External Static Pressure Calculation (Revision 1)

SEF-B1-01(Smoke Exhaust Fan for Compartment D Carpark SES System)

20/4/2016

Remark

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Cross Sectional Area(m2)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

Fitting Coefficient

Duct Fitting Loss (Pa)

Exhaust Air Grille


90 Bend
Contraction
Linear Duct
Enlargement
Linear Duct
Branch
Linear Duct
Branch
90 Bend
VCD
Linear Duct
Enlargement
Linear Duct
Branch
45 Bend
Linear Duct
Enlargement
Linear Duct
Branch
45 Bend
Linear Duct
Branch
Linear Duct
Enlargement
Linear Duct
45 Bend
Contraction
90 Bend
Linear Duct
VCD
Flexible Connector
Contraction
Ventilation Fan
Enlargement
Flexible Connector
Enlargement
90 Bend
Riser
90 Bend
Contraction
Linear Duct
45 Bend
Enlargement
Smoke Extraction Louvre

2200
2200
2200
2200
2200
2200
4400
4400
4800
4800
4800
4800
4800
4800
11400
11400
11400
11400
11400
15800
15800
15800
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000

1500
1500
1000
1000
1000
1400
1400
1400
1400
1400
1400
1400
1400
1800
1800
1800
1800
1800
2400
2400
2400
2400
2400
2400
2400
1500
1500
1200
1200
1200
1200
1200
1200

1500
1500
300
300
300
300
300
300
300
300
300
300
300
500
500
500
500
500
550
550
550
550
550
550
550
1500
1500
1000
1000
1000
1000
1000
1000

2.25
2.25
0.30
0.30
0.30
0.42
0.42
0.42
0.42
0.42
0.42
0.42
0.42
0.90
0.90
0.90
0.90
0.90
1.32
1.32
1.32
1.32
1.32
1.32
1.32
2.25
2.25
1.20
1.20
1.20
1.20
1.20
1.20

1
1
7
7
7
5
10
10
11
11
11
11
11
5
13
13
13
13
9
12
12
12
14
14
14
8
8
15
15
15
15
15
15

1
1
32
32
32
16
66
66
78
78
78
78
78
17
96
96
96
96
45
86
86
86
112
112
112
38
38
135
135
135
135
135
135

1
1
1

0.21
0.12

30.00
0.12
3.87

0.17

5.49

0.40

26.34

1
1
1

0.20
0.21
0.50

15.67
16.46
39.18

0.17

13.32

2
2

0.40
0.21

77.01
40.43

0.17

16.37

1
2

0.30
0.21

25.79
36.10

0.20

22.31

0.17

18.97

2
1
1

0.21
0.12
0.21

16.13
16.20
28.35

1
1
1

0.50
0.12

67.50
5.00
16.20

1200
1200
1200
1150
1150
1150
1200
1200
1200
1200
3000

1000
1000
1000
1300
1300
1300
1000
1000
1000
1000
3000

1.20
1.20
1.20
1.50
1.50
1.50
1.20
1.20
1.20
1.20
9.00

15
15
15
12
12
12
15
15
15
15
2

135
135
135
87
87
87
135
135
135
135
2

1
1
1
2

0.17
0.10
0.10
0.21

22.95
5.00
12.83
36.53

1
1

0.21
0.12

18.27
16.20

1
1
1

0.21
0.17

##

1
1-2
1-2
1-2
1-2
1-2
2-3
2-3
3-4
3-4
3-4
3-4
3-4
3-4
4-5
4-5
4-5
4-5
4-5
5-6
5-6
5-6
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
7-8
8-9
8-9
8-9
8-9
8-9
8-9

28.35
22.95
50.00

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

11

1.33

14.76

0.65

1.60

2.42

2.24

14

2.86

39.68

0.38

1.76

1.98

9.16

0.81

2.50

1.51

13.97

1.93

7.74

13

0.37

4.79

15

1.81

27.90

22

1.04

22.68

10

1.81

18.32

Sum
Safety
Total
Design External
Static Pressure

600

Pa

Remark
*
##

Fitting Coefficient is referred to CIBSE Guide C (2007)


Duct Pressure Loss is referred to the "Pressure Loss Chart'' for Internal Duct Liner from Manufacturer Owens Corning
Reference from the external louvre's static pressure chart as attached

Sub Total Cummulativ


Section e Section
Loss (Pa) Loss (Pa)
30.00
0.12
3.87
14.76
5.49
1.60
26.34
2.24
15.67
16.46
39.18
39.68
13.32
1.76
77.01
40.43
9.16
16.37
2.50
25.79
36.10
13.97
22.31
7.74
18.97
4.79
16.13
16.20
28.35
27.90
67.50
5.00
16.20
0.00
22.95
5.00
12.83
36.53
22.68
18.27
16.20
18.32
28.35
22.95
50.00
916.99
20%
1110

30.00
30.12
33.99
48.76
54.24
55.84
82.18
84.42
100.10
116.55
155.74
195.42
208.74
210.50
287.51
327.94
337.10
353.47
355.97
381.75
417.86
431.83
454.14
461.88
480.84
485.64
501.76
517.96
546.31
574.22
641.72
646.72
662.92
662.92
685.87
690.87
703.69
740.22
762.91
781.17
797.37
815.69
844.04
866.99
916.99

Pa

External Static Pressure Calculation (Revision 1)


SEF-B1-01(Smoke Exhaust Fan for Compartment D Carpark SES System)

20/4/2016

Remark

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Cross Sectional Area(m2)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

Fitting Coefficient

Duct Fitting Loss (Pa)

Exhaust Air Grille


90 Bend
Contraction
Linear Duct
Enlargement
Linear Duct
Branch
Linear Duct
Branch
90 Bend
VCD
Linear Duct
Enlargement
Linear Duct
Branch
45 Bend
Linear Duct
Enlargement
Linear Duct
Branch
45 Bend
Linear Duct
Branch
Linear Duct
Enlargement
Linear Duct
45 Bend
Contraction
90 Bend
Linear Duct
VCD
Flexible Connector
Contraction
Ventilation Fan
Enlargement
Flexible Connector
Enlargement
90 Bend
Riser
90 Bend
Contraction
Linear Duct
45 Bend
Enlargement
Smoke Extraction Louvre

2300
2300
2300
2300
2300
2300
4500
4500
4900
4900
4900
4900
4900
4900
11500
11500
11500
11500
11500
15900
15900
15900
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100

1500
1500
1000
1000
1000
1400
1400
1400
1400
1400
1400
1400
1400
1800
1800
1800
1800
1800
2400
2400
2400
2400
2400
2400
2400
1500
1500
1200
1200
1200
1200
1200
1200

