Climatizacion Sala De Capacitacion

HVAC Load Analysis


for

Asociacion P. De Agentes Inmobiliarios


Lima
Lima

Prepared By:
Ing. Jerry Franco Milla
Generafrio, S. A. C
Lima
Lima
jueves, 11 de Febrero de 2016

Chvac - Full Commercial HVAC Loads Calculation Program


pReJkEr
Hell

Elite Software Development, Inc.


Climatizacion Sala De Capacitacion
Page 2

General Project Data Input


General Project Information
Project file name:

C:\Users\Generafrio
3\Documents\CLIENTES\CLIENTES\MIRAFLORES - SAN
ISIDRO\CALCULO DE CARGA SALA DE REUNIONES.CHV
Climatizacion Sala De Capacitacion
Ing. Jerry Franco Milla
Jueves, 11 De Febrero 2016
Calculo de Carga Termica Proyecto
LIMA, PERU
Asociacion P. De Agentes Inmobiliarios
Lima
Lima
Generafrio, S. A. C
Ing. Jerry Franco Milla
Lima
Lima

Project title:
Designed by:
Project date:
Project comment:
Weather reference city:
Client name:
Client address:
Client city:
Company name:
Company representative:
Company address:
Company city:
Barometric pressure:
Altitude:
Latitude:
Mean daily temperature range:
Starting & ending time for HVAC load calculations:
Number of unique zones in this project:

29.876
42
-12
11.5
8am - 6pm
1

in.Hg.
feet
Degrees
Degrees

Building Default Values


Calculations performed:
Lighting requirements:
Equipment requirements:
People sensible load multiplier:
People latent load multiplier:
Zone sensible safety factor:
Zone latent safety factor:
Zone heating safety factor:
People diversity factor:
Lighting profile number:
Equipment profile number:
People profile number:
Building default ceiling height:
Building default wall height:

Cooling loads only


2.00
1.50
250
220
10
10
10
100
1
1
1
8.00
8.00

Watts per square foot


Watts per square foot
Btuh per person
Btuh per person
%
%
%
%

feet
feet

Internal Operating Load Profiles (C = 100)


1
2
3
4
5
6
7
8
9
10

hr
1
C
C
C
C
C
C
C
C
C
C

hr
2
C
C
C
C
C
C
C
C
C
C

hr
3
C
C
C
C
C
C
C
C
C
C

hr
4
C
C
C
C
C
C
C
C
C
C

hr
5
C
C
C
C
C
C
C
C
C
C

hr
6
C
C
C
C
C
C
C
C
C
C

hr
7
C
C
C
C
C
C
C
C
C
C

hr
8
C
C
C
C
C
C
C
C
C
C

hr
9
C
C
C
C
C
C
C
C
C
C

hr
10
C
C
C
C
C
C
C
C
C
C

C:\ ...\CALCULO DE CARGA SALA DE REUNIONES.CHV

hr
11
C
C
C
C
C
C
C
C
C
C

hr
12
C
C
C
C
C
C
C
C
C
C

hr
13
C
C
C
C
C
C
C
C
C
C

hr
14
C
C
C
C
C
C
C
C
C
C

hr
15
C
C
C
C
C
C
C
C
C
C

hr
16
C
C
C
C
C
C
C
C
C
C

hr
17
C
C
C
C
C
C
C
C
C
C

hr
18
C
C
C
C
C
C
C
C
C
C

hr
19
C
C
C
C
C
C
C
C
C
C

hr
20
C
C
C
C
C
C
C
C
C
C

hr
21
C
C
C
C
C
C
C
C
C
C

hr
22
C
C
C
C
C
C
C
C
C
C

hr
23
C
C
C
C
C
C
C
C
C
C

hr
24
C
C
C
C
C
C
C
C
C
C

jueves, 11 de Febrero de 2016, 2:49 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


pReJkEr
Hell

Elite Software Development, Inc.


