Column 3
Various fuse types are listed in Column 3. The LPJ_SP is a 600Vac, 0 - 600 amp,
time-delay, Class J, Low-Peak fuse, with a 300,000 amp interrupting rating. The
TCF is a 600Vac, 1 - 100 amp dual-element, time-delay, IP-20 finger-safe fuse with
Class J performance. The LP-CC is a 600Vac, 0 - 30 amp, time-delay, Class CC,
Low-Peak fuse with a 200,000 amp interrupting rating. The LPS-RK_SP and LPNRK_SP are 600 and 250Vac, 0 - 600 amp, time-delay, Class RK1, Low-Peak fuses
with interrupting ratings of 300,000 amps. FRS-R and FRN-R are 600 and 250Vac,
0 - 600 amp, time-delay, Class RK5, Fusetron Dual-Element fuses with interrupting
ratings of 200,000 amps. The KRP-C_SP is a 600Vac, 601 - 6000 amp, time-delay,
Class L, Low-Peak fuse, with a 300,000 amp AC interrupting rating. The DC listed
ratings for these fuses are:
LPJ
TCF
LP-CC
LP-CC
LP-CC
1 to 600SP
1 to 100
1
2 to 2 810
3 to 15
20 to 30
300Vdc
300Vdc
300Vdc
150Vdc
300Vdc
LPN-RK
LPN-RK
LPS-RK
FRN-R
FRS-R
0 to 60SP
70 to 600SP
0 to 600SP
0 to 600
0 to 600
125Vdc
250Vdc
300Vdc
125Vdc
300Vdc
LP-CC 20 to 30A: 300% (150% for DC) or the next larger Cooper Bussmann size if
300% (150% for DC) does not correspond to a Cooper Bussmann fuse amp
rating.
LPS-RK_SP and LPN-RK_SP: 130% or the next larger Cooper Bussmann amp rating if 130% does not correspond to a Cooper Bussmann fuse amp rating.
FRS-R and FRN-R: 125% or the next larger Cooper Bussmann amp rating if 125%
does not correspond to a Cooper Bussmann fuse amp rating.
Sizes shown for the LP-CC can also be used for non-time delay fuses such as
JKS, KTN-R, KTS-R, JJN, JJS, AND KTK-R.
Column 7
Horsepower-rated switch sizes given in Column 7 are based on 115% (430.110) of
Column 2. Switch sizes need to be increased when, because of starting requirements, the fuses are sized above the rating of the switch shown in this column.
Column 8
Sizes listed are for general-purpose magnetic controllers (single speed, fullvolt-age for limited plugging and jogging-duty) as shown in NEMA Standards
Publication ICS-2-2000.
145
Column 10
Copper wire sizes are based upon 125% (430.22) of values shown in Column 2
and ampacities listed in Table 310.16 for 75C terminals. Although the NEC
allows 60C terminations for equipment rated 100 amp or less, most
equipment terminations have been rated for 75C conductors. If equipment terminations are rated for 60C conductors only, the 60C ampacities must be utilized
and therefore larger conductor sizes may be required than those shown in this column. See 110.14(C) (1)(a)(4).
These rigid metallic conduit sizes are based upon copper conductors with THWN
or THHN insulation, Table C8 of Annex C, and 75C equipment terminals.
2
Motor
FLA
Table
430.250
AMPS
2.5
3.7
4.8
1 12
6.9
7.8
11
17.5
7 12
25.3
10
32.2
15
48.3
20
62.1
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
AMPS1
4
6
5
3 12
3 210
5 610
6
7 12
5
5
8
10
10
6 14
6
12
15
15
9
9
12
15
25
12
10
17 12
17 12
25
15
15
30
30
25
25
40
40
35
35
50
50
45
45
80
80
70
70
100
100
90
80
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
6
6
10
6
6
10
10
15
10
10
10
10
15
10
10
15
15
25
15
15
15
15
25
15
15
20
20
20
20
35
35
35
35
45
45
45
45
60
60
60
60
90
90
90
90
110
110
110
Conduit sizes are for three conductors per circuit for three phase motors and two
conductors per circuit for single phase and DC motors. Conduit sizes may need to
be increased if equipment grounding conductors or neutrals are also installed in
the conduit.
