Beruflich Dokumente
Kultur Dokumente
Ventilation
APPROVED DOCUMENT
Ventilation
Approved Document
Contents
PAGE
USE OF GUIDANCE
MEANS OF VENTILATION
THE REQUIREMENT F1
GUIDANCE
Performance
Definitions
6
6
Introduction to provisions
7
Ventilation of non-habitable rooms not containing 9
openable windows
Ventilation of habitable rooms through other
9
rooms and spaces
Interaction of mechanical extract ventilation
10
and open-flued combustion appliances
Alternative approaches
10
Section 2: Non-domestic buildings
11
Introduction to provisions
Mechanical ventilation of rooms
Ventilation of common spaces in nondomestic buildings
Alternative approaches
Ventilation of specialist activities
Ventilation of car parks
Design of mechanical ventilation/airconditioning plant
Alternative approaches
Access for maintenance
Commissioning
11
12
12
14
14
14
CONDENSATION IN ROOFS
THE REQUIREMENT F2
15
GUIDANCE
Performance
Introduction to provisions
PAGE
DIAGRAMS
F1
1. Provisions for background ventilation
2. Two rooms treated as a single room for
ventilation purposes
3. A habitable room ventilated through an
adjoining space
4. Provisions for background ventilation
5. Space for access
12
14
F2
6. Ventilating roof voids
7. Ventilating roof voids
16
17
TABLES
F1
1. Ventilation of rooms containing openable
windows (ie located on an external wall)
2. Ventilation of rooms containing openable
windows (ie located on an external wall)
8
9
9
11
12
13
13
13
15
15
17
Standards referred to
18
18
Approved Document
17
Ventilation
1
Use of Guidance
THE APPROVED DOCUMENTS
The Building Regulations 2000 (SI 2000/2531), which
come into operation on 1 st January 2001, replace the
Building Regulations 1991 (SI 1991/2768) and
consolidate all subsequent revisions to those
regulations. This document is one of a series that has
been approved and issued by the Secretary of State
for the purpose of providing practical guidance with
respect to the requirements of Schedule 1 to and
regulation 7 of the Building Regulations 2000 for
England and Wales.
At the back of this document is a list of all the
documents that have been approved and issued
by the Secretary of State for this purpose.
Approved Documents are intended to provide
guidance for some of the more common building
situations. However, there may well be alternative
ways of achieving compliance with the requirements.
Thus there is no obligation to adopt any
particular solution contained in an Approved
Document if you prefer to meet the relevant
requirement in some other way.
Other requirements
The guidance contained in an Approved Document
relates only to the particular requirements of the
Regulations which the document addresses. The
building work will also have to comply with the
requirements of any other relevant paragraphs in
Schedule 1 to the Regulations.
There are Approved Documents which give
guidance on each of the Parts of Schedule 1 and
on regulation 7.
LIMITATION ON REQUIREMENTS
In accordance with regulation 8, the requirements in
Parts A to K and N of Schedule 1 to the Building
Regulations do not require anything to be done
except for the purpose of securing reasonable
standards of health and safety for persons in or about
buildings (and any others who may be affected by
buildings or matters connected with buildings).
F
THE WORKPLACE (HEALTH,
SAFETY AND WELFARE)
REGULATIONS 1992
The Workplace (Health, Safety and Welfare)
Regulations 1992 contain some requirements which
affect building design. The main requirements are
now covered by the Building Regulations, but for
further information see: Workplace health, safety and
welfare, The Workplace (Health, Safety and Welfare)
Regulations 1992, Approved Code of Practice and
Guidance; The Health and Safety Commission, L24;
Published by HMSO 1992; ISBN 0-11-886333-9.
The Workplace (Health, Safety and Welfare)
Regulations 1992 apply to the common parts of flats
and similar buildings if people such as cleaners and
caretakers are employed to work in these common
parts. Where the requirements of the Building
Regulations that are covered by this Part do not apply
to dwellings, the provisions may still be required in the
situations described above in order to satisfy the
Workplace Regulations.