Climatizacion Sala De Capacitacion
Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design
Month
December
January
February
March
April
May
June
July
August
September
October
November
Winter

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

83
86
87
88
85
82
80
77
75
75
74
78
58

73
76
76
76
75
72
71
68
67
67
66
69

50%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%

72
72
72
72
72
72
72
72
72
72
72
72
75

47.40
54.51
55.22
52.39
50.96
40.30
36.72
22.80
21.93
21.21
16.46
26.03

-2
2
3
3
0
-2
-4
-7
-9
-10
-11
-7

Master Roofs
Roof
No.

ASHRAE
Roof#

Roof
U-Fac

Dark
Color

Susp.
Ceil

0.600

No

No

ASHRAE
Group

Wall
U-Fac

Wall
Color

0.400

Partition
U-Factor

Cool
T-D

Heat
T-D

0.070

10

15

Master Walls
Wall
No.
1

Master Partitions
Partition
No.
1

Master Glass
Glass
No.
1

Summer
U-Factor

Winter
U-Factor

Glass
Shd.Coef.

Interior
Shading

Interior
Shd.Coef

0.700

0.700

1.000

0.000

C:\ ...\CALCULO DE CARGA SALA DE REUNIONES.CHV

jueves, 11 de Febrero de 2016, 2:49 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


pReJkEr
Hell

Elite Software Development, Inc.


Climatizacion Sala De Capacitacion
Page 4

Zone Input
Zone 1: Sala De Capacitacion (1291.2 sq.ft) (Group 0)
Air Handler number:
Zone length: (feet)
Lighting Watts:
Number of people in zone:
Lighting profile number:
Ceiling height (feet):
Sensible safety factor (%):
Sensible heat per person (Btuh):
Cooling ventilation method:
Cooling infiltration method:
Heating ventilation method:
Heating infiltration method:
Winter exhaust air CFM:
Minimum supply CFM:
Ceil. exposed to plenum (sq.ft):
Cooling loads only are calculated for this zone.
Part

1
10.76
1,937
1
1
10
10
220
0.000
0.000
0.000
0.000
0
0
70

U-Factor

Cool TD

Heat TD

Height

Width

Area

1
1

0.07
0.07

10.000
10.000

15.000
15.000

8.00
8.00

26.25
26.25

210.0
210.0

Type

ASHRAE#

U-Factor

Color

Height

Width

Area

Direction

1
1

C
C

0.400
0.400

M
M

8.00
8.00

49.20
49.20

393.6
393.6

E
W

1
2
Glass

Zone occurrences:
Zone width (feet):
Equipment Watts:
People profile number:
Equipment profile number:
Heating safety factor (%):
Latent safety factor (%):
Latent heat per person (Btuh):
Cooling ventilation value:
Cooling infiltration value:
Heating ventilation value:
Heating infiltration value:
Summer exhaust air CFM:
Latent Btuh equipment load:
Exposed floor slab perimeter (ft):

Type

3
4
Wall

1
120.00
2,582
45
1
8.00
10
250
Direct
Direct
Direct
Direct
0
0
1,291

Type

S.U-F.

Shd C.

Height

Width

Occur.

Area

Shade

Tilt

Ref

0.700

1.000

5.91

32.00

189.1

90

C:\ ...\CALCULO DE CARGA SALA DE REUNIONES.CHV

jueves, 11 de Febrero de 2016, 2:49 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


pReJkEr
Hell

Elite Software Development, Inc.


Climatizacion Sala De Capacitacion
Page 5

Building Summary Loads


Building peaks in March at 6pm.

Bldg Load
Descriptions

Area
Quan

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

0
598
189
70

0
0
0
0

0.00
0.00
0.00
0.00

0
0
0
0

0
6,301
2,206
0

0
6,301
2,206
0

0.00
11.69
4.09
0.00

0.00

8,507

8,507

15.78

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

0
0
10,890
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

9,693
7,269
12,375
323
0
0
0
0
0
0
0
1,732
0
0
2,068
1,034
0
0

9,693
7,269
23,265
323
0
0
0
0
0
0
0
1,732
0
0
2,068
1,034
0
0

17.99
13.49
43.17
0.60
0.00
0.00
0.00
0.00
0.00
0.00
0.00
3.21
0.00
0.00
3.84
1.92
0.00
0.00