If equipment terminations are rated for 60C conductors only, the 60C ampacities
must be utilized and therefore larger conductor sizes and conduit sizes may be
required.
20
20
35
35
35
35
50
50
50
50
70
70
70
100
100
100
100
125
125
125
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
00
14
30
00
14
30
00
14
30
00
14
30
14
30
14
30*
12
60
10**
60*
8**
100
6**
100*
4**
2**
2**
4**
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
1 Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
** If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
146
2
Motor
FLA
Table
430.250
AMPS
25
78.2
30
92
40
120
50
150
60
177
75
221
100
285
125
359
150
414
200
552
*
1
**
2
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
LPN-RK_SP
FRN-R
KRP-C_SP
KRP-C_SP
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
L
J
RK1
RK5
L
J
RK1
RK5
L
RK1
RK5
L
L
AMPS 1
125
110
100
150
125
125
200
175
150
225
200
200
300
250
225
350
300
300
450
400
400
600
500
450
600
600
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS 1
150
150
150
175
175
175
225
225
225
300
300
300
350
350
350
400
400
400
500
500
500
700
800
1000
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS 1
175
175
175
200
200
200
250
250
250
300
300
300
350
350
350
450
450
450
650
600
600
600
800
1000
1200
1600
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
100*
3**
1**
200
2**
1**
200*
1/0
1 14
200*
3/0
1 12
400
4/0
400*
300
400*
500
600*
4/0 2/PHASE
(2)2
600*
300 2/PHASE
(2)2
1200
72
500 2/PHASE
(2)3
Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
These sizes are typical. They are not shown in NEMA ICS 2-2000.