1500
1500
300
300
300
300
300
300
300
300
300
300
300
500
500
500
500
500
550
550
550
550
550
550
550
1500
1500
1000
1000
1000
1000
1000
1000

2.25
2.25
0.30
0.30
0.30
0.42
0.42
0.42
0.42
0.42
0.42
0.42
0.42
0.90
0.90
0.90
0.90
0.90
1.32
1.32
1.32
1.32
1.32
1.32
1.32
2.25
2.25
1.20
1.20
1.20
1.20
1.20
1.20

1
1
8
8
8
5
11
11
12
12
12
12
12
5
13
13
13
13
9
12
12
12
14
14
14
8
8
15
15
15
15
15
15

1
1
35
35
35
18
69
69
82
82
82
82
82
18
98
98
98
98
46
87
87
87
113
113
113
39
39
137
137
137
137
137
137

1
1
1

0.21
0.12

30.00
0.13
4.23

0.17

6.00

0.40

27.55

1
1
1

0.20
0.21
0.50

16.33
17.15
40.83

0.17

13.88

2
2

0.40
0.21

78.37
41.14

0.17

16.65

1
2

0.30
0.21

26.12
36.56

0.20

22.56

0.17

19.18

2
1
1

0.21
0.12
0.21

16.31
16.38
28.67

1
1
1

0.50
0.12

68.25
5.00
16.38

1200
1200
1200
1150
1150
1150
1200
1200
1200
1200
3000

1000
1000
1000
1300
1300
1300
1000
1000
1000
1000
3000

1.20
1.20
1.20
1.50
1.50
1.50
1.20
1.20
1.20
1.20
9.00

15
15
15
12
12
12
15
15
15
15
2

137
137
137
88
88
88
137
137
137
137
2

1
1
1
2

0.17
0.10
0.10
0.21

23.21
5.00
12.97
36.94

1
1

0.21
0.12

18.47
16.38

1
1
1

0.21
0.17

##

1
1-2
1-2
1-2
1-2
1-2
2-3
2-3
3-4
3-4
3-4
3-4
3-4
3-4
4-5
4-5
4-5
4-5
4-5
5-6
5-6
5-6
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
7-8
8-9
8-9
8-9
8-9
8-9
8-9

28.67
23.21
50.00

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

11

1.45

16.10

0.71

1.75

2.53

2.34

14

2.97

41.21

0.40

1.85

2.01

9.30

0.83

2.56

1.53

14.15

1.95

7.82

13

0.40

5.18

15

1.83

28.21

22

1.06

23.12

10

1.82

18.42

Sum
Safety
Total
Design External
Static Pressure

600

Pa

Remark
*
##

Fitting Coefficient is referred to CIBSE Guide C (2007)


Duct Pressure Loss is referred to the "Pressure Loss Chart'' for Internal Duct Liner from Manufacturer Owens Corning
Reference from the external louvre's static pressure chart as attached

Sub Total Cummulativ


Section e Section
Loss (Pa) Loss (Pa)
30.00
0.13
4.23
16.10
6.00
1.75
27.55
2.34
16.33
17.15
40.83
41.21
13.88
1.85
78.37
41.14
9.30
16.65
2.56
26.12
36.56
14.15
22.56
7.82
19.18
5.18
16.31
16.38
28.67
28.21
68.25
5.00
16.38
0.00
23.21
5.00
12.97
36.94
23.12
18.47
16.38
18.42
28.67
23.21
50.00
934.52
20%
1130

30.00
30.13
34.36
50.46
56.45
58.21
85.76
88.10
104.43
121.58
162.41
203.62
217.51
219.36
297.73
338.87
348.17
364.82
367.38
393.50
430.06
444.21
466.77
474.59
493.77
498.95
515.26
531.64
560.30
588.52
656.77
661.77
678.15
678.15
701.35
706.35
719.32
756.26
779.38
797.85
814.23
832.65
861.31
884.52
934.52

Pa

External Static Pressure Calculation (Revision 1)


SEF-B1-02(Smoke Exhaust Fan for Compartment D Carpark SES System)

20/4/2016

Remark

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Cross Sectional Area(m2)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

Fitting Coefficient

Duct Fitting Loss (Pa)

Exhaust Air Grille


90 Bend
Contraction
Linear Duct
Enlargement
Linear Duct
Branch
Linear Duct
Branch
90 Bend
VCD
Linear Duct
Enlargement
Linear Duct
Branch
Linear Duct
Enlargement
Linear Duct
Branch
45 Bend
Linear Duct
Branch
Linear Duct
Enlargement
Linear Duct
45 Bend
Contraction
90 Bend
Linear Duct
VCD
Flexible Connector
Contraction
Ventilation Fan
Enlargement
Flexible Connector
Enlargement
90 Bend
Riser
90 Bend
Contraction
Linear Duct
45 Bend
Enlargement
Smoke Extraction Louvre

2200
2200
2200
2200
2200
2200
4400
4400
4800
4800
4800
4800
4800
4800
11400
11400
11400
11400
15800
15800
15800
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000
18000

1500
1500
1000
1000
1000
1400
1400
1400
1400
1400
1400
1400
1400
1800
1800
1800
1800
2400
2400
2400
2400
2400
2400
2400
1500
1500
1200
1200
1200
1200
1200
1200

1500
1500
300
300
300
300
300
300
300
300
300
300
300
500
500
500
500
550
550
550
550
550
550
550
1500
1500
1000
1000
1000
1000
1000
1000

2.25
2.25
0.30
0.30
0.30
0.42
0.42
0.42
0.42
0.42
0.42
0.42
0.42
0.90
0.90
0.90
0.90
1.32
1.32
1.32
1.32
1.32
1.32
1.32
2.25
2.25
1.20
1.20
1.20
1.20
1.20
1.20

1
1
7
7
7
5
10
10
11
11
11
11
11
5
13
13
13
9
12
12
12
14
14
14
8
8
15
15
15
15
15
15

1
1
32
32
32
16
66
66
78
78
78
78
78
17
96
96
96
45
86
86
86
112
112
112
38
38
135
135
135
135
135
135

1
1
1

0.21
0.12

30.00
0.12
3.87

0.17

5.49

0.40

26.34

1
1
1

0.20
0.21
0.50

15.67
16.46
39.18

0.17

13.32

0.40

77.01

0.17

16.37

1
2

0.30
0.21

25.79
36.10

0.20

22.31

0.17

18.97

2
1
1

0.21
0.12
0.21

16.13
16.20
28.35

1
1
1

0.50

67.50
5.00
16.20

1200
1200
1200
1150
1150
1150
1200
1200
1200
1200
3000

1000
1000
1000
1300
1300
1300
1000
1000
1000
1000
3000

1.20
1.20
1.20
1.50
1.50
1.50
1.20
1.20
1.20
1.20
9.00

15
15
15
12
12
12
15
15
15
15
2

135
135
135
87
87
87
135
135
135
135
2

1
1
1
2

0.17
0.17
0.21

22.95
5.00
22.95
36.53

1
1

0.21
0.12

18.27
16.20

1
1
1

0.21
0.17

##

1
1-2
1-2
1-2
1-2
1-2
2-3
2-3
3-4
3-4
3-4
3-4
3-4
3-4
4-5
4-5
4-5
4-5
5-6
5-6
5-6
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
7-8
8-9
8-9
8-9
8-9
8-9
8-9

