LAHMEYER INTERNATIONAL
SCALE
1/1
Power Environment
Hydro
Ce document proprit de ALSTOM ne doit pas tre utilis, copi ou communiqu des tiers sans son autorisation
This document is the exclusive property of ALSTOM and shall not be used, copied or communicated to third parties without their prior authorization
AHS M RW 00
INTERNAL USE
LNA- FM100
1/3
1/9
10
9
VERIFIE
APPROUVE
ESTABLISHED
CHECKED
APPROVED
GSCHWEND
KIECHL
KIECHL
09/05/06
FIRST ISSUE
GFE
GSCHWEND
KIECHL
KIECHL
07/06/06
GFE
PA 401 A
REV
DATE
MODIFICATIONS
STAT.
2/A
CONTENTS
3/B
Unit
Manufacturer
Data
GUTOR
Designation
Standard
IEC
Type
PDW
Input parameters:
V AC
400 VAC
frequency
Hz
50
+ 10 / - 15 %
Hz
50 HZ
kVA
60 kVA
nominal voltage
V AC
230 VAC
nominal current
151 A
frequency
Hz
50 Hz
number of phases
ph
efficiency
> 89%
power factor
p.f. 0.8
Overall dimensions:
Height
mm
2300
Depth
mm
800
Width
mm
3575
Mass
4/B
b_PDW_GB_Flyer
31.3.2006
15:56 Uhr
Seite 1
5/B
b_PDW_GB_Flyer
31.3.2006
15:56 Uhr
Seite 2
General Data
Ambient temperature range for storage
Ambient temperature range for operating
Altitude above sea level
Allowable air humidity
Noise level standard n+1 fan system
Noise level 100% redundant fans
Degree of protection
Painting
Safety
EMC
Performance
UPS Classification
Conformity
Efficiency
Cooling
3x380/400/415V
+/-10%
+10/-15%
3x380/400/415V +/-10%
50/60Hz +/-6%
<10x IN (Input current)
110/125/220/400VDC
+/-1% IU characteristic
100 - 115% programmable
100 - 125% programmable
1-24h programmable
depending on battery programmable
+20/-15%
typical +/-25%
6/B
b_PDW_GB_Flyer
31.3.2006
15:56 Uhr
Seite 3
Voltage ( VDC )
110
125
220
400
10
15
20
30
40
60
80
10
15
20
30
40
60
80
10
15
20
30
40
60
80
100
120
160
120
160
220
Rectifier fuse
Bypass input switch
Bypass input MCCB
Rectifier input MCCB
Sensor for temperature dependent battery charging voltage,
recommended for sealed batteries and wide temperature range
Battery temperature alarm
Serial diode ( for parallel Rectifiers )
Diode for reverse polarity protection
Rectifier output isolator
Rectifier output circuit breaker
Battery fuse in UPS
Battery fuse box
Battery MCCB in UPS
Battery MCCB box
Inverter input isolator
Inverter input circuit breaker
Larger inverter Power Module +1 step* / +2 steps*
Static Switch EA ( Inverter side )
Manual Bypass 3 pos in UPS
Battery Monitor ( programmable battery data )
Battery asymmetry supervision
DC earth fault alarm
AC earth fault alarm
RS 232 Interface (event log download)
RS 485 Interface
RJ 45 Ethernet port for WEB browser based monitoring
RS 485 MODBUS Protocol (slave)
External time synchronisation
Top cable entry
Top & bottom cable entry
Space heaters
Panel lighting
Ambient temperature maximum +55 C
Allowable altitude <4000 m above sea level
Protection up to IP52
Air filters at air inlet
Other colours
Bypass isolation transformer
Bypass stabilizer with isolation transformer
* within type range
Additional analogue meters 96x96, cl. 1.5
- Set with VM DC, AM Bat & output FM, VM & AM with select switch
- Set with Input VM & AM with select switch
- kW of output
- Power factor
Relay board A077, 16 failsafe NO/NC contacts:
- Rectifier mains fault
- Inverter fuse blown
- DC out of tolerance
- Bypass mains fault
- Rectifier fuse blown
- Overtemperature
- Battery discharged
- Fan failure
- Earth fault DC
- Power supply unit fault
- 5x options
Relay board A078, 16 failsafe
- EA inhibited
- EN inhibited
- Manual Bypass ON
- Asynchronous
- Overload Inverter / Bypass
- Inverter fault
- Battery disconnected
- Battery operation
NO/NC contacts:
- Rectifier failure
- EN ON
- EA ON
- Inverter ON
- Boost charge
- Rectifier ON
- External horn
b_PDW_GB_Flyer
31.3.2006
15:56 Uhr
Seite 4
The front panel which is identical for both AC and DC Systems facilitates a comprehensive and flexible man-machine interface.