2
Motor
FLA
Table
430.250
AMPS
2.4
3.5
4.6
1 12
6.6
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
AMPS1
4
6
5
3 12
3
5 610
6
7
5
4 12
7
10
10
6
6
10
10
15
9
9
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
6
6
10
6
6
10
10
15
10
10
10
10
15
10
10
15
15
20
15
15
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
6
6
10
6
6
10
10
15
10
10
10
10
15
10
10
15
15
25
15
15
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
00
14
30
00
14
30
00
14
30
00
14
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
1 Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
**If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
147
2
Motor
FLA
Table
430.250
AMPS
7.5
10.6
16.7
7 12
24.2
10
30.8
15
46.2
20
59.4
25
74.8
30
88
40
114
50
143
60
169
75
211
100
273
125
343
150
396
200
528
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
KRP-C_SP
J
J
CC
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
L
J
RK1
RK5
L
J
RK1
RK5
L
J
RK1
RK5
L
L
AMPS1
12
15
15
10
10
17 12
17 12
15
15
30
30
25
25
40
40
35
35
50
50
45
40
70
70
70
60
90
90
80
80
125
100
100
150
125
110
175
150
150
225
200
200
300
225
225
350
300
300
450
400
350
600
450
450
600
600
500
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
15
15
25
15
15
20
20
20
20
30
30
30
30
45
45
45
45
60
60
60
60
90
90
90
90
110
110
110
150
150
150
175
175
175
200
200
200
300
300
300
300
300
300
400
400
400
500
500
500
601
700
1000
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
15
15
30
15
15
20
20
20
20
35
35
35
35
50
50
50
50
60
60
60
60
100
100
100
100
125
125
125
150
150
150
175
175
175
250
250
250
300
300
300
350
350
350
450
450
450
601
600
600
600
800
1000
1100
1500
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
14
30
14
30*
12
60
10**
60
60*
6**
100*
4**
100*
3**
1**
200
2**
1**
200*
1/0
1 14
200*
3/0
1 12
400
4/0
400*
300
400*
500
600*
4/0 2/PHASE
(2)2
600*
250 2/PHASE
(2)2
1200*
400 2/PHASE
(2)2-2 12
2**
4**
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
1 Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
**If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
148
2
Motor
FLA
Table
430.250
AMPS
2.2
3.2
4.2
1 12
6.8
9.6
15.2
7 12
22
10
28
15
42
20
54
25
68
30
80
40
104
50
130
60
154
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
AMPS1
3 12
6
4 12
3
2 8/10
5
6
7
4 12
4
7
10
9
5 610
5 810
9
10
12
8
7 12
12
15
15
9
9
15
15
30
15
12
25
25
20
20
35
34
30
30
45
45
40
35
70
70
60
60
90
90
80
70
110
90
90
125
110
100
175
150
150
200
175
175
250
225
200
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
6
6
10
6
6
6
6
10
6
6
10
10
15
10
10
15
15
20
15
15
15
15
25
15
15
20
20
30
20
20
30
30
30
30
40
40
40
40
50
50
50
50
80
80
80
80
100
100
100
100
125
125
125
150
150
150
200
200
200
250
250
250
300
300
300
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
6
6
10
6
6
7
6
12
7
7
10
10
15
10
10
15
15
20
15
15
15
15
25
15
15
20
20
30
20
20
30
30
30
30
45
45
45
45
60
60
60
60
90
90
90
90
110
110
110
150
150
150
175
175
175
225
225
225
250
250
250
300
300
300
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
00
14
30
00
14
30
00
14
30
00
14
30
14
30
14
30
14
30*
10
60
10**
60*
100*
100*
4**
100*
3**
1**
200*
1**
1 14**
200*
2/0
1 12
200*
3/0
1 12
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
1 Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
**If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
149
2
Motor
FLA
Table
430.250
AMPS
75
192
100
248