28.35
22.95
50.00

0.12

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

12

1.33

15.96

0.65

1.60

2.42

7.26

14

2.86

39.68

0.38

1.76

1.98

9.16

0.81

2.50

1.51

13.97

1.93

7.74

13

0.37

4.79

15

1.81

27.90

20

1.04

20.80

10

1.81

18.32

Sum
Safety
Total
Design External
Static Pressure

600

Pa

Remark
*
##

Fitting Coefficient is referred to CIBSE Guide C (2007)


Duct Pressure Loss is referred to the "Pressure Loss Chart'' for Internal Duct Liner from Manufacturer Owens Corning
Reference from the external louvre's static pressure chart as attached

Sub Total Cummulative


Section
Section
Loss (Pa)
Loss (Pa)
30.00
0.12
3.87
15.96
5.49
1.60
26.34
7.26
15.67
16.46
39.18
39.68
13.32
1.76
77.01
9.16
16.37
2.50
25.79
36.10
13.97
22.31
7.74
18.97
4.79
16.13
16.20
28.35
27.90
67.50
5.00
16.20
0.00
22.95
5.00
22.95
36.53
20.80
18.27
16.20
18.32
28.35
22.95
50.00
891.02
20%
1070

30.00
30.12
33.99
49.95
55.44
57.04
83.38
90.64
106.31
122.77
161.96
201.64
214.96
216.72
293.73
302.89
319.25
321.75
347.54
383.65
397.61
419.93
427.66
446.63
451.42
467.55
483.75
512.10
540.00
607.50
612.50
628.70
628.70
651.65
656.65
679.60
716.14
736.94
755.20
771.40
789.72
818.07
841.02
891.02

Pa

External Static Pressure Calculation (Revision 1)


SEF-B1-02(Smoke Exhaust Fan for Compartment D Carpark SES System)

20/4/2016

Remark

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Cross Sectional Area(m2)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

Fitting Coefficient

Duct Fitting Loss (Pa)

Exhaust Air Grille


90 Bend
Contraction
Linear Duct
Enlargement
Linear Duct
Branch
Linear Duct
Branch
90 Bend
VCD
Linear Duct
Enlargement
Linear Duct
Branch
Linear Duct
Enlargement
Linear Duct
Branch
45 Bend
Linear Duct
Branch
Linear Duct
Enlargement
Linear Duct
45 Bend
Contraction
90 Bend
Linear Duct
VCD
Flexible Connector
Contraction
Ventilation Fan
Enlargement
Flexible Connector
Enlargement
90 Bend
Riser
90 Bend
Contraction
Linear Duct
45 Bend
Enlargement
Smoke Extraction Louvre

2300
2300
2300
2300
2300
2300
4500
4500
4900
4900
4900
4900
4900
4900
11500
11500
11500
11500
15900
15900
15900
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100
18100

1500
1500
1000
1000
1000
1400
1400
1400
1400
1400
1400
1400
1400
1800
1800
1800
1800
2400
2400
2400
2400
2400
2400
2400
1500
1500
1200
1200
1200
1200
1200
1200

1500
1500
300
300
300
300
300
300
300
300
300
300
300
500
500
500
500
550
550
550
550
550
550
550
1500
1500
1000
1000
1000
1000
1000
1000

2.25
2.25
0.30
0.30
0.30
0.42
0.42
0.42
0.42
0.42
0.42
0.42
0.42
0.90
0.90
0.90
0.90
1.32
1.32
1.32
1.32
1.32
1.32
1.32
2.25
2.25
1.20
1.20
1.20
1.20
1.20
1.20

1
1
8
8
8
5
11
11
12
12
12
12
12
5
13
13
13
9
12
12
12
14
14
14
8
8
15
15
15
15
15
15

1
1
35
35
35
18
69
69
82
82
82
82
82
18
98
98
98
46
87
87
87
113
113
113
39
39
137
137
137
137
137
137

1
1
1

0.21
0.12

30.00
0.13
4.23

0.17

6.00

0.40

27.55

1
1
1

0.20
0.21
0.50

16.33
17.15
40.83

0.17

13.88

0.40

78.37

0.17

16.65

1
2

0.30
0.21

26.12
36.56

0.20

22.56

0.17

19.18

2
1
1

0.21
0.12
0.21

16.31
16.38
28.67

1
1
1

0.50

68.25
5.00
16.38

1200
1200
1200
1150
1150
1150
1200
1200
1200
1200
3000

1000
1000
1000
1300
1300
1300
1000
1000
1000
1000
3000

1.20
1.20
1.20
1.50
1.50
1.50
1.20
1.20
1.20
1.20
9.00

15
15
15
12
12
12
15
15
15
15
2

137
137
137
88
88
88
137
137
137
137
2

1
1
1
2

0.17
0.17
0.21

23.21
5.00
23.21
36.94

1
1

0.21
0.12

18.47
16.38

1
1
1

0.21
0.17

##

1
1-2
1-2
1-2
1-2
1-2
2-3
2-3
3-4
3-4
3-4
3-4
3-4
3-4
4-5
4-5
4-5
4-5
5-6
5-6
5-6
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
6-7
7-8
8-9
8-9
8-9
8-9
8-9
8-9

28.67
23.21
50.00

0.12

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

12

1.45

17.40

0.71

1.75

2.53

7.59

14

2.97

41.21

0.40

1.85

2.01

9.30

0.83

2.56

1.53

14.15

1.95

7.82

13

0.40

5.18

15

1.83

28.21

20

1.06

21.20

10

1.82

18.42

Sum
Safety
Total
Design External
Static Pressure

600

Pa

Remark
*
##

Fitting Coefficient is referred to CIBSE Guide C (2007)


Duct Pressure Loss is referred to the "Pressure Loss Chart'' for Internal Duct Liner from Manufacturer Owens Corning
Reference from the external louvre's static pressure chart as attached

Sub Total Cummulative


Section
Section
Loss (Pa)
Loss (Pa)
30.00
0.13
4.23
17.40
6.00
1.75
27.55
7.59
16.33
17.15
40.83
41.21
13.88
1.85
78.37
9.30
16.65
2.56
26.12
36.56
14.15
22.56
7.82
19.18
5.18
16.31
16.38
28.67
28.21
68.25
5.00
16.38
0.00
23.21
5.00
23.21
36.94
21.20
18.47
16.38
18.42
28.67
23.21
50.00
908.25
20%
1090

