C O N D U I T
NEC Requirements
www.steelconduit.org
NEC Article 250 contains the general requirements for grounding and bonding of
electrical installations as well as other specific requirements. According to the 2008
NEC Handbook: Sections 250.4(A) and (B)General Requirements for Grounding
and Bonding set forth in detail what must be accomplished by the grounding and
bonding of metal parts of the electrical system. The metal parts must form an
effective low-impedance path to ground in order to safely conduct any fault current
and facilitate the operation of overcurrent devices protecting the enclosed circuit
conductors.
The National Electrical Code and NEC are registered trademarks of the National Fire Protection
Association, Quincy, MA.
Georgia Institute of
Technology Grounding
Research
One of the top experts in the field of
grounding, Dr. Sakis Meliopoulos, professor
of Electrical & Computer Engineering at
Georgia Tech, headed the grounding
research which was completed in 1994.
This research represented the first update on
the impedance and permeability of steel
conduit in over forty years.
The first phase of the grounding research at
Georgia Tech consisted of resistance and
Free Downloads
of GEMI Software
Maximum length of steel conduit/EMT that may safely be used as an equipment-grounding circuit
conductor. Based on a ground-fault current of 400% of the overcurrent device rating.
Circuit 120 volts to ground; 40 volts drop at the point of fault. Ambient temperature 25C.
Maximum
Length of
Run
(in feet)
using
Copper
Equipment
Ground
Conductor
Aluminum
Equipment
Grounding
Conductor
AWG Size***
Aluminum
Circuit
AWG
Conductors
Maximum
Length of
Run
(in feet)
using
Aluminum
Equipment
Grounding
Conductor
253
300
319
12
10
8
12
12
8
244
226
310
15
20
30
60
80
120
294
228
229
8
8
6
8
4
1
232
221
222
40
60
100
160
240
400
250 kcm
500 kcm
900 kcm
195
204
192
200
300
400
800
1200
1600
1/0
2/0
3/0
2-400 kcm
2-500 kcm
3-400 kcm
163
161
131
500
600
800
2000
2400
3200
114
106
93
4/0
250 kcm
350 kcm
4-400 kcm
4-500 kcm
4-900 kcm
115
107
97
1000
1200
1600
4000
4800
6400
5-600 kcm
6-600 kcm
8-500 kcm
78
*
*
400 kcm
600 kcm
600 kcm
5-800 kcm
6-900 kcm
8-750 kcm
79
*
*
2000
2500
3000
8,000
10,000
15,000
8-1000 kcm
10-1000 kcm
12-1000 kcm
*
*
*
800 kcm
1200 kcm
1200 kcm
8-1500 kcm
10-1500 kcm
12-1500 kcm
*
*
*
4000
5000
6000
16,000
20,000
24,000
Copper
Equipment
Grounding
Conductor
AWG Size***
Copper
Circuit
AWG
Conductors
14
12
10
14
12
10
10
10
8
8
6
3
6
4
3
3/0
350 kcm
600 kcm
201
210
195
4
2
1
2
1
1/0
2-4/0
2-300 kcm
3-300 kcm
160
160
134
2/0
3/0
4/0
4-250 kcm
4-300 kcm
4-600 kcm
250 kcm
350 kcm
400 kcm
500 kcm
700 kcm
800 kcm
*Calculations necessary
** 60C for 20- and 30-ampere devices
*** Based on NEC Chapter 9, Table 8
This table shows examples of calculations from the GEMI (Grounding and ElectroMagnetic Interference)
analysis software program.
Reprinted from Soares Book on Bonding and Grounding, 10th edition, by permission of International
Association of Electrical Inspectors.
Maximum length of steel conduit/EMT that may safely be used as an equipment-grounding circuit
conductor. Based on a ground-fault current of 400% of the overcurrent device rating.
Circuit 120 volts to ground; 40 volts drop at the point of fault. Ambient temperature 25C.
Conductors
AWG
Overcurrent
Device Rating
Amperes
75C*
Fault Clearing
Current 400% O.C.
Device
Rating Amperes
Maximum
Length
of
Rigid
Run in feet
Maximum
Length
of
IMC
Run in feet
Maximum
Length
of
EMT
Run in feet
(16)
3-12
4-10
20
30
80
120
384
364
398
383
395
358
(21)
4-10
4-8
30
50
120
200
386
334
399
350
404
332
1 (27)
4-8
3-4
50
85
200
340
350
357
362
382
370
365
1 (35)
3-2
115
460
365
392
391
1 (41)
3-1
3-2/0
130
175
520
700
377
348
402
377
407
364
2 (53)
3-3/0
3-4/0
200
230
800
920
363
347
389
375
390
367
2 (63)
3-250 kcm
255
1020
356
368
406
3 (78)
3-350 kcm
3-500 kcm
3-600 kcm
1240
1520
1680
355
327
314
367
338
325
404
370
353
4 (103)
3-900 kcm
3-1000 kcm
2080
2180
310
304
320
314
353
347
Trade Size
310
380
420
520
545
Portions of this document are reprinted with permission from NFPA 70-2008, National
Electrical Code, Copyright 2008, National Fire Protection Association, Quincy, MA 02169.
This reprinted material is not the complete and official position of the NFPA on the referenced
subject, which is represented only by the standard in its entirety.
Portions of this document are reprinted with permission from NFPA 70HB-2008, National
Electrical Code Handbook, Copyright 2008, National Fire Protection Association, Quincy,
MA 02169.
TTGR-S