Emergency Light Fittings for Fluorescent Lamps Series EXLUX 6008

Luminous Characteristics
Lamps

2 x 36 W W

Battery

7 Ah

Lighting hours

1.5 / 3 h (emergency light)

Explosion protection
Global (IECEx)
IECEx

IECEx PTB 07.0053

Gas explosion protection

Ex d e mb IIC T4

Dust explosion protection

Ex tD A21 IP66 T80C

Europe (ATEX)
Gas explosion protection

PTB 97 ATEX 2032

Gas explosion protection

E II 2 G Ex d e mb IIC T4

Dust explosion protection

PTB 97 ATEX 2032

Dust explosion protection

E II 2 D Ex tD A21 IP6. T80C

Certificates and approvals


Certificates

IECEx, ATEX, Brazil (UL do Brasil), India (PESO), Canada (CSA), Kazakhstan (GOST-K), Russia (GOST-R), Ukraine (GOST-U), USA (FM), Belarus (GOST-B), Serbia (IZP), Corea KGS),
China (CQST)

Other approvals

ship approval (GL)

Further parameters
Marking (CE)

C 0158

Electrical data
Rated voltage

220 ... 254 V, 50 / 60 Hz


110 ... 127 V, 50 / 60 Hz available on request

Disconnection of the light

When opening the light


Switch with safety lock; when opening the central lock, all poles of the voltage supply to the
ballast are disconnected; contacts of the switching element are NC contacts, they can only
switched on again when the lamp cover and the central locking system are closed.
In case of a lamp fault, the electronic ballast disconnects the defective lamp from the power
supply.

Emergency light electronics


Operating modes

Continuous operation, continuous operation with emergency light blocking and stand-by
switching

Battery charge

Intelligent battery management, controlled microprocessor (charging time max. 14 h) total discharge
protection to avoid a pole reversal

R. STAHL Schaltgerte GmbH


P.O. Box 40 - D-74636 Waldenburg - Tel. 07942 943-0 - Fax 07942 943-4333
e-mail: info@stahl.de - Internet: http://www.stahl.de

169732

R. STAHL Schaltgerte GmbH


Data Sheet
Switchover voltage

Page 2 / 2
27.08.2012

from mains to battery operation for U < 0.74 x UN


from battery to mains operation for U > 0.80 x UN

Test functions
Functional test

The emergency light function is checked once a week


First test takes place 1 hour after putting into operation
For the first test, both lamps are switched on for 1 minute and the battery is charged with the
rated current.
Battery errors and lamp faults are detected and indicated via the LED.

Light duration test of the Test of the battery capacity in time intervals of 12 months; operation of the device in the
emergency lighting
emergency light mode during 2/3 of rated operation time. If the light is switched off by the
discharge protection before the time has elapsed, the battery cannot be used for the emergency mode.
The red LED indicates the error.
Battery set
Version

Gas-tight NiCd battery

Operating voltage

6 V

Capacity

7 Ah

Replacing the battery set

When the battery enclosure is opened, the battery set is de-energised;


the battery set can be removed from the enclosure after disconnection of the plug-in
contacts

Mechanical data
Ambient conditions
Ambient temperature

Standard operation: - 20 ... + 50 C


Battery operation: - 5 ... + 50 C charging, - 20 ... + 50 C discharging

Material
Enclosure material

Polyester, glass fibre reinforced, colour: white, similar to RAL 9010

Lamp cover

Polycarbonate

Gasket

Polyurethane foam gasket in the lamp cover

Lamp locking

Central locking which can be opened/closed using a socket key M8 / wrench size 13, hinged
lamp cover

Connection

Polyamide terminal block with cover


Marking: L1, N, PE, L (L = charging phase)
Connection range: max. 2 x 6 mm2 (solid), 2 x 4 mm2 (flexible)

Weight

10.400 kg

Cable entry

Connection side: 1 cable gland M 25 x 1.5 and 1 stopping plug M 25 x 1.5


Opposite side: 1 stopping plug M 25 x 1.5

Connection

Polyamide terminal block with cover


Marking: L1, N, PE, L (L = charging phase)
Connection range: max. 2 x 6 mm2 (solid), 2 x 4 mm2 (flexible)

Through wiring

without

Dimensions
Dimensional Drawings (All Dimensions in mm) - Subject to Alterations

We reserve the right to make alterations to the technical data, weights, dimensions,
designs and products available without notice. The illustrations cannot be considered
binding.

R. STAHL Schaltgerte GmbH


P.O. Box 40 - D-74636 Waldenburg - Tel. 07942 943-0 - Fax 07942 943-4333
e-mail: info@stahl.de - Internet: http://www.stahl.de

169732

Das könnte Ihnen auch gefallen