125
312
150
360
200
480
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
LPJ_SP
LPN-RK_SP
FRN-R
KRP-C_SP
FRN-R
KRP-C_SP
J
RK1
RK5
J
RK1
RK5
L
J
RK1
RK5
L
J
RK1
RK5
L
RK5
L
AMPS1
300
250
250
400
350
350
500
450
400
600
500
450
600
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
350
350
350
450
450
450
600
600
600
6004
6004
700
1000
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
400
400
400
500
500
500
700
900
1000
1400
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
400
250
400*
350
2 12
400*
3/0 2/PHASE
(2) 1 12
600*
4/0 2/PHASE
(2) 2
600*
350 2/PHASE
(2) 2-2 12
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
1 Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
**If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
4 Limited by 600 amp being the largest amp rating for FRN-R and LPN-RK_SP.
2
Motor
FLA
Table
430.250
AMPS
1.1
1.6
2.1
1 12
3.4
4.8
7.6
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
AMPS1
1 810
3
2 14
1 112
1 410
2 12
3
3 210
2 14
2
3 210
6
4 12
2 810
2 810
4 12
6
6
4
4
5 610
6
71
4 12
4 12
8
10
10
6 14
6
12
15
25
10
10
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
3
3
6
3
3
3
3
6
3
3
6
6
10
6
6
6
6
10
6
6
6
6
5
6
6
10
10
15
10
10
15
15
25
15
15
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
3
3
6
3
3
3 12
3
6 14
3 12
3 12
6
6
10
6
6
6
6
12
6 14
6 14
7
6
15
7
7 12
10
10
15
10
10
15
15
30
15
15
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
00
14
30
00
14
30
00
14
30
00
14
30
00
14
30
14
30
14
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
1 Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
** If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
150
2
Motor
FLA
Table
430.250
AMPS
7 2
11
10
14
15
21
20
27
25
34
30
40
40
52
50
65
60
77
75
96
100
124
125
156
150
180
200
240
250
302
300
361
350
414
400
477
450
500
515
590
*
1
**
4
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
KRP-C_SP
LPJ_SP
LPS-RK_SP
FRS-R
KRP-C_SP
LPJ_SP
LPS-RK_SP
FRS-R
KRP-C_SP
LPS-RK_SP
FRS-R
KRP-C_SP
KRP-C_SP
FRS-R
KRP-C_SP
KRP-C_SP
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
L
J
RK1
RK5
L
J
RK1
RK5
L
RK1
RK5
L
L
RK5
L
L
AMPS1
17 12
17 12
15
15
25
25
20
17 12
35
35
30
30
45
45
40
35
60
60
45
45
60
60
60
50
80
80
70
70
100
100
90
90
125
110
100
150
125
125
200
175
175
250
225
200
300
250
225
400
350
300
500
400
400
600
500
500
600
600
600
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
20
20
20
20
25
25
25
25
40
40
40
40
50
50
50
50
60
60
60
60
70
70
70
70
100
100
100
100
125
125
125
150
150
150
175
175
175
225
225
225
300
300
300
350
350
350
450
450
450
600
600
600
6004
6004
700
800
1000
1000
1200
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
20
20
20
20
30
30
30
30
45
45
45
45
60
60
60
60
70
70
70
70
90
90
90
90
110
110
110
125
125
125
150
150
150
200
200
200
250
250
250
350
350
350
400
400
400
500
500
500
700
900
1000
1200
1400
1500
1600
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
14
30
14
30*
10
60
10**
60*
8**
60*
8**
100*
6**
100*
4**
100*
3**
1**
200
1**
1 14**
200*
2/0
1 12
200*
3/0
1 12
400
4/0
400*
350
2 12
400*
3/0 2/PHASE
(2) 1 12
600*
4/0 2/PHASE
(2) 2
600*
300 2/PHASE
(2) 2
600*
350 2/PHASE
(2 )2 12
1200*
1200*
7
7
400 2/PHASE
500 2/PHASE
(2) 2 12
(2) 3
2**
2**
4**
Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
Limited by 600 amp being the largest amp rating for FRS-R and LPS-RK_SP.
Class J performance, special finger-safe dimensions.