30.00
30.13
34.36
51.76
57.76
59.51
87.06
94.65
110.98
128.13
168.97
210.18
224.06
225.91
304.28
313.58
330.23
332.79
358.91
395.47
409.62
432.18
440.00
459.18
464.36
480.67
497.05
525.71
553.93
622.18
627.18
643.56
643.56
666.76
671.76
694.97
731.91
753.11
771.58
787.96
806.38
835.04
858.25
908.25

Pa

External Static Pressure Calculation


(Revision 1)
SMF-B1-01(Make Up Fan for Compartment D Carpark SES System)

20/4/2016

Remark

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Cross Sectional Area(m2)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

Fitting Coefficient

Duct Fitting Loss (Pa)

##

1
1-2
1-2
2-3
3-4
3-4
3-4
4-5
4-5
4-5
4-5
4-5
4-5
4-5
4-5
4-5
4-5
4-5
5-6
6-7
6-7
6-7
7-8
8-9
8-9
8-9
9-10
10-11
10-11
10-11
10-11
10-11

Fresh Air Louvre


Contraction
Tee
Riser
90 Bend
Enlargement
Linear Duct
Branch
VCD
Flexible Connector
Contraction
Ventilation Fan
Enlargement
Flexible Connector
Linear Duct
90 Bend
Transition
Linear Duct
Riser
90 Bend
Linear Duct
Transition
Riser
90 Bend
Linear Duct
90 Bend
Riser
Enlargement
90 Bend
Linear Duct
Contraction
Wire Mesh

14400
14400
14400
7200
7200
7200
7200
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400

2236
800
800
400
400
1200
1200
1200
1200
1200
1200

2236
1200
1200
1200
1200
800
800
800
800
800
800

5.00
0.96
0.96
0.48
0.48
0.96
0.96
0.96
0.96
0.96
0.96

3
15
15
15
15
8
8
15
15
15
15

5
135
135
135
135
34
34
135
135
135
135

1
1
1

0.12
0.33

50.00
16.20
44.55

1
1

0.21
0.17

28.35
5.74

1
1
1
1

0.40
0.50

54.00
67.50
5.00
16.20

1200
1200
1200
1200
1200
600
600
600
600
1700
1700
1700
1700
1700
1700
1700
5000
5000
5000
5000

800
800
800
800
800
1700
1700
1700
1700
600
600
600
600
600
600
600
700
700
625
625

0.96
0.96
0.96
0.96
0.96
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
3.50
3.50
3.13
3.13

15
15
15
15
15
14
14
14
14
14
14
14
14
14
14
14
4
4
5
5

135
135
135
135
135
120
120
120
120
120
120
120
120
120
120
120
10
10
13
13

1
1

0.17

22.95
5.00

2
1

0.21
0.06

56.70
7.83

0.12

0.21

75.34

0.06

6.94

0.21

25.11

0.21

25.11

1
1

0.17
0.21

20.33
2.13

1
1

0.12

1.53
5.00

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

3.76

7.52

0.57

2.04

2.11

9.44

5
4

2.08
2.08

10.54
7.87

19

2.08

40.32

2.08

7.87

2.08

6.20

2.08

8.91

0.14

0.14

Total
Safety
Final
Design External
Static Pressure

350

Pa

Remark
*
##

Fitting Coefficient is referred to CIBSE Guide C (2007)


Duct Pressure Loss is referred to the "Pressure Loss Chart'' for Internal Duct Liner from Manufacturer Owens Corning
Reference from the external louvre's static pressure chart as attached

Sub Total Cummulative


Section
Section
Loss (Pa)
Loss (Pa)
50.00
16.20
44.55
7.52
28.35
5.74
2.04
54.00
67.50
5.00
16.20
0.00
22.95
5.00
9.44
56.70
7.83
10.54
7.87
75.34
40.32
6.94
7.87
25.11
6.20
25.11
8.91
20.33
2.13
0.14
1.53
5.00
642.37
20.00%
780

50.00
66.20
110.75
118.27
146.62
152.36
154.40
208.40
325.05
280.90
297.10
297.10
320.05
325.05
334.49
391.19
399.02
409.56
417.43
492.77
533.09
540.03
547.90
573.01
579.21
604.33
613.24
633.57
635.70
635.84
637.37
642.37

Pa

External Static Pressure Calculation


(Revision 1)
SMF-B1-01(Make Up Fan for Compartment D Carpark SES System)

20/4/2016

Remark

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Cross Sectional Area(m2)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

Fitting Coefficient

Duct Fitting Loss (Pa)

##

1
1-2
1-2
2-3
3-4
3-4
3-4
4-5
4-5
4-5
4-5
4-5
4-5
4-5
4-5
4-5
4-5
4-5
5-6
6-7
6-7
6-7
7-8
8-9
8-9
8-9
9-10
10-11
10-11
10-11
10-11
10-11

Fresh Air Louvre


Contraction
Tee
Riser
90 Bend
Enlargement
Linear Duct
Branch
VCD
Flexible Connector
Contraction
Ventilation Fan
Enlargement
Flexible Connector
Linear Duct
90 Bend
Transition
Linear Duct
Riser
90 Bend
Linear Duct
Transition
Riser
90 Bend
Linear Duct
90 Bend
Riser
Enlargement
90 Bend
Linear Duct
Contraction
Wire Mesh

14500
14500
14500
7300
7300
7300
7300
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500

2236
800
800
400
400
1200
1200
1200
1200
1200
1200

2236
1200
1200
1200
1200
800
800
800
800
800
800

5.00
0.96
0.96
0.48
0.48
0.96
0.96
0.96
0.96
0.96
0.96

3
15
15
15
15
8
8
15
15
15
15

5
137
137
139
139
35
35
137
137
137
137

1
1
1

0.12
0.33

50.00
16.43
45.17

1
1

0.21
0.17

29.14
5.90

1
1
1
1

0.40
0.50

54.75
68.44
5.00
16.43

1200
1200
1200
1200
1200
600
600
600
600
1700
1700
1700
1700
1700
1700
1700
5000
5000
5000
5000

800
800
800
800
800
1700
1700
1700
1700
600
600
600
600
600
600
600
700
700
625
625

0.96
0.96
0.96
0.96
0.96
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
3.50
3.50
3.13
3.13