F1
MEANS OF VENTILATION
The Requirement
This Approved Document deals with the following
Requirement from Part F of Schedule 1 to the
Building Regulations 2000.
Requirement
Limits on application
Means of ventilation
F1.
There shall be adequate means of ventilation
provided for people in the building.
Previous page
is blank
Approved Document
Means of Ventilation
5
F1
Guidance
Performance
In the Secretary of State's view the requirement of
F1 will be met if ventilation is provided which under
normal conditions is capable (if used) of restricting
the accumulation of such moisture (which could
lead to mould growth) and pollutants originating
within a building as would otherwise become a
hazard to the health of the people in the building.
This could be achieved by the provision of
ventilation to:
a. extract, before it is generally widespread, water
vapour from areas where it is produced in
significant quantities (eg kitchens, utility rooms and
bathrooms);
b. extract, before they are generally widespread,
pollutants which are a hazard to health, from areas
where they are produced in significant quantities
(eg rooms containing processes which generate
harmful contaminants and rest rooms where
smoking is permitted);
c. rapidly dilute when necessary, pollutants and
water vapour produced in habitable rooms,
occupiable rooms and sanitary accommodation;
d. make available over long periods a minimum
supply of fresh air for occupants and to disperse
where necessary, residual water vapour. Such
ventilation should not significantly affect comfort
and where necessary, should be reasonably secure
and provide protection against rain penetration.
AND
Definitions
0.1 A ventilation opening can include any
means of ventilation (whether it is permanent or
closable) which opens directly to external air, such
as the openable parts of a window, a louvre,
airbrick, progressively openable ventilator, or
window trickle ventilator. It also includes any door
which opens directly to external air.
0.2 Habitable room means a room used for
dwelling purposes but which is not solely a kitchen.
0.3 Bathroom means a room containing a bath or
a shower, and can include sanitary accommodation.
Means of ventilation
Approved Document
F1
Section 1
DOMESTIC BUILDINGS
Introduction to provisions
1.1 This Approved Document shows two main
ways of complying with the requirement by:
a. following the provisions set out in paragraphs
1.2 to 1.8; or
b. alternative approaches set out in paragraph 1.9.
General
1.2 The performance will be achieved if the
following provisions are made in accordance with
Table 1:
a. for rapid ventilation, one or more ventilation
openings with some part of the ventilation opening at
high level (typically 1.75m above the floor level), eg
an opening window; and
b. for background ventilation, a ventilation
opening (or openings), eg trickle ventilators, air
bricks with a "hit and miss" ventilator, or where
appropriate, suitably designed opening windows
(see Diagram 1). The ventilation opening(s) should
Room
Rapid ventilation
(eg opening windows)
Habitable room
8000 mm2
Kitchen
opening window
(no minimum size)
4000 mm2
30 litres/second adjacent to
a hob or 60 litres/second
elsewhere(4) or PSV
opening window
(no minimum size)
4000 mm2
30 litres/second or PSV
opening window
(no minimum size)
4000 mm2
15 litres/second or PSV
(6)
Utility
room(5)
Bathroom
(with or without WC)
Approved Document
Means of ventilation
7
F1
background
ventilation at
top of window
outside
a) In window frames
ironmongery to
secure window
when open for
background
ventilation
outside
b) In glazed openings
outside
lockable
fastener with
two opening
positions
minimum area
to comply with
requirements
in Table 1
Means of ventilation
Approved Document
F1
habitable
room
8000mm background
ventilation in each
position
conservatory or
similar space
both openings to provide
rapid ventilation at least
1/20th of the combined
floor area
Approved Document
Means of ventilation
9
F1
Alternative approaches
1.9 As an alternative to paragraphs 1.2 to 1.7 the
requirement will be satisfied by following the
relevant recommendations of:
a. BS 5925: 1991 Code of practice for ventilation
principles and designing for natural ventilation. The
relevant clauses are 4.4, 4.5, 4.6.1, 4.6.2, 5.1, 6.1,
6.2, 7.2, 7.3, 12 and 13; or
b. BS 5720: 1979 Code of practice for mechanical
ventilation and air-conditioning in buildings. The
relevant clauses are 2.3.2.1, 2.3.3.1, 2.5.2.9,
3.1.1.1, 3.1.1.3 and 3.2.6; or
c. BS 5250: 1989 Code of practice for the control
of condensation in buildings. The relevant clauses
are 6, 7, 8, 9.1, 9.8, 9.9.1 to 9.9.3 and Appendix C; or
d. BRE Digest 398 Continuous mechanical
ventilation in dwellings: design, installation and
operation. For the design of either:
- continuous balanced (supply and extract)
mechanical ventilation to be provided throughout
the dwelling; or
- continuous mechanical extract ventilation to be
provided in kitchens, utility rooms, bathrooms and
sanitary accommodation.