151
2
Motor
FLA
Table
430.250
AMPS
0.9
1.3
1.7
1 12
2.4
2.7
3.9
6.1
7 12
10
11
15
17
20
22
25
27
30
32
40
41
50
52
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
AMPS1
1 410
3
1 810
1 14
1 18
2
3
2 810
1 810
1 810
2 810
3
3 12
2 14
2 14
4
6
5
3 210
3
4 12
6
5 610
4
3 12
6
6
5
5 610
5
10
10
15
8
8
15
15
30
12
12
17 12
17 12
15
15
30
30
25
25
35
35
30
30
45
45
40
35
50
50
45
40
70
70
60
60
80
80
70
70
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
3
3
3
3
3
3
3
6
3
3
3
3
6
3
3
6
6
10
6
6
6
6
10
6
6
10
10
15
10
10
15
15
20
15
15
20
20
30
20
20
20
20
20
20
30
30
30
30
40
40
40
40
50
50
50
50
60
60
60
60
80
80
80
80
100
100
100
100
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
3
3
3 12
3
3
3
3
6
3
3
3 12
3
6 14
3 12
3 12
6
6
10
6
6
6
6
10
6
6
10
10
15
10
10
15
15
20
15
15
20
20
30
20
20
20
20
20
20
35
35
35
35
45
45
45
45
60
60
60
60
70
70
70
70
90
90
90
90
110
110
110
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
14
30
14
30
14
30
14
30
14
30
14
30
14
30
14
30
14
30*
12
30*
10
60
10**
60*
60*
100*
6**
2**
4**
*Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
1 Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
**If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
2 These sizes are typical. They are not shown in NEMA ICS 2-2000.
152
2
Motor
FLA
Table
430.250
AMPS
60
62
75
77
100
99
125
125
150
144
200
192
250
242
300
289
350
336
400
382
450
412
500
472
*
1
**
2
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
LPJ_SP
LPS-RK_SP
FRS-R
KRP-C_SP
LPJ_SP
LPS-RK_SP
FRS-R
KRP-C_SP
LPJ_SP
LPS-RK_SP
FRS-R
KRP-C_SP
LPJ_SP
LPS-RK_SP
FRS-R
KRP-C_SP
LPS-RK_SP
FRS-R
KRP-C_SP
FRS-R
KRP-C_SP
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
L
J
RK1
RK5
L
J
RK1
RK5
L
J
RK1
RK5
L
RK1
RK5
L
RK5
L
AMPS1
100
90
80
125
110
100
150
150
125
200
175
175
225
200
200
300
250
250
400
350
350
450
400
400
600
450
450
600
500
500
600
600
600
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
110
110
110
150
150
150
175
175
175
225
225
225
300
300
300
350
350
350
450
450
450
600
600
600
600
600
600
601
700
800
1000
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
125
125
125
150
150
150
200
200
200
250
250
250
300
300
300
400
400
400
500
500
500
700
600
600
600
800
1000
1100
1200
1400
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
100*
4**
100*
3**
1**
200
1**
1 14**
200*
2/0
1 12
200*
3/0
1 12
400
250
400*
350
2 12
400*
500
600*
4/0 2/PHASE
(2) 2
600*
250 2/PHASE
(2) 2
600*
300 2/PHASE
(2) 2
600*
350 2/PHASE
(2) 2 12
Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
These sizes are typical. They are not shown in NEMA ICS 2-2000.
153
2
Motor
FLA
Table
430.248
AMPS
4.4
5.8
7.2
9.8
13.8
16
1 12
20
24
34
56
7 12
80
10
100
*
1
**
2
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
AMPS1
8
10
9
6
5 6/10
9
10
12
8
7 12
12
15
15
10
9
15
15
30
15
15
25
25
20
17 12
25
25
25
20
30
30
30
25
40
40
35
30
60
60
45
45
90
90
80
70
125
110
100
150
150
125
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
10
10
15
10
10
15
15
20
15
15
15
15
25
15
15
20
20
30
20
20
25
25
25
25
30
30
30
30
35
35
35
35
45
45
45
45
60
60
60
60
100
100
100
100
150
150
150
175
175
175
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
10
10
15
10
10
15
15
20
15
15
15
15
25
15
15
20
20
30
20
20
30
30
30
30
35
35
35
35
45
45
45
45
50
50
50
50
70
70
70
70
125
125
125
175
175
175
225
225
225
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
00
14
30
00
14
30
00
14
30
14
30
14
30*
14
30*
12
30*
10
60*
8**
100*
100*
3**
1**
200*
42
1 14
2**
4**
Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
These sizes are typical. They are not shown in NEMA ICS 2-2000.
Class J performance, special finger-safe dimensions.
