Sie sind auf Seite 1von 7

Data sheet

Customer item no.:Boiler Feed CI


Communication dated: 19/06/2015
Doc. no.: Hoddeson - Cooling System Pumps
Quantity: 1

Number: 4002472206
Item no.: 800
Date: 16/02/2016
Page: 1 / 7
Version no.: 19

Multitec D 50/ 15-4.1 20.81

Operating data
Requested flow rate
32.80 m/h
Operating data determined for maximum inlet pressure
Requested developed head
587.58 m
Pumped medium
Water, boiler feed water
Mode of operation AF
Not containing chemical and
mechanical substances which
affect the materials
Solids content max. 50 ppm
Ambient air temperature
20.0 C
Fluid temperature
Fluid density
Fluid viscosity
Suction pressure max.
Suction pressure min.
NPSH available
Vapour pressure
Mass flow rate
Max. power on curve
Minimum flow for stable curve
Minimum allowable flow for
continous operation

104.8 C
954 kg/m
0.29 mm/s
1.20 bar.g
1.20 bar.g
10.76 m
1.19 bar.a
8.70 kg/s
93.23 kW
23.86 m/h
8.38 m/h

Actual flow rate


Actual developed head
Efficiency
Power absorbed
Pump speed of rotation
NPSH required
Permissible operating
pressure
Discharge press.

32.80 m/h
587.64 m
68.3 %
73.24 kW
2979 rpm
2.14 m
63.00 bar.g

Shutoff pressure
Min. allow. flow for short term
operation
Min. mass flow for stable
curve
Min. allow. mass flow for
continuous operation
Min. allow. mass flow short
term operation
Shutoff head
Max. allow. flow rate
Max. allow. mass flow
Design
Performance test

61.91 bar.g
8.38 m/h

56.21 bar.g

6.33 kg/s
2.22 kg/s
2.22 kg/s
648.60 m
50.31 m/h
13.34 kg/s
Single system 1 x 100 %
Yes

Data sheet

Customer item no.:Boiler Feed CI


Communication dated: 19/06/2015
Doc. no.: Hoddeson - Cooling System Pumps
Quantity: 1

Number: 4002472206
Item no.: 800
Date: 16/02/2016
Page: 2 / 7
Version no.: 19

Multitec D 50/ 15-4.1 20.81

Design
Variant
Stage number
Balance drum
Design
Orientation
Suction nominal dia.
Suction nominal pressure
Suction position
Suction flange drilled
according to standard
Discharge nominal dia.
Discharge norminal pressure
Discharge position
Discharge flange drilled
according to standard
Shaft seal
Manufacturer
Type
Material code

D
15
with piston
Baseplate mounted, longcoupled
Horizontal
DN 80
PN 25
top (0/360)
EN 1092-1
DN 50
PN 63
top (0/360)
Viewed from the drive
EN 1092-1
Single acting mechanical seal
Burgmann
H7N
Q1AEGG

Shaft seal code


Sealing plan

81
E Single acting mechanical
(external circulation)
Minimum requirements for hot water quality: treatment acc. to
VdTV regulation TCH 1466
With SiO2-content up to max. 10 mg/l. Conductivity max. 50
S/cm for water with low salt content up to 160C or
conductivity max. 250 S/cm up to 140C for water with higher
salt content
Solids content up to max. 5 mg/l and no additives forming a
greasy film on the seal faces.
Seal chamber design
Standard seal chamber
Wear ring
Casing wear ring
Impeller diameter
173.0 mm
Minimum impeller diameter
155.0 mm
Full impeller diameter
173.0 mm
Free passage size
10.0 mm
Direction of rotation from drive Anticlockwise
Bearing bracket construction Standard (normal) two-sided
Bearing bracket size
50
Bearing seal
Thrower
Bearing type
Anti-friction bearings
Lubrication type
Grease
Temperature sensor PT100
Without
mts
Color
Ultramarine blue (RAL 5002)
KSB-blue

Driver, accessories
Manufacturer
Coupling type
Nominal size
Spacer length

Flender
Eupex NH
160
140.0 mm

Coupling guard type


Guard size
Guard material

Lightweight, not treadproof


(ZN79)
B189
Galvanised steel ST TZN

Baseplate type
Baseplate size

Steel baseplate for Multitec


GP13

Driver type
Drive standard mech.
Model (make)
Drive supplied by

Electric motor
IEC
KSB-Motor
Standard motor supplied by
KSB - mounted by KSB
B3
280M
Efficiency class IE3 acc. to
IEC60034-30-1
2979 rpm

Motor const. type


Motor size
Efficiency class
Motor speed

Frequency
Rated voltage
Rated power P2
Available reserve
Rated current
Starting current ratio
Insulation class
Motor enclosure
Cos phi at 4/4 load
Motor efficiency at 4/4 load
Temperature sensor
Terminal box position
Motor winding
Number of poles
Connection mode
Motor cooling method
Motor material
Motor noise pressure level

