Transmission lines constitute more than 60% of asset of power


transmission.
They traverse an incredible range of kilometer in harsh
environments, climates and terrains.

Transmissio
n lines

In India many of the Transmission lines currently in service


were built in the 1960s and 70s and are subject to many
problems including ageing.
With growing demands, there is huge expectations from
transmission companies to keep the transmission line uptime
near to 100%.
Hence accurate fault location, health check / monitoring the
same is very much essential.

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

Type of
common
faults in
overhead
Transmission
lines

All Types of Open & Short Category faults

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

Overhead
Transmission
line fault
locator &
Analyzer

Pre-Commissioning Check of EHV Lines Continuity,


Phase Sequence, line length verification.
Ascertaining line healthiness before re-Charging.
For Preventive & Predictive Maintenance of
existing EHV Lines.
Restore the EHV lines ASAP to maintain UP TIME.

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

Fault
Locator and
types of
fault locator

OVER HEADTRANSMISSIONLINE FAULT


LOCATOR (OHFL)
Online
Offline

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

OHFL
Basic
Principals of
working

ONLINE-Systems works on the principal of power


system Parameters & Data is taken during stressed
breakdown condition and this data is in percentage
accuracy depending on the residual impedance of
the line.
OFFLINE-Systems works on the principal of Multiple
pulse Eco Co-relation technique & doesn't require
any input parameters for accurate fault finding.

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

Online
method
some of its
limitations

Each Line require one dedicated


equipment.
It is not helpful for spur lines.
Open Circuit faults cant locate through
online systems.
Fault locating accuracy may vary in
percentage. (+/_ 10% or more)
Pre-Commissioning tests are not possible.

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

Advanced high frequency multiple pulse


co-relation technique

Offline
method

How it works:
- High frequency Coded pulse sent in to
the powerline
- picks up different types of disturbance
and location
- Information Decoded
- Generates User Friendly Report and gives
complete vision of the line end to end

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

Offline
methods
and its
advantages

It is accurate up to +/- 100Mtr.


One equipment is enough for whole sub station.
It can be used for Spur line fault locating.
Pre Commissioning tests are possible.
Offline system can identify the secondary faults
before re charging the line.
It can find out Open Circuit faults.
Does not require any complimentary system at other
end of the sub station.
It can Locate faults up to 2500KM.

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

Offline
OHFL
Diagnostic
outputs

Fault Locator(Breakdown): For finding the faults at


accurate distance.
Line Signature Analysis: for understanding the
healthiness of the line.

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

10

Overhead
transmission
line fault
locator
benefits

Apart from finding dead faults , useful for


predictive and preventive maintenancei) It can detect developing faults .
ii) It can detect nature of the fault(Open/Short)
iii) It can indicate severity of the fault (Level of the
Faults).

Less time to find faults and its location.


Healthiness check up for the entire line .

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

11

Case
Studies

Short circuit Fault


De-capping
All jumpers not through in Quad line
Leaky Insulators
Clearance related problems
High frequency effects on transmission lines

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

12

CASE STUDIES

SHORT CIRCUIT FAULT at 112 KM

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related problems
High frequency effects on
transmission lines

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

13

CASE
STUDIES

Decapping Fault at 69 Km in B Phase

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

Decapping
Fault

14

CASE
STUDIES

ALL JUMPERS NOT THROUGH AT 55 KM

Short circuit Fault


De-capping
All jumpers not through
in Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

15

CASE
STUDIES

Corona due to loose jumper

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

16

CASE
STUDIES

SIGNATURE AFTER THROUGH JUMPER

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

17

CASE
STUDIES

Flashover insulator at 5.8 and 5.3 KM

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

18

CASE
STUDIES

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

19

CASE
STUDIES

Trees very close to Transmission Line in B-phase

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

20

CASE
STUDIES

After Removal of trees

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

21

CASE
STUDIES
Line Signature Analyser could identify the stress of the line
caused by high frequency noise flowing on the surface of
insulators and flashover.

Line Signature Analyser printout with and without filters


reveal the presence of several kVs of high frequency noise
and really a cause for flash over of insulators

Short circuit Fault


De-capping
All jumpers not through in
The noise was later found due to parallel HVDC lines and
Quad line
thyristor switching action
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das
Tauruspowertronics Pvt. Ltd
prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

22

CASE
STUDIES

Annexure A without filter


Padghe BBLR gain 1 without filter-Lots of noise

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

23

CASE
STUDIES

Annexure B with HVDC filter


Padghe BBLR Gain1 No noise observed

Short circuit Fault


De-capping
All jumpers not through in
Quad line
Leaky Insulators
Clearance related
problems
High frequency effects on
transmission
lines
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

24

CASE
STUDIES

OFFLINE
OVERHEAD
LINE FAULT
LOCATOR

Case Studies of 25 lines taken in a Transmission ZONE during 2011-2012 . Statistics are based on the OnM internal
record maintained for 365 days
With
Ideally
Time
Without OHFL
No. Of
Time taken
Average
with
taken to
Tota
OHFL time time
Lines in
Total
to find
Line
No. of
OHFL OHFL
find
OHFL
l EXTRA
taken to taken to the Zone
Trippi
fault in
Lengths in
Tripping
time used
fault
not
time HOUR
rectify the rectify
(Total
ngs in
HRS
KMs
in a
would
at
with
used
take S
fault in a fault in a Sample 25
a Year
without
Year/Line
have
OHFL in
n
line (Hrs)
line
lines)
OHFL (Hrs)
taken
( Hrs)
(Hrs)
0 to 150
KMs

15

19

57

171
hrs

30
places

90
hrs

27
places

405
hrs

495 324
hrs hrs

150 to
250 Kms

19

32
hrs

5
Places

20
hrs

3
Places

95
hrs

115
hrs

83
hrs

250 to
350 Kms

23

16
hrs

1
places

4
hrs

1
place

23
hrs

27
hrs

11
hrs

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

25

Case
Studies

Case Studies of 73 new lines in a Utility Transmission company in India


No. of lines
No.of Lines signature successfully charged
test was done
after Signature
Analyzer

KV of the line

No.of Lines

No of Tripping
Without Line
Signature test

OFFLINE OHFL

132KV

Line
Signature

220KV

20

11

400KV

40

16

14

14

765KV

Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

26

Important
parameterswhile
choosing an
overheadtransmis
sion line fault

Equipment should be Portable & Battery operated.


Induction Voltage Suppression capability.
Auto Impedance matching facility for the kit to be
used in any EHV Lines.
Instrument should be EMI/EMC Compliance.

locator
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

27

PAPER
Presented by
POWERGRID IN CBIP
INTERNATIONAL
CONFERENCE

Using Offline Fault


Locator
TO DIAGNOSE THE
TRANSMISSION LINE
Prashant Das

Tauruspowertronics Pvt. Ltd

prashant.das@tauruspowertronics.com

www.tauruspowertronics.com

28

29