step forward or
backward through
previously viewed
pages.
Click to return
to this page
at any time.
Click to select
the subsection
to view / edit.
Edit Configuration
4.3
MODULE
Edit Configuration
4.3.1
MODULE OPTIONS
Enables support
for right-to-left
Languages
Event logging
options, Tick
to enable the
type of event
to be logged.
Miscellaneous Options
Manaul Reset if Mains Out of
Limits
Description
= Mains decoupling alarms cannot be manually reset using the Reset
push button unless the mains is available.
= Mains decoupling alarms can be manually reset using the Reset
push button even if the mains is not available.
= User configured alarm text appears as left-to-right.
= User configured alarm text appears as right-to-left.
= Module powers up assuming mains is available.
= Module powers up assuming mains is not available. The mains
decoupling output is active when first powered.
Standard Compliance
Standard
Description
G59/2 = Module tripping reaction times conform to the G59/2 standard.
G59/3 = Module tripping reaction times conform to the G59/3 standard.
Description
= Power up events are not logged in the modules event log
= Power up events are logged when the DC Supply is applied to the
module or whenever the module is rebooted
= Alarms are not logged in the modules event log
= Logs an event upon the occurance of any alarm
= Alarm resets are not logged in the modules event log
= Logs an event when an alarm is reset
= Mains supervision enabled events are not logged in the modules
event log
= Logs an event to indicate when the mains supervision was enabled
= Mains supervision disabled events are not logged in the modules
event logged
= Logs an event to indicate when the mains supervision was disabled
Alarms
Resets
Supervision Enabled
Supervision Disabled
Edit Configuration
4.3.2
CONFIGURABLE STATUS
Option
Not Used
Active Config
Battery Voltage
Mains Decoupling
Mains Frequency
Mains Phase Sequence
Mains Voltage L-L
Mains Voltage L-N
Rolling Average L-L
Rolling Average L-N
Sequence Voltages
Summary Screen
Voltage Asymmetry
Description
No instrument is selected to show on the configurable status page
Shows the selected configuration on the configurable status page
Shows the battery voltage
Shows the mains decoupling state
Shows the mains frequency
Shows the mains phase sequence
Shows the mains line to line voltage
Shows the mains line to neutral voltage
Shows the rolling average line to line voltage
Shows the rolling average line to neutral voltage
Shows the sequence voltages
Shows a summary of the modules instruments
Shows the voltage asymmetry
Edit Configuration
4.4
DIGITAL INPUTS
Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor
devices and software programs. Where the DSE input functions can be represented by IEEE 37.2, the
function number is listed below.
Function
Generator Closed Auxiliary
IEEE 37.2 - 3
Checking Or Interlocking relay
Mains Closed Auxiliary
IEEE 37.2 - 3
Checking Or Interlocking Relay
Alarm Reset
Alt Config Select
Auxiliary Mains Fail
Description
This input is used to provide feedback to give true indication of the
contactor or circuit breaker switching status. It should be connected to the
generator load switching device auxiliary contact.
This input is used to provide feedback to give true indication of the
contactor or circuit breaker switching status. It should be connected to the
mains load switching device auxiliary contact.
This input is used to reset any latched alarms from a remote location.
This input is used to instruct the module to follow the alternative
configuration settings instead of the main configuration settings.
The module monitors the incoming single or three phase supply for Over
voltage, Under Voltage, Over Frequency or Under frequency. It may be
required to monitor a different mains supply or some aspect of the
incoming mains not monitored by the controller. If the devices providing
this additional monitoring are connected to operate this input, the
controller operates as if the incoming mains supply has fallen outside of
limits.
Removal of the input signal causes the module to act if the mains has
returned to within limits providing that the mains sensing also indicates
that the mains is within limits.
10
Edit Configuration
4.5
DIGITAL OUTPUTS
Select if the relay
is to energise or
de-energise upon
activation of the
source.
Select what
the output is
to control.
These labels
match the
typical wiring
diagram.
4.5.1
OUTPUT SOURCES
The list of output sources available for configuration of the module relay.
Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor
devices and software programs. Where the DSE output functions can be represented by IEEE 37.2, the
function number is listed below.
The outputs are in
alphabetical order with
the parameter first.
