Automatic Transfer Switch, 72x72 DIN Size

ATS-10
Automatic Transfer Switch
72 x 72 DIN Size

Description
The ATS-10 provides the mains voltage monitoring and automatic transfer switching. In the event of a mains
voltage failure, the remote start relay output is energized and the unit automatically transfers the load from the
mains to the generator. Microprocessor technology allows exact measurement, set point adjustment and timing
functions with the parameters to be simply programmed and displayed from the front panel.
Operation
The ATS-10 automatic transfer switch can detect failure of any phase of the mains supply. If at least one of the
mains phase voltages goes outside set limits, the unit operates as follows:
- The Mains Voltage Okay led turns from green to red. The mains contactor output is deenergized and the
green Mains Contactor Closed led is extinguished.
- The remote start output is energised after the Remote Start Delay parameter has expired. The generator
start module receives this signal and initiates the engine start.
- If the Unit Usage Type parameter (P00) is selected as 0 (Type-1); When the generator voltage is within set
limits, the yellow Generator Running led will illuminate. The unit will allow the generating set to run without
load until the Engine Heating Period parameter is expired. After this time, the yellow Generator Contactor
Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter.
If the Unit Usage Type parameter (P00) is selected as 1 (Type-2); When the Engine running signal is
present, the yellow Generator Running led will illuminate. The unit will allow the generating set to run
without load until the Load gen. signal is present. If this signal is present, the yellow Generator Contactor
Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter.
- The generator contactor output will be energized and the yellow Generator Contactor Closed led will
illuminate steadily when the Generator Contactor Delay parameter is expired.
- If the mains voltage return to within limits, the Mains Voltage Okay led will turn to green and the unit waits
for the Mains Return delay parameter for the mains voltage stabilization.
- When the Mains Return Delay parameter is expired, the yellow Generator Contactor Closed led is
extinguished and the generator contactor output is deenergized. Then the green Mains Contactor Closed
led will start blinking and then the unit will wait for the Mains contactor Delay parameter.
- When the Mains contactor Delay parameter is expired, the green Mains Contactor Closed led will
illuminate steadily and the mains contactor output is energized. Then the remote start output is deenergized.
- The unit is ready for a new mains failure.
The ATS-10 has got a TEST mode feature. This mode allows the generating set to be tested without taking the
load. This mode is also called Emergency backup mode which keeps the generating set running and makes a
quick transfer if a mains failure occurs.
In this mode, The remote start output will be energized but no load transfer will take place unless the occurrence of
a mains failure. If a mains failure occurs, the load will be transferred to the generating set. If the mains voltage
return to within limits and the Mains Return Delay parameter is expired, the load will be transferred to the mains,
but the generating set will be kept running. The remote start output will only deenergized when the Test mode is
cancelled.

Introduction Brochure. ENG ATS-10 01 V01 08/13

Automatic Transfer Switch, 72x72 DIN Size


Specifications
Equipment Use
Housing & Mounting
Panel Cut-out
Protection
Weight
Environmental Rating
Operating / Storage Temperature
Operating / Storage Humidity
Installation Over Voltage Cat.
Pollution Degree
Mode of Operation
EMC