15
15
15
15
15
14
14
14
14
14
14
14
14
14
14
14
4
4
5
5

137
137
137
137
137
121
121
121
121
121
121
121
121
121
121
121
10
10
13
13

1
1

0.17

23.27
5.00

2
1

0.21
0.06

57.49
7.94

0.12

0.21

76.39

0.06

7.03

0.21

25.46

0.21

25.46

1
1

0.17
0.21

20.61
2.16

1
1

0.12

1.55
5.00

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

3.86

7.72

0.58

2.08

2.14

9.57

5
4

2.11
2.11

10.70
7.99

19

2.11

40.90

2.11

7.99

2.11

6.29

2.11

9.04

0.19

0.19

Total
Safety
Final
Design External
Static Pressure

350

Pa

Remark
*
##

Fitting Coefficient is referred to CIBSE Guide C (2007)


Duct Pressure Loss is referred to the "Pressure Loss Chart'' for Internal Duct Liner from Manufacturer Owens Corning
Reference from the external louvre's static pressure chart as attached

Sub Total Cummulative


Section
Section
Loss (Pa)
Loss (Pa)
50.00
16.43
45.17
7.72
29.14
5.90
2.08
54.75
68.44
5.00
16.43
0.00
23.27
5.00
9.57
57.49
7.94
10.70
7.99
76.39
40.90
7.03
7.99
25.46
6.29
25.46
9.04
20.61
2.16
0.19
1.55
5.00
651.09
20.00%
790

50.00
66.43
111.60
119.32
148.46
154.36
156.43
211.19
329.32
284.63
301.05
301.05
324.32
329.32
338.89
396.39
404.32
415.02
423.01
499.40
540.30
547.33
555.31
580.78
587.07
612.53
621.57
642.19
644.35
644.54
646.09
651.09

Pa

External Static Pressure Calculation (Revision 1)


SMF-B1-02(Make Up Fan for Compartment D Carpark SES System)
Remark

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Equ Diameter(mm)

Velocity (m/s)

Velocity Pressure (Pa)

##

1
1-2
1-2
1-2
2-3
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
4-5
5-6
5-6
5-6
5-6
5-6
6-7
7-8
7-8
7-8
7-8
7-8

Fresh Air Louvre


Contraction
Linear Duct
90 Bend
Riser
90 Bend
Transition
Linear Duct
VCD
Flexible Connector
Contraction
Ventilation Fan
Enlargement
Flexible Connector
Linear Duct
90 Bend
Riser
90 Bend
Linear Duct
Enlargement
Linear Duct
90 Bend
Riser
Transition
90 Bend
Linear Duct
Contraction
Wire Mesh

14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400
14400

2250
1200
1200
1200
1200
1200
800
800
800
800
800

2200
800
800
800
800
800
1200
1200
1200
1200
1200

4.95
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96

3
15
15
15
15
15
15
15
15
15
15

5
135
135
135
135
135
135
135
135
135
135

600
600
600
600
600
600
600
600
900
900
900
5000
5000
5000
5000
5000

1700
1700
1700
1700
1700
1700
1700
1700
1100
1100
1100
700
700
700
625
625

1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
0.99
0.99
0.99
3.50
3.50
3.50
3.13
3.13

14
14
14
14
14
14
14
14
15
15
15
4
4
4
5
5

120
120
120
120
120
120
120
120
127
127
127
10
10
10
13
13

Design External
Static Pressure

350

Pa

Remark
*
##

Fitting Coefficient is referred to CIBSE Guide C (2007)


Duct Pressure Loss is referred to the "Pressure Loss Chart'' for Internal Duct Liner from Manufacturer Owens Corning
Reference from the external louvre's static pressure chart as attached

20/4/2016
Fitting Qty.
1
1
1
1
1

Fitting Coefficient

Duct Fitting Loss (Pa)

0.12

50.00
16.20

0.21
0.21
0.06

1
1
1

0.50

1
1

0.17

2
1
1
1
1
1
1
1

0.12

0.21
0.21
0.17
0.21
0.17
0.21
0.12

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

2.11

6.29

10

2.11

21.75

2.11

1.26

2.08

12.41

2.08

7.87

10

2.08

20.86

1.92

3.65

1.92

15.49

0.14

0.14

28.35
28.35
7.83
67.50
5.00
16.20
20.33
5.00
50.23
25.11
20.33
26.66
1.73
2.13
1.53
5.00
Sum
Safety
Total

Sub Total Cummulative


Section
Section
Loss (Pa)
Loss (Pa)
50.00
16.20
6.29
28.35
21.75
28.35
7.83
1.26
67.50
5.00
16.20
0.00
20.33
5.00
12.41
50.23
7.87
25.11
20.86
20.33
3.65
26.66
15.49
1.73
2.13
0.14
1.53
5.00
467.20
20%
570

50.00
66.20
72.49
100.84
122.60
150.95
158.78
160.03
227.53
232.53
248.73
248.73
269.06
274.06
286.47
336.70
344.57
369.68
390.54
410.87
414.52
441.18
456.67
458.40
460.53
460.67
462.20
467.20

Pa

External Static Pressure Calculation (Revision 1)


SMF-B1-02(Make Up Fan for Compartment D Carpark SES System)
Remark

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Equ Diameter(mm)

Velocity (m/s)

Velocity Pressure (Pa)

##

1
1-2
1-2
1-2
2-3
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
4-5
5-6
5-6
5-6
5-6
5-6
6-7
7-8
7-8
7-8
7-8
7-8

Fresh Air Louvre


Contraction
Linear Duct
90 Bend
Riser
90 Bend
Transition
Linear Duct
VCD
Flexible Connector
Contraction
Ventilation Fan
Enlargement
Flexible Connector
Linear Duct
90 Bend
Riser
90 Bend
Linear Duct
Enlargement
Linear Duct
90 Bend
Riser
Transition
90 Bend
Linear Duct
Contraction
Wire Mesh

14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500
14500

2250
1200
1200
1200
1200
1200
800
800
800
800
800

2200
800
800
800
800
800
1200
1200
1200
1200
1200

4.95
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96

3
15
15
15
15
15
15
15
15
15
15

5
137
137
137
137
137
137
137
137
137
137

600
600
600
600
600
600
600
600
900
900
900
5000
5000
5000
5000
5000

1700
1700
1700
1700
1700
1700
1700
1700
1100
1100
1100
700
700
700
625
625

1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
0.99
0.99
0.99
3.50
3.50
3.50
3.13
3.13

14
14
14
14
14
14
14
14
15
15
15
4
4
4
5
5

121
121
121
121
121
121
121
121
129
129
129
10
10
10
13
13

Design External
Static Pressure

350

Pa

Remark
*
##

Fitting Coefficient is referred to CIBSE Guide C (2007)


Duct Pressure Loss is referred to the "Pressure Loss Chart'' for Internal Duct Liner from Manufacturer Owens Corning
Reference from the external louvre's static pressure chart as attached