It is divided into four sections:
1.) The system panel shows the systems current operation status, meaning which system part is supplying the load at the moment and which is in
stand-by mode. LEDs also indicate possible faults.
2.) Operations for turning on and off the system and a lamp test button for checking if all LED indications function properly.
3.) On the alarm indication panel the respective LED lights up, after an alarm has occurred
4.) The display unit consist of a LC display, an alarm LED, an acoustic alarm and a key-pad. With this the user can set following operational parameters,
obtain a list of measurement data, and get access to the event and alarm log.
Operational parameters
- Selectable second display language
- Autostart
- Bypass operation
- Boost charge
- Auto boost (charge)
- Battery capacity test
- Battery monitor test (optional)
- Set date / time
Measurements
- Load in % of nominal kVA rating
- AC rectifier mains 1 voltage and current
- AC bypass mains 2 voltage
- DC total current, battery voltage and current
- Battery temperature (with optional sensor)
- AC Inverter current
- AC output voltage, current and frequency
- AC output peak current
- Time left in battery operation with actual load (optional with
programmed battery data)
- Event log with date and time (change in operating mode and alarm)
GUTOR offices:
Headquarters
GUTOR Electronic Ltd Hardstrasse 72-74 CH-5430 Wettingen Switzerland
Phone: +41 (0)56 437 34 34 Fax: +41 (0)56 437 34 44 e-mail: gutor.info@apcc.com www.gutor.com
Asia-Pacific
GUTOR Electronic Asia Pacific Sdn. Bhd 6th Floor, Wisma Genting, Jalan Sultan Ismail 50250 Kuala Lumpur Malaysia
Phone: +603 2161 3440 Fax: +603 2161 3441 e-mail: gutor.asia-pacific@apcc.com www.gutor.com
Q410.100 GB4
North America
GUTOR North America 132 Fairgrounds Road West Kingston RI USA 02892
Phone: +1 (888) 994 8867, ext. 3299 Fax: +1 (401) 788 2698 e-mail: gutor.usa@apcc.com www.gutor.com
Representative offices in China, Emirates, Germany, India, Japan, Mexico, Russia, Saudi Arabia
AHS MRW 00 LNA FM100
8/B
Unit
Data
HOPPECKE
Manufacturer
Symbols
Standards
Type
Rated voltage
Number of cells in battery
Capacity with 10-hour discharge
Discharge rated current (10-hour)
Trickle-charging voltage (floating)
Rated voltage of fully charged cell
Charging voltage at cells
End-discharge voltage per cell (after 10-hour
rated discharge current)
Electrolyte type
Electrolyte density
Permitted temperature range
Cell dimensions
height
width
depth
Weight per cell
Container material
Storage battery mass
Rack dimensions and weight
raw number
step number
height (highest point of installed cell)
width
depth
-
weight
IEC 896-11
DIN 40736-P1
V
pcs
Ah
A
V/cell
V/cell
V/cell
V/cell
8 OPzS 800
220
110
800
81
2,23
2,08
2,23 2,4
1,8
kg/dm3
C
Sulphuric Acid
1,24
-20C - + 40C
mm
mm
mm
kg
kg
710
215
193
61,3
SAN
6743
mm
mm
mm
2 racks needed
2
1967,5
3150
720
kg
254,3
kg
7251,6
9/B