50 Hz
400 V
90.00 kW
22.88 %
159.6 A
8
F to IEC 34-1
IP55
0.86
95.0 %
3 PTC resistors
0/360 (top)
Viewed from the drive
400 / 690 V
2
Delta
Surface cooling
Grey cast iron GG/CAST
IRON
81 dBa

Data sheet

Customer item no.:Boiler Feed CI


Communication dated: 19/06/2015
Doc. no.: Hoddeson - Cooling System Pumps
Quantity: 1

Number: 4002472206
Item no.: 800
Date: 16/02/2016
Page: 3 / 7
Version no.: 19

Multitec D 50/ 15-4.1 20.81

Materials 20
Notes
Quality AF: pH > 9 (target >= 9.3) at 25C and O2 content <=
0.02 mg/kg for unalloyed cast iron components.
Quality AF: pH > 9 (target >= 9.3) at 25C for unalloyed steel or
cast steel components.
Suction casing (106)
Carbon steel GP240GH+N
Discharge casing (107)
Carbon steel GP240GH+N
Stage casing (108)
Steel 1.0576 S355J2H
Diffuser (171)
Grey cast iron EN-GJL-250
Shaft (210)
Chrome steel
1.4021QT700+SR
Impeller (230)
Grey cast iron EN-GJL-250
Impeller, suction stage (231) Grey cast iron EN-GJL-250

Bearing housing (350)


O-Ring (412)
Shaft seal housing (441)
Casing wear ring (502.1)
Shaft sleeve (523)
Bush (540)
Disc (550.1)
Piston (59-4)
Tie bolt (905)

Grey cast iron EN-GJL-250


EPDM 80
Carbon steel GP240GH+N
Grey cast iron EN-GJL-250
Chrome steel 1.4057+QT800
Grey cast iron EN-GJL-250
Stainless steel 1.4301
Chrome steel
1.4021QT700+SR
30NCD16

Certifications
Hydraulic performance test
Acceptance standard
Quantity meas. points Q-H
Certificate
Test participation
Quantity, non-witnessed
Quantity, witnessed

ISO 9906 class 3B


5
Inspection cert. 3.2 to EN
10204
Witnessed
0
1

Hydrostatic test (room temp.)


Range
Pressure-retaining
components individually

Suction casing
Discharge casing
Stage Casing
Shaft Seal Housing
Test time
Certificate
Test participation

33.00 bar.g
82.00 bar.g
82.00 bar.g
82.00 bar.g
2.0 min
Inspection cert. 3.1 to EN
10204
Non-witnessed

Material certificates: Suction casing, Discharge casing,


Stage casing, Shaft seal hous, Tie bolt (106, 107, 108, 441,
905)
Certificate
Test report 2.2 to EN 10204

Performance curve

Customer item no.:Boiler Feed CI


Communication dated: 19/06/2015
Doc. no.: Hoddeson - Cooling System Pumps
Quantity: 1

Number: 4002472206
Item no.:800
Date: 16/02/2016
Page: 4 / 7
Version no.: 19

Multitec D 50/ 15-4.1 20.81

Qmin

Total developed head

600
[m]

500

Qmax

400
173.0

10

[m/h]

20

30

40

50

60

10

[m/h]

20

30

40

50

60

10

[m/h]

20

30

40

50

60

10

[m/h]

20

30
Flow

40

50

60

NPSH req.

[m]

Efficiency

50

[%]

Power Input

100

[kW]

50

Curve data
Speed of rotation
Fluid density
Viscosity
Flow rate
Requested flow rate
Total developed head
Requested developed head

2979 rpm
954 kg/m
0.29 mm/s
32.80 m/h
32.80 m/h
587.64 m
587.58 m

Efficiency
Power absorbed
NPSH required
Curve number
Impeller diameter
Acceptance standard

68.3 %
73.24 kW
2.14 m
1777.407521/03 GG
173.0 mm
ISO 9906 class 3B

Installation plan

Customer item no.:Boiler Feed CI


Communication dated: 19/06/2015
Doc. no.: Hoddeson - Cooling System Pumps
Quantity: 1

Number: 4002472206
Item no.:800
Date: 16/02/2016
Page: 5 / 7
Version no.: 19

Multitec D 50/ 15-4.1 20.81

140

1071
200

338

957

262

200
6
65

28

k7

DN1

DN2

200

445

80

380

1050
1329

717

250

2100
770
2600
930

2800

Drawing is not to scale


Motor
Motor manufacturer
Motor size
Motor power
Number of poles
Speed of rotation
Position of terminal box

Baseplate
Design
Size
Material
Leakage drain baseplate
(8B)
Foundation bolts

Dimensions in mm

KSB-Motor
280M
90.00 kW
2
2979 rpm
0/360 (top)
Viewed from the drive

Steel baseplate for


Multitec
GP13
Rp1, Without
M20x320 (Not in scope of
supply)

Connect pipes without stress or strain!