20/4/2016
Fitting Qty.
1
1
1
1
1

Fitting Coefficient

Duct Fitting Loss (Pa)

0.12

50.00
16.43

0.21
0.21
0.06

1
1
1

0.50

1
1

0.17

2
1
1
1
1
1
1
1

0.12

0.21
0.21
0.17
0.21
0.17
0.21
0.12

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

2.14

6.38

10

2.14

22.06

2.14

1.28

2.11

12.58

2.11

7.99

10

2.11

21.16

1.94

3.69

1.94

15.66

0.19

0.19

28.75
28.75
7.94
68.44
5.00
16.43
20.61
5.00
50.93
25.46
20.61
27.03
1.75
2.16
1.55
5.00
Sum
Safety
Total

Sub Total Cummulative


Section
Section
Loss (Pa)
Loss (Pa)
50.00
16.43
6.38
28.75
22.06
28.75
7.94
1.28
68.44
5.00
16.43
0.00
20.61
5.00
12.58
50.93
7.99
25.46
21.16
20.61
3.69
27.03
15.66
1.75
2.16
0.19
1.55
5.00
472.82
20%
580

50.00
66.43
72.81
101.55
123.62
152.36
160.30
161.58
230.02
235.02
251.44
251.44
272.06
277.06
289.64
340.57
348.55
374.02
395.18
415.79
419.48
446.51
462.16
463.91
466.08
466.27
467.82
472.82

Pa

SMF-7F-01(Make Up Fan for Compartment S SES System)


EXHAUST
AIR

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Equ Diameter(mm)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

**Fitting Coefficient

Duct Fitting Loss (Pa)

1
1-2
1-2
2-3
2-3
2-3
2-3
2-3
2-3
3-4
3-4
3-4
3-4
4-5
5-6
5-6
5-6
5-6
5-6
5-6
5-6
5-6
5-6
5-6
5-6

MAD Opening
Wire Mesh
Riser
90 Bend
Enlargement
Linear Duct
45 Bend
Enlargement
Linear Duct
Branch
Linear Duct
Silencer
90 Bend
Riser
90 Bend
Enlargement
Linear Duct
45 Bend
Tee
VCD
90 Bend
Ventilation Fan
Wire Mesh
Enlargement
MAD Opening

17000
17000
17000
17000
17000
17000
17000
17000
17000
34000
34000
34000
34000
34000
34000
34000
34000
34000
34000
34000
34000
34000
34000
34000
34000

1100
1100
1100
1100
1100
2000
2000
2000
1000
1000
1000
1000
1000
1000
1000
1000
2100
2100
2100
2100
2100
2100
2100
2100
2450

1100
1100
1100
1100
1100
1000
1000
1000
4000
4000
4000
4000
4000
4000
4000
4000
2000
2000
2000
2000
2000
2000
2000
2000
2450

1202.48
1202.48
1202.48
1202.48
1202.48
1523.37
1523.37
1523.37
2067.70
2067.70
2067.70
2067.70
2067.70
2067.70
2067.70
2067.70
2240.16
2240.16
2240.16
2240.16
2240.16
2240.16
2240.16
2240.16
2678.26

14.98
14.98
14.98
14.98
14.98
9.33
9.33
9.33
5.07
10.13
10.13
10.13
10.13
10.13
10.13
10.13
8.63
8.63
8.63
8.63
8.63
8.63
8.63
8.63
6.04

134.58
134.58
134.58
134.58
134.58
52.25
52.25
52.25
15.39
61.58
61.58
61.58
61.58
61.58
61.58
61.58
44.69
44.69
44.69
44.69
44.69
44.69
44.69
44.69
21.88

1
1

0.50

30.00
67.29

1
1

0.67
0.13

90.17
17.50

2
1

0.67
0.17

70.01
8.88

0.60

36.95

1
1

0.67

70.00
41.26

1
1

0.67
0.06

41.26
3.57

1
1
1
1

0.67
1.41
0.50
0.67

29.95
63.02
22.35
29.95

1
1
1

0.50
0.10

22.35
4.25
30.00

Design Pressure
Remark
*
**
#
##

700.00

Pa

Pressure loss in Ventilation Fan are included in the internal pressure loss
Reference from CIBSE Guide C (2007)
The section of duct size has revised, due to high linear duct static pressure loss (i.e. Pa/m > 1)
Reference from the external louvre's static pressure chart as attached (but min. 50 Pa should be assumed for safe)

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

1.58

14.38

29

0.48

14.10

0.10

0.15

13

0.39

5.15

0.39

1.37

22

0.26

5.79

Total
Safety
Final
SAY

Total
Section
Loss (Pa)
30.00
67.29
14.38
90.17
17.50
14.10
70.01
8.88
0.15
36.95
5.15
70.00
41.26
1.37
41.26
3.57
5.79
29.95
63.02
22.35
29.95
0.00
22.35
4.25
30.00
719.68
20.00%
863.62
900.00

Pa

SEF-7F-08 (Smoke Extraction Fan for Compartment S SES System)


EXHAUST
AIR

##

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Equ Diameter(mm)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

**Fitting Coefficient

Duct Fitting Loss (Pa)

1
1-2
1-2
1-2
1-2
2-3
2-3
3-4
3-4
4-5
4-5
5-6
5-6
6-7
6-7
6-7
7-8
7-8
8-9
8-9
9-10
9-10
9-10
10-11
10-11
11-12
11-12
11-12
12-13
12-13
13-14
13-14
13-14
13-14
13-14
14-15
14-15
15-16
15-16
15-16
15-16
15-16
15-16
15-16
15-16
15-16
15-16

Smoke Extraction Grille


VCD
90 Bend
Linear Duct
45 Bend
Tee
Linear Duct
Branch
Linear Duct
Branch
Linear Duct
Branch
Linear Duct
Branch
Enlargement
Linear Duct
Branch
Linear Duct
Branch
Linear Duct
Branch
Linear Duct
Enlargement
Tee
Linear Duct
Branch
Linear Duct
Enlargement
Branch
Linear Duct
Branch
Linear Duct
90 Bend
Enlargement
Motorized Fire and Smoke Damper
Tee
Riser
Branch
Motorized Fire and Smoke Damper
Linear Duct
90 Bend
Ventilation Fan
90 Bend
Enlargement
90 Bend
Linear Duct
External Smoke Exhaust Louvre

220
220
220
220
220
580
580
670
670
760
760
850
850
940
940
940
1030
1030
1120
1120
1210
1210
1210
1500
1500
3040
3040
3040
3790
3790
4240
4240
4240
4240
4240
5900
5900
6200
6200
6200
6200
6200
6200
6200
6200
6200
6200

200
200
200
200
200
400
400
400
400
400
400
400
400
400
400
600
600
600
600
600
600
600
600
600
600
600
600
600
800
800
800
800
800
800
800
800
800
1200
1200
1200
1200