154
2
Motor
FLA
Table
430.248
AMPS
2.2
2.9
3.6
4.9
6.9
1 12
10
12
17
28
7 12
40
10
50
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
AMPS1
3 12
6
4 12
3
2 810
4 12
6
6
4
4
5 610
6
7
5
4 12
8
10
10
8
6 14
12
15
15
9
9
12
15
25
12
10
15
15
30
15
15
20
20
25
17 12
15
30
30
25
25
45
45
40
35
60
60
60
50
80
80
70
70
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
6
6
10
6
6
6
6
10
6
6
10
10
15
10
10
10
10
15
10
10
15
15
25
15
15
15
15
25
15
15
20
20
30
20
20
25
25
25
25
30
30
30
30
50
50
50
50
70
70
70
70
90
90
90
90
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
6
6
10
6
6
6
6
10
6 14
6 14
10
10
15
10
10
10
10
15
10
10
15
15
25
15
15
17 12
17 12
30
17 12
17 12
20
20
30
20
20
25
25
25
25
35
35
35
35
60
60
60
60
90
90
90
90
110
110
110
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
00
14
30
00
14
30
00
14
30
00
14
30
00
14
30
00
14
30
14
30
14
30*
12
60
10**
60*
8**
100*
6**
2**
2**
* Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
1 Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
** If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
155
2
Motor
FLA
Table
430.257
AMPS
4.0
5.2
6.8
9.6
1
**
2
3
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LPC_CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
AMPS1
6
6
6
6
5
8
10
10
8
7
12
15
15
9
9
15
15
15
15
12
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
6
6
6
6
6
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
6
6
15
9
9
10
10
20
10
10
15
15
25
15
15
20
20
30
20
20
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
14
30
14
30
14
30
14
Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
These sizes are typical. They are not shown in NEMA ICS 2-2000.
All equipment manufacturers should be consulted about DC voltage ratings of their equipment.
Class J performance, special finger-safe dimensions.
156
2
Motor
FLA
Table
430.257
AMPS
3.1
4.1
5.4
7.6
9.5
1 12
13.2
17
25
40
7 12
58
10
76
*
1
**
2
3
5
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LP-CC
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
TCF
LPN-RK_SP
FRN-R
LPJ_SP
LPN-RK_SP
FRN-R
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
RK1
RK5
AMPS1
5
6
6
4 12
4
7
10
9
5 610
5 610
9
10
10
7 12
7
12
15
15
10
10
15
15
15
15
12
20
20
20
17 12
17 12
30
30
30
25
25
40
40
35
35
60
60
60
50
90
90
80
80
125
100
100
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
6
6
6
6
6
10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
30
30
30
30
30
40
40
40
40
60
60
60
60
90
90
90
90
125
125
125
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
6
6
12
6 14
6 14
10
10
15
10
10
12
10
20
12
12
15
15
30
15
15
20
20
305
20
20
25
25
305
25
25
35
35
305
35
35
50
50
50
35
90
60
90
90
125
125
125
150
150
150
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
14
30
14
30
14
30
14
30
14
30
14
30*
12
60
10**
60*
8**
100*
4**
100*
3**
2**
4**
Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
Reduced voltage magnetic controller ratings
All equipment manufacturers should be consulted about DC voltage ratings of their equipment.
Largest LP-CC Fuse 30 amp. With other type fuse, could use larger amp rating in this application.
Class J performance, special finger-safe dimensions.
157
2
Motor
FLA
Table
430.257
AMPS
2.0
2.6
3.4
4.8
6.1
1 12
8.3
10.8
16
27
*
1
**
2
3
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
RK1
RK5
AMPS1
3
3
2 810
2 12
4
6
3 12
3 12
5 610
6
4 12
4 12
8
10
6 14
6
10
10
8
8
15
15
12
12
15
15
20
15
15
25
25
25
20
20
40
40
40
35
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
3
3
3
3
6
6
6
6
6
6
6
6
10
10
10
10
10
10
10
10
15
15
15
15
20
20
20
20
20
25
25
25
25
25
45
45
45
45
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
4 12
3
4 12
4 12
6
6
6
6
6
6
6 14
7 12
10
10
10
10
12
10
12
12
17 12
15
30
17 12
17 12
20
20
30
20
20
35
35
30
35
35
60
60
60
60
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
14
30
14
30
14
30
14
30
14
30
14
30
14
30*
14
60
10**
Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
These sizes are typical. They are not shown in NEMA ICS 2-2000.
All equipment manufacturers should be consulted about DC voltage ratings of their equipment.
Class J performance, special finger-safe dimensions.
