FEATURES
■ ENCLOSURE ■ SAFETY
The load bank system is housed in a The load bank will remove the test source
modified 30-foot ISO NEMA 3R shipping load when any condition is present which
container. Modifications include a cable could damage the bank or present a safety
access door and framing for the installation hazard to the operator. These conditions
of three louvers. The enclosure includes a include louver position, cooling failures
cable locker that provides 16, 75-foot (loss of cooling airflow, high intake, or
lengths of lugged 535 MCM cable. high exhaust temperature), reactor
overtemperature, and the position of the
■ CONNECTIONS
interior door.
Lugged cables from the test source are
connected to the main bus bars in the load ■ LOUVERS & VENTILATION
bank through an access door in the right The three load bank louvers are manually
side of the container. Control power can be operated. As a safety feature, all louvers
provided from an external source instead of must be open to apply loads. The large
the test source. forward louvers provide cooling air for the
resistive section. The remaining louver
■ OPERATION
provides interior ventilation.
The load bank is designed to apply a
discrete, selectable resistive/reactive load to ■ COMPUTER CONTROL
a power source. The operator can select and Microsoft® Excel® software program loaded
apply loads manually or via a computer. on IBM® 486 industrial grade on-board
The desired load is entered at the keyboard computer provides detailed, comprehensive
in computer mode. The data is monitored graphics and tabular report writing
by a G.E. Genius Power Trac® and displayed capability for customer analysis of
on the computer’s monitor. The load bank generator set performance and definition of
includes a rack-mounted Gould TA 240® repair/maintenance needs.
dual strip chart recorder that features
thermal array recording, extensive
annotation features, and true RMS voltage
and frequency recording of the test source.
RESISTIVE/REACTIVE MOBILE LOAD BANK
DIMENSIONS
L H W WGT
17 cm in cm in cm in kg lbs
16
935 368 401 158 243 96 15 890 35 000
15
NOTE: Restrict access within 50 ft. of resistive section exhaust
louvers. All internal controls are powered from either the bus bars
or the external power connection. If using bus bars for power, then
loss of generator power will shut down the load bank.
13 18 9
10 3 5 6
11 7 8 1 2
14
RESISTIVE/REACTIVE MOBILE LOAD BANK
Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication.
LEHX9145 Printed in U.S.A. © 1999 Caterpillar Inc.
Supersedes LEHX7302 All rights reserved.