200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
400
400
400
400
400
400
400
400
400
400
400
1200
1200
1200
800
800
800
800

218.63
218.63
218.63
218.63
218.63
304.67
304.67
304.67
304.67
304.67
304.67
304.67
304.67
304.67
304.67
365.31
365.31
365.31
365.31
365.31
365.31
365.31
365.31
532.81
532.81
532.81
532.81
532.81
609.35
609.35
609.35
609.35
609.35
609.35
1065.63
1065.63
1065.63
1065.63
1065.63
1065.63
1065.63

5.86
5.86
5.86
5.86
5.86
7.96
7.96
9.19
9.19
10.43
10.43
11.66
11.66
12.90
12.90
8.97
9.83
9.83
10.69
10.69
11.55
11.55
11.55
6.73
6.73
13.64
13.64
13.64
13.00
13.00
14.55
14.55
14.55
14.55
4.76
6.62
6.62
6.96
6.96
6.96
6.96

20.62
20.62
20.62
20.62
20.62
38.01
38.01
50.72
50.72
65.27
65.27
81.64
81.64
99.84
99.84
48.31
58.00
58.00
68.58
68.58
80.05
80.05
80.05
27.18
27.18
111.65
111.65
111.65
101.44
101.44
126.96
126.96
126.96
126.96
13.57
26.28
26.28
29.03
29.03
29.03
29.03

1
1
1

0.50
0.67

30.00
10.31
13.82

3
1

0.67
0.25

41.46
9.50

0.35

17.75

0.35

22.84

0.35

28.57

1
1

0.30
0.10

29.95
9.49

0.30

17.40

0.30

20.57

0.30

24.01

1
1

0.20
2.73

16.01
74.21

0.60

133.98

1
1

0.10
1.10

10.61
111.59

0.35

44.44

1
1
1
1

0.67
0.38
0.50
0.60

85.07
48.25
6.79
15.77

1
1

1.52
0.50

44.12
14.51

0.67

19.45

1200
1200
1730
1730
1730

800
800
1730
1730
1730

1065.63
1065.63
1891.18
1891.18
1891.18

6.96
6.96
2.21
2.21
2.21

29.03
29.03
2.93
2.93
2.93

1
1
1

0.67
0.43
0.67

19.45
12.48
1.96

Design Pressure
Remark
*
**
#
##

350.00

Pa

Pressure loss in Ventilation Fan are included in the internal pressure loss
Reference from CIBSE Guide C (2007)
The section of duct size has revised, due to high linear duct static pressure loss (i.e. Pa/m > 1)
Reference from the external louvre's static pressure chart as attached (but min. 50 Pa should be assumed for safe)

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

12

2.13

25.69

2.53

4.36

3.33

5.74

4.24

7.31

5.24

9.03

2.55

4.39

3.03

5.22

3.56

6.13

4.12

9.46

0.93

2.67

3.57

8.20

2.76

1.59

3.42

15.71

0.39

3.55

24

0.43

10.46

0.02

0.03

50.00
Total
Safety
Final
SAY

Total
Section
Loss (Pa)
30.00
10.31
13.82
25.69
41.46
9.50
4.36
17.75
5.74
22.84
7.31
28.57
9.03
29.95
9.49
4.39
17.40
5.22
20.57
6.13
24.01
9.46
16.01
74.21
2.67
133.98
8.20
10.61
111.59
1.59
44.44
15.71
85.07
48.25
6.79
15.77
3.55
44.12
14.51
10.46
19.45
0.00
19.45
12.48
1.96
0.03
50.00
1103.90
20.00%
1324.68
1400.00

Pa

SEF-7F-07 (Smoke Extraction Fan for Compartment S SES System)


EXHAUST
AIR

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Equ Diameter(mm)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

**Fitting Coefficient

Duct Fitting Loss (Pa)

1
1-2
1-2
1-2
1-2
2-3
2-3
2-3
2-3
3-4
3-4
3-4
4-5
4-5
4-5
5-6
5-6
5-6
5-6
6-7
6-7
6-7
7-8
8-9
8-9
8-9
9-10
9-10
9-10
9-10
10-11
11-12
11-12
12-13
12-13
12-13
12-13
12-13
12-13
13-14
13-14
14

Smoke Extraction Grille


VCD
Contraction
Linear Duct
90 Bend
Branch
Enlargement
45 Bend
Linear Duct
Branch
Linear Duct
Enlargement
Branch
Linear Duct
Enlargement
90 Bend
Branch
Linear Duct
90 Bend
Branch
Enlargement
90 Bend
Riser
90 Bend
Branch
Linear Duct
Branch
Linear Duct
Motorized Fire and Smoke Damper
Contraction
Riser
90 Bend
Linear Duct
Branch
45 Bend
Linear Duct
Ventilation Fan
90 Bend
Enlargement
Riser
Wire Mesh
Smoke Extraction Opening

113
113
113
113
113
226
226
226
226
452
452
452
904
904
904
904
1130
1130
1130
1270
1270
1270
1270
1270
1570
1570
2010
2010
2010
2010
2010
2010
2010
3250
3250
3250
3250
3250
3250
3250
3250
3250

150
150
150
150
150
150
150
200
200
200
200
200
400
400
400
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
500
500
500
500
500
500

300
300
200
200
200
200
200
300
300
300
300
300
300
300
300
300
300
300
300
300
300
800
800
800
800
800
800
800
800
800
500
500
500
500
500
500

228.51
228.51
188.85
188.85
188.85
188.85
188.85
266.41
266.41
266.41
266.41
266.41
377.71
377.71
377.71
457.01
457.01
457.01
457.01
457.01
457.01
755.42
755.42
755.42
755.42
755.42
755.42
755.42
755.42
755.42
546.58
546.58
546.58
546.58
546.58
546.58

2.76
2.76
4.04
4.04
4.04
8.07
8.07
4.06
4.06
8.11
8.11
8.11
8.07
8.07
8.07
5.51
6.89
6.89
6.89
7.75
7.75
2.84
2.84
2.84
3.50
3.50
4.49
4.49
4.49
4.49
8.57
8.57
8.57
13.86
13.86
13.86

4.56
4.56
9.77
9.77
9.77
39.09
39.09
9.87
9.87
39.49
39.49
39.49
39.09
39.09
39.09
18.24
28.50
28.50
28.50
36.00
36.00
4.82
4.82
4.82
7.37
7.37
12.08
12.08
12.08
12.08
44.07
44.07
44.07
115.23
115.23
115.23