Output Source
Not Used
Alarm Reset
Alternative Config Select
Asymmetry High
IEEE 37.2 59
Overvoltage Relay
Auxiliary Mains Failure
Breaker Failed to Open
Description
The output does not change state (Unused)
Indicates that an alarm reset operation is in progress by digital input
Indicates if the alternative configuration has been selected
Active when the Asymmetry Alarm is active
Edit Configuration
Output Source
Over Frequency (1 or 2)
IEEE 37.2 81H
Frequency Relay
Over Voltage (1 to 5)
IEEE 37.2 59
Overvoltage Relay
Positive Sequence Voltage High
IEEE 37.2 47
Phase-Sequence Or Phase
Balance Voltage Relay
ROCOF
IEEE 37.2 81R
Frequency Relay
Under Frequency (1 or 2)
IEEE 37.2 81L
Frequency Relay
Under Voltage (1 to 5)
IEEE 37.2 27
Undervoltage Relay
Vector Shift Alarm
IEEE 37.2 78
Phase-Angle Measuring Relay
Zero Sequence Voltage High
IEEE 37.2 47
Phase-Sequence Or Phase
Balance Voltage Relay
Description
Active when the Mains frequency has become higher than the Mains High
Frequency Alarm stage 1 (or stage 2)
Active when the Mains voltage has become higher than the Mains High
Voltage Alarm stage 1 (or stage 2)
Active when the Positive Sequence Alarm is active
Active when the Mains frequency has become lower than the Mains Low
Frequency Alarm stage 1 (or stage 2)
Active when the Mains voltage has become lower than the Mains Low
Voltage Alarm stage 1 (or stage 2)
Active when the Vector Shift Alarm is active
12
Edit Configuration
4.6
TIMERS
Enable the
Auto-Reset
feature in
order to
unlock these
features.
Timer
Supervision Timer
Auto-Reset Enable
Auto-Reset Delay
Reset if Mains Out Of
Limits
Description
When Mains Closed Auxiliary and Gen Closed Auxiliary inputs become active the
Supervision Timer begins, when the Supervision Timer expires all protections
become active.
= The module requires a manual reset when any alarm occurs
= Alarms are reset when the Mains has been consistently within limits for the
duration of the Auto-Reset Delay timer.
Time delay before initiating the normal Auto-Reset, during this time the Mains must
remain consistently within limits.
= The Auto-Reset only occurs if the Mains is back within limits
= The delay timer starts immediately after a trip regardless of the state of the
mains. All alarms are reset when it expires.
NOTE: This option is available when the Fast-Reset is disabled.
Fast-Reset Enable
Fast-Reset Window
Fast-Reset Delay
Page Timer
Scroll Timer
Breaker Fail to Open
Enable
Use Generator Closed
Auxiliary
Delay
13
Edit Configuration
4.7
MAINS
4.7.1
MAINS OPTIONS
Select the
AC system.
Click to enable or
disable the feature.
The relevant values
below appear
greyed out if the
feature is disabled.
14
Edit Configuration
4.7.1.1
15
Edit Configuration
4.7.2
MAINS VOLTAGE
NOTE: For further details on mains voltage alarms, refer to DSE Publication: 057-184 DSEP100
Mains Decoupling Relay Operator Manual.
Type the
value or
click the up
and down
arrows to
change the
settings.
Alarm
Mains Under Voltage
IEEE 37.2 - 27AC
Undervoltage Relay
Stage 1 to Stage 5 Under
Voltage Alarm Trip
Description
These are 5 stage alarms.
Stage 1 allows for a delayed operation should the voltage stray by a small
amount.
Stage 2 to 5 allows for a faster trip should the voltage change by a larger
amount.
= Alarm is disabled
= When enabled, the alarm activates when the voltage falls below the
configured Under Voltage Alarm Trip level for the configured Delay time.
These are 5 stage alarms.
Stage 1 allows for a delayed operation should the voltage stray by a small
amount.
Stage 2 to 5 allows for a faster trip should the voltage change by a larger
amount.
= Alarm is disabled
= When enabled, the alarm activates when the voltage exceeds the
configured Over Voltage Alarm Trip level for the configured Delay time.
= Alarm is disabled
= When enabled, the alarm activates when the average voltage of the three
phases exceeds the configured High Average Voltage over the preceeding ten
seconds (10s rolling average).
16
Edit Configuration
4.7.3
NOTE: For further details on mains sequence alarms, refer to DSE Publication: 057-184 DSEP100
Mains Decoupling Relay Operator Manual.
Click to enable or disable the
alarms. The relevant values
below appears greyed out if
the alarm is disabled.
Type the
value or
click the up
and down
arrows to
change the
settings.
Alarm
Zero Sequence Alarm
IEEE 37.2 47H
Phase-Sequence Or Phase
Balance Voltage Relay
Positive Sequence Alarm
IEEE 37.2 47L
Phase-Sequence Or Phase
Balance Voltage Relay
Negative Sequence Alarm
IEEE 37.2 47H
Phase-Sequence Or Phase
Balance Voltage Relay
Asymmetry Alarm
IEEE 37.2 59
Overvoltage Relay
17
Edit Configuration
4.7.4
NOTE: For further details on mains frequency alarms, refer to DSE Publication: 057-184 DSEP100
Mains Decoupling Relay Operator Manual.
Type the
value or click
the up and
down arrows
to change
the settings.
Click to enable or
disable the alarms.
The relevant values
below appears
greyed out if the
alarm is disabled.
