SCHEDULE 2 - SUBMITTALS
PRODUCT DATA SHEET 0 - Product Data: For each type of product indicated, include rated
capacities, operating characteristics, furnished specialties, electrical characteristics, and
accessories.
PRODUCT DATA SHEET 1 - Shop Drawings: For packaged terminal air conditioners. Include plans,
elevations, sections, details for wall penetrations, and attachments to other work.
1.1
1.2
PRODUCT DATA SHEET 2 - Color Samples: For unit cabinet, discharge grille, and exterior louver,
and for each color and texture specified.
PRODUCT DATA SHEET 3 - Product Test Reports: Based on evaluation of comprehensive tests
performed by manufacturer and witnessed by a qualified testing agency, for packaged terminal
air conditioners.
PRODUCT DATA SHEET 4 - Field quality-control reports.
PRODUCT DATA SHEET 5 - Warranty: Sample of special warranty.
Kilmer Homes II
K&A #12112
Compliance:
Applicable
requirements
in
SCHEDULE 5 - COORDINATION
PRODUCT DATA SHEET 0 - Coordinate layout and installation of packaged terminal heat pumps and
wall construction with other construction that penetrates walls or is supported by them.
SCHEDULE 6 - WARRANTY
PRODUCT DATA SHEET 0 - Special Warranty: Manufacturer's standard form in which manufacturer
agrees to repair or replace components of packaged terminal air conditioners that fail in
materials or workmanship within specified warranty period.
0.1
0.2
Warranty Period for Sealed Refrigeration System: Manufacturer's standard, but not less
than five years from date of Substantial Completion, including components and labor.
Warranty Period for Nonsealed System Parts: Manufacturer's standard, but not less than
one year from date of Substantial Completion, including only components and excluding
labor.
PART 2 - PRODUCTS
SCHEDULE 0 - MANUFACTURERS
PRODUCT DATA SHEET 0 - Basis-of-Design Product: Subject to compliance with requirements,
provide product indicated on Contract Drawings or comparable product by one of the following:
0.1
0.2
0.3
Kilmer Homes II
K&A #12112
2.2
2.3
Each unit shall have a matching, easily removable,textured finish, wrap-around room
cabinet molded of high-temperature styrene to resist corrosion and damage. The room
cabinet shall have slide-out washable filters accessible without requiring removal of
room cabinet from chassis.
A hermetically sealed R-410A refrigerant system with external vibration isolated
rotary-type compressor, condenser and evaporator coils and capillary refrigerant
control. Airflow system consisting of one permanently lubricated two-speed fan motor
for the outdoor fan and a separate permanently lubricated two-speed fan motor for
the indoor fan. Outdoor fan shall be multi-blade axial-flow design made of noncorrosive material. Indoor fan shall be of a design to optimize airflow and operating
sound. All motors on the exterior side of the weather barrier shall be of an enclosed
design to reduce the effects of moisture and corrosion.
Line-cord connected units shall be provided with a line-cord power connection kit with
integral Leakage Current Detection and Interruption device or Arc Fault Current
Interrupter as required by National Electrical Code (NEC) and Underwriters
Laboratories. The unit shall have a universal resistance heater with output determined
by connection to the power source with the appropriate power connection kit to
provide specified heat output.
2.4 A fan-cycle option to permit continuous fan operation or fan cycle operation,
independently selectable for heating and cooling operation.
2.5 Fan-only operation in either high or low fan speed selectable by room occupant.
2.6 A positive cooling condensate disposal system which meets the test requirements of
applicable AHRI Standard 380 for Packaged Terminal Heat Pumps.
2.7 Condenser and evaporator coils shall be constructed of copper tubing and aluminum
plate fins designed to achieve EER and COP rating of the unit.
2.8 Indoor and outdoor airflows shall match the capacity of the coils for efficient heat
transfer. Water blow-off shall not occur on the indoor coil.
2.9 Adjustable indoor discharge air louvers that provide a 50 off vertical air pattern with
an alternate position to provide a 40 off vertical air pattern.
2.10 Easily accessible controls for selection of unit operation and thermostat setting.
Controls shall be covered by a hinged door.
Kilmer Homes II
K&A #12112
2.11 Positive-closing, manually controlled, three-position fresh-air vent with closed setting.
Vent door is to be secured for shipping.
2.12 Solid-state thermostat control to sense room temperature.
2.13 Electronic temperature limiting with seven independent heating and cooling settings to
limit maximum and minimum temperatures without restricting movement of
thermostat control knob.
2.14 Freeze Sentinel to automatically activate the electric resistance heater and fan motor
to warm and circulate indoor air to help prevent damage due to freezing temperatures.
Freeze Sentinel shall operate as long as unit is connected to powered electrical circuit
and unit shall provide ability for owner to defeat the Freeze Sentinel operation.
2.15 Heat Sentinel shall automatically activate air conditioner operation when the unit is in
the STOP setting when the room temperature warms to 85F and turns air conditioner
operation off when the room temperature cools to 80F, if selected by owner.
2.16 Remote programmable Thermostat compatibility with Class 2 remote thermostat
(Model RAK148PI).
PRODUCT DATA SHEET 3 - Unit shall have means of electrical connection listed by Underwriters
Laboratories and compatible with the units required voltage and ampacity in conformance
with National Electrical Code and local codes.