1
1
1

0.50
0.12

30.00
2.28
1.17

1
1
1
1

0.67
0.60
0.20
0.67

6.55
23.46
7.82
6.61

0.60

23.70

1
1

0.20
0.60

7.90
23.46

1
1
1

0.13
0.67
0.35

5.08
12.22
9.98

1
1
1
1

0.67
0.30
0.38
0.67

19.10
10.80
13.68
3.23

1
1

0.67
0.35

3.23
2.58

0.35

4.23

1
1

0.50
0.12

6.04
1.45

0.67

88.59

1
2

0.53
0.50

61.07
115.23

500
500
800
800
800

500
500
1000
1000
1000

546.58
546.58
976.24
976.24
976.24

13.86
13.86
4.34
4.34
4.34

115.23
115.23
11.32
11.32
11.32

2
1

0.67
0.40

154.40
46.09

1
1

0.50

5.66
30.00

Design Pressure
Remark
*
**
#
##

350.00

Pa

Pressure loss in Ventilation Fan are included in the internal pressure loss
Reference from CIBSE Guide C (2007)
The section of duct size has revised, due to high linear duct static pressure loss (i.e. Pa/m > 1)
Reference from the external louvre's static pressure chart as attached (but min. 50 Pa should be assumed for safe)

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

1.25

5.99

0.83

1.02

3.10

4.24

2.00

5.47

1.18

5.65

0.12

0.64

0.18

0.44

0.28

0.48

1.43

5.36

14

1.43

20.55

12

3.56

43.84

0.19

0.67

Total
Safety
Final
SAY

Total
Section
Loss (Pa)
30.00
2.28
1.17
5.99
6.55
23.46
7.82
6.61
1.02
23.70
4.24
7.90
23.46
5.47
5.08
12.22
9.98
5.65
19.10
10.80
13.68
3.23
0.64
3.23
2.58
0.44
4.23
0.48
6.04
1.45
5.36
88.59
20.55
61.07
115.23
43.84
0.00
154.40
46.09
0.67
5.66
30.00
819.96
20.00%
983.96
1000.00

Pa

SEF-7F-11, SEF-7F-12 (Smoke Extraction Fan for Compartment S SES System)


EXHAUST
AIR

##

Duct Section

Duct Element

Air Flow Rate (l/s)

Width (mm)

Height (mm)

Equ Diameter(mm)

Velocity (m/s)

Velocity Pressure (Pa)

Fitting Qty.

**Fitting Coefficient

Duct Fitting Loss (Pa)

1
1-2
1-2
1-2
1-2
1-2
2-3
2-3
3-4
3-4
4-5
4-5
5-6
5-6
5-6
6-7
6-7
6-7
6-7
6-7
6-7
7-8
8-9
8-9
8-9
8-9
8-9
8-9
8-9
8-9
9-10
9-10
9-10
9-10
9-10
10-11
10-11
10-11

Smoke Extraction Opening


Wire Mesh
Linear Duct
Enlargement
90 Bend
Linear Duct
Branch
Linear Duct
Branch
Linear Duct
Branch
Linear Duct
Branch
Linear Duct
Silencer
Branch
Silencer
Linear Duct
90 Bend
Transition
90 Bend
Riser
90 Bend
45 Bend
Linear Duct
Tee
Motorized Fire and Smoke Damper
Contraction
Linear Duct
Branch
Contraction
Linear Duct
Ventilation Fan
90 Bend
Enlargement
Tee
Linear Duct
External Smoke Extraction Louvre

8580
8580
8580
8580
8580
8580
17160
17160
25740
25740
34320
34320
42900
42900
42900
56000
56000
56000
56000
56000
56000
56000
56000
56000
56000
56000
56000
56000
56000
56000
28000
28000
28000
28000
28000
56000
56000
56000

1350
1350
1350
1350
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
3100
3100
3100
3100
3100
3100
3100
3100
2400
2400
2400
1500
1500
1500
1500
1500
4400
4400
4400

1350
1350
1350
1350
3100
3100
3100
3100
3100
3100
3100
3100
3100
3100
3100
3100
3100
3100
3100
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
1500
1500
1500
1500
1500
4400
4400
4400

1475.77
1475.77
1475.77
1475.77
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2705.80
2392.52
2392.52
2392.52
1639.75
1639.75
1639.75
1639.75
1639.75
4809.93
4809.93
4809.93

5.02
5.02
5.02
5.02
1.49
1.49
2.99
2.99
4.48
4.48
5.97
5.97
7.46
7.46
7.46
9.74
9.74
9.74
9.74
9.74
9.74
9.74
9.74
9.74
9.74
9.74
9.74
12.46
12.46
12.46
13.27
13.27
13.27
13.27
13.27
3.08
3.08
3.08

15.11
15.11
15.11
15.11
1.34
1.34
5.35
5.35
12.04
12.04
21.40
21.40
33.43
33.43
33.43
56.96
56.96
56.96
56.96
56.96
56.96
56.96
56.96
56.96
56.96
56.96
56.96
93.19
93.19
93.19
105.59
105.59
105.59
105.59
105.59
5.70
5.70
5.70

1
1

0.50

30.00
7.56

1
1

0.55
0.67

8.31
0.90

0.60

3.21

0.53

6.38

0.44

9.41

0.35

11.70

1
1
1

0.30

70.00
17.09
70.00

1
1
1

0.67
0.06
0.67

38.17
3.30
38.17

1
1

0.67
0.67

38.17
38.17

1
1
1

1.41
0.50
0.12

80.32
28.48
11.18

1
1

0.84
0.12

78.28
12.67

Design Pressure
Remark
*
**
#
##

NA

Pa

Pressure loss in Ventilation Fan are included in the internal pressure loss
Reference from CIBSE Guide C (2007)
The section of duct size has revised, due to high linear duct static pressure loss (i.e. Pa/m > 1)
Reference from the external louvre's static pressure chart as attached (but min. 50 Pa should be assumed for safe)

2
1
1
1

0.67
1.23
0.63

Duct Length (m)

Duct Pressure Loss


(Pa/m)

Duct Friction
Loss (Pa)

0.15

0.60

0.01

0.08

0.03

0.12

0.06

0.46

0.10

0.38

0.16

1.23

40

0.26

10.48

0.26

0.94

18

0.26

4.74

0.48

0.94

20

0.86

16.81

0.01

0.02

141.49
129.87
3.59
50.00
Total
Safety
Final
SAY

Total Section
Loss (Pa)
30.00
7.56
0.60
8.31
0.90
0.08
3.21
0.12
6.38
0.46
9.41
0.38
11.70
1.23
70.00
17.09
70.00
10.48
38.17
3.30
38.17
0.94
38.17
38.17
4.74
80.32
28.48
11.18
0.94
78.28
12.67
16.81
0.00
141.49
129.87
3.59
0.02
50.00
963.22
20.00%
1155.86
1200.00

Pa