Means of ventilation
10
Approved Document
F1
Section 2
NON-DOMESTIC BUILDINGS
Introduction to provisions
2.1 This Approved Document shows the main
ways of complying with the requirement:
a. by following the provisions set out in paragraphs
2.2 to 2.5 or by following the alternative approaches
set out in paragraph 2.6; and where relevant,
b. for specialist activities by following the
provisions set out in paragraph 2.7; and
c. for car parks by following the provisions set out
in paragraph 2.8 or the alternative approach set out
in paragraph 2.9;
AND FOR MECHANICAL VENTILATION/AIRCONDITIONING PLANT
d. by following the provisions set out in
paragraphs 2.11 to 2.13 or the alternative
approaches set out in paragraph 2.14 for the
design of mechanical ventilation/air-conditioning
plant and the provisions set out in paragraphs 2.15
and 2.16 for access for maintenance; and
Extract ventilation(3,4)
fan rates
Rapid ventilation
(eg opening windows)
Background ventilation
(see Diagram 4)
up to 10m2 - 4000mm2;
greater than 10m2 - at the
rate of 400mm2/m2 of floor area
Kitchen(2)
(domestic type)
opening window
(no minimum size)
4000 mm2
30 litres/second adjacent
to hob, or 60 litres/second
elsewhere
Bathrooms
(including showerrooms)
opening window
(no minimum size)
15 litres/second per
bath/shower
Sanitary accommodation
(and/or washing facilities)
Room
Occupiable
room(1)
Notes:
1. For specific rooms designed for heavy smoking, such
as rest rooms where smoking is permitted, see
paragraph 2.7(e).
2. A domestic type kitchen is one where the appliances
and usage are of a domestic nature. This provision is
not intended to cover commercial kitchens, see
paragraph 2.7(f).
Approved Document
Means of ventilation
11
F1
a) In window frames
outside
b) In glazed openings
outside
c) Above window
frames
2. Airbrick with "hit and miss" ventilator
Alternative approaches
2.6 As an alternative to paragraphs 2.2 and 2.5
the requirement will be satisfied:
a. by following the relevant recommendations of
BS 5925: 1991 Code of practice for ventilation
principles and designing for natural ventilation. The
relevant clauses are 5.1, 5.2, 6.1, 6.2, 7.3, 12 and
13; or
b. by following the relevant recommendations of
CIBSE Guide A: Design data and CIBSE Guide B:
Installation and equipment data. The relevant
sections are A4 Air infiltration and natural
ventilation, B2 Ventilation and air-conditioning
(requirements).
Means of ventilation
12
Approved Document
F1
Approved Document
b.
Alternative approach
2.9 As an alternative to paragraph 2.8, the
requirement will be satisfied if the mean predicted
pollutant levels are calculated and the ventilation
designed to limit the concentration of carbon
monoxide to not more than 50 parts per million
averaged over an eight hour period and peak
concentrations, such as by ramps and exits, not to
go above 100 parts per million for periods not
exceeding 15 minutes.