PRODUCT DATA SHEET 4 - Heat pump units shall provide operation that will either: A)
automatically phase in electric resistance heat, if outdoor temperature is below 46F, if heat
pump alone is unable to maintain room temperature; or B) use partial electric resistance
heat simultaneous with heat pump operation any time the outdoor temperature is below
46F. Selection of A or B operation shall be made by means of a selector concealed from
room occupant. In either A or B operation, the unit shall switch to full resistance heat if room
temperature continues to decline or the outdoor temperature falls below 25F. If the outdoor
temperature is above 46F, unit shall lock out electric resistance heat and operate on heat
pump only.
PRODUCT DATA SHEET 5 - Heat pump unit shall include Reverse Cycle Defrost that
automatically begins a defrost cycle when microprocessor determines criteria for defrosting
has been met. Defrosting shall be accomplished by systematically ceasing heat pump
operation, pausing to allow internal refrigerant pressures to equalize, then operating the
compressor with the flow of refrigerant reversed to allow the hot gas to flow through the
outdoor coil, melting the accumulated frost. The unit shall automatically resume heat pump
operation, after pausing to allow refrigerant pressures to equalize, at conclusion of defrost
cycle.
PRODUCT DATA SHEET 6 - In the event of compressor failure during heat pump operation, unit
shall automatically switch to electric resistance heat to maintain selected room temperature
regardless of outdoor temperatures.
PRODUCT DATA SHEET 7 - The unit shall have a switch concealed from room occupant to allow
heat pump operation to be overridden and heat provided by electric resistance heat
regardless of outdoor temperature.
PRODUCT DATA SHEET 8 - The unit shall have a factory-installed Internal Condensate Removal
(ICR) system to permit unit to automatically dispose of heat-pump-generated condensate
water with no overflow to outdoors during heating under outdoor ambient of 55f drybulb,
Kilmer Homes II
K&A #12112
90% relative humidity; indoor ambient 70f dry bulb, 52% relative humidity, for four hours
of continuous run time.
PRODUCT DATA SHEET 9 - The wall case shall be constructed of heavy-gauge, insulated, zinccoated phosphated steel with a protective baked-on enamel finish. Bottom critical points of
the steel wall case shall be coated with petroleum microcrystalline wax for added corrosion
protection and shall meet ASTM B-117, 1800-hour hot air aerated salt spray test. The chassis
shall be the slide-in type, ready to operate after installation.
Kilmer Homes II
K&A #12112
demonstrate to the owner or his representative the operation of units for both summer and
winter functions.
PRODUCT DATA SHEET 16 - The warranty shall be a full one-year parts and labor on the entire
unit, plus an additional full four years parts and labor for the sealed refrigerating system,
including service call for diagnosis and transportation to and from service shop (if
necessary) at no charge to the customer. The warranty shall also include a limited secondthroughfifth-year parts-only warranty for fan motors, switches, thermostat, heater, heater
protectors, compressor overload, solenoids, circuit boards, auxiliary controls, thermistors,
frost controls, ICR pump, capacitors, varistors and indoor blower bearing.
PRODUCT DATA SHEET 17 - Units shall be installed according to the manufacturer's
recommendations and the manufacturer shall not be responsible for unit failure as a result
of improper installation, or unit performance when installed with accessories not approved
by the manufacturer.
SCHEDULE 2 - CAPACITIES AND CHARACTERISTICS
PRODUCT DATA SHEET 0 - Refer to schedule on the Contract Drawings for performance
requirements.
SCHEDULE 3 - SOURCE QUALITY CONTROL
PRODUCT DATA SHEET 0 - Sound-Power Level Ratings: Factory test to comply with ARI 300,
"Sound Rating and Sound Transmission Loss of Packaged Terminal Equipment."
PRODUCT DATA SHEET 1 - Unit Performance Ratings:
Factory test to comply
ARI 310/380/CSA C744, "Packaged Terminal Air-Conditioners and Heat Pumps."
with
PART 3 - EXECUTION
SCHEDULE 0 - INSTALLATION
PRODUCT DATA SHEET 0 - Install units level and plumb, maintaining manufacturer's recommended
clearances and tolerances.
PRODUCT DATA SHEET 1 - Install wall sleeves in finished wall assembly; seal and weatherproof.
Joint-sealant materials and applications are specified in Division 7.
PRODUCT DATA SHEET 2 - Install and anchor wall sleeves to withstand, without damage to
equipment and structure, seismic forces required by building code.
SCHEDULE 1 - FIELD QUALITY CONTROL
PRODUCT DATA SHEET 0 - Tests and Inspections:
Kilmer Homes II
K&A #12112
0.1
0.2
0.3
0.4
Inspect for and remove shipping bolts, blocks, and tie-down straps.
After installing packaged terminal heat pumps and after electrical circuitry has been
energized, test for compliance with requirements.
Operational Test: After electrical circuitry has been energized, start units to confirm
proper motor rotation and unit operation.
Test and adjust controls and safeties. Replace damaged and malfunctioning controls and
equipment.
PRODUCT DATA SHEET 1 - Packaged terminal heat pumps will be considered defective if they do
not pass tests and inspections.
PRODUCT DATA SHEET 2 - Prepare test and inspection reports.
END OF SECTION