Electrical control equipment for generating sets


72mmx72mmx95mm (including connectors) DIN43700 plastic housing for panel mounting
69mmx69mm
NEMA4X (IP65 at front panel, IP20 at rear side)
Approximately 0.27 kg
Standard, indoor at an altitude of less then 2000 meters with non-condensing humidity
-25C to +70C / -40C to +85C
90% max. (Non-condensing)
II appliances, portable equipment
II, Normal office or workplace, non-conductive pollution
Continuous
EN-61000-6-4, EMC generic emission standard for industrial equipment
EN-61000-6-2, EMC generic immunity standard for industrial equipment
Electrical Safety
EN-61010-1, safety requirements for electrical equipment for measurement, control and
laboratory use
Battery Supply Voltage(Z)
8-32 VZ max. Operating current is 240 mA
Generator Voltage Measurement 35-300VL-NVRMS (@15.6-99.9 Hz). Accuracy: 1% FS. Resolution : 1V
35-300VL-NVRMS (@15.6-99.9 Hz). Accuracy: 1% FS. Resolution : 1V
Mains Voltage Measurement
Cranking Dropouts
Battery voltage can be 0VZ for max. 100msn during cranking (battery voltage should be
at least nominal voltage before cranking)
Contact Sensing Inputs
Load Generator Signal (NO)
Engine Running Signal (NO)
Relay Outputs
Remote Start Relay (1NO+1NC. 12A@32V Z)
Mains Contactor Relay (1NC. 5A@250V V)
Generator Contactor Relay (1NO. 5A@250V V)
4 Digits, 7 segments LED display showing :
Display
Mains Voltage (Phase-Phase and Phase-Neutral)
Alternator Voltage. (If the Unit Usage Type parameter (P00) is selected as 0 (Type-1))
Program Parameters
Status Indicators
TEST Mode LED
PROG Mode LED
Mains Volgage Okay LED
Generator Running LED
Mains Contactor Closed LED
Generator Contactor Closed LED

Automatic Transfer Switch, 72x72 DIN Size


Dimensions
Maximum 15mm / 0.590 inch
ATS-10

VL23

VL31

GEN V.

72mm

VL12

PROG

TEST

TEST
GEN-ATS

11.5mm / 0.452 inch

72mm

69mm / 2.72 inch

Panel Cut-Out

69mm / 2.72 inch

83.5 mm / 3.287 inch

Automatic Transfer Switch, 72x72 DIN Size


Front View

Terminal Connections

ATS-10

VL23

VL31

GEN V.

12 A @220VV

3
+ BAT OR
- BAT

2
+ BAT

- BAT

Type - 1 (P00 = 0): When Generator Voltage detected by ATS-10


Parameters List
Definition of Parameter

P00 Unit Usage Type


P01 Mains Voltage Connection Level
P02 Mains Voltage Disconnection Level
P03 Mains Voltage Upper Limit
P04 Mains Return Delay
P05 Generator Contactor Delay
P06 Mains Contactor Delay
P07 Remote Start Delay
P08 Engine Heating Period
P09 Alternator Voltage Lower Limit
P10 Alternator Voltage Upper Limit
P11 Password

Min

0
60
60
60
0
0.1
0.1
0
0
60
60
0

Max Default

1
600
600
600
9999
25.0
25.0
9999
250
600
600
9999

Unit

0
320
300
440
30
1.0
1.0
0
10
320
440
0

VV
VV
VV
sec
sec
sec
sec
sec
VV
VV

Type - 2 (P00 = 1): When Load Generator Logic Input detected by ATS-10
Parameters List
No

Definition of Parameter

Min

P00
P01
P02
P03
P04
P05
P06
P07
P11

Unit Usage Type


Mains Voltage Connection Level
Mains Voltage Disconnection Level
Mains Voltage Upper Limit
Mains Return Delay
Generator Contactor Delay
Mains Contactor Delay
Remote Start Delay
Password

0
60
60
60
0
0.1
0.1
0
0

Max Default

1
600
600
600
9999
25.0
25.0
9999
9999

Unit

1
320
300
440
30
1.0
1.0
0
0

VV
VV
VV
sec
sec
sec
sec

NC

ATS-10 Parameters List

No

MAINS
RELAY

P/N : ATS-10

19

10

11
LOAD GEN.
INPUT
+

NO

18

ENGINE RUN.
INPUT
+

TEST

TEST

17

GEN. L1

16

GEN. N

15

MAINS L3

MAINS L2

14

REMOTE
START OUT

PROG

13

MAINS N

12

MAINS L1

2X5A
@220VV

GEN. RELAY

VL12

Automatic Transfer Switch, 72x72 DIN Size


Three Phase Connection Schematic For Type - 1 (P00 = 0)
NOTE: If single phase sensing is required the single phase can be fed into
all three phase inputs.