Description
These are 2 stage alarms.
Stage 1 allows for a delayed operation should the frequency stray by a small
amount.
Stage 2 allows for a faster trip should the frequency change by a larger amount.
= Alarm is disabled
= When enabled, the alarm activates when the voltage falls below the
configured Under Frequency Alarm Trip level for the configured Delay time.
These are 2 stage alarms.
Stage 1 allows for a delayed operation should the frequency stray by a small
amount.
Stage 2 allows for a faster trip should the frequency change by a larger amount.
= Alarm is disabled
= When enabled, the alarm activates when the voltage exceeds the
configured Over Frequency Alarm Trip level for the configured Delay time.
18
Edit Configuration
4.7.5
MAINS DECOUPLING
NOTE: For further details on mains decoupling alarms, refer to DSE Publication: 057-184 DSEP100
Mains Decoupling Relay Operator Manual
Click to enable or
disable the alarms.
The relevant values
below appears
greyed out if the
alarm is disabled.
Type the
value or click
the up and
down arrows
to change
the setting.
Parameter
R.O.C.O.F.
IEEE 37.2 81R
Frequency Relay
Function
The alarm activates when the Rate of Change of Frequency (R.O.C.O.F.) is greater
than the configured settings of the R.O.C.O.F. alarm for more than the configured
Delay time.
R.O.C.O.F. detection of mains failure when in parallel relies upon the relative steady
state of the utility power grid frequency. Normally supplied by a myriad of large power
generating stations, the frequency cannot normally change quickly over a short
period of time.
Filter Cycles
Vector Shift
IEEE 37.2 78
Phase-Angle
Measuring Relay
A failure of the utility supply usually leads to sudden increase or decrease in the
active load of the local generator and a subsequent drop or rise in its frequency. This
is detected by the R.O.C.O.F. alarm.
The frequency of the AC supply is monitored and filtered over the configured number
of voltage cycles. When the R.O.C.O.F. has changed by more than the configured
level for more than the configured Delay time the alarm activates.
The alarm activates when the Vector Shift in one or more of the monitored phases of
the waveform has been measured greater than the configured settings of the Vector
Shift alarm.
Vector Shift detection of mains failure when in parallel relies upon the relative steady
state of the utility power grid.
Should the utility supply fail, the resulting change in load of the local supply (example
local site generator) leads to a jump in the phase of the local supply.
If this jump is greater than the setting of the Vector Shift Alarm, the trip is generated.
19
Edit Configuration
4.8
4.8.1
COMMUNICATIONS
COMMUNICATION OPTIONS
Free text entries for
identification.
This text is displayed on
the SCADA screen when
the module is connected
to the PC.
4.8.2
For advanced Modbus users of the controller, a configurable Gencomm page is available.
The intention is to allow the user to create personal collection of data in subsequent registers to minimise the
number of modbus reads required by the master, and hence speed up data collection.
All configurable Gencomm registers are 32-bit unsigned format.
Hex Address
A600
Decimal Address
42496
Edit Configuration
4.9
ALTERNATIVE CONFIGURATION
An Alternative Configuration is provided to allow the system designer to cater for different AC requirements
utilising the same system.
The Alternative Configuration can be selected using either:
4.9.1
The Alternative Configurations Editor allows for editing of the parameters that are to be changed when an
Alternative Configuration is selected.
Alternative configuration options contain a subset of the main configuration. The adjustable parameters are
not discussed here as they are identical to the main configuration options :
Configuration menus for the Alternative
Configuration.
For information about the configuration
items within this section, you are referred to
their description in the Main configuration.
21
SCADA
5 SCADA
SCADA stands for Supervisory Control And Data Acquisition and is provided both as a service tool and also
as a means of monitoring / controlling the module.
As a service tool, the SCADA pages are to check the operation of the controllers inputs and outputs as well
as checking the generators operating parameters.
Click to open the connection to the module. If no
module is connected, the SCADA opens to show
the screens for the type of module currently
open in the configuration.
22
SCADA
5.1
MODULE IDENTITY
5.2
MIMIC
This screen provides a mimic of the control module and allows the operator to change the control mode of the
module.
5.3
LANGUAGES
Current language
in the module.
Select new
language
23
SCADA
5.4
DIGITAL INPUTS
5.5
DIGITAL OUTPUTS
The function
the output is
configured for.
Shows if the output channel is active or
not. This output is closed and is active.
The output is configured to be energise.
24
SCADA
5.6
MAINS
25
SCADA
5.7
ALARMS
5.8
STATUS
26
SCADA
5.9
EVENT LOG
27
SCADA
5.10 MAINTENANCE
The Maintenance section is subdivided into smaller sections.
Select the required section with the mouse.
5.10.1 TIME
This section allows the day and time to be set and changed on the controller.
Display of the
modules current
date and time.
28
SCADA
29
30