Beruflich Dokumente
Kultur Dokumente
Fellow, IEEE
Department of Electrical and Computer Engineering,
Dalhousie University Halifax, Nova Scotia, Canada
E-mail: ElHawary@dal.ca
I. INTRODUCTION
II. HARMONIC POWER FLOW FOR RADIAL DISTRIBUTION
SYSTEMS
128
(1)
(12)
(13)
is the magnitude of the ith branch current, R is
Where
the ith branch resistance and br is the number of branches in
RDS.
(2)
(3)
Now in the forward voltage sweep and apply Kirchhoffs
voltage law (KVL) to obtain the bus voltages and second
relationship matrix as follows:
(4)
(5)
Hence, by substituting (3) in (5),
current injections is expressed as follows:
in terms of bus
(6)
(7)
Where [DLF] = the relationship matrix between voltage
drops and bus current injections. Moreover, the following
equations are solved iteratively to get the power flow solution:
(8)
(9)
(14)
(10)
Where
by loads and
129
(15)
(23)
Where
is the harmonic voltage of bus i for
iteration k +1.
is the harmonic voltage of bus i for
iteration k. The total real power loss for hth harmonic is
defined by:
(16)
is the relationship matrix between bus
Where
current injection and branch current flows at hth harmonic.
Furthermore the forward voltage sweep and KVL is applied to
calculate harmonic bus voltages and is expressed in vector
form as follows:
(24)
(17)
(25)
is the
Where is the smallest harmonic order,
highest harmonic order,
is the magnitude of the ith
is the ith
branch current for the hth harmonic order and
branch resistance for the hth harmonic order. The root mean
) can be known from
square values of the bus voltages (
the harmonic bus voltages calculated for all harmonic
frequencies by utilizing the process described above:
(18)
is the row vectors of the matrix
Where
associated with the bus at which filter is placed. The
harmonic voltage of filter placed at bus i in terms of its
harmonic impedance is given as follows:
(26)
(19)
Where
(27)
(20)
Where
denote the harmonic current
vector of loads and
is the harmonic current absorbed by
the filter which can be found by following equation:
(21)
(22)
130
(29)
(30)
A. Step 1: Initialization
Generate a matrix for the total number of available filter
sizes as stages and the number of possible bus locations as
states and select a suitable value for control parameters (, ),
coefficient of pheromone evaporation (), the number of ants,
and
states and stages. Also generate initial pheromone
for all states.
is set to be the
heuristic information
reciprocal of filters to be placed so if a bigger filter size is
selected by an ant the heuristic information is less attractive.
This is done because larger size filters are more expensive.
(28)
Where
(33)
131
Where
is the contribution of ant which used
filter j and selected bus i to and resulted in best objective
function. It is calculated as:
(35)
(36)
is the best objective function achieved and
Where
is the maximum number of ants.
TABLE I.
Vrms (pu)
Bus
Before Placement
After Placement
0.979
0.981
0.975
0.977
0.973
0.975
0.966
0.970
0.961
0.967
0.958
0.966
0.965
0.969
0.972
0.974
10
0.969
0.971
11
0.961
0.965
12
0.960
0.964
0.960
0.964
13
Fig. 3. 13-bus radial distribution system
Ploss (KW)
Fundamental
49.36
35.06
Harmonics
12.63
8.85
Total
61.997
43.91
132
Line
no.
From
Bus
To
Bus
R()
X()
P
(kW)
Q
(kVAR)
0.117
0.048
100
30
0.107
0.044
20
730
0.165
0.046
150
225
0.150
0.042
50
10
0.150
0.042
120
540
0.314
0.054
40
700
0.210
0.036
75
90
0.314
0.054
50
150
10
0.210
0.036
125
825
10
11
0.131
0.023
210
800
11
11
12
0.105
0.018
80
300
12
11
13
0.157
0.027
95
30
REFERENCES
[1]
VI. CONCLUSION
This paper presents an application of the Ant Colony
System based algorithm for optimizing filter placement and
sizing on a radial distribution system in order to reduce power
losses and keep the root mean squared voltages and total
harmonic distortion (THD) to lie within prescribed limits. A
radial distribution power flow (RDPF) and harmonic power
flow (HPF) algorithms are employed which use backwardforward sweep techniques to produce power flow solution.
RDPF and HPF are performed to demonstrate the effect of
harmonic sources on total power loss. Then the Ant colony
algorithm is used in conjunction with both power flow
algorithms to select a filter size from a number of available
sizes and place it at the best possible location so that both
power loss and THD are minimized. A 13-bus radial
distribution test system is used to validate the results.
It takes 35 iterations for ACS algorithm to find the
best possible solution. By placing the harmonic filters the
effect of harmonics is suppressed. It resulted in a decrease in
total real power loss and improving voltage profile. Filters are
a cheaper solution and low voltage systems like the three test
systems can prove to be more economically efficient solution
than by using shunt capacitor as done in [6, 7, 8, 9 and 10].
Furthermore ACS has proven to be fast in convergence. Best
filter size chosen by ACS for the test systems is 600 Kvar and
the best locations found to place this filter is 7. The real power
loss is reduced by 29.17% of the power loss before placing the
133