2.10 Further guidance can be found in Code of
practice for ground floor, multi-storey and
underground car parks published by the Association
for Petroleum and Explosives Administration and in
CIBSE Guide B, Section B2-6 and Table B2-7.
Design of mechanical
ventilation/air-conditioning plant
2.11 The requirement will be satisfied if provision
is made to protect the fresh air supplies from
contaminants injurious to health. Air inlets for
ventilation systems should not be sited where they
may draw in excessively contaminated air (for
example close to a flue, an exhaust ventilation
system outlet, an evaporative cooling tower, or from
an area in which vehicles manoeuvre).
2.12 Guidance on design measures to avoid
legionella contamination, including design features
not related to the ventilation of the building, is
covered in HSE's The control of legionellosis
including legionnaires' disease. The relevant
paragraphs are 71 to 89.
Means of ventilation
13
F1
passageway
Alternative approaches
600mm
2.0m
General
1.1m
1.4m
690mm
Kneel
Commissioning
2.17 Where mechanical ventilation and airconditioning systems are installed to serve floor
areas in excess of 200m2 and the relevant
provisions in paragraphs 2.3 to 2.16 have been
undertaken, the requirement will be satisfied if the
building control body is provided with confirmation
that the mechanical ventilation systems have been
commissioned and tested to demonstrate that they
are operating effectively for the purpose of
ventilation. A way of demonstrating compliance with
the requirements would be to present test reports
and commissioning certificates which certify that
commissioning and testing have been carried out in
accordance with the CIBSE commissioning codes
and that the systems perform in accordance with the
specification.
Means of ventilation
14
Approved Document
F2
CONDENSATION IN ROOFS
The Requirement
This Approved Document deals with the following
Requirement from Part F of Schedule 1 to the
Building Regulations 2000.
Requirement
Limits on application
Condensation in Roofs
F2.
Adequate provision shall be made to
prevent excessive condensation a) in a roof; or
b) in a roof void above an insulated ceiling.
Guidance
Performance
In the Secretary of State's view, the requirement of
F2 will be met if condensation in a roof and in the
spaces above insulated ceilings is limited so that,
under normal conditions:
a. the thermal performance of the insulating
materials and
b. the structural performance of the roof
construction
will not be substantially and permanently reduced.
Introduction to provisions
0.1 The requirement will be met by the ventilation
of cold deck roofs, ie those roofs where the
moisture from the building can permeate the
insulation, as in sections 1 and 2 below.
Approved Document
Condensation in roofs
15
F2
Section 1
ROOFS WITH A PITCH OF 15 OR
MORE (PITCHED ROOFS)
Introduction
1.1 If the ceiling follows the pitch of the roof, see
section 2.
at least equal to
continuous strip
10mm wide
Alternative approach
at least equal to
continuous strip
5mm wide
at least equal to
continuous strip
10mm wide
Condensation in roofs
16
Approved Document
F2
Section 2
ROOFS WITH A PITCH OF LESS
THAN 15 AND THOSE WHERE
THE CEILING FOLLOWS THE
PITCH OF THE ROOF
Alternative approach
2.8 The requirement can also be met by following the
relevant recommendations of BS 5250:1989 Code of
practice for the control of condensation in buildings.
The relevant clauses are 9.1, 9.2 and 9.4.
at least equal to
continuous strip
25mm wide
at least equal to
continuous strip
25mm wide
at least 50mm
at least 50mm
at least equal to
continuous strip
25mm wide
Approved Document
at least 50mm
at least equal to
continuous strip
25mm wide
Condensation in roofs
17
F2
Standards referred to
F1 and F2
BS 4434: 1989 Specification for safety aspects in the
design, construction and installation of refrigerating
appliances and systems.
BS 5250: 1989 Code of practice for the control of
condensation in buildings.