Dimensional tolerances for shaft axis height:
Dimensions without tolerances, middle tolerances to:
Connection dimensions for pumps:
Dimensions without tolerances - welded parts:
Dimensions without tolerances - gray cast iron parts:

Connections
Suction nominal size DN1
Discharge nominal size DN2
Nominal pressure suct.
Rated pressure disch.

DN 80 / EN 1092-1
DN 50 / EN 1092-1
PN 25
PN 63

Coupling
Coupling manufacturer
Coupling type
Coupling size
Spacer

Flender
Eupex NH
160
140.0 mm

Weight net
Pump
Baseplate
Coupling
Coupling guard
Motor
Total
DIN 747
ISO 2768-m
EN735
ISO 13920-B
ISO 8062-CT9

250 kg
286 kg
15 kg
2 kg
762 kg
1315 kg
For auxiliary connections see
separate drawing.

Connection plan

Customer item no.:Boiler Feed CI


Communication dated: 19/06/2015
Doc. no.: Hoddeson - Cooling System Pumps
Quantity: 1

Number: 4002472206
Item no.:800
Date: 16/02/2016
Page: 6 / 7
Version no.: 19

Multitec D 50/ 15-4.1 20.81

1M.2

1M.1
20E.1

20E.2

8B.1

8B.2

737D61BF

6B.1

6B.2

Connections
1M.1 Pressure gauge
connection
1M.2 Pressure gauge
connection
6B.1 Pumped liquid drain
6B.2 Pumped liquid drain
8B.1 Leakage drain
8B.2 Leakage drain
20E.1 Grease nipple
20E.2 Grease nipple

G 1/2

Pressure sensor for PumpMeter fitted

G 1/2

Pressure sensor for PumpMeter fitted

G 1/4
G 1/4
Rp 3/8
Rp 3/8

Drilled and plugged.


Drilled and plugged.
Drilled
Drilled
Mounted at the factory
Not executed

Data sheet

Customer item no.:Boiler Feed CI


Communication dated: 19/06/2015
Doc. no.: Hoddeson - Cooling System Pumps
Quantity: 1

Number: 4002472206
Item no.: 810
Date: 16/02/2016
Page: 7 / 7

PumpMeter
Intelligent Pressure Transmitter PumpMeter - with on-site display of
operating point

Version no.: 19

General description:

Sensors:

PumpMeter in an intelligent pressure transmitter with on-site


display of measurement values and operating data of the
pump. It comes factory-provided completely assembled and
parameterised for your individual pump, to be connected via
M12 connector and immediately ready to operate. PumpMeter
records the pumps load profile during operation in order to if
applicable provide information on the potential for energy
savings or increased availability.

Two gauge pressure transmitters, one each factory provided on


both, inlet and discharge side of pump. Connected to display
unit via connector.

On-site display unit:

2.5% for fluid temperature -30 -10 C and 100 140 C

Backlit display unit for on-site display of measurement values


and operating data of pump with intuitive and internationally
comprehensible icons, rotatable in steps of 90.

Material of measuring cell: stainless steel (no internal gasket)

Display values:

-1 ...3 bar (gauge pressure)

suction pressure, pressure at inlet of pump in bar, gauge


pressure
discharge pressure, pressure at outlet of pump in bar, gauge
pressure
differential pressure between in- and outlet of pump in bar
qualitative indication of operating point

-1 ...65 bar (gauge pressure)

Connection of display unit via connector (M12 x 1, 5-pin for


power supply and utilization of communication interface.
Making alternatively available:
measurement value of discharge pressure via analogue signal
4 20 mA
calculated value of differential pressure via analogue signal 4
20 mA
all display values via serial interface RS 485 (Modbus RTU).
Service interface RS232 for parameterisation.
Factory provided parameterisation for individual pump.

Ambient temperature:
-30C 80C (during transport, storage)
-10C 60C (operation)

Accuracy of measurement (sum of errors; relating to


measurement range):
1% for fluid temperature -10 100 C

Available measurement ranges:

Ambient conditions:
Type of protection: IP 65

Fluid temperature: -30C 140C


Scuff resistance:
Ultraviolet resistance (outdoor installation)
Resistance to most cleaning agents
Resistance to oil mist
Silicone free:
No detrimental to paint adhesion
Electric data:
Power supply:
24V DC 10%, min. 140 mA
Interfaces, alternatively utilisable:
4 20 mA, 3-conductor (discharge pressure or differential
pressure)
RS485, Modbus RTU (Slave)
Service interface: RS232
EMC:
EN 61326 (Immunity: industrial environment, Emissions:
applicable in home and building environment)

Das könnte Ihnen auch gefallen