2
Motor
FLA
Table
430.257
AMPS
1.6
2.0
*
1
**
2
3
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LPN-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
J
J
RK1
RK5
J
J
RK1
RK5
AMPS1
2 12
3
2 14
2
3
3
2 810
2 12
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
3
3
3
3
3
3
3
3
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
3 12
3
3 12
3 12
4 12
3
4 12
4 12
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
14
30
14
Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
Reduced voltage magnetic DC controller ratings.
All equipment manufacturers should be consulted about DC voltage ratings of their equipment.
Class J performance, special finger-safe dimensions.
158
2
Motor
FLA
Table
430.257
AMPS
2.7
3.8
4.7
1 12
6.6
8.5
12.2
20
7 12
29
10
38
15
55
20
72
25
89
30
106
40
140
50
173
60
206
75
255
100
341
*
1
**
2
3
3
Fuse
4
Optimal
Branch Ckt
Protection
Type
Class
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LP-CC
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPS-RK_SP
FRS-R
LPJ_SP
TCF
LPN-RK_SP
FRS-R
LPJ_SP
LPN-RK_SP
FRS-R
LPJ_SP
LPN-RK_SP
FRS-R
LPJ_SP
LPN-RK_SP
FRS-R
LPJ_SP
LPN-RK_SP
FRS-R
LPJ_SP
LPN-RK_SP
FRS-R
LPJ_SP
LPN-RK_SP
FRS-R
LPJ_SP
LPN-RK_SP
FRS-R
LPJ_SP
LPN-RK_SP
FRS-R
J
J
RK1
RK5
J
J
CC
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
CC
RK1
RK5
J
J
CC
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
J
RK1
RK5
AMPS1
4 12
6
4
3 12
6
6
5
5
8
10
6 14
6
10
10
9
9
15
15
12
12
20
20
20
17 12
17 12
30
30
30
30
25
45
45
40
40
60
60
50
50
90
90
80
70
110
100
90
150
125
125
175
150
150
225
200
175
300
225
225
350
300
300
400
350
350
600
450
450
5
NEC
Max for
Gen. Applic
430.52(C)(1)
Exc. No. 1
AMPS1
6
6
6
6
6
6
6
6
10
10
10
10
10
10
10
10
15
15
15
15
20
20
20
20
20
30
30
30
30
30
45
45
45
45
60
60
60
60
90
90
90
90
110
110
110
150
150
150
175
175
175
225
225
225
300
300
300
350
350
350
400
400
400
600
600
600
6
NEC Max
for Heavy
Start
430.52(C)(1)
Exc. No. 2
AMPS1
6
6
6
6
8
6
15
8
8
10
10
10
10
12
10
12
12
17 12
15
17 12
17 12
25
25
30
25
25
45
45
30
45
45
60
60
60
60
80
60
80
80
110
110
110
150
150
150
200
200
200
225
225
225
300
300
300
350
350
350
450
450
450
500
500
500
7
Minimum
Switch
Size
430.110
AMPS
8
Minimum
NEMA
Starter
NEMA ICS 22000
Size2
9
Minimum
Copper Wire
THWN or THHN AWG
or KCMIL
Table 310.16
Size
10
Minimum
Rigid Metallic
Conduit
Annex C
Table C8
Inches
30
14
30
14
30
14
30
14
30
14
30
14
30*
12
60
60*
8**
100*
3/4**
100*
3**
200
2**
1**
200*
1/0**
1 14
200*
2/0**
1 14**
400
4/0**
1 12**
400*
300**
2**
400*
400**
2**
600
4/0 2/PHASE
(2) 1 12**
2**
Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch.
Per 430.52(C)(2), if the motor controller manufacturers overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6.
If equipment terminations are rated for 60C conductors only, the 60C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required.
Reduced voltage magnetic DC controller ratings.
All equipment manufacturers should be consulted about DC voltage ratings of their equipment.
Class J performance, special finger-safe dimensions.
159