BS 5440: Part 1: 1990 Specification for installation of
flues.
BS 5720: 1979 Code of practice for mechanical
ventilation and air-conditioning in buildings.
BS 5925: 1991 Code of practice for ventilation
principles and designing for natural ventilation.
Ventilation
18
Approved Document
Approved Documents
The following documents have been approved and
issued by the Secretary of State for the purpose of
providing practical guidance with respect to the
requirements of the Building Regulations 2000.
Approved Document A - Structure: 1992 Edition,
fourth impression (with amendments) 1994, further
amended 2000
Approved Document B - Fire safety: 2000 Edition,
amended 2000
Approved Document C - Site preparation and
resistance to moisture: 1992 Edition, second
impression (with amendments) 1992. further
amended 2000
Approved Document D - Toxic Substances: amended
1992, further amended 2000
Approved Document E - Resistance to the passage of
sound: 1992 Edition, second impression (with
amendments) 1992, further amended 2000
Approved Document F - Ventilation: 1995 Edition,
amended 2000
Approved Document G - Hygiene: 1992 Edition,
second impression (with amendments) 1992. further
amended 2000
Approved Document H - Drainage and Waste
Disposal: amended 1992, further amended 2000
Approved Document J - Heat Producing Appliances:
amended 1992, further amended 2000
Approved Document K - Protection from falling,
collision and impact: 1998 Edition, amended 2000
Approved Document L - Conservation of fuel and
power: 1995 Edition, amended 2000
Approved Document M - Access and facilities for
disabled people: 1999 Edition, amended 2000
Approved Document N - Glazing - safety in relation to
impact, opening and cleaning: 1998 Edition,
amended 2000
Approved Document to support regulation 7 materials and workmanship: 1999 Edition, amended
2000
Ventilation
19
APPROVED DOCUMENTS
Approved Documents
The following documents have been approved
and issued by the Secretary of State for the
purpose of providing practical guidance with
respect to the requirements of the Building
Regulations 2000.
Approved Document A - Structure: 1992
Edition, fourth impression (with amendments)
1994, further amended 2000
Approved Document B - Fire Safety: 2000
Edition, amended 2000
Approved Document C - Site preparation
and resistance to moisture: 1992 Edition,
second impression (with amendments) 1992,
further amended 2000
Approved Document D - Toxic substances:
amended 1992, further amended 2000
Approved Document E - Resistance to the
passage of sound: 1992 Edition, second
impression (with amendments) 1992, further
amended 2000
Approved Document F -Ventilation: 1995
Edition, amended 2000
Approved Document G - Hygiene: 1992
Edition, second impression (with amendments)
1992, further amended 2000
Approved Document H - Drainage and waste
disposal: 2002 Edition
Approved Document J - Combustion
appliances and fuel storage systems:
2002 Edition
Approved Document K - Protection from
falling, collision and impact: 1998 Edition,
amended 2000
Approved Document L1 - Conservation of
fuel and power in dwellings: 2002 Edition
Approved Document L2 - Conservation of
fuel and power in buildings other than
dwellings: 2002 Edition
Approved Document M - Access and
facilities for disabled people: 1999 Edition,
amended 2000
Approved Document N - Glazing - safety in
relation to impact, opening and cleaning:
1998 Edition, amended 2000
Approved Document to support regulation 7
- Materials and workmanship: 1999 Edition,
amended 2000
Approved Document F
Ventilation
Online
www.tso.co.uk/bookshop
Mail,Telephone, Fax & E-mail
TSO
PO Box 29. Norwich, NR3 1GN
Telephone orders/General enquiries: 0870 600 5522
Fax orders: 0870 600 5533
E-mail: book.orders@tso.co.uk
Textphone 0870 240 3701
APPROVED DOCUMENT F
TSO Shops
Ventilation
Crown copyright 1992. Published for the Office of the Deputy Prime Minister under licence from the