0.00

10,890

43,002

53,892

100.00

Roof
Wall
Glass
Floor Slab
Skin Loads
Lighting
Equipment
People
Partition
Cool. Pret.
Heat. Pret.
Cool. Vent.
Heat. Vent.
Cool. Infil.
Heat. Infil.
Draw-Thru Fan
Blow-Thru Fan
Reserve Cap.
Reheat Cap.
Supply Duct
Return Duct
Misc. Supply
Misc. Return

2,582
1,937
45
420
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Building Totals

Building
Summary

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Ventilation
Infiltration
Pretreated Air
Zone Loads
Plenum Loads
Fan & Duct Loads

0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00

0
0
0
10,890
0
0

0
0
0
38,167
0
4,835

0
0
0
49,057
0
4,835

0.00
0.00
0.00
91.03
0.00
8.97

Building Totals

0.00

10,890

43,002

53,892

100.00

Check Figures
Total Building Supply Air (based on a 19 TD):
Total Building Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

C:\ ...\CALCULO DE CARGA SALA DE REUNIONES.CHV

1,883 CFM
0 CFM
1,291
1.4583
287.5080
0.0035
0.00

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft
Btuh/Sq.ft

0 Btuh
4.49 Tons

jueves, 11 de Febrero de 2016, 2:49 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


pReJkEr
Hell

Elite Software Development, Inc.


Climatizacion Sala De Capacitacion
Page 6

Air Handler #1 - Sala De Capacitacion - Summary Loads


Zn
No

Description
Zone Peak Time

Sala De Capacitacion
6pm March

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,291
0
38,167
10,890
None
45
0
1,883
0
0
10,330
0.00
1.46
0
0
Runout duct size: 6 in. dia, Diffusers: 15, CFM/runout: 126, Velocity: 639.3 ft/min, Pressure drop: 0.261 in.wg./100ft
Zone Peak Totals:
1,291
0
38,167
10,890
Total Zones: 1
45
0
1,883
0
Unique Zones: 1
10,330
0.00
1.46
0
Main trunk duct size: 19 in. h x 18in. w, Velocity: 863.1 ft/min, Pressure drop: 0.069 in.wg./100ft

C:\ ...\CALCULO DE CARGA SALA DE REUNIONES.CHV

0
0

None
0
0

0
0

jueves, 11 de Febrero de 2016, 2:49 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


pReJkEr
Hell

Elite Software Development, Inc.


Climatizacion Sala De Capacitacion
Page 7

Air Handler #1 - Sala De Capacitacion - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Sala De Capacitacion Constant Volume - Proportion


Blow-Thru with program estimated horsepower of 0.68 HP
65% motor and fan efficiency with 1.5 in. water across the fan
0.79
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

6pm in March.
85 DB, 75 WB, 116.28 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
38,167
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
2,068
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh
Btuh
40,236 Btuh

Cooling Supply Air: 40,236 / (.998 X 1.1 X 19) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
1,034
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
1,732
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

1,883 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
2,767 Btuh
43,002 Btuh

Zone space latent gain:


10,890 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

10,890 Btuh
53,892 Btuh

Check Figures
Total Air Handler Supply Air (based on a 19 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

C:\ ...\CALCULO DE CARGA SALA DE REUNIONES.CHV

1,883 CFM
0 CFM
1,291
1.4583
287.5080
0.0035
0.00

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft
Btuh/Sq.ft

0 Btuh
4.49 Tons

jueves, 11 de Febrero de 2016, 2:49 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


pReJkEr
Hell

Elite Software Development, Inc.


Climatizacion Sala De Capacitacion
Page 8

Building Pie Charts


Building peaks in March at 6pm.

Wall - 11.69%

Return Duct - 1.92%


Supply Duct - 3.84%
Blow-Thru Fan - 3.21%
Partition - 0.60%

Glass - 4.09%

Building
Net Gain
53,892
Btuh

Lighting - 17.99%

People - 43.17%

Equipment - 13.49%

C:\ ...\CALCULO DE CARGA SALA DE REUNIONES.CHV

jueves, 11 de Febrero de 2016, 2:49 p. m.

Das könnte Ihnen auch gefallen