15

12

14

GENERATOR CONTACTOR
N
L1
L2
L3
GENERATOR

FUSE-2

FUSE-4

FUSE-5

N
L1
L2
L3
MAINS

LOAD
L3 L2 L1 N

FUSE-3

MAINS CONTACTOR

19

18

13

GEN. RELAY
5A@250VV

MAINS RELAY
5A@250VV

MEASUREMENT
CIRCUIT

NO

16

17

MEASUREMENT
CIRCUIT

12A@220VV
NC

FUSE-1

-BAT

+BAT

11
NOT CONNECTED

REMOTE
START

BATTERY

+BAT
OR
-BAT

10
NOT CONNECTED

BATTERY NEGATIVE MUST BE GROUNDED

Three Phase Connection Schematic For Type - 2 (P00 = 1)


NOTE: If single phase sensing is required the single phase can be fed into
all three phase inputs.

15

12

14

GENERATOR CONTACTOR
N
L1
L2
L3
GENERATOR

FUSE-2

FUSE-4

FUSE-5

N
L1
L2
L3
MAINS

LOAD
L3 L2 L1 N

FUSE-3

MAINS CONTACTOR

19

18

13

NO

16

GEN. RELAY
5A@250VV

MAINS RELAY
5A@250VV

MEASUREMENT
CIRCUIT

NOT CONNECTED

17

12A@220VV
NC

BATTERY

11
LOAD GENERATOR INPUT

FUSE-1

REMOTE
START

+BAT
OR
-BAT

10

+BAT

+BAT

-BAT

ENGINE RUNNING INPUT


OPTIONAL: USING FOR
GEN. RUNNING LED

+BAT

BATTERY NEGATIVE MUST BE GROUNDED

The fuses should be as follows:


1A. T
FUSE-1
FUSE-2, FUSE-3 1A. T
FUSE-4, FUSE-5 1A. T

1- Connect the unit as shown in the appropriate diagram above. Be sure to connect the battery supply the right way round and
battery negative should be grounded. The connectors can be unplugged from the rear of the unit to facilitate connection.

Automatic Transfer Switch, 72x72 DIN Size


Easy Access Diagram to Programming Parameters

The Programming mode must be entered only while the mains voltage okay and the load supplied from mains.
It is your responsibility if this equipment is used in a manner not specified in this instruction manual.
Operation screen
F

PROG
TEST

PROG

PROG

TEST

TEST

Press
button for
accessing to the
password
entering screen

When the button is pressed


for 10 seconds, password is
asked for accessing to the
parameters.

Note: If Enter button is pressed


and the password parameter is
zero, pass screen is ignored
and p 00 screen is shown.

Press the increment button.


Operator password
F

PROG

PROG

TEST

Enter password with


increment and decrement
buttons.

PROG

TEST

TEST

Press the Enter button to


confirm the password. If its
correct, P00 is displayed. If
the password is incorrect, the
unit will drop out of program
mode.

Press the increment button to


access to the parameter value.

Press Enter button to confirm


the changed value and access
to the following parameter. On
this way you can access to the
all parameters.

PROG
TEST

Change the parameter value with


increment and decrement buttons.

Note: If the PROG button is pressed or if no buttons are pressed for a period of 2 minutes,
the unit will return to the normal operation screen.

Product Code
ATS-10

Automatic Transfer Switch, 72mmx72mmx95mm Size

Automatic Transfer Switch, 72x72 DIN Size


Other Informations
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A..
Demirta Organize Sanayi Blgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Repair and Maintenance Service Information:
Emko Elektronik Sanayi ve Ticaret A..
Demirta Organize Sanayi Blgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912

Your Technology Partner

Thank you very much for your preference to use Emko Elektronik
products, please visit our web page to download detailed user
manual.
www.emkoelektronik.com.tr
7

Das könnte Ihnen auch gefallen