Beruflich Dokumente
Kultur Dokumente
EHV
AC Lines
J. R. Booker (Member)
Senior Engineer
AEP Service Corp. - Columbus
Abstract
A small number of failures of standard porcelain suspension insulators used on
American Electric Power CO's (AEP) 765 kV lines were found with the porcelain
shed broken away from the cap and pin assembly, allowing a lldonutll
of porcelain
to fall to the hardware below.
The investigation of these failures was approached from many angles to determine
the sequence of events leading to the failure. Additionally, it was desired to
determine if this phenomena was the result of aging porcelain under electrical
and/or mechanical stress.
1.
Introduction
AEP's older 765 kV lines are designed using 3-phase, 4-conductor bundles
of 954 MCM 45/7 Rail conductors strung in horizontal configuration with
two 7#8 aluminum clad steel ground wires supported at the top. The newer
lines use a bundle of 1351.5 MCM 45/7 ACSR Dipper conductors and two 7#8
aluminum clad steel ground wires. The supporting structures are fourlegged self-supporting steel towers and lattice type guyed "V" aluminum
towers with center grillage foundation and four guys. The typical span is
1400 to 1500 ft. in flat terrain.
65'+/-
38'+/-
80
0-7803-2506-0/95/$4.00 01995 IEEE
TESTS
180
170
am
$2 160
n=24
>"
2! 150
3
+
0
LT
a,
n = size of sample
140
130
#I
-28
#29
#30
#31
Position in String
#32
Graph 1
Graph 1 shows the oil puncture voltage of grouped insulators. Note the
decrease in puncture voltage toward the energized end of the string.
2B.
Dissipation Factor
Dissipation factor was measured on several insulator strings. Graph 2A
shows the resulting data for one complete "V" string, demonstrating an
increase in dissipation factor at both the energized and the ground ends.
Similar measurements were recorded at one manufacturer's laboratory. For
reference, the dissipation factor was also measured on eight insulators
from stock, which were of similar age, type and manufacturer, but had
never been energized. These units tested in the 2 . 8 to 3.0% range. Graph
2B shows the typical change in dissipation factor with respect to
temperature on one sample.
16
Position in String
82
Graph 2A
32
-a
20
40
TEMPERATURE
80
In
1M)
120
140
OF
Graph 2B
2C.
Graph 3
Graph 3 shows the curves generated using the P I D device. Note the
discontinuity for the insulator in the "17" location. Due to physical
interference, the first and last insulators in the string are not included
in the measurement.
2D.
X-Ray Examinations
As part of the investigation, seven insulators were X-rayed. One of the
seven units was previously subjected to the oil-puncture test, two units
were field punctured units and the remaining four were believed to be
highly stressed units. The X-ray showed that the puncture path did not
follow a straight line between the metal cap on the outside surface to the
metal pin on the inside surface of the porcelain. This puncture path
indicates that the punctures occurred over a period of time following a
path of least resistance while crossing through the porcelain body. There
were no other cracks in the porcelain.
MECHANICAL LOAD TESTS
Over 8 0 0 insulators of 25,000 lbs. and 36,000 lbs. (M&E) strength were
tested mechanically to failure. As was done for oil puncture test data,
the failure load values of the insulators from 1 through 2 8 (position in
the insulator string) were averaged as a group and the test values for
insulator numbers 2 9 , 30, 31, and 32 were averaged separately. The test
values were then plotted on Graph 4 .
84
48
46 0
0
0
7
x
u)
44
42
40
n=size of sample
n=25
CL
n=26
38 36 34
n=33
II
#I
-28
#29
#30
#31
Position in String
#32
Graph 4
Graph
CONCLUSION
The following conclusions are based on electrical and mechanical tests, X-ray
examinations and observations on approximately 1100 porcelain suspension
insulators over the period of 2% years.
Tests were conducted at two
manufacturers' laboratories and at AEP's John E. Dolan Engineering Laboratory.
It is concluded that the puncture process is the result of a combination of
several factors.
1.
2.
3.
85
4.
The trends seen in the oil puncture and dissipation factor tests indicate
that long-term high electrical stress affects the electrical properties of
the porcelain over time. The mechanical load-to-failureresults may also
show a physical affect, although less distinct. However the changes due
to long term exposure to electrical stress could not be shown to be the
sole cause of any failure.
5.
6.
This failure phenomenon may pertain primarily to the insulators which are
weakened either during routine factory tests or during shipping and field
handling prior to their installation.
In addition, localized high
electrical stress is also believed to be caused by variations in the
manufacturing process that leave sharp edges on the metal caps and pins or
which position the pin eccentrically in the porcelain head.
86