Job Procedure
No. LTCDECC DIVISION
SSPL-STCIVIL-JP-11
: SIDHPUR - SANGANER PIPELINE PROJECT.
: M/S INDIAN OIL CORPORATION LIMITED
LARSEN & TOUBRO LTD
Project
Owner
Index
Sl. No. Description
Page No.
Scope
Reference
Material
Procedure
Documentation
ITP
LTCD-SSPL-ST-CIVIL-ITP-11
Format
LTCD-SSPL-ST-CIVIL-FM-11
Page 2 of 5
Rev. 0
Job Procedure
No. LTCDECC DIVISION
SSPL-STCIVIL-JP-11
: SIDHPUR - SANGANER PIPELINE PROJECT.
: M/S INDIAN OIL CORPORATION LIMITED
LARSEN & TOUBRO LTD
Project
Owner
Page 3 of 5
Rev. 0
1.0
SCOPE
This procedure covers the minimum requirements for supervision of all waterproofing treatment of roofs and to ensure
proper quality control at site.
2.0
CONTROLLING SPECIFICATIONS
a) IOCL
specification
IOCL(PL)-IVIL-SPEC
of
Contract
PL/E&C/CONTR/CIVIL/SSPL/ML/2002-03/20 (Volume II).
3.0
3.1
3.2
3.3
4.0
Document
No.
MATERIAL
All the materials used for water proofing shall conform to the relevant specifications.
The primer shall confirm to IS : 3384 - 1986
The bitumen shall confirm to IS : 73 - 1961
The self finished synthetic felts shall confirm to IS : IS 7941 - 1976. It shall have 3 layers of LDPE/HDPE and 1 layer of 2
mm foam insulation. It shall be waterproof, acid resistant and fire resistant.
PROCEDURE
4.1
Grading of the area to be treated shall be done with PCC 1:2:4 with 10 mm down aggregates to 40 mm average thickness
with smooth finishing. It shall have a minimum slope of 1 in 120 or as per the instruction of the Client's site representative.
4.2
The junctions between the roof and vertical faces of parapet wall etc. shall be cased running triangular fillets 75x75 mm
size in PCC 1:2:3. The fillets shall be suitably cut back and rounded off at the drain mouths for easy application of water
proofing treatment and easy flow of water.
4.3
For carrying over and tucking in the water proofing felts into parapet wall etc. a horizontal groove 65 mm deep and 75 mm
wide section with its lower edge not less than 150 mm above the graded roof surface shall be left on the inner face of the
parepet wall or it shall be cut out neatly after construction. The base and the rear of the groove shall be finished smooth
with cement mortar 1:4.
4.4
Tucking in of the water proofing felt will be required where parapet wall exceeds 450 mm in height from graded surface.
Where the height is 450 mm or less, no groove will be required and the water proofing treatment will be carried over the
top of the parapet wall to its full thickness.
4.5
The graded surface of the roof and concrete fillets and face of walls etc. shall be thoroughly cleaned with wire brushes & all
lose scale etc. shall be removed. The cracked surface shall be cut to 'V' section, cleaned and filled up flush with cement
mortar slurry 1:4.
4.6
After grouting the crack, if any, with Cement grout the bitumenous primer shall be brushed over the cleaned and dried
surface before the bonding material is applied. The primer confirming to IS:3384 - 1986 shall be applied at minimum rate of
0.30 litre/sq.m as the first layer of the water proofing treatment.
The second layer consisting of straight run bitumen conforming to IS :73 - 1961 shall be applied @ 0.70 Kg/ Sqm in hot
condition with temperature more than 50 deg C as per IS :7290 -1979.
The 3rd layer shall consists of self finished synthetic felts confirming to IS : 7941 - 1976. The felt film forming the 3rd
course shall be cut to the required length, brushed clean of dust materials and laid in single piece of very long length as
they are likely to shrink. Length of 6 to 8 meter is suitable. Each strip shall have overlap of 75 mm with adjacent strip duly
bonded with cold cut back adhesive @ 0.35 kg/sqm. All the overlaps shall be levelled and pressed down to level the
unevenness. The felt shall be carried over up to the adjacen parapet wall anchored thereto with cement grout by inserting
the felt in the groove on the wall.
The fourth layer shall consists of cold cut back bitumen @ 1 Kg/sq.m over the felt.
The fifth and final course shall consist of coarse sand @ 0.75 Kg/sq.m over bitumen and subsequent preparation of the
surface.
4.7
4.8
4.9
4.10
5.0
Documentation:
ITP:
Format:
LTCD-SSPL-ST-CIVIL-ITP-10
LTCD-SSPL-ST-CIVIL-FM-11
Note: In case of any conflict between this procedure and contract specification the later shall govern.
Project:Client:-
Contractor
S.No
Activity Description
Inspection by
L&T
Verification by
IOCL
Material check
MTC
Surface preparation
RM
LTCD-SSPL-ST-CIVIL-FM-11
RM
-DO-
RM
-DO-
RM
-DO-
RM
-DO-
RM
-DO-
RM
-DO-
-DO-
W - Witness
RM - Random
R - Review Documents
23.02.04
SML
RKS
OPK
Rev.
No.
Date
Description
Prepared by
L&T
Checked by L&T
LTCD-SSPL-ST-CIVIL-ITP-11
LOCATION:
DATE:
Description
Surface preparion
Leak Test
Checked by L&T
Reviewed by
IOCL
Remarks
The work at the above location was checked and found to be in accordance with relevant drawings
and specification of the contract.
For L & T
For IOCL
LTCD-SSPL-ST-